Professional Documents
Culture Documents
Technical Submittal - FP330 Pipe Collar - 050723 - Rev0 - Compressed
Technical Submittal - FP330 Pipe Collar - 050723 - Rev0 - Compressed
PROTECT
PASSIVE FIRE RESISTANT
SOLUTIONS FOR LINEAR JOINTS
AND SERVICE PENETRATIONS
FIRE PROTECT
TTECHNICAL SUBMITTAL FOR
FP330 PIPE COLLAR
FIRE
Passive fire resistant products are the primary means,
used in the construction of a building, of limiting the
PROTECT
spread of flames, heat and smoke and hugely
increasing fire safety.
By correct application of these products the basic, legal compartmentalisation
requirements will be met. These products contribute to the structural stability of a
INTRODUCTION
building and provide time for people to get out of a building safely and gives emergency
services time to act and fight the fire. Passive fire resistance limits the spread of flames
BOSTIK
and smoke and thus the transfer and flashover of fire between compartments.
The new logo and the new house style with the characteristic green gecko is more than just
a visual appearance. “Smart Adhesives” is a reflection of our positioning with regard to the
development of smart and innovative sealing and bonding solutions that are safe, flexible
and efficient. PASSIVE FIRE PROTECTION:
Bostik Fire Protect is a complete, fully - SAVES LIVES
We develop innovative sealing and bonding solutions that, whatever is constructed, connected certified, approved range of passive fire - LIMITS MATERIAL DAMAGE LOSS
or built, are smarter and can adjust better to the forces and challenges in our daily life.
resistant products for use in movement - MINIMISES BUSINESS LOSS
THE GECKO - INSPIRING ADHESION joints, connection joints, openings and - PROTECTS THE BUILDING, WHICH MEANS IT IS
For centuries, scientists have been inspired by geckos because of their unique bonding service penetrations between fire ACCESSIBLE AFTER THE FIRE
mechanism. They can stick to almost any surface, can climb super-fast against smooth
compartments.
polished glass and can easily carry their entire body weight with just one toe.
Creating fire compartments in a building is an essential part of passive fire safety. The
underlying aim is to restrict the spread of smoke and flames in the case of a fire to one
The Bostik gecko is flexible, easy to adapt to environments, is open to new situations and
single compartment and thus to slow down the spread of the fire.
is courageous. It symbolizes Bostik’s smart and innovative sealing and bondig solutions for
the challenges which today’s market faces. As passive fire safety is becoming increasingly important, both in new buildings and in
renovation work, Bostik has decided to focus its efforts on product development and
certification for this market segment. With our huge experience in the field of solutions
for linear joints (EN 1366-4) we are proud to present our Fire Protect range which also
includes solutions for openings and service penetrations (EN 1366-3).
www.bostik.com
PIPE
COLLAR
FP 330
FAST EXPANDING FIRE
RETARDANT PIPE COLLAR
FIRE PROTECT
split white coated, circular steel casing designed to
fit around plastic pipes.
white
EN 1366-3
www.bostik.com
TECHNICAL DATASHEET
www.bostik.com
FP 330 Pipe Collar
VASTLY EXPANDING COLLAR IN CASE OF FIRE
ADVANTAGES
PRODUCT
Bostik FP 330 Pipe Collar is a fire collar which expands in the
case of a fire to fill voids left by melting plastic and burning
of combustible pipe insulation. Bostik FP 330 Pipe Collar
consists of a split white coated, circular steel casing
designed to fit around plastic pipes. The collars have a
secure and simple locking device. The steel sleeve contains the opening around the pipe is too large
a graphite based expanding material which on exposure to - Tested and certified for U/U pipe end applications
heat fills voids left by combustible pipes and pipe insulation - No emissions, environmental and user friendly
passing through fire walls and floors. - Very easy to install using widely available standard fixings
- Excellent sound insulation
APPLICATIONS - Unlimited storage time (under correct conditions)
The intended use of Bostik FP 330 Pipe Collar is to reinstate
the fire resistance performance of flexible walls, rigid walls METHOD OF USE
and floor constructions where they are penetrated by For sealing plastic pipes in floors, a single pipe collar is
plastic pipes and combustible pipe insulation. installed to the underside of the floor. For flexible and solid
The fire collar is placed and anchored around the pipe. In walls, a pipe collar is installed on both sides of the wall.
concrete floors, only one Bostik FP 330 Pipe Collar needs to Before fitting the pipe collar ensure that any gaps between
be fitted to the floor or soffit. In case of wall penetration a the pipe and the separating element are sealed as follows:
fire collar on both sides is required. - In gypsum walls, gaps between the pipe and the
Bostik FP 330 Pipe Collar prevents the spread of heat, construction below 8mm must have a bead of Bostik FP
smoke and fire to the next compartment. 310 Intumescent Acoustic Acrylic to cover the opening,
and for gaps 8mm or above, the seal must be plugged
FEATURES with 25mm deep Bostik FP 310 Intumescent Acoustic
- Certified to the latest European standards EN 1366-3 Acrylic.
- CE marked to ETAG 026-2 - In masonry/concrete walls, gaps between the pipe and
- Fire resistance up to 4 hours for both integrity and the construction below 8mm must have a bead of Bostik
insulation FP 310 Intumescent Acoustic Acrylic to cover the
- Fast expanding graphite material opening, and for gaps 8mm or above, the seal must be
- Classified for fire sealing all types of constructions and plugged with 20mm deep Bostik FP 310 Intumescent
many different building service penetrations including Acoustic Acrylic on 20mm deep backing of stonewool.
plastic pipes, composite pipes, metal pipes and cable - In floors, gaps between the pipe and the construction
bundles below 10mm must have 20mm deep stonewool to plug
- Approved plastic pipe sizes range from smallest pipes the opening, and for gaps 10mm or above, the seal must
available to Ø 400mm, each with a wide range of pipe be plugged with 10mm deep Bostik FP 310 Intumescent
wall thicknesses Acoustic Acrylic on 40mm deep backing of stonewool.
- Collars are available in two different heights for different Place a pipe collar around the service penetration (pipe) and
fire classifications to maximize cost efficiency ensure that the fixing lugs are positioned tightly to the
- Smaller pipes can be fitted within larger collars with the surface of the wall or the floor so that the anchors/fixings
benefit of accommodating pipes that are at an angle or if can be inserted fully.
Where the surface is uneven, apply a sealing bead of Bostik
Technical data
FP 310 Intumescent Acoustic Acrylic between the wall/floor
and the pipe collar.
Technical Approval ETAG 026-2
Attach the pipe collar with steel screws, anchors or fixings Shell Powder coated 1mm steel
that are suitable for the substrate that the pipe collar will be
Expansion ratio 17:1
fitted to. For flexible walls use ≥ Ø4 mm gypsum-, wood
screws or anchors with a length suitable for the number of Expansion pressure 65.4 N/cm2
boards that form the wall. For concrete/masonry walls and
Colour White shell with anthracite inlay
floors, use ≥ Ø4 x 50mm long masonry screws or expansion
bolts. Graphite weight 1.4 kg/m² per mm thickness
On site where the penetration size is greater than the pipe
Graphite density 1409 kg/m³
diameter and/or the pipe is in an angle an oversized collar
can be used. Bostik FP 330 Pipe Collar are tested ‘oversize’, i. Expansion time Less than 2 minutes
e. the internal diameter of the collar can be larger than the Minimum expansion 105 °C
pipe. In this case the empty space between collar and pipe temperature
has to be filled with Bostik FP 310 Intumescent Acoustic
Acrylic. Durability Z2 intended for use in internal
conditions with humidity classes
Before application consult the installation instructions and other than Z1, excluding
ETA to ensure to achieve the intended fire resistance. temperatures below 0°C
FURTHER INFORMATION
Available on request:
- Material safety data sheet
- Installation Instructions Bostik FP 330 Pipe Collar
- ETA 19/0391
Smart help
T: +31 (0) 162491000 T: +32 (0) 92551717 T: +44 (0) 1785 272625 T: +353 (1) 8624900
www.bostik.nl www.bostik.be www.bostik.co.uk www.bostik.ie
All advice, recommendations, figures and safety instructions are based upon thorough research as well as the current state of our experience and are non-binding. Despite the greatest care having
been taken to compile the documentation, we assume no responsibility for inaccuracies, mistakes, typographical or print errors. We reserve the right to alter the product whenever we deem
necessary. Considering that the design and conditions of the substrate and the circumstances under which the application takes place are beyond our control, no responsibility with regard to the
executed works can be assumed on the basis of this documentation. Therefore we advise you to perform a test on the spot yourself. All our sales and deliveries are subject to our General Conditions
of Sale and Delivery.
METHOD STATEMENT
www.bostik.com
Installation
instructions
Bostik FP330
Pipe Collar
FP 330 PIPE COLLAR
In floors:
Support structures: Cracks between pipe and structure of less than
Partition walls must be at least 100 mm thick and consist 10mm should be filled with 20mm stone wool,
of a framework of steel or wood clad on both sides with while cracks of 10mm and more should be filled
at least 2 wall plates of 12.5 mm thick. Solid walls must be with 10mm Bostik FP 310 Intumescent Acoustic
Acrylic on a 40mm thick rock wool underlay.
at least 100 mm thick and consist of concrete, aerated
concrete or masonry and have a minimum density of 650
kg/m3. Solid floors must be at least 150 mm thick and 3. Place the sleeve around the pipe ensuring that the
consist of aerated concrete or concrete and have a sleeve sleeve and fixing eyes are tight against the
minimum density of 650 kg/m3. The supporting structure wall or floor to allow the plugs/screws to be fully
must be classified for required fire resistance time driven in.
according to EN 13501-2.
4. If the surface is uneven, apply a sealing joint of
Bostik FP 310 Intumescent Acoustic Acrylic
between the wall/floor and the sleeve sleeve.
* ) In the case of a wooden frame, the distance between
the opening seal and the wood must be at least 100 mm 5. Fasten the collar with steel screws, plugs or bolts
and must be filled with at least 100 mm of insulation suitable for the surface on which the collar is to
material of class A1 or A2 (according to EN 13501-1). be mounted. For plaster walls, use plaster or
wood screws ≥ Ø 4 mm with a length suitable for
the number of boards the wall is made of. Note:
M5 drywall plugs are required for some drywall
applications. For walls and floors made of
concrete or masonry, use masonry screws or
expansion bolts ≥ Ø 4 x 40 mm long.
