Sunny Island 8.0H 13 3010268867parameter Export 2023 03 22 17 06 50

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Sunny Island 8.

0H-13 3010268867

Type Label
Inverter
Rated active power WMaxInRtg -6,000 W
Rated active power WMinOutRtg 0W
Rated active power WMinInRtg 0W
Rated reactive power VArMaxQ1Rtg 6,000 var
Rated reactive power VArMaxQ2Rtg 6,000 var
Rated reactive power VArMaxQ3Rtg -6,000 var
Rated reactive power VArMaxQ4Rtg -6,000 var
Rated cos φ PFMinQ1Rtg 0.0000
Rated cos φ PFMinQ2Rtg 0.0000
Rated cos φ PFMinQ3Rtg 0.0000
Rated cos φ PFMinQ4Rtg 0.0000
Rated apparent power VAMaxOutRtg 6,000 VA
Rated apparent power VAMaxInRtg 6,000 VA

Type Label
Serial number

Device name SN 3010268867


Device class Battery Inverter
Device type Sunny Island 8.0H-13
Manufacturer SMA
Software package 3.21.4.R
Serial number 3010268867
MAC address 00:40:AD:B0:F6:21
WLAN-MAC address 58:D5:0A:A9:E2:C4
Communication version 1.1.1.1
Serial no. Slave1 (Phase L2) 0
Serial no. Slave2 (Phase L3) 0

Device
Country settings

Language of the user interface English

Cooling system
Fan test -------

Inverter
Cluster

Maximum active power device 6,000 W


Reference voltage selection Nominal voltage
Frequency droop P(f) -0.199 Hz/kW
Voltage droop Q (U) -1.729 V/kVAr
Maximum AC battery charge current 26.100 A
Set active power limit 6,000 W
Inverter nominal voltage 230 V
Inverter nominal frequency 50 Hz
Functions for grid/offgrid operation Functions for offgrid operation
Nominal voltage and frequency 230V_50Hz
System performance -------
Device address Master
AST type SIAST50-48-12
Cluster configuration Three-phase
Cluster system Multi-cluster
Cluster in the multi-cluster Main-cluster
Extension cluster address 1

Operation
Time control

General operating mode Stop


Acoustic signal for event messages Yes
Cluster behaviour when a device fails Further operation
Reset operating data -------
Load parameter -------
Max. start attempts after error 3
Time-controlled inverter operation No
Start date for time-controlled inverter
Jan 1, 2011 12:00:00 AM
operation
Operating time for time-controlled inverter op. 0 s
Repeat cycle for time-controlled inverter op. Once

System
Initiate device restart -------

Time settings
Automatic time synchronization No
Standard/Daylight saving time conversion on Yes
Current time is daylight savings time No
Time zone (UTC+08:00) Kuala Lumpur, Singapore
NTP server ntp.sunny-portal.com

Multifunction relay
Timer

Operating mode of multifunction relay [A] Network disconnect in emer op


Operating mode of multifunction relay [B] Earthing in emer op
Slave 1: Operating mode of multifunction
Off
relay [A]
Slave 1: Operating mode of multifunction
Off
relay [B]
Slave 2: Operating mode of multifunction
Off
relay [A]
Slave 2: Operating mode of multifunction
Off
relay [B]
Temp lmt for multifunct. relay with batt comp
40.0 °C
fan
Start date of relay control for timer [A] Jan 1, 2011 12:00:00 AM
Start date of relay control for timer [B] Jan 1, 2011 12:00:00 AM
Duration for which multifunction relay is
0s
activated for timer [A]
Duration for which multifunction relay is
0s
activated for timer [B]
Repeat cycle time of relay control for timer
Once
[A]
Repeat cycle time of relay control for timer
Once
[B]

Control of add. loads

Minimum time for the use of excess energy 10 min


Voltage difference for the use of excess energy 0.15 V

Self-consumption
Rise in self-consumption switched on No
Energy saving mode in own consumption
No
switched on