Space between the pipe and the construction ≤ 8 mm Space between the pipe and the construction ≥ 8 mm
1 1
2 2
3 3
4 4
Space between the pipe and the construction ≤ 8 mm Space between the pipe and the construction ≤ 8 mm
1 1
2 2
3 3
4 4
Space between the pipe and the construction ≤ 8 mm Space between the pipe and the construction ≤ 8 mm
1 1
2 2
3 3
4 4
PP Pipes
Tube and sleeve descriptions Fire ratings
1 1
2 2
3 3
4 4
1 1
2 2
3 3
4 4
PP Pipes
75 2.8–6.8 50 EI 90 (E 120) - - -
82 2.8–7.5 50 EI 90 (E 120) - - -
110 2.7 – 10.0 50 EI 90 (E 120) - - -
125 3.3 – 11.3 60 EI 90 (E 120) - - -
160 4.9–14.6 60 EI 120 (E 120) - - -
1 1
2 2
3 3
4 4
32 30 EI 120 (E 120) - - -
Aquatherm Green SDR9 40 – 50 50 EI 120 (E 120) - - -
63-110 50 EI 60 (E 120) - - -
Geberit Silent PP
32 – 50 50 EI 120 (E 120) EI 120 (E 120) EI 120 (E 120) EI 120 (E 120)
75-110 50 EI 60 (E 120) EI 60 (E 120) EI 60 (E 120) EI 60 (E 120)
Polo-Kal NG pipes
75-110 50 EI 90 (E 120) EI 90 (E 120) EI 90 (E 120) EI 90 (E 120)
125 60 EI 120 (E 120) EI 120 (E 120) (E120) (E120)
160 60 EI 120 (E 120) EI 120 (E 120) EI 120 (E 120) EI 120 (E 120)
EMPTY STORAGE WITH FIRE RESISTANCE EI 60 (E 120) EMPTY STORAGE WITH FIRE RESISTANCE EI 120 (E 120)
Maximum opening Ø 110 mm Maximum opening Ø 160 mm
1 1
2 2
3 3
1:The hole should be filled with on both sides 1:The hole should be filled with on both sides
rock wool of 25 mm thick rock wool of 25 mm thick
2:≤ Ø110mm: Bostik FP 330 Pipe Collar with a height 2:Ø160mm: Bostik FP 330 Pipe Collar with a height of
≥ 30 mm on both sides 60mm on both sides
3:Fastening with wood, plaster or stone screws 3:Fastening with wood, plaster or stone screws
with Ø 4 mm with Ø 4 mm
CABLE BUNDLE WITH FIRE RESISTANCE EI 60 (E 120) CABLE BUNDLE WITH FIRE RESISTANCE EI 60 (E 120)
spaces between beam and structure ≤ 10 mm spaces between beam and structure ≤ 10 mm
1 1
2 2
3 3
4 4
1 1
2 2
3 3
4 4
COPPER OR STEEL PIPE WITH FIRE RESISTANCE EI 90 C/ COPPER OR STEEL PIPE WITH FIRE RESISTANCE EI 60 C/
C (E 120) C (E 120)
1 1
2 2
3 3
4 4
5 5
10. Installation instructions - PLASTERBOARD, MASONRY OR CONCRETE WALLS WITH A THICKNESS ≥ 100 MM
FP 330 PIPE COLLAR
PLASTERBOARD, MASONRY OR CONCRETE WALLS
WITH A THICKNESS ≥ 100 MM
1
2
3
4
5
Installation instructions - PLASTERBOARD, MASONRY OR CONCRETE WALLS WITH A THICKNESS ≥ 100 MM 11.
FP 330 PIPE COLLAR
MASONRY OR CONCRETE WALLS WITH A THICKNESS ≥ 150 MM
PVC & PE PLASTIC PIPES WITH FIRE RESISTANCE EI 60 - PVC & PE PLASTIC PIPES WITH FIRE RESISTANCE EI 60 -
240 240
Space between the pipe and the construction ≤ 8 mm Space between the pipe and the construction ≤ 8 mm
1 1
2 2
3 3
4 4
75 2.3 – 4.9 50 EI 180 (E 180) EI 180 (E 180) EI 180 (E 180) EI 180 (E 180)
82 2.4–5.2 50 EI 180 (E 180) EI 180 (E 180) EI 180 (E 180) EI 180 (E 180)
110 2.7–6.6 50 EI 180 (E 180) EI 180 (E 180) EI 180 (E 180) EI 180 (E 180)
125 3.1–7.5 60 EI 240 (E 240) EI 240 (E 240) EI 240 (E 240) EI 240 (E 240)
160 4.0 – 9.5 60 EI 240 (E 240) EI 240 (E 240) EI 240 (E 240) EI 240 (E 240)
PP PLASTIC PIPES WITH FIRE RESISTANCE EI 60-240 PP PLASTIC PIPES WITH FIRE RESISTANCE EI 60 -
240
Space between the pipe and the construction ≤ 8 mm Space between the pipe and the construction ≥ 8 mm
1 1
2 2
3 3
4 4
PP Pipes
Tube and sleeve descriptions Fire ratings
Tube Diameter TubeWall MinimalCollar C/C U/C C/U U/U
[mm] Thickness[mm] Height[mm]
PVC PLASTIC PIPES WITH FIRE RESISTANCE EI 60 - PVC PLASTIC PIPES WITH FIRE RESISTANCE EI 60 -
120 120
Space between the tube and the construction ≤ 10mm Space between the tube and the construction ≤ 10mm
1 1
2 2
3 3
4 4
PE PLASTIC PIPES WITH FIRE RESISTANCE EI 60 - PE PLASTIC PIPES WITH FIRE RESISTANCE EI 60 - 240
240
Space between the tube and the construction ≤ 10mm Space between the tube and the construction ≥ 10mm
1 1
2 2
3 3
4 4
PP PLASTIC PIPES WITH FIRE RESISTANCE EI 30-240 PP PLASTIC PIPES WITH FIRE RESISTANCE EI 30 -
240
Space between the tube and the construction ≤ 10mm Space between the tube and the construction ≥ 10mm
1 1
2 2
3 3
4 4
PP Pipes
Tube and sleeve descriptions Fire ratings
Tube Diameter TubeWall MinimalCollar C/C U/C C/U U/U
[mm] Thickness[mm] Height[mm]
1
2
3
4
1:Plastic tube
2:FP 330 Pipe Collar on top
3:Spaces should be at the top of the cuff
sealed with Bostik FP 310 Intumescent Acoustic Acrylic
4:Fastening with stone screws with Ø 4 mm
1
2
3
4
1:Plastic tube
2:FP 330 Pipe Collar on top
3:Spaces should be at the top of the cuff
sealed with Bostik FP 310 Intumescent Acoustic Acrylic
4:Fastening with stone screws with Ø 4 mm
PP Pipes
Tube and sleeve descriptions Fire ratings
Tube Diameter TubeWall MinimalCollar C/C U/C C/U U/U
[mm] Thickness[mm] Height[mm]
COMPOSITE PLASTIC PIPES WITH FIRE RESISTANCE PE PLASTIC PIPES WITH FIRE RESISTANCE EI 60-240
EI 60 - 240
Space between the tube and the construction ≤ 10mm Space between the tube and the construction ≥ 10mm
1 1
2 2
3 3
4 4
32 30 EI 240 (E 240) - - -
Aquatherm Green SDR9 40 – 50 50 EI 240 (E 240) - - -
63-110 50 EI 120 (E 120) - - -
Geberit Silent PP
32 – 50 50 EI 240 (E 240) EI 240 (E 240) EI 240 (E 240) EI 240 (E 240)
75-110 50 EI 180 (E 180) EI 180 (E 180) EI 180 (E 180) -
Polo-Kal NG pipes
75-110 50 EI 240 (E 240) EI 240 (E 240) EI 240 (E 240) EI 90 (E 120)
125 60 EI 240 (E 240) EI 240 (E 240) - -
160 60 EI 240 (E 240) EI 240 (E 240) E 240) -
EMPTY STORAGE WITH FIRE RESISTANCE EMPTY STORAGE WITH FIRE RESISTANCE
EI 60 (E 240) EI 120 (E 120)
Maximum opening Ø 55mm Maximum opening Ø 160 mm
1 1
2 2
3 3
1:The hole should be filled at the bottom with 1:The hole should be filled at the bottom with
rock wool of 25 mm thick rock wool of 25 mm thick
2:≤ Ø 55mm: FP 330 Pipe Collar with a height ≥ 30 mm 2:Ø 160mm: FP 330 Pipe Collar with a height of 60 mm
At the bottom At the bottom
3:Fastening with stone screws with Ø 4 mm 3:Fastening with stone screws with Ø 4 mm
CABLE BUNDLE WITH FIRE RESISTANCE EI CABLE BUNDLE WITH FIRE RESISTANCE EI
120 (E 120) 90 (E 90)
spaces between beam and structure ≤ 10 mm spaces between beam and structure ≤ 10 mm
1 1
2 2
3 3
4 4
1 1
2 2
3 3
4 4
5
Installation Instruction
All advice, recommendations, figures and safety instructions are based on thorough research and the current state of our experience and are not binding. While every care has been taken in compiling
the documentation, we accept no responsibility for inaccuracies, errors, typographical or printing errors. We reserve the right to change the product when we deem it necessary. Since the design and
conditions of the substrate and the conditions under which the application takes place are beyond our control, no responsibility can be accepted with regard to the works carried out on the basis of this
documentation. That is why we advise you to carry out a test yourself on site.
www.bostik.com
Translated from Polish to English - www.onlinedoctranslator.com
1.1. Product ID
Application: fire protection collar for sealing penetrations in walls and ceilings
Uses advised against: not specified
1.3. Details of the supplier of the safety data sheet
Importer/Distributor:
Bostik Sp. z o. o
st. Poznańska 11b, Sady
62-080 Tarnowo Podgórne
Person responsible for the product: Wiktor Loręcki, phone: +48 61 89 61 740
1.4. Emergency telephone number
+ 48 61 89 61 740 8.00 - 16.00
--
Chemical nature:mixture
SAFETY DATA SHEET
Based on the Decree Commission (EU) No 2015/830 of 28 May 2015
-- -- -- --
The full meaning of the H-phrases is included in section 16
notify the relevant administrative and control authorities and rescue organizations.
6.3. Methods and materials for containment and cleaning up
Secure damaged packaging. Collect
the released product mechanically.
Collect into appropriate containers and send for destruction.
6.4. References to other sections
Individual protection measures: section
8 Disposal methods: section 13
-- -- -- -- -- --
DNELs / PNECs
No data
Hand protection
If necessary, use protective gloves in accordance with the requirements of EN374. Select the glove
material taking into account the breakthrough time, permeation rate and degradation.
It is recommended to regularly change the gloves and replace them immediately if there are signs of wear,
damage (tears, holes) or changes in appearance (color, elasticity, shape).
Body protection
It is not required under normal
circumstances. Respiratory protection
It is not required under normal circumstances.
Environmental exposure control
Do not discharge into drains or the environment.
General safety and hygiene instructions Follow
good personal hygiene practices.
Flash-point: No data
Flammability (solid, gas): Not applicable
Upper/lower flammability or explosive limits: No data
10.1. Reactivity
Under conditions of proper storage and use, the mixture is not chemically reactive.
10.2. Chemical stability
Under conditions of proper storage and use, the mixture is chemically stable.
10.3. Possibility of hazardous reactions
They are not known
Avoid heating
10.5. Incompatible materials
Strong acids, strong bases
10.6. Hazardous decomposition products
They do not occur when used as intended.
12.1. Toxicity
Acute toxicity
Based on available data, the classification criteria are not met.
12.2. Persistence and degradability
It is not biodegradable
12.3. Bioaccumulative potential
No potential for bioaccumulation.
12.4. Mobility in the soil
The product is insoluble in water.
12.5. PBT and vPvB assessment results
The product does not contain ingredients that meet the PBT or vPvB criteria
12.6. Other harmful effects
No data
Waste code
Act of December 14, 2012 on waste (consolidated text: Journal of Laws of 2019, item 701, as amended) Regulation of the
Minister of Climate of January 2, 2020 on the catalog of waste (Journal of Laws of 2020, item 10)
The waste code must be assigned individually at the place of waste generation, depending on the industry of the place of use.
ADR/RID
14.1. UN number (UN number) Not applicable
14.2. Proper shipping name) Not applicable
14.3. Transport hazard class(es). Not applicable
Warning sticker Not applicable
14.4. Packing group Not applicable
14.5. Environmental hazards NO
14.6. Special precautions for users Not applicable
14.7. Transport in bulk in accordance with Annex II to Not applicable
MARPOL and the IBC Code
15.1. Safety, health and environmental regulations/legislation specific for the substance or mixture
The safety data sheet was developed on the basis of:
− Regulation (EC) No. 1907/2006 PEiR of December 18, 2006. on the Registration, Evaluation, Authorization and
Restriction of Chemicals (REACH), establishing a European Chemicals Agency, amending Directive 1999/45/EC
and repealing Council Regulation (EEC) No 793/93 and Commission Regulation (EC) No 1488/ 94 as well as
Council Directive 76/769/EEC and Commission Directives 91/155/EEC, 93/67/EEC, 93/105/EC and 2000/21/EC as
amended
− Regulations (EC) No. 1272/2008 of 16.12.2008 on classification, labeling and packaging of substances and
mixtures, amending and repealing Directives 67/548/EEC and 1999/45/EC and amending Regulation (EC) No.
1907/ 2006 as amended
− Commission Regulation (EU) No. 2015/830 of 28 May 2015 amending Regulation (EC) No. 1907/2006 of the
European Parliament and of the Council on the Registration, Evaluation, Authorization and Restriction of
Chemicals (REACH) with a corrigendum
− Act on substances and their mixtures of February 25, 2011. (consolidated text: Journal of Laws of 2019, item 1225)
− Regulation of the Minister of Family, Labor and Social Policy of June 12, 2018 on the maximum permissible concentrations
and intensities of factors harmful to health in the work environment (Journal of Laws of 2018, item 1286)
− Act of 14 December 2012 on waste (consolidated text: Journal of Laws 2019, item 701, as amended)
− Regulation of the Minister of Climate of January 2, 2020 on the catalog of waste (Journal of Laws 2020, item 10)
− Regulations of the Minister of Labor and Social Policy of September 26, 1997 on general occupational health and
safety regulations (consolidated text: Journal of Laws 2003 No. 169, item 1650, as amended)
− Regulation of the Minister of Health of 30 December 2004 on occupational health and safety related to the presence of
chemical agents in the workplace (consolidated text: Journal of Laws of 2016, item 1488)
− Classification of dangerous goods in accordance with the European Agreement concerning the International Carriage of
Dangerous Goods by Road (ADR)
--
Training Tips
Read the Safety Data Sheet before use
Explanation of abbreviations and acronyms used in the safety data sheet CAS
(Chemical Abstracts Service)
The EC number stands for one of the three numbers listed below:
• number assigned to the substance in the European Inventory of Existing Commercial Substances (EINECS)
• the number assigned to the substance in the European List of Notified Substances (ELINCS)
• number in the list of chemical substances listed in the publication of the European Commission "No-longer polymers" (NLP) NDS -
the highest permissible concentrations of substances harmful to health in the work environment
STEL - the highest permissible temporary concentration.
STEL - the highest permissible ceiling concentration
UN No. - Material identification number (UN number, UN number)
ADR - European Agreement concerning the International Carriage of Dangerous Goods by Road RID -
Regulations for the International Carriage of Dangerous Goods by Rail
IMDG - International Maritime Dangerous Goods Code IATA -
International Air Transport Association
vPvB (Substance) Very Persistent and Very Bioaccumulative PBT (Substance)
Persistent, Bioaccumulative and Toxic
LD50 Dose at which death is observed in 50% of test animals LC50
Concentration at which death is observed in 50% of test animals
ECX Concentration at which X % decrease in growth or growth rate is observed NOEL
Highest concentration of the substance at which no effects are observed
BOD Biochemical Oxygen Demand (BOD) COD Chemical Oxygen Demand
(COD) ThOD Theoretical Oxygen Demand
The product described in the safety data sheet should be stored and used in accordance with good industrial practice and in
accordance with all legal regulations.
The information contained in the safety data sheet, based on the current state of knowledge, is intended to describe the product from the point of
view of legal regulations in the field of safety, health and environmental protection. They should not be understood as a guarantee of specific
properties.
The user is responsible for creating conditions for safe use of the product and it is the user who takes responsibility for the
consequences resulting from the improper use of this product.
The safety data sheet was developed by:
EKOS sc
80-177 Gdańsk, ul. Lubczykowa 5
phone: +48 58 305 37 46, e-mailekos@ekos.gda.pl
www.ekos.gda.pl
DECLARATION OF
PERFORMANCE
www.bostik.com
DECLARATION OF PERFORMANCE
in accordance with Annex III of Regulation (EU) No 305/2011
(Construction Product Regulation)
2. Type, batch or serial number or any other element allowing identification of the
construction product as required to Article 11 (4):
2.1 Bostik FP 330 Pipe Collar is supplied in various diameters and heights.
2.2 In accordance with article 11(4) all products are supplied with product code and batch
number with all manufacturing processes traceable through Factory Production
Controls (FPC) held in the product technical files.
3. Intended use or uses of the construction product, in accordance with the applicable
harmonized technical specification, as foreseen by the supplier, and in accordance
with the applicable European Assessment Document (Hereinafter EAD): EAD 350454-
00-1104 (penetration seals).
3.1. The intended use of system Bostik FP 330 Pipe Collar is to reinstate the fire resistance
performance of flexible and rigid wall, and floor constructions where they are
penetrated by various services.
3.2. The specific elements of construction that the system Bostik FP 330 Pipe Collar may
be used to provide a penetration seal in, are as follows:
Flexible walls: The wall must have a minimum thickness of 75 mm and comprise of steel
studs lined on both faces with minimum 1 layer of 12.5 mm thick boards 1).
Timber walls: The wall must have a minimum thickness of 100 mm and comprise solid
wood or cross laminated timber.
Rigid walls: The wall must have a minimum thickness of 75mm and comprise concrete,
aerated concrete or masonry, with a minimum density of 650 kg/m3 1).
10-Dec-21 Page 1 of 4
Rigid floors: The floor must have a minimum thickness of 150 mm 2) and comprise aerated
concrete or concrete with a minimum density of 650 kg/m3.
Timber floors: The floor must have a minimum thickness of 150 mm and comprise solid
wood or cross laminated timber.
The supporting construction must be classified in accordance with EN 13501-2 for the
required fire resistance period.
3.3. The system Bostik FP 330 Pipe Collar may be used to provide a penetration seal with
various services (for details see ETA 21/0551 Annex A).
3.4. The provisions made in the European Technical Assessment (21/0551) are based on an
assumed working life of the Bostik FP 330 Pipe Collar for 10 years, however provided
that the conditions laid down in the product datasheet and instructions for the
packaging/transport/storage/installation/ use/repair are met the assumed working
life of Bostik FP 330 Pipe Collar for internal conditions without exposed to UV or
moisture is 30 years. The indications given on the working life cannot be interpreted
as a guarantee given by the producer/supplier but are to be regarded only as a means
for choosing the right products in relation to the expected economically reasonable
working life of the works.
3.5. Type Z2: intended for use at internal conditions with humidity classes other than Z1,
excluding temperatures below 0°C.
4. Name, registered name or registered trademark and contact address for the
manufacturer/supplier as required to Article 11 (5):
5. Where applicable, name and contact address of the authorized representative whose
mandate cover the tasks specified in Article 12(2):
Not applicable
AVCP-System 1
10-Dec-21 Page 2 of 4
8. In case of the declaration of performance concerning a construction product for
which a European Technical Assessment has been issued:
This Declaration of Performance has been prepared in accordance with the guidelines
set out within EAD 350454-00-1104 (penetration seals).
9. Declared performance:
10-Dec-21 Page 3 of 4
10. The performance of the product identified in points 1 and 2 is in conformity with the
declared performance in point 9. This declaration of performance is issued under the
sole responsibility of the manufacturer/supplier identified in point 4.
Vincent Imbos
Managing Director
Oosterhout, 12/2021
10-Dec-21 Page 4 of 4
TEST REPORTS &
CERTIFICATIONS
www.bostik.com
EC CERTIFICATE
A pipe closure device used to form penetration seals where combustible pipes, cables and metal pipes with insulation
penetrate walls and floors. Bostik FP 330 Pipe Collar is supplied with intumescent liner complete within metal steel shell,
to be clamped around the service and screw fixed back to the supporting element. The Bostik FP 330 Pipe Collar may be
supplied with powder coated steel or stainless steel shells.
Bostik BV
Denariusstraat 11, 4903 RC Oosterhout, The Netherlands
and produced in the manufacturing plant(s)
A/003
This certificate attests that all provisions concerning the assessment and verification of constancy of performance
described in the
ETA 19/0391, issued on 23/07/2020
and
This certificate was first issued on 12th July 2019 and will remain valid as long as neither the ETA, the EAD, the
construction product, the AVCP methods nor the manufacturing conditions in the plant are modified significantly, unless
suspended or withdrawn by the notified product certification body.
Applicant designation: Bostik BV, Denariusstraat 11, 4903 RC Oosterhout, The Netherlands
Product Information
Manufacturer A/003
This is to certify that representative samples of the Certified Product listed above have been investigated by Underwriters
Laboratories to the Standard(s) indicated on this Certificate, in accordance with the UL Global Services Agreement and the UL-EU
Mark Service Terms and Conditions (“Agreement”). The Certificate Holder is entitled to use the UL-EU Mark for the Certified Product
Authorized Certification Decision Maker listed on the certificate and manufactured at the production site(s) listed, in accordance with the terms of the Agreement. Only
those products bearing the UL-EU Mark for Europe should be considered as being covered by UL’s UL-EU Mark Service. This
Chris Miles Certificate shall remain valid through the Expiration date, unless a Standard identified on this Certificate is amended or withdrawn
prior to that date or there is a non-compliance with the Agreement.
This certificate relates to the use of Bostik FP 330 Pipe Collar for fire stopping where there are service penetrations through floors
and walls. The detailed scope is given in pages 3 to 23 of this Certificate. This shows the thickness and acceptable dimensions,
substrates and orientations required to provide fire resistance periods of up to 240 minutes for differing services and wall/floor
constructions.
The durability class of Bostik FP 330 Pipe Collar is Z2 - intended for use at internal conditions with humidity classes other than
Z1, excluding temperatures below 0°C.
The Bostik FP 330 Pipe Collar may be supplied with powder coated steel or stainless steel shells.
Declaration of manufacturer Content, emission and/or release of Use categories: IA1, S/W3
& EN 16516 dangerous substances Declaration of manufacturer
BWR 4 Safety in use
EOTA TR 001:2003 Mechanical resistance and stability No performance determined
EOTA TR 001:2003 Resistance to impact/movement No performance determined
EOTA TR 001:2003 Adhesion No performance determined
EAD 350454-00-1104,
Durability Z2
Clause 2.2.9
BWR 5 Protection against noise
EN 10140-1,2,4,5/ EN ISO
Airborne sound insulation Rw (C;Ctr): 58 (-1;-7)
717-1
BWR 6 Energy economy and heat retention
EN 12664, EN 12667, EN
12939, EN ISO 8990, EN
ISO 6946, EN ISO 14683, Thermal properties No performance determined
EN ISO 10211, EN ISO
10456
EN ISO 12572, EN 12086,
Water vapour permeability No performance determined
EN ISO 10456
Bostik FP 330 Pipe Collar: Service Penetration Seals in Drywalls and Masonry Walls
Minimum Fire Resistance (mins.)