Software component
Communication Bootloader

Version of communication Bootloader 2.2.1.R

Version of WebUI

Version of WebUI 1.17.8.R

Time zone database

Version of time zone database 1.2.0.R

Load shedding 1
Additional time range

Lmt value battery state of charge for start load


30 %
shedding 1
Lmt value battery state of charge for stop load
50 %
shedding 1
Start time additional time range load shedding
00:00:00
1
Time load shedding 1 00:00:00
Limit battery state of charge for start load
30 %
shedding 1 in add time range
Limit battery state of charge for stop load
50 %
shedding 1 in add time range

Load shedding 2
Additional time range

Lmt value battery state of charge for start load


30 %
shedding 2
Lmt value battery state of charge for stop load
50 %
shedding 2
Time load shedding 2 00:00:00
Start time additional time range load shedding
00:00:00
2
Limit battery state of charge for start load
30 %
shedding 2 in add time range
Limit battery state of charge for stop load
50 %
shedding 2 in add time range

User Rights
Access Control

Set user password ••••••••


Set installer password ••••••••

DC Side
System
Type of additional DC sources AC sources and DC charge controllers

AC Side
Inverter

PV system control

Phase assignment Phase L1


Nominal cos φ PFMinQ1 0.0000
Nominal cos φ PFMinQ2 0.0000
Nominal cos φ PFMinQ3 0.0000
Nominal cos φ PFMinQ4 0.0000
Nominal active power WMaxIn -6,000 W
Nominal active power WMinOut 0W
Nominal active power WMinIn 0W
Nominal apparent power VAMaxOut 6,000 VA
Nominal apparent power VAMaxIn 6,000 VA
Nominal reactive power VArMaxQ1 6,000 var
Nominal reactive power VArMaxQ2 6,000 var
Nominal reactive power VArMaxQ3 -6,000 var
Nominal reactive power VArMaxQ4 -6,000 var
Nominal reactive power VArMaxZerWQ1 0 var
Nominal reactive power VArMaxZerWQ2 0 var
Nominal reactive power VArMaxZerWQ3 0 var
Nominal reactive power VArMaxZerWQ4 0 var
Grid nominal voltage 230 V
Applicable voltages Phase voltage

Cluster

Phase assignment device 1 Phase L2


Phase assignment device 2 Phase L3

Measured values
Grid measurements

Set offset of the supplied energy -38 kWh


Set offset of the absorbed energy 0 kWh
Selection of mains exchange capacity
MC box
measurement method

Operation
Grid creating generator No
Grounding type TN grid
Automatic frequency control Off
Current control mode Off

System
Type of AC subdistribution Multicluster Box 12-2

Public electricity mains


Power monitoring

Manual control of network connection -------


Maximum current from public grid 200.000 A
Power feedback to public grid allowed No
Maximum network reverse power 100 W
Maximum network reverse power tripping
10 s
time

Network request via battery state of charge

Additional time range

Network request via battery state of charge


No
switched on
Lmt battery state of charge for connection to
40 %
grid
Lmt battery state of charge for disconnection
80 %
from grid
Limit battery state of charge for connect to
40 %
grid in add time range
Limit battery state of charge for disconnect
80 %
from grid in add time range
Start interval for network request 00:00:00
Start time additional time range grid request 00:00:00

Network request via charge type

Network request via charge type Equalization charge

Network request via power

Network request via power switched on No


Network request switch-on power limit 4,000 W
Network request switch-off power limit 2,000 W

Measurements of external power connection


Cut-off time until connection to external
20 min
network

Energy saving mode


Energy saving mode switched on No
Time until change-over to energy saving mode 3 h 3 s
Maximum duration of energy saving mode 12 h 12 s