Wall
Substrate Penetrating Services Seal Position Collar Inlay
Thickness E EI
(mm)
PVC-U pipe according to EN 1329-1, EN 1452-1 and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 32 mm, wall thickness 1.2-3.7 mm*
Diameter 40 mm, wall thickness 1.2-3.7 mm* 30 x 3.0 mm 90 60
Diameter 50 mm, wall thickness 1.2-4.6 mm*
Diameter 55 mm, wall thickness 1.3-4.7 mm* 30 x 3.2 mm
Diameter 63 mm, wall thickness 1.5-5.0 mm* 30 x 3.6 mm
Diameter 75 mm, wall thickness 1.8-5.4 mm* 30 x 4.2 mm
60 60
Diameter 82 mm, wall thickness 2.0-5.6 mm* 30 x 4.6 mm
Diameter 90 mm, wall thickness 2.2-5.9 mm* 30 x 5.0 mm
Diameter 110 mm, wall thickness 2.7-6.6 mm* 30 x 6.0 mm
Diameter 110 mm, wall thickness 2.7-6.6 mm** 50 x 6.0 mm
Diameter 125 mm, wall thickness 2.9-7.4 mm** 50 x 8.8 mm 90 60
Gypsum Diameter 140 mm, wall thickness 3.0-8.3 mm** 50 x 11.5 mm
board/ Diameter 160 mm, wall thickness 3.2-9.5 mm* 50 x 15.0 mm 90 90
100
Masonry/ Diameter 32 mm, wall thickness 2.4-4.6 mm** Both Sides
Concrete
Diameter 40 mm, wall thickness 2.4-4.6 mm** 30 x 3.0 mm
Diameter 50 mm, wall thickness 2.4-4.6 mm**
Diameter 55 mm, wall thickness 2.5-4.7 mm** 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.5-5.0 mm** 50 x 3.6 mm 90 60
Diameter 75 mm, wall thickness 2.6-5.4 mm** 50 x 4.2 mm
Diameter 82 mm, wall thickness 2.6-5.6 mm** 50 x 4.6 mm
Diameter 90 mm, wall thickness 2.6-5.9 mm** 50 x 5.0 mm
Diameter 110 mm, wall thickness 2.7-6.6 mm** 50 x 6.0 mm
Diameter 110 mm, wall thickness 2.7-6.6 mm** 60 x 6.0 mm 90 60
Diameter 125 mm, wall thickness 2.9-7.4 mm** 60 x 9.0 mm
Diameter 140 mm, wall thickness 3.0-8.3 mm** 60 x 11.5 mm 60 60
Diameter 160 mm, wall thickness 3.2-9.5 mm** 60 x 15.0 mm
Diameter 315 mm, wall thickness 9.2 mm~ 75 x 18 mm 60 60
All pipe classifications marked ‘*‘ are pipe end configuration U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘**‘ are pipe end configuration U/U, C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘~‘ are pipe end configuration C/C only - C=Capped
Bostik FP 330 Pipe Collar: Service Penetration Seals in Drywalls and Masonry Walls
Minimum Fire Resistance (mins.)
Wall
Substrate Penetrating Services Seal Position Collar Inlay
Thickness E EI
(mm)
PE pipe according to EN 1519-1, EN 12201-2 and EN 12666-1, ABS according to EN 1455-1 and pipes made from SAN+PVC
according to EN 1565-1
Diameter 32 mm, wall thickness 3.0-4.6 mm**
Diameter 40 mm, wall thickness 3.0-4.6 mm** 90 45
Diameter 50 mm, wall thickness 3.0-4.6 mm**
30 x 3.0 mm
Diameter 32 mm, wall thickness 3.0-5.6 mm*
Diameter 40 mm, wall thickness 3.0-5.6 mm* 90 60
Diameter 50 mm, wall thickness 3.0-5.6 mm*
Diameter 55 mm, wall thickness 3.0-6.0 mm* 30 x 3.2 mm
Diameter 63 mm, wall thickness 3.1-6.6 mm* 30 x 3.6 mm
Diameter 75 mm, wall thickness 3.2-7.5 mm* 30 x 4.2 mm
60 60
Diameter 82 mm, wall thickness 3.2-8.0 mm* 30 x 4.6 mm
Diameter 90 mm, wall thickness 3.3-8.6 mm* 30 x 5.0 mm
Diameter 110 mm, wall thickness 3.4-10.0 mm* 30 x 6.0 mm
Gypsum Diameter 110 mm, wall thickness 3.4-10.0 mm** 50 x 6.0 mm 90 60
board/ Diameter 125 mm, wall thickness 4.2-9.8 mm* 50 x 9.0 mm
100
Masonry/ Diameter 140 mm, wall thickness 5.1-9.6 mm* 50 x 11.5 mm 60 60
Concrete Both Sides
Diameter 160 mm, wall thickness 6.2-9.5 mm* 50 x 15.0 mm
Diameter 32 mm, wall thickness 3.0-4.6 mm**
Diameter 40 mm, wall thickness 3.0-4.6 mm** 120 90
50 x 3.0 mm
Diameter 50 mm, wall thickness 3.0-4.6 mm**
Diameter 55 mm, wall thickness 3.1-5.0 mm** 50 x 3.2 mm
Diameter 63 mm, wall thickness 3.1-5.7 mm** 50 x 3.6 mm
Diameter 75 mm, wall thickness 3.2-6.8 mm** 50 x 4.2 mm 90 60
Diameter 82 mm, wall thickness 3.2-7.4 mm** 50 x 4.6 mm
Diameter 90 mm, wall thickness 3.3-8.1 mm** 50 x 5.0 mm
Diameter 110 mm, wall thickness 3.4-10.0 mm** 60 x 6.0 mm
Diameter 125 mm, wall thickness 4.0-11.5 mm** 60 x 8.8 mm 90 60
Diameter 140 mm, wall thickness 4.4-12.8 mm** 60 x 11.5 mm
Diameter 160 mm, wall thickness 4.9-14.6 mm** 60 x 15.0 mm 90 90
Diameter 200 mm, wall thickness 18.2 mm~ 75 x 10.8 mm
60 60
Diameter 250 mm, wall thickness 22.7 mm~ 75 x 12.6 mm
All pipe classifications marked ‘*‘ are pipe end configuration U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘**‘ are pipe end configuration U/U, C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘~‘ are pipe end configuration C/C only - C=Capped
Bostik FP 330 Pipe Collar: Service Penetration Seals in Drywalls and Masonry Walls
Minimum Fire Resistance (mins.)
Wall
Substrate Penetrating Services Seal Position Collar Inlay
Thickness E EI
(mm)
PP pipe according to EN 1451-1
Diameter 32 mm, wall thickness 3.0-5.6 mm*
Diameter 40 mm, wall thickness 3.0-5.6 mm* 30 x 3.0 mm 90 60
Diameter 50 mm, wall thickness 3.0-5.6 mm*
Diameter 32 mm, wall thickness 1.8-4.6 mm**
Diameter 40 mm, wall thickness 1.8-4.6 mm** 30 x 3.0 mm 90 60
Diameter 50 mm, wall thickness 1.8-4.6 mm**
Diameter 50 mm, wall thickness 1.8-5.6 mm* 30 x 3.0 mm
Diameter 55 mm, wall thickness 2.0-5.7 mm* 30 x 3.2 mm
Diameter 63 mm, wall thickness 2.2-5.8 mm* 30 x 3.6 mm
Diameter 75 mm, wall thickness 2.5-5.9 mm* 30 x 4.2 mm 90 60
Diameter 82 mm, wall thickness 2.7-6.0 mm* 30 x 4.6 mm
Diameter 90 mm, wall thickness 2.9-6.1 mm* 30 x 5.0 mm
Diameter 110 mm, wall thickness 3.4-6.3 mm* 30 x 6.0 mm
Diameter 50 mm, wall thickness 1.8-5.6 mm* 50 x 3.0 mm 90 60
Diameter 55 mm, wall thickness 2.0-6.0 mm* 50 x 3.2 mm
Gypsum Diameter 63 mm, wall thickness 2.2-6.6 mm* 50 x 3.6 mm
board/
100 Diameter 75 mm, wall thickness 2.5-7.6 mm* 50 x 4.2 mm
Masonry/ Both Sides
Concrete Diameter 82 mm, wall thickness 2.7-8.2 mm* 50 x 4.6 mm
Diameter 90 mm, wall thickness 2.9-8.9 mm* 50 x 5.0 mm 60 60
Diameter 110 mm, wall thickness 3.4-10.5 mm* 50 x 6.0 mm
Diameter 125 mm, wall thickness 3.8-11.7 mm* 50 x 8.8 mm
Diameter 140 mm, wall thickness 4.2-12.9 mm* 50 x 11.5 mm
Diameter 160 mm, wall thickness 4.9-14.6 mm* 50 x 15.0 mm
Diameter 50 mm, wall thickness 1.8-4.6 mm** 50 x 3.0 mm
Diameter 55 mm, wall thickness 2.0-4.7 mm** 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.2-5.0 mm** 50 x 3.6 mm
Diameter 75 mm, wall thickness 2.5-5.4 mm** 50 x 4.2 mm 90 60
Diameter 82 mm, wall thickness 2.7-5.6 mm** 50 x 4.6 mm
Diameter 90 mm, wall thickness 2.9-5.9 mm** 50 x 5.0 mm
Diameter 110 mm, wall thickness 3.4-6.6 mm** 50 x 6.0 mm
Diameter 110 mm, wall thickness 3.4-6.6 mm** 60 x 6.0 mm 90 60
Diameter 125 mm, wall thickness 3.9-9.0 mm** 60 x 9.0 mm
Diameter 140 mm, wall thickness 4.4-11.4 mm** 60 x 11.5 mm 60 60
Diameter 160 mm, wall thickness 4.9-14.6 mm** 60 x 15.0 mm
All pipe classifications marked ‘*‘ are pipe end configuration U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘**‘ are pipe end configuration U/U, C/U, U/C and C/C - U=Uncapped, C=Capped
Bostik FP 330 Pipe Collar: Service Penetration Seals in Drywalls and Masonry Walls
Minimum Fire Resistance (mins.)
Wall
Substrate Penetrating Services Seal Position Collar Inlay
Thickness E EI
(mm)
Wavin SiTech + PP-M B according to EN 13501-1
32-40 mm diameter/ 1.8 mm wall thickness* 50 x 3.0 mm
120 120
50 mm diameter/ 1.8 mm wall thickness * 50 x 3.2 mm
75 mm diameter/ 1.8-2.5 mm wall thickness* Both Sides 50 x 4.2 mm
90 mm diameter/ 1.8-2.9 mm wall thickness* 50 x 5.0 mm 120 60
110 mm diameter/ 1.8-3.4 mm wall thickness * 50 x 6.0 mm
Aquatherm Green SDR9 MF PP-RP according to ISO 21003
32 mm diameter/3.0-5.6 mm wall thickness** 30 x 3.0 mm
40 mm diameter/3.0-5.6 mm wall thickness** 50 x 3.0 mm 120 120
50 mm diameter/3.0-5.6 mm wall thickness** 50 x 3.2 mm
63 diameter/3.6-7.0 mm wall thickness** Both Sides 50 x 3.6 mm
75 diameter/4.1-8.4 mm wall thickness** 50 x 4.2 mm
120 60
90 diameter/4.7-10.1 mm wall thickness** 50 x 5.0 mm
110 diameter/5.6-12.3 mm wall thickness** 50 x 6.0 mm
Geberit Silent PP according to DIN 4102
32-50 mm diameter/ 1.8 mm wall thickness* 50 x 3.0 mm 120 120
Gypsum
75 mm diameter/1.8-2.5 mm wall thickness* 50 x 4.2 mm
board/ Both Sides
100 90 mm diameter/1.8-2.9 mm wall thickness* 50 x 5.0 mm 120 60
Masonry/
Concrete 110 mm diameter/1.8-3.4 mm wall thickness* 50 x 6.0 mm
Polo-Kal NG Poloplast PP-MV according to DIN 4102
32-40 mm diameter/1.8-2.0 mm wall thickness* 50 x 3.0 mm
120 120
50 mm diameter/1.8-2.0 mm wall thickness* 50 x 3.2 mm
75 mm diameter/1.9-2.6 mm wall thickness* 50 x 4.2 mm
90 mm diameter/1.9-2.9 mm wall thickness* Both Sides 50 x 5.0 mm 120 90
110 mm diameter/2.0-3.4 wall thickness* 50 x 6.0 mm
Diameter 125 mm, wall thickness 3.9 mm* 60 x 9.0 mm 120 120
Diameter 160 mm, wall thickness 4.9 mm* 60 x 15 mm 120 120
Rehau Raupiano Plus PP-DD according to DIN 4102
40 mm diameter/1.8 mm wall thickness* 50 x 3.0 mm
120 90
50 mm diameter/1.8 mm wall thickness* 50 x 3.2 mm
75 mm diameter/1.8-2.2 mm wall thickness* 50 x 4.2 mm
90 mm diameter/1.8-2.4 mm wall thickness* Both Sides 50 x 5.0 mm 120 60
110 mm diameter/1.8-2.7 mm wall thickness* 50 x 6.0 mm
Diameter 125 mm, wall thickness 3.1 mm* 60 x 9.0 mm
120 120
Diameter 160 mm, wall thickness 3.9 mm* 60 x 15.0 mm
All pipe classifications marked ‘*‘ are pipe end configuration U/U, C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘**‘ are pipe end configuration C/C only - C=Capped
Bostik FP 330 Pipe Collar: Service Penetration Seals in Drywalls and Masonry Walls
Minimum Fire Resistance (mins.)
Wall
Substrate Penetrating Services Seal Position Collar Inlay
Thickness E EI
(mm)
BluePower Multilayer pipe – TR02-PP according to
EN 1451-1
32-40 mm diameter/1.8 mm wall thickness** 50 x 3.0 mm
Gypsum 120 90
board/ 50 mm diameter/1.8 mm wall thickness** 50 x 3.2 mm
100 75 mm diameter/1.8-2.5 mm wall thickness* 50 x 4.2 mm
Masonry/
Concrete 90 mm diameter/1.8-2.9 mm wall thickness* Both Sides 50 x 5.0 mm 120 60
110 mm diameter/1.8-3.4 mm wall thickness* 50 x 6.0 mm
125 mm diameter/2.3-3.8 mm wall thickness* 60 x 9.0 mm 60 60
160 mm diameter/3.4-4.9 mm wall thickness* 60 x 15.0 mm 90 90
All pipe classifications marked ‘*‘ are pipe end configuration C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘**‘ are pipe end configuration U/U, C/U, U/C and C/C - U=Uncapped, C=Capped
Bostik FP 330 Pipe Collar: Service Penetration Seals in Drywalls and Masonry Walls
Minimum Fire Resistance (mins.)
Wall
Substrate Penetrating Services Seal Position Collar Inlay
Thickness E EI
(mm)
PVC-U pipe according to EN 1329-1, EN 1452-1 and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 32-50 mm, wall thickness 2.4-3.7 mm 50 x 3.0 mm
Diameter 55 mm, wall thickness 2.4-3.9 mm 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.5-4.3 mm 50 x 3.6 mm
Diameter 75 mm, wall thickness 2.5-4.9 mm 50 x 4.2 mm 120 120
Diameter 82 mm, wall thickness 2.6-5.2 mm 50 x 4.6 mm
Diameter 90 mm, wall thickness 2.6-5.6 mm Both Sides 50 x 5.0 mm
Diameter 110 mm, wall thickness 2.7-6.6 mm 50 x 6.0 mm
Diameter 125 mm, wall thickness 3.1-7.5 mm 60 x 8.8 mm
Diameter 140 mm, wall thickness 3.5-8.4 mm 60 x 11.5 mm 120 120
Diameter 160 mm, wall thickness 4.0-9.5 mm 60 x 15.0 mm
Diameter 50 mm, wall thickness 2.4 mm # 60 x 15.0 mm 90 90
PE pipe according to EN 1519-1, EN 12201-2 and EN 12666-1, ABS according to EN 1455-1 and pipes made from SAN+PVC
according to EN 1565-1
Diameter 32-50 mm, wall thickness 3.0-4.6 mm 50 x 3.0 mm 120 120
Diameter 55 mm, wall thickness 3.1-5.0 mm 50 x 3.2 mm
Diameter 63 mm, wall thickness 3.1-5.7 mm 50 x 3.6 mm
Gypsum Diameter 75 mm, wall thickness 3.2-6.8 mm 50 x 4.2 mm
board/ 120 90
120 Diameter 82 mm, wall thickness 3.2-7.5 mm 50 x 4.6 mm
Masonry/
Concrete Diameter 90 mm, wall thickness 3.3-8.2 mm 50 x 5.0 mm
Both Sides
Diameter 110 mm, wall thickness 3.4-10.0 mm 50 x 6.0 mm
Diameter 110 mm, wall thickness 3.4 mm 50 x 6.0 mm 120 120
Diameter 125 mm, wall thickness 3.9-9.8 mm 60 x 8.8 mm
Diameter 140 mm, wall thickness 4.4-9.7 mm 60 x 11.5 mm 90 90
Diameter 160 mm, wall thickness 4.9-9.5 mm 60 x 15.0 mm
Diameter 160 mm, wall thickness 9.5 mm 60 x 15.0 mm 120 120
PP pipe according to DIN 8077/8078
Diameter 32-50 mm, wall thickness 2.9-4.6 mm 50 x 3.0 mm 120 120
Diameter 55 mm, wall thickness 2.9-5.0 mm 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.9-5.7 mm 50 x 3.6 mm
Diameter 75 mm, wall thickness 2.8-6.8 mm 50 x 4.2 mm
120 90
Diameter 82 mm, wall thickness 2.8-7.5 mm 50 x 4.6 mm
Both Sides
Diameter 90 mm, wall thickness 2.8-8.2 mm 50 x 5.0 mm
Diameter 110 mm, wall thickness 2.7-10 mm 50 x 6.0 mm
Diameter 125 mm, wall thickness 3.3-11.3 mm 60 x 8.8 mm
120 90
Diameter 140 mm, wall thickness 4.0-12.8 mm 60 x 11.5 mm
Diameter 160 mm, wall thickness 4.9-14.6 mm 60 x 15.0 mm 120 120
All pipe classifications are pipe end configuration C/C only - C=Capped
#Pipe fitted at 45° to the face of the partition in a horizontal plane
Bostik FP 330 Pipe Collar: Service Penetration Seals in Drywalls and Masonry Walls
Minimum Fire Resistance
Wall Seal (mins.)
Substrate Penetrating Services Collar Collar Inlay
Thickness Position
E EI
(mm)
Cables up to 21 mm Ø, in partial or fully filled
Up to 110 mm collar Between 3.0
tied bundles up to 110 mm Ø (Collar internal 120 60
at 30 mm height and 6.0 mm
diameter to match cable bundle size)
Up to 110 mm collar
Cables up to 80 mm Ø, in partial or fully filled
at 50 mm height, Between 3.0
tied bundles up to 160 mm Ø (Collar internal 120 60
125-160 mm at 60 and 15.0 mm
diameter to match cable bundle size) Both Sides
Gypsum mm height
board/ None (blank). Hole behind collar to be fitted with
120 Up to 110 mm collar Between 3.0
Masonry/ minimum 25 mm thick stone mineral wool 120 60
Concrete at 30 mm height and 6.0 mm
insulation at minimum 33 kg/m3.
None (blank). Hole behind collar to be fitted with
160 mm collar at 60
minimum 25 mm thick stone mineral wool 15.0 mm 120 120
mm height
insulation at minimum 33 kg/m3.
Uponor Aqua PEX pipe in pipe system
Diameter up to 25 mm pipes, wall thickness 0.6 55 mm collar at 30
Both Sides 3.2 mm 120 90
mm, in bundles up to 55 mm mm height
Bostik FP 330 Pipe Collar: Service Penetration Seals in Drywalls and Masonry Walls
Minimum Fire Resistance
Wall Seal (mins.)
Substrate Penetrating Services Collar Service Insulation
Thickness Position
E EI
(mm)
Copper pipe or mild steel
19 mm thick
Ø 110 x 50 x Elastomeric
Gypsum Diameter 54 mm, wall thickness 1.2 mm 120 90
6.0 mm insulation minimum
board/ class B-s3,d0
120
Masonry/ Both Sides Ø 110 x 50 x 25 mm thick
Concrete Diameter 54 mm, wall thickness 1.2 mm 6.0 mm Phenolic Foam 120 60
insulation
Ø 110 x 50 x 20 mm thick PE
Diameter 54 mm, wall thickness 1.2 mm 120 90
6.0 mm foam insulation
All pipe classifications are pipe end configuration C/C only - C=Capped
Bostik FP 330 Pipe Collar: Service Penetration Seals Comprising 1x 50 mm Bostik FP 320 Fire Batt
2-S in Drywalls and Masonry Walls - Maximum aperture size 1200 mm x 600 mm
Minimum Fire Resistance (mins.)
Wall
Substrate Penetrating Services Seal Position Collar Inlay
Thickness E EI
(mm)
PVC-U pipe according to EN 1329-1, EN 1452-1 and EN 1453-1 and PVC-C according to EN 1566-1
32-50 mm diameter / 1.9-3.7 mm wall thickness* 50 x 3.0 mm 120 60
55 mm, / 1.9-4.0 mm wall thickness* 50 x 3.2 mm
63 mm, / 2.0-4.4 mm wall thickness* 50 x 3.6 mm
75 mm, / 2.2-4.9 mm wall thickness* Both Sides 50 x 4.2 mm
90 60
82 mm, / 2.3-5.3 mm wall thickness* 50 x 4.6 mm
90 mm, / 2.4-5.7 mm wall thickness* 50 x 5.0 mm
Gypsum
110 mm diameter / 2.7-6.6 mm wall thickness* 50 x 6.0 mm
board/
120 PE pipe according to EN 1519-1, EN 12201-2 and EN 12666-1, ABS according to EN 1455-1 and pipes made from SAN+PVC
Masonry/
Concrete according to EN 1565-1
32-50 mm diameter / 3.0-4.6 mm wall thickness* 50 x 3.0 mm 120 60
55 mm, / 3.0-5.2 mm wall thickness** 50 x 3.2 mm
63 mm, / 3.0-5.9 mm wall thickness** 50 x 3.6 mm
75 mm, / 3.1-6.9 mm wall thickness** Both Sides 50 x 4.2 mm
90 60
82 mm, / 3.1-7.6 mm wall thickness** 50 x 4.6 mm
90 mm, / 3.2-8.3 mm wall thickness** 50 x 5.0 mm
110 mm, / 3.4-10.0 mm wall thickness** 50 x 6.0 mm
All pipe classifications marked ‘*‘ are pipe end configuration U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘**‘ are pipe end configuration C/C only - C=Capped
All pipe classifications marked ‘*‘ are pipe end configuration U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘**‘ are pipe end configuration U/U, C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘~‘ are pipe end configuration C/C only - C=Capped
All pipe classifications marked ‘*‘ are pipe end configuration U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘**‘ are pipe end configuration U/U, C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘*‘ are pipe end configuration U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘**‘ are pipe end configuration U/U, C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘*‘ are pipe end configuration U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘**‘ are pipe end configuration U/U, C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘~‘ are pipe end configuration C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘*‘ are pipe end configuration U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘**‘ are pipe end configuration U/U, C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘*‘ are pipe end configuration U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘**‘ are pipe end configuration U/U, C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘~‘ are pipe end configuration C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘^‘ are pipe end configuration C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘*‘ are pipe end configuration U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘**‘ are pipe end configuration U/U, C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications marked ‘~ ‘ are pipe end configuration C/U, U/C and C/C - U=Uncapped, C=Capped
All pipe classifications are pipe end configuration C/C - U=Uncapped, C=Capped
All pipe classifications are pipe end configuration C/C - U=Uncapped, C=Capped
All pipe classifications are pipe end configuration U/C and C/C - U=Uncapped, C=Capped
All pipe classifications are pipe end configuration U/C and C/C - U=Uncapped, C=Capped
The minimum height of the registered trademark symbol ® shall be 1 mm. When the overall diameter of
the UL-EU Mark is less than 9.5 mm, the trademark symbol may be omitted if it is not legible to the naked
eye.