External network
Start feed-in PV 04:00:00
Stop feed-in PV 22:00:00

Grid Monitoring
Grid monitoring

Country standard

Country standard set Island mode


Set country standard -------
Underlying country standard Island mode

Frequency monitoring

Anti-islanding sensitivity Normal


Reconnection time after grid fault 1.00 min
Nominal frequency 50.00 Hz
Frequency monitoring upper maximum
66.00 Hz
threshold
Frequency monitoring upper max. threshold
30,000 ms
trip. time
Frequency monitoring median maximum
60.00 Hz
threshold
Frq. monitoring median max. threshold trip.
30,000 ms
time
Frequency monitoring, lower maximum
51.50 Hz
threshold
Frequency monitoring, lower max. threshold
100 ms
trip. time
Frequency monitoring upper minimum
47.50 Hz
threshold
Frequency monitoring, upper min. threshold
100 ms
trip. time
Frequency monitoring median minimum
44.00 Hz
threshold
Frq. monitoring median min. threshold trip.
30,000 ms
time
Frequency monitoring, lower minimum
44.00 Hz
threshold
Frequency monitoring, lower min. threshold
30,000 ms
trip. time
Minimum switching frequency 47.50 Hz
Maximum switching frequency 50.10 Hz

Voltage monitoring

Voltage increase protection enabled No


Voltage monitoring, upper maximum
1.300 p.u.
threshold
Voltage monitoring, median maximum
1.300 p.u.
threshold
Voltage monitoring, lower maximum
1.250 p.u.
threshold
Voltage monitoring, upper minimum threshold 0.800 p.u.
Voltage monitoring, median minimum
0.200 p.u.
threshold
Voltage monitoring, lower minimum threshold 0.300 p.u.
Voltage monitoring, upper max. threshold trip.
30,000 ms
time
Volt. increase prot. 1.900 p.u.
Max. voltage for reconnection 1.100 p.u.
Min. voltage for reconnection 0.850 p.u.
Voltage monitoring, median max. threshold
30,000 ms
trip.time
Voltage monitoring, lower max. threshold trip.
100 ms
time
Voltage monitoring, lower min. threshold trip.
3,000 ms
time
Voltage monitoring, median min. threshold
10,000 ms
trip.time
Voltage monitoring, lower min. threshold trip.
30,000 ms
time

Generator
Operation
Generator nominal frequency 50.00 Hz
Average operating time of generator 15 min
Average idle period of generator 15 min
Cooling down time of generator 5 min
Idle period after generator fault 1h1s
Warm-up time of generator 1 min
Limitation type of generator current Fixed limit value for current limitation
Sensitivity of generator failure detection Normal
Reactive power compensation On

Generator
Frequency monitoring

Automatic generator start On


Manual generator control -------
Rated generator current 200.000 A
Generator request Automatic generator start
Current control mode No
Frequency monit. generator lower minimum
44.64 Hz
threshold
Frequency monit. generator without max.
60.00 Hz
threshold
Frequency monit. gener. hysteresis min.
0.02 Hz
threshold
Freq. Monit. generator hysteresis max.
0.02 Hz
threshold

Operation

Acknowledge generator errors -------

Voltage monitoring

Voltage monit. gener. lower minimum


172.50 V
threshold
Voltage monit. gener. upper maximum
250.00 V
threshold
Voltage monit. gener. hysteresis min.
2.00 V
threshold
Voltage monit. hysteresis generator max.
2.00 V
threshold

Power monitoring

Generator maximum reverse power 100 W


Generator maximum reverse power tripping
30 s
time

Generator queries state of charge


Additional time range

Limit battery state of charge generator start in


40 %
time range
Limit battery state of charge gen. shutdown in
80 %
time range
Battery state of charge limit, generator start in
40 %
additional time period
Battery state of charge limit, generator
80 %
shutdown in additional time period
Start time additional time range generator
00:00:00
request
End time additional time period, generator
00:00:00
request

Generator request via power


Generator request via power on No
Generator shutdown load limit 2,000 W
Generator startup load limit 4,000 W
Average time for generator request via power 1 min

Generator request via charge type


Generator request with set charge type Full and equalization charge

Generator request via digital input


Reaction to digital input of generator request Off

Time-controlled generator operation


Time-controlled generator operation No
Start time for time-controlled generator op. Jan 1, 2011 12:00:00 AM
Operating time for time-controlled generator
0s
op.
Repeat cycle of time-controlled generator op. Once