The UL-EU Mark may appear on a label, nameplate, or may be cast, stamped or molded into the product.
When appearing on a label or nameplate, the Manufacturer’s name or trademark along with a model
number are also required on that same label or nameplate. If cast, stamped or molded, the Manufacturer’s
name or trademark and model number shall also appear elsewhere on the product.
All content shall be in accordance with the details provided on this UL-EU Certificate.
PROCUREMENT
The Production site may reproduce the Mark or obtain it from a UL authorized supplier. The list of UL
authorized suppliers can be found on UL’s online directory at www.ul.com.
In compliance with Regulation 305/2011/EU of the European Parliament and of the Council of 9 March 2011 (the Construction
Products Regulation or CPR), this certificate applies to the construction product
This certificate attests that all provisions concerning the assessment and verification of constancy of performance described
in the
under system 1 for the performance set out in the ETA are applied and that the factory production control conducted by
the Manufacturer is assessed to ensure the
Constancy of performance of the construction product.
This certificate will remain valid as long as neither the ETA, the EAD, the construction product, the AVCP methods nor the
manufacturing conditions in the plant are modified significantly unless suspended or withdrawn by the notified product
certification body.
This European Technical 103 pages including 2 annexes which form an integral
Assessment contains: part of the document
Translations of this European Technical Assessment in other languages shall fully correspond to the original issued document and should be
identified as such.
Communication of this European Technical Assessment, including transmission by electronic means, shall be in full. However, partial
reproduction may be made, with the written consent of the issuing Technical Assessment Body. Any partial reproduction has to be identified
as such.
Page 3 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
Table of Contents
1) Bostik FP 330 Pipe Collar is a pipe closure device used to form penetration seals where combustible pipes,
cables and metal pipes with insulation penetrate walls and floors.
2) The Bostik FP 330 Pipe Collar is supplied with intumescent liner complete within metal steel shell, to be
clamped around the service and screw fixed back to the supporting element. The Bostik FP 330 Pipe Collar
may be supplied with powder coated steel or stainless steel shells.
3) In flexible walls, gaps between the pipe and the construction below 8mm must have a bead of Bostik FP
310 Intumescent Acoustic Acrylic to cover the opening, and for gaps 8mm or above, the seal must be
plugged with 25mm deep Bostik FP 310 Intumescent Acoustic Acrylic.
In rigid walls, gaps between the pipe and the construction below 8mm must have a bead of Bostik FP 310
Intumescent Acoustic Acrylic to cover the opening, and for gaps 8mm or above, the seal must be plugged
with 20mm deep Bostik FP 310 Intumescent Acoustic Acrylic on 20mm deep backing of stonewool.
In floors, gaps between the pipe and the construction below 10mm must have 20mm deep stonewool to
plug the opening, and for gaps 10mm or above, the seal must be plugged with 10mm deep Bostik FP 310
Intumescent Acoustic Acrylic on 40mm deep backing of stonewool. For collars installed on top side of floors,
gaps between the pipe and the top side of the collar must have a bead of Bostik FP 310 Intumescent
Acoustic Acrylic to cover the opening.
Bostik FP 330 Pipe Collar are oversized to allow for the natural gradient of pipework for flow purposes and
inconsistencies of pipe installation.
4) The applicant has submitted a written declaration that the product and/or constituents of the product
contains no substances which have been classified as dangerous according to Directive 67/548/EEC and
Regulation (EC) No. 1272/2008 and listed in the ‘indicative list on dangerous substances’ of the EGDS –
taking into account the installation conditions of the construction product and the release scenarios
resulting from there.
In addition to the specific clauses relating to dangerous substances contained in this European Technical
Assessment, there may be other requirements applicable to the products falling within its scope (e.g.
transposed European legislation and national laws, regulations and administrative provisions). In order to
meet the provisions of the Construction Products Regulation, these requirements need also to be complied
with, when and where they apply.
5) The use category of Bostik FP 330 Pipe Collar in relation to BWR 3 (Hygiene, health and environment) is IA1,
S/W2
Page 5 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
2 Specification of the intended uses of the product in accordance with the applicable European Assessment
Document (Hereinafter EAD): EAD 350454-00-1104
The intended use of system Bostik FP 330 Pipe Collar is to reinstate the fire resistance performance of
flexible wall and rigid wall and floor constructions, where they are penetrated by services.
1) The specific elements of construction that the system Bostik FP 330 Pipe Collar may be used to
provide a penetration seal in, are as follows:
a. Flexible walls: The wall must have a minimum thickness of 75 mm and comprise steel
studs or timber studs* lined on both faces with minimum 1 layer of 12.5
mm thick boards.
b. Timber walls: The wall must have a minimum thickness of 100 mm and comprise solid
wood or cross-laminated timber.
c. Rigid walls: The wall must have a minimum thickness of 75 mm and comprise
concrete, aerated concrete or masonry, with a minimum density of 650
kg/m3.
d. Rigid floors: The floor must have a minimum thickness of 150 mm and comprise
aerated concrete or concrete with a minimum density of 650 kg/m3.
e. Timber floors: The floor must have a minimum thickness of 150 mm and comprise solid
wood or cross-laminated timber.
* no part of the penetration seal may be closer than 100 mm to a stud, the cavity must be closed
between the penetration seal and the stud, and minimum 100 mm of insulation of class A1 or A2
according to EN 13501-1 must be provided within the cavity between the penetration seal and the
stud.
The supporting construction must be classified in accordance with EN 13501-2 for the required
fire resistance period.
Bostik FP Fire Protection Systems which involve services penetrating both sides of a flexible wall
may also be used in the situation where the services penetrates one side of the wall only and the
remaining side of the wall is not penetrated at the same point (i.e. the services continues on the
inside of the wall). All fire integrity and thermal insulation ratings for such single-sided
penetrations remain the same as for the equivalent double-sided penetration.
2) The system Bostik FP 330 Pipe Collar may be used to provide a penetration seal with specific
supporting constructions and substrates (for details see Annex A).
3) Where single sided top face seals are described in Annex A, these can also be used in composite
floors.
4) Where PP pipes are mentioned in Annex A, this includes PP-MV, PP-H, PP-R and similar if the pipe
is according to EN 1451-1 or DIN 8077/8078. Where PE pipes are mentioned, this includes PE-LD,
PE-MD, PE-HD, PE-X and similar according to EN 1519-1, EN 12201-2 or EN 12666-1.
5) Solutions in Annex A for 100 mm thick flexible walls and 150 mm thick rigid floors, can be used in
timber walls limited to EI 90, and in timber floors limited to EI 120 (see 2.1). In timber walls and
floors, gaps between the pipe and the construction must be plugged with 25 mm deep Bostik FP
310 Intumescent Acoustic Acrylic on 25 mm deep backing of stone-wool on both sides before
collars are attached, with minimum 80 mm long wood screws in walls, and 100 mm long wood
screws in floors. The minimum annular gap must be 10 mm wide, and the maximum aperture sizes
must be Ø 180 mm in walls and Ø 220 mm in floors. For larger apertures, the annular gap must be
10 mm (+/- 2 mm).
Page 6 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
6) The provisions made in this European Technical Assessment are based on an assumed working life
of the Bostik FP 330 Pipe Collar of 30 years, provided that the conditions laid down in the
manufacturers datasheet and instructions for the packaging/transport/storage/installation/
use/repair are met. The indications given on the working life cannot be interpreted as a guarantee
given by the producer or the Technical Assessment Body but are to be regarded only as a means
for choosing the right products in relation to the expected economically reasonable working life of
the works.
7) Type Z2: intended for use at internal conditions with humidity classes other than Z 1, excluding
temperatures below 0°C.
Page 7 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
3 Performance of the product and references to the methods used for its assessment
Product-type: Pipe Collar Intended use: Penetration Seal
According to the decision 1999/454/EC – Commission Decision of date 22nd June 1999 on the procedure for
attesting the conformity of construction products pursuant to Article 20(2) of Council Directive 89/106/EEC as
regards fire stopping, fire sealing and fire protective products, published in the Official Journal of the European
Union (OJEU) L178/52 of 14/07/1999, (see https://eur-lex.europa.eu/oj/direct-access.html) of the European
Commission1, as amended, the system(s) of assessment and verification of constancy of performance (see
Annex V to Regulation (EU) No 305/2011) given in the following table(s) applies (apply).
5 Technical details necessary for the implementation of the AVCP system, as provided for in the applicable
EAD
Technical details necessary for the implementation of the AVCP system are laid down in the control plan
deposited at ETA-Danmark A/S prior to CE marking
Thomas Bruun
1
Official Journal of the European Communities L178/52 of 14/7/1999
Page 9 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
Construction details:
Page 10 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.1.1.1
A.1.2
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes made
from SAN+PVC according to EN 1565-1
Diameter 32 mm, wall thickness 3.0-4.6 mm
Diameter 40 mm, wall thickness 3.0-4.6 mm 30 x 3.0 mm
Diameter 50 mm, wall thickness 3.0-4.6 mm
Diameter 55 mm, wall thickness 3.0-5.0 mm* 30 x 3.2 mm E 60 U/C, E 60 C/C
Diameter 63 mm, wall thickness 3.1-5.8 mm* 30 x 3.6 mm EI 30 U/C, EI 30 C/C
Diameter 110 mm, wall thickness 3.4-10.0 mm* 30 x 6.0 mm EI 60 U/C, EI 60 C/C
Diameter 125 mm, wall thickness 4.2-9.8 mm* 60 x 8.8 mm
E 60 U/C, E 60 C/C
Diameter 140 mm, wall thickness 5.1-9.6 mm* 60 x 11.5 mm
EI 45 U/C, EI 45 C/C
Diameter 160 mm, wall thickness 6.2-9.5 mm* 60 x 15.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 13 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
Page 14 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.1.3
A.2 Flexible or rigid wall constructions with wall thickness of minimum 100 mm
A.2.1 Penetration seals, in drywalls and concrete/masonry walls
Penetration Seal: Combustible pipes fitted with Bostik FP 330 Pipe Collar, to both sides of the wall.
Construction details:
A.2.1.1.1
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 32 mm, wall thickness 1.2-3.7 mm
E 90 U/C, E 90 C/C
Diameter 40 mm, wall thickness 1.2-3.7 mm 30 x 3.0 mm
EI 60 U/C, EI 60 C/C
Diameter 50 mm, wall thickness 1.2-4.6 mm*
Diameter 55 mm, wall thickness 1.3-4.7 mm* 30 x 3.2 mm
Diameter 63 mm, wall thickness 1.5-5.0 mm* 30 x 3.6 mm
A.2.1.1.2
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 110 mm, wall thickness 2.7-6.6 mm* 50 x 6.0 mm E 90 U/U, E 90 C/U,
E 90 U/C, E 90 C/C
Diameter 125 mm, wall thickness 2.9-7.4 mm* 50 x 8.8 mm
EI 60 U/U, EI 60 C/U,
Diameter 140 mm, wall thickness 3.0-8.3 mm* 50 x 11.5 mm EI 60 U/C, EI 60 C/C
Diameter 160 mm, wall thickness 3.2-9.5 mm* 50 x 15.0 mm EI 90 U/C, EI 90 C/C
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 19 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.2.1.1.3
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 32 mm, wall thickness 2.4-4.6 mm
Diameter 40 mm, wall thickness 2.4-4.6 mm 30 x 3.0 mm
Diameter 50 mm, wall thickness 2.4-4.6 mm
Diameter 55 mm, wall thickness 2.5-4.7 mm* 50 x 3.2 mm E 90 U/U, E 90 C/U,
Diameter 63 mm, wall thickness 2.5-5.0 mm* 50 x 3.6 mm E 90 U/C, E 90 C/C
EI 60 U/U, EI 60 C/U,
Diameter 75 mm, wall thickness 2.6-5.4 mm* 50 x 4.2 mm EI 60 U/C, EI 60 C/C
Diameter 82 mm, wall thickness 2.6-5.6 mm* 50 x 4.6 mm
Diameter 90 mm, wall thickness 2.6-5.9 mm* 50 x 5.0 mm
Diameter 110 mm, wall thickness 2.7-6.6 mm* 50 x 6.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 20 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.2.1.1.4
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
E 90 U/U, E 90 C/U,
E 90 U/C, E 90 C/C
Diameter 110 mm, wall thickness 2.7-6.6 mm* 60 x 6.0 mm
EI 60 U/U, EI 60 C/U,
EI 60 U/C, EI 60 C/C
Diameter 125 mm, wall thickness 2.9-7.4 mm* 60 x 9.0 mm
Diameter 140 mm, wall thickness 3.0-8.3 mm* 60 x 11.5 mm EI 60 U/U, EI 60 C/U
Diameter 160 mm, wall thickness 3.2-9.5 mm* 60 x 15.0 mm
Diameter 200 mm, wall thickness 4.9-11.9 mm* 60 x 18 mm EI 120 U/C, EI 120 C/C
A.2.1.2
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes made
from SAN+PVC according to EN 1565-1
Diameter 32 mm, wall thickness 3.0-4.6 mm E 90 U/U, E 90 C/U,
E 90 U/C, E 90 C/C
Diameter 40 mm, wall thickness 3.0-4.6 mm
EI 45 U/U, EI 45 C/U,
Diameter 50 mm, wall thickness 3.0-4.6 mm EI 45 U/C, EI 45 C/C
30 x 3.0 mm
Diameter 32 mm, wall thickness 3.0-5.6 mm
E 90 U/C, E 90 C/C
Diameter 40 mm, wall thickness 3.0-5.6 mm
EI 60 U/C, EI 60 C/C
Diameter 50 mm, wall thickness 3.0-5.6 mm*
Diameter 55 mm, wall thickness 3.0-6.0 mm* 30 x 3.2 mm
Diameter 63 mm, wall thickness 3.1-6.6 mm* 30 x 3.6 mm
A.2.1.2.1
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes made
from SAN+PVC according to EN 1565-1
Diameter 110 mm, wall thickness 3.4-10.0 mm* 50 x 6.0 mm E 90 U/U, E 90 C/U,
E 90 U/C, E 90 C/C
EI 60 U/U, EI 60 C/U,
EI 60 U/C, EI 60 C/C
Diameter 125 mm, wall thickness 4.2-9.8 mm* 50 x 9.0 mm
Diameter 140 mm, wall thickness 5.1-9.6 mm* 50 x 11.5 mm EI 60 U/C, EI 60 C/C
Diameter 160 mm, wall thickness 6.2-9.5 mm* 50 x 15.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 23 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.2.1.2.2
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes made
from SAN+PVC according to EN 1565-1
Diameter 32 mm, wall thickness 3.0-4.6 mm
Diameter 40 mm, wall thickness 3.0-4.6 mm 50 x 3.0 mm E 120 U/U, EI 90 U/U
Diameter 50 mm, wall thickness 3.0-4.6 mm*
Diameter 55 mm, wall thickness 3.1-5.0 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 3.1-5.7 mm* 50 x 3.6 mm
E 90 U/U, E 90 C/U,
Diameter 75 mm, wall thickness 3.2-6.8 mm* 50 x 4.2 mm
E 90 U/C, E 90 C/C
Diameter 82 mm, wall thickness 3.2-7.4 mm* 50 x 4.6 mm EI 60 U/U, EI 60 C/U,
EI 60 U/C, EI 60 C/C
Diameter 90 mm, wall thickness 3.3-8.1 mm* 50 x 5.0 mm
Diameter 110 mm, wall thickness 3.4-10.0 mm* 50 x 6.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 24 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.2.1.2.3
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes made
from SAN+PVC according to EN 1565-1
Diameter 110 mm, wall thickness 3.4-10.0 mm* 60 x 6.0 mm E 90 U/U, E 90 C/U,
E 90 U/C, E 90 C/C
Diameter 125 mm, wall thickness 4.0-11.5 mm* 60 x 8.8 mm
EI 60 U/U, EI 60 C/U,
Diameter 140 mm, wall thickness 4.4-12.8 mm* 60 x 11.5 mm EI 60 U/C, EI 60 C/C
EI 90 U/U, EI 90 C/U,
Diameter 160 mm, wall thickness 4.9-14.6 mm* 60 x 15.0 mm
EI 90 U/C, EI 90 C/C
E 120 U/C, E 120 C/C
Diameter 200 mm, wall thickness 6.2-18.2 mm* 60 x 18.0 mm
EI 90 U/C, EI 90 C/C
Diameter 400 mm, wall thickness 36.3 mm* 100 x 40.0 mm EI 90 C/C
* Typical pipe diameters shown, see below graphs for intermediate sizes
Page 25 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.2.1.3
Services Collar Inlay Classification
PP pipe according to EN 1451-1
Diameter 32 mm, wall thickness 3.0-5.6 mm
E 90 U/C, E 90 C/C
Diameter 40 mm, wall thickness 3.0-5.6 mm 30 x 3.0 mm
EI 60 U/C, EI 60 C/C
Diameter 50 mm, wall thickness 3.0-5.6 mm
Diameter 32 mm, wall thickness 1.8-4.6 mm E 90 U/U, E 90 C/U,
E 90 U/C, E 90 C/C
Diameter 40 mm, wall thickness 1.8-4.6 mm 30 x 3.0 mm
EI 60 U/U, EI 60 C/U,
Diameter 50 mm, wall thickness 1.8-4.6 mm EI 60 U/C, EI 60 C/C
Diameter 50 mm, wall thickness 1.8-5.6 mm* 30 x 3.0 mm
Diameter 55 mm, wall thickness 2.0-5.7 mm* 30 x 3.2 mm
Diameter 63 mm, wall thickness 2.2-5.8 mm* 30 x 3.6 mm
Diameter 75 mm, wall thickness 2.5-5.9 mm* 30 x 4.2 mm E 90 U/C, E 90 C/C
EI 60 U/C, EI 60 C/C
Diameter 82 mm, wall thickness 2.7-6.0 mm* 30 x 4.6 mm
Diameter 90 mm, wall thickness 2.9-6.1 mm* 30 x 5.0 mm
Diameter 110 mm, wall thickness 3.4-6.3 mm* 30 x 6.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 26 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.2.1.3.1
Services Collar Inlay Classification
PP pipe according to EN 1451-1
50 x 3.0 mm E 90 U/C, E 90 C/C
Diameter 50 mm, wall thickness 1.8-5.6 mm*
EI 60 U/C, EI 60 C/C
Diameter 55 mm, wall thickness 2.0-6.0 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.2-6.6 mm* 50 x 3.6 mm
Diameter 75 mm, wall thickness 2.5-7.6 mm* 50 x 4.2 mm
Diameter 82 mm, wall thickness 2.7-8.2 mm* 50 x 4.6 mm
EI 60 U/C, EI 60 C/C
Diameter 90 mm, wall thickness 2.9-8.9 mm* 50 x 5.0 mm
Diameter 110 mm, wall thickness 3.4-10.5 mm* 50 x 6.0 mm
A.2.1.3.2
Services Collar Inlay Classification
PP pipe according to EN 1451-1
Diameter 50 mm, wall thickness 1.8-4.6 mm* 50 x 3.0 mm
Diameter 55 mm, wall thickness 2.0-4.7 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.2-5.0 mm* 50 x 3.6 mm
Diameter 75 mm, wall thickness 2.5-5.4 mm* 50 x 4.2 mm E 90 U/U, E 90 C/U,
E 90 U/C, E 90 C/C
Diameter 82 mm, wall thickness 2.7-5.6 mm* 50 x 4.6 mm EI 60 U/U, EI 60 C/U,
Diameter 90 mm, wall thickness 2.9-5.9 mm* 50 x 5.0 mm EI 60 U/C, EI 60 C/C
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 28 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.2.1.3.3
Services Collar Inlay Classification
PP pipe according to EN 1451-1
E 90 U/U, E 90 C/U,
E 90 U/C, E 90 C/C
Diameter 110 mm, wall thickness 3.4-6.6 mm* 60 x 6.0 mm
EI 60 U/U, EI 60 C/U,
EI 60 U/C, EI 60 C/C
Diameter 125 mm, wall thickness 3.9-9.0 mm* 60 x 9.0 mm
EI 60 U/U, EI 60 C/U, EI 60
Diameter 140 mm, wall thickness 4.4-11.4 mm* 60 x 11.5 mm U/C, EI 60 C/C
Diameter 160 mm, wall thickness 4.9-14.6 mm* 60 x 15.0 mm
E 120 U/C, E 120 C/C
Diameter 200 mm, wall thickness 4.9-18.2 mm* 60 x 18.0 mm
EI 90 U/C, EI 90 C/C
Diameter 400 mm, wall thickness 22.7 mm* 100 x 40.0 mm EI 60 C/C
* Typical pipe diameters shown, see below graphs for intermediate sizes
Page 29 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.2.1.4.1
Services Collar Inlay Classification
Wavin SiTech + PP-M B according to EN 13501-1
32-40 mm diameter/ 1.8 mm wall thickness 50 x 3.0 mm
EI 120 U/U
50 mm diameter/ 1.8 mm wall thickness 50 x 3.2 mm
75 mm diameter/ 1.8-2.5 mm wall thickness 50 x 4.2 mm
90 mm diameter/ 1.8-2.9 mm wall thickness 50 x 5.0 mm E 120 U/U, EI 60 U/U
110 mm diameter/ 1.8-3.4 mm wall thickness 50 x 6.0 mm
Aquatherm Green SDR9 MF PP-RP according to ISO 21003
A.2.1.4.1
Construction details:
Page 32 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.2.2.1
Services Collar Collar Inlay Classification
A.2.3.1
Services Insulation Collar Classification
Copper pipe or mild steel
9-50 mm thick Up to 110 mm collar at
Maximum diameter 54 mm, wall
Elastomeric insulation 50 mm height, 125-160 E 90 C/C, EI 60 C/C
thickness 0.7-14.2 mm*
minimum class B-s3, d0 mm at 60 mm height
Diameter 54 mm, wall thickness 25 mm thick Phenolic
Ø 110 x 50 x 6.0 mm E 120 C/C, EI 60 C/C
1.2 mm Foam insulation
Diameter 54 mm, wall thickness 20 mm thick PE foam
Ø 110 x 50 x 6.0 mm E 120 C/C, EI 90 C/C
1.2 mm insulation
Alupex pipe
Up to 110 mm collar at
9-50 mm thick
Maximum diameter 75 mm, wall 50 mm height, 125-
Elastomeric insulation E 90 C/C, EI 60 C/C
thickness 2.25-4.6 mm* 200 mm at 60 mm
minimum class B-s3, d0
height
* Typical pipe diameters shown, see below graphs for intermediate sizes
Page 34 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
Page 35 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.2.3.1.1
Construction details:
A.2.4.1
A.2.4.2
A.3 Flexible or rigid wall constructions with wall thickness of minimum 120 mm
A.3.1 Penetration seals, in drywalls and concrete/masonry walls
Penetration Seal: Combustible pipes fitted with Bostik FP 330 Pipe Collar, to both sides of the wall.