Battery
Battery

Operation

Battery nominal capacity 0 Wh


Battery nominal capacity 5,000 Ah
Battery type Valve Regulated Lead Acid battery (VRLA)
Nominal battery voltage 48 V
Current sensor type (60mV 50mV) -------
Current sensor gain 100 A
Max. battery temperature 40.0 °C
Battery switch-on limit after overtemp.
35.0 °C
shutdown
Output resistance of battery connection 0.000 Ohm
Manual equalization charge -------

Calibration

Auto-calibration of the external battery current


-------
sensor

Charge
Max. battery charging current 900.000 A
Battery boost charge time 3h
Battery equalization charge time 12 h
Battery full charge time 6h
Battery discharge cut-off voltage 35.00 V
Maximum battery discharge current 900.000 A
Cell charge nominal voltage for boost charge 2.40 V
Cell charge nominal voltage for full charging 2.50 V
Cell charge nominal voltage for equalization
2.55 V
charge
Cell charge nominal voltage for float charge 2.25 V
Cycle time full charge 14 d
Cycle time equalization charge 90 d
Battery temperature compensation 0.004 V/°C
Automatic equalization charge On
Voltage setpoint with deactivated battery
54.00 V
mgmt

Battery switch
Batt. manuf's max. charge capac. 5,000 W
Batt. manuf's max. disch. capac. 0W

Battery charge
Process specification battery charge current 0.0 A

Battery discharge
Process specification battery discharge current 0.0 A

Areas of application
Lower lmt deep disch. protect area prior
10 %
shutdown
Minimum width of deep discharge protection
5%
area
Minimum width of backup power area 0%
Area width for conserving battery state of
5%
charge
Minimum width of own consumption area 35 %
Most productive month for battery usage
June profitable
range
Season operation active Yes

Protection mode
Start time of battery protection mode level [A] 22:00:00
Start time of battery protection mode level [B] 17:00:00
End time of battery protection mode level [A] 06:00:00
End time of battery protection mode level [B] 09:00:00
Battery state of charge for protection mode
20.0 %
[A]
Battery state of charge for protection mode
15.0 %
[B]
Battery state of charge for protection mode
10.0 %
[C]

System communication
Measured values

Meter on Speedwire

Speedwire meter serial no. 0


Usable meters on Speedwire [A] -------
Usable meters on Speedwire [B] -------
Usable meters on Speedwire [C] -------

Device update
Operating mode of the device update Time-controlled
Time of the update 05:00:00

Speedwire
Encryption Unencrypted
Automatic speedwire configuration switched
Yes
on
Speedwire IP address 192.168.0.170
Speedwire subnet mask 255.255.255.0
Speedwire gateway address 192.168.0.170
Speedwire DNS server address 192.168.0.170
Send IGMP requests Version 3
IGMP query interval 2.08 min

WLAN
Security

WLAN is turned on Yes


Soft-access-point is turned on Yes
Activate WPS -------
Automatic configuration of WLAN is turned
Yes
on
IP address of WLAN 192.168.0.173
Subnet mask of WLAN 255.255.255.0
IP address of WLAN gateway 192.168.0.173
IP address of WLAN DNS server 192.168.0.173
Perform WLAN scan -------
SSID of WLAN
WLAN password ••••••••
Encryption for WLAN WPA2-AES

External Communication
Modbus

TCP server

Modbus TCP server on No


Modbus TCP server port 502

UDP server

Modbus UDP server on No


Modbus UDP server port 502

Webconnect
Webconnect version 1.5.1.R
Webconnect functionality switched on No

CAN
Battery and control interface Off

Device Components
Type Label

Main processor

Firmware version of the main processor 1.9.8.R


Serial number of the main processor 3007701931
SUSyID of the main processor 357

Communication assembly

Firmware version of the communication


1.5.33.R
assembly
Hardware version of the communication
R5
assembly
Revision status of the communication
0
assembly
Serial number of the communication assembly 3007549499
SUSyID of the communication assembly 370

Logic component

Firmware version of the logic component 1.9.4.R

WLAN component

Firmware version of WLAN component 1.0.0.R

System and device control


Grid monitoring
Design of the generation plant Symmetric

Inverter
Reactive power mode

Reconnect gradient after grid fault 10 %/min


Soft start-up P after grid fault On
Soft start-up rate P 1,200 %/min

Q(V) characteristic curve

Reactive power mode, reference size for


Maximum active power WMax
reactive power setting
Nom-cos φ PFMinQ1-Q4 Off
Activation threshold for active power output 5.000 %
Deactivation threshold for active power output 5.000 %
Activation threshold for active power draw 5.000 %
Deactivation threshold for active power draw 5.000 %
Reactive power mode, hysteresis active power 0 W
Reactive power mode, hysteresis time 0.00 s
Reactive power mode in case of active power
Off
output
Reactive power mode in case of active power
Off
draw
Reactive power for zero active power Off
Reactive power fallback process in case of
Maintain procedure
active power output
Reactive power fallback process in case of
Maintain procedure
active power draw
Reactive power fallback process in case of
Maintain procedure
zero active power

Characteristic

Q(V), voltage value [A] 0.940 p.u.


Q(V), voltage value [B] 0.970 p.u.
Q(V), voltage value [C] 1.030 p.u.
Q(V), voltage value [D] 1.060 p.u.
Q(V), voltage value [E] 1.000 p.u.
Q(V), voltage value [F] 1.000 p.u.
Q(V), voltage value [G] 1.000 p.u.
Q(V), voltage value [H] 1.000 p.u.
Q(V), reactive power value [A] 44.000 %
Q(V), reactive power value [B] 0.000 %
Q(V), reactive power value [C] 0.000 %
Q(V), reactive power value [D] -44.000 %
Q(V), reactive power value [E] 0.000 %
Q(V), reactive power value [F] 0.000 %
Q(V), reactive power value [G] 0.000 %
Q(V), reactive power value [H] 0.000 %
Q(V), number of support points to be used 4

Reference voltage adjustment

Q(V), operating mode for reference voltage


Off
adaption
Q(V), setting time of automatic reference
5.00 min
voltage adaption

Dynamics

Q(V), setting time, nominal value filter 10 s


Q(V), nominal value filter On
Q(V), limitation of change rate Off
Q(V), increase rate 100.00 %/s
Q(V), decrease rate 100.00 %/s
Q(V), tripping delay 0s

Q(P) characteristic curve

Characteristic

Q(P), max. number of support points 8


Q(P), number of support points to be used 4
Q(P), active power value [A] 50.000 %
Q(P), active power value [B] 60.000 %
Q(P), active power value [C] 90.000 %
Q(P), active power value [D] 100.000 %
Q(P), active power value [E] 100.000 %
Q(P), active power value [F] 100.000 %
Q(P), active power value [G] 100.000 %
Q(P), active power value [H] 100.000 %
Q(P), reactive power value [A] 0.000 %
Q(P), reactive power value [B] -5.000 %
Q(P), reactive power value [C] -33.000 %
Q(P), reactive power value [D] -33.000 %
Q(P), reactive power value [E] -33.000 %
Q(P), reactive power value [F] -33.000 %
Q(P), reactive power value [G] -33.000 %
Q(P), reactive power value [H] -33.000 %

Dynamics

Q(P), tripping delay 0s


Q(P), nominal value filter On
Q(P), setting time, nominal value filter 10.00 s
Q(P), limitation of change rate Off
Q(P), increase rate 100.00 %/s
Q(P), decrease rate 100.00 %/s

Trigger

Q(P), upper deactivation voltage 0.00 p.u.


Q(P), upper activation voltage 0.00 p.u.

Manual cos φ specification

Manual cos φ setting, cos φ nominal value in


1.0000
case of active power generation
Manual cos φ setting, excitation type in case
Underexcited
of active power generation
Manual cos φ setting, cos φ nominal value in
1.0000
case of active power draw
Manual cos φ setting, excitation type in case
Underexcited
of active power draw

cos φ(P) charac. curve

Characteristic

cos φ(P), number of support points to be used 2


cos φ(P), excitation type [A] Underexcited
cos φ(P), excitation type [B] Underexcited
cos φ(P), excitation type [C] Underexcited
cos φ(P), excitation type [D] Underexcited
cos φ(P), cos φ nominal value [A] 1.0000
cos φ(P), cos φ nominal value [B] 0.9000
cos φ(P), cos φ nominal value [C] 0.9000
cos φ(P), cos φ nominal value [D] 0.9000
cos φ(P), active power [A] 50 %
cos φ(P), active power [B] 100 %
cos φ(P), active power [C] 100 %
cos φ(P), active power [D] 100 %

Dynamics

cos φ(P), tripping delay 0s


cos φ(P), actual value filter for active power
Off
measured value
cos φ(P), setting time, actual value filter 1.50 s
cos φ(P), nominal value filter On
cos φ(P), setting time, nominal value filter 10.00 s
cos φ(P), limitation of change rate Off
cos φ(P), increase rate 1,200.00 %/s
cos φ(P), decrease rate 1,200.00 %/s

Trigger

cos φ(P), upper deactivation voltage 0.00 p.u.


cos φ(P), upper activation voltage 0.00 p.u.

Manual reactive power setting for active power output

Manual reactive power setting for active


0 var
power output
Manual reactive power setting for active
100.0 %
power output

Manual reactive power setpoint for zero power output

Manual reactive power setpoint for zero


0 var
power output
Manual reactive power setpoint for zero
100.0 %
power output

Advanced settings for cos φ setpoint specifications

Dynamics

cos φ setting, actual value filter for active


Off
power value
cos φ setting, actual value filter for active
1.50 s
power value
cos φ setting, nominal value filter On
cos φ setting, setting time, nominal value filter 10.00 s
cos φ setting, limitation of change rate Off
cos φ setting, increase rate 1,200.00 %/s
cos φ setting, decrease rate 1,200.00 %/s

Advanced settings for reactive power setpoint specifications

Characteristic

Reactive power setting with voltage limitation Off


Reactive power setting with voltage
0.94 p.u.
limitation, voltage value [A]
Reactive power setting with voltage
0.96 p.u.
limitation, voltage value [B]
Reactive power setting with voltage
1.04 p.u.
limitation, voltage value [C]
Reactive power setting with voltage
1.06 p.u.
limitation, voltage value [D]
Reactive power setting with voltage
33.00 %
limitation, reactive power value [A]
Reactive power setting with voltage
0.00 %
limitation, reactive power value [B]
Reactive power setting with voltage
0.00 %
limitation, reactive power value [C]
Reactive power setting with voltage
-33.00 %
limitation, reactive power value [D]

Dynamics

Reactive power setting, nominal value filter On


Reactive power setting, setting time, nominal
10.00 s
value filter
Reactive power setting, limitation of change
Off
rate
Reactive power setting, increase rate 1,200.00 %/s
Reactive power setting, decrease rate 1,200.00 %/s

Manual reactive power setting in case of active power draw

Manual reactive power setpoint for active


100.0 %
power draw
Manual reactive power setting in case of
0 var
active power draw

Active power mode

External setting

Grid disconnection for 0% active power


-------
setting
Operating mode active power setting Off

Dynamics

External active power setting, setting time,


3.00 s
nominal value filter
External active power setting, limitation of
Off
change rate
External active power setting, increase rate 20.00 %/s
External active power setting, decrease rate 20.00 %/s
External active power setting, nominal value
Off
filter

Voltage-dependent active power adjustment P(U)

Characteristic

P(U), activation Off


P(U), nominal value filter Off
P(U), setting time, nominal value filter 1.00 s
P(U), limitation of change rate Off
P(U), increase rate 20.00 %/s
P(U), decrease rate 20.00 %/s
P(U), tripping delay 0s
P(U), type of reference voltage Mean value of phase voltages
P(U), type of reference active power Maximum active power WMax
P(U), max. number of support points 8
P(U), number of points used 2
P(U), voltage value [A] 1.100 p.u.
P(U), voltage value [B] 1.120 p.u.
P(U), voltage value [C] 2.000 p.u.
P(U), voltage value [D] 2.000 p.u.
P(U), voltage value [E] 2.000 p.u.
P(U), voltage value [F] 2.000 p.u.
P(U), voltage value [G] 2.000 p.u.
P(U), voltage value [H] 2.000 p.u.
P(U), active power value [A] 100.000 %
P(U), active power value [B] 0.000 %
P(U), active power value [C] 0.000 %
P(U), active power value [D] 0.000 %
P(U), active power value [E] 0.000 %
P(U), active power value [F] 0.000 %
P(U), active power value [G] 0.000 %
P(U), active power value [H] 0.000 %

Frequency-dependent active power adapt. P(f)

P(f) characteristic curve

P(f), reference value for active power for


Maximum active power export
underfrequency
P(f) characteristic curve Off
P(f) reference value for active power in case
Maximum active power export
of overfrequency
P(f), setting time 0.50 s
P(f), active power change rate after fault end 10 %/min
P(f), lag time 0s
P(f), tripping delay 0 ms
P(f), hysteresis in case of overfrequency Off
P(f), hysteresis in case of underfrequency Off
P(f), buckling overfrequency [A] 52.000 Hz
P(f), buckling overfrequency [B] 66.000 Hz
P(f), buckling overfrequency [C] 66.000 Hz
P(f), active power change per Hz in case of
-40.000 %
overfrequency [A]
P(f), active power change per Hz in case of
-40.000 %
overfrequency [B]
P(f), active power change per Hz in case of
-40.000 %
overfrequency [C]
P(f), buckling underfrequency [A] 48.000 Hz
P(f), buckling underfrequency [B] 44.000 Hz
P(f), buckling underfrequency [C] 44.000 Hz
P(f), active power change per Hz in case of
-40.000 %
underfrequency [A]
P(f), active power change per Hz in case of
-40.000 %
underfrequency [B]
P(f), active power change per Hz in case of
-40.000 %
underfrequency [C]
P(f), reset underfrequency 52.000 Hz
P(f), reset underfrequency 48.000 Hz

Dynamic grid support

Dynamic grid support, reactive power


Off
dynamic after error end
Dynamic grid support, operating mode Limited dynamic grid support
Dynamic grid support, long-term averaging
1.00 min
time of the pre-fault voltage
Dynamic grid support, averaging of threshold
Nominal system voltage
value detection
Dynamic grid support, overvoltage threshold
1.20 p.u.
for zero current
Dynamic grid support, undervoltage threshold
0.70 p.u.
for zero current
Dynamic grid support, hysteresis voltage 0.02 p.u.

System control and fallback behavior

Q, external setting

Source of ref. meas. for reactive/active power


MC box
reduction
Phased reactive/act. power specification -------
External reactive power setting, fallback
Apply fallback values
behavior
External reactive power setting, timeout 3s
External reactive power setting, fallback value 0.00 %

cos φ, external setting

External cos φ setting, fallback behavior Apply fallback values


External cos φ setting, timeout 5 min
External cos φ setting, fallback value of cos φ
1.0000
in case of active power output
External cos φ setting, fallback value of
Underexcited
excitation type in case of active power output

External setting

External active power setting, fallback


Apply fallback values
behavior
External active power setting, timeout 5 min
External active power setting, fallback value
6,000.00 W
of maximum active power

External reference voltage setting

Q(V), fallback of reference voltage 1.00 p.u.

Grid connection point


Self-consumption

Load unbalance limit Off


Maximum unsymmetric load 1,000,000 W
Operating mode of act. power limit. at grid
Off
connection pt
Set active power limit at grid connection point 0 W
Set active power limit at grid connection point 100 %
Setpoint at the grid connection point in self-
0W
consumption

Areas of application
Upper state of charge for reactivating feed-in 70 %
Lower state of charge for locking feed-in 60 %

Grid connection
PV system
Total system power 2,500 W

You might also like