Construction details:
A.3.1.1
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 32-50 mm, wall thickness 2.4-3.7 mm* 50 x 3.0 mm
Diameter 55 mm, wall thickness 2.4-3.9 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.5-4.3 mm* 50 x 3.6 mm
Diameter 75 mm, wall thickness 2.5-4.9 mm* 50 x 4.2 mm EI 120 C/C
A.3.1.1.1
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 110 mm, wall thickness 2.7-6.6 mm* 50 x 6.0 mm
Diameter 125 mm, wall thickness 3.1-7.5 mm* 60 x 8.8 mm
EI 120 C/C
Diameter 140 mm, wall thickness 3.5-8.4 mm* 60 x 11.5 mm
Diameter 160 mm, wall thickness 4.0-9.5 mm* 60 x 15.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 43 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.3.1.2
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes made
from SAN+PVC according to EN 1565-1
Diameter 32-50 mm, wall thickness 3.0-4.6 mm* 50 x 3.0 mm EI 120 C/C
Diameter 55 mm, wall thickness 3.1-5.0 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 3.1-5.7 mm* 50 x 3.6 mm
Diameter 110 mm, wall thickness 3.4 mm* 50 x 6.0 mm EI 120 C/C
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 44 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.3.1.2.1
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes made
from SAN+PVC according to EN 1565-1
Diameter 110 mm, wall thickness 3.4-10.0 mm* 50 x 6.0 mm E 120 C/C, EI 90 C/C
Diameter 125 mm, wall thickness 3.9-9.8 mm* 60 x 8.8 mm
EI 90 C/C
Diameter 140 mm, wall thickness 4.4-9.7 mm* 60 x 11.5 mm
Diameter 160 mm, wall thickness 4.9-9.5 mm* 60 x 15.0 mm EI 120 C/C
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 45 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.3.1.2.2
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes made
from SAN+PVC according to EN 1565-1
Diameter 110 mm, wall thickness 3.4 mm* 50 x 6.0 mm
Diameter 125 mm, wall thickness 3.9-5.3 mm* 60 x 8.8 mm
EI 120 C/C
Diameter 140 mm, wall thickness 4.3-7.1 mm* 60 x 11.5 mm
Diameter 160 mm, wall thickness 4.9-9.5 mm* 60 x 15.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 46 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.3.1.3
Services Collar Inlay Classification
PP pipe according to DIN 8077/8078
Diameter 32-50 mm, wall thickness 2.9-4.6 mm 50 x 3.0 mm EI 120 C/C
Diameter 55 mm, wall thickness 2.9-5.0 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.9-5.7 mm* 50 x 3.6 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 47 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.3.1.3.1
Services Collar Inlay Classification
PP pipe according to DIN 8077/8078
Diameter 110 mm, wall thickness 2.7-10 mm* 50 x 6.0 mm
Diameter 125 mm, wall thickness 3.3-11.3 mm* 60 x 8.8 mm E 120 C/C, EI 90 C/C
Diameter 140 mm, wall thickness 4.0-12.8 mm* 60 x 11.5 mm
Diameter 160 mm, wall thickness 4.9-14.6 mm* 60 x 15.0 mm EI 120 C/C
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 48 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
Construction details:
A.3.4.1
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 50 mm, wall thickness 2.4 mm # 60 x 15.0 mm EI 90 C/C
#Pipe fitted at 45° to the face of the partition in a horizontal plane
Page 49 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.4.1.1
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 32 mm, wall thickness 2.0-3.7 mm* E 240 U/U, E 240 C/U,
Diameter 40 mm, wall thickness 2.0-3.7 mm* E 240 U/C, E 240 C/C
50 x 3.0 mm
EI 180 U/U, EI 180 C/U,
Diameter 50 mm, wall thickness 2.0-3.7 mm* EI 180 U/C, EI 180 C/C
Diameter 55 mm, wall thickness 2.1-3.9 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.2-4.3 mm* 50 x 3.6 mm
Diameter 75 mm, wall thickness 2.3-4.9 mm* 50 x 4.2 mm
EI 180 U/U, EI 180 C/U,
Diameter 82 mm, wall thickness 2.4-5.2 mm* 50 x 4.6 mm EI 180 U/C, EI 180 C/C
Diameter 90 mm, wall thickness 2.5-5.6 mm* 50 x 5.0 mm
Diameter 110 mm, wall thickness 2.7-6.6 mm* 50 x 6.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 50 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
Page 51 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.4.1.1.1
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 110 mm, wall thickness 2.7-6.6 mm* 50 x 6.0 mm EI 180 U/U, EI 180 C/U,
EI 180 U/C, EI 180 C/C
Diameter 125 mm, wall thickness 3.1-7.5 mm* 60 x 8.8 mm
EI 240 U/U, EI 240 C/U,
Diameter 140 mm, wall thickness 3.5-8.4 mm* 60 x 11.5 mm EI 240 U/C, EI 240 C/C
Diameter 160 mm, wall thickness 4.0-9.5 mm* 60 x 15.0 mm
A.4.1.2
A.4.1.2.1
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes made
from SAN+PVC according to EN 1565-1
50 x 6.0 mm E 240 U/U, E 240 C/U,
E 240 U/C, E 240 C/C
Diameter 110 mm, wall thickness 3.4 mm*
EI 180 U/U, EI 180 C/U,
EI 180 U/C, EI 180 C/C
Diameter 125 mm, wall thickness 3.9-5.2 mm* 60 x 9.0 mm
60 x 11.5 mm EI 180 U/U, EI 180 C/U,
Diameter 140 mm, wall thickness 4.3-7.0 mm*
EI 180 U/C, EI 180 C/C
Diameter 160 mm, wall thickness 4.9-9.5 mm* 60 x 15.0 mm
A.4.1.2.2
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes made
from SAN+PVC according to EN 1565-1
EI 240 U/U, EI 240 C/U,
Diameter 50 mm, wall thickness 3.0-4.6 mm* 50 x 3.0 mm
EI 240 U/C, EI 240 C/C
Diameter 55 mm, wall thickness 3.1-4.8 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 3.1-5.0 mm* 50 x 3.6 mm
Diameter 75 mm, wall thickness 3.2-5.4 mm* 50 x 4.2 mm
Diameter 82 mm, wall thickness 3.2-5.7 mm* 50 x 4.6 mm E 180 U/C, E 180 C/C
Diameter 90 mm, wall thickness 3.3-5.9 mm* 50 x 5.0 mm EI 120 U/C, EI 120 C/C
A.4.1.3
Services Collar Inlay Classification
PP pipe according to EN 1451-1
Diameter 32 mm, wall thickness 1.6-5.5 mm*
Diameter 40 mm, wall thickness 1.6-5.5 mm* 30 x 3.0 mm
Diameter 50 mm, wall thickness 1.6-5.5 mm*
Diameter 55 mm, wall thickness 1.7-5.9 mm* 50 x 3.2 mm
50 x 3.6 mm EI 240 U/C, EI 240 C/C
Diameter 63 mm, wall thickness 1.8-6.5 mm*
Diameter 75 mm, wall thickness 2.1-7.3 mm* 50 x 4.2 mm
Diameter 82 mm, wall thickness 2.2-7.9 mm* 50 x 4.6 mm
Diameter 90 mm, wall thickness 2.3-8.5 mm* 50 x 5.0 mm
Diameter 110 mm, wall thickness 2.7-10.0 mm* 50 x 6.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 57 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.4.1.3.1
Services Collar Inlay Classification
PP pipe according to EN 1451-1
Diameter 110 mm, wall thickness 2.7-10.0 mm* 50 x 6.0 mm EI 240 U/C, EI 240 C/C
Diameter 125 mm, wall thickness 3.3-11.4 mm* 60 x 9.0 mm
60 x 11.5 mm E 240 U/C, E 240 C/C
Diameter 140 mm, wall thickness 4.0-12.8 mm*
EI 180 U/C, EI 180 C/C
Diameter 160 mm, wall thickness 4.9-14.6 mm* 60 x 15.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 58 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.4.1.3.2
Services Collar Inlay Classification
PP pipe according to EN 1451-1
Diameter 32 mm, wall thickness 1.6-5.5 mm*
EI 240 U/U, EI 240 C/U,
Diameter 40 mm, wall thickness 1.6-5.5 mm* 30 x 3.0 mm
EI 240 U/C, EI 240 C/C
Diameter 50 mm, wall thickness 1.6-5.5 mm*
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 59 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.4.1.3.3
Services Collar Inlay Classification
PP pipe according to EN 1451-1
EI 240 U/U, EI 240 C/U,
Diameter 50 mm, wall thickness 1.6-5.5 mm* 50 x 3.0 mm
EI 240 U/C, EI 240 C/C
Diameter 55 mm, wall thickness 1.7-5.9 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 1.8-6.5 mm* 50 x 3.6 mm
Diameter 75 mm, wall thickness 2.1-7.3 mm* 50 x 4.2 mm E 240 U/U, E 240 C/U,
Diameter 82 mm, wall thickness 2.2-7.9 mm* 50 x 4.6 mm EI 60 U/U, EI 60 C/U
Diameter 90 mm, wall thickness 2.3-8.5 mm* 50 x 5.0 mm
Diameter 110 mm, wall thickness 2.7-10.0 mm* 50 x 6.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 60 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.4.1.3.4
Services Collar Inlay Classification
PP pipe according to EN 1451-1
EI 240 U/U, EI 240 C/U,
Diameter 50 mm, wall thickness 1.6-5.5 mm* 50 x 3.0 mm
EI 240 U/C, EI 240 C/C
Diameter 55 mm, wall thickness 1.7-5.6 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 1.8-5.7 mm* 50 x 3.6 mm
Diameter 75 mm, wall thickness 2.0-5.9 mm* 50 x 4.2 mm
E 240 U/U, EI 90 U/U
Diameter 82 mm, wall thickness 2.1-6.0 mm* 50 x 4.6 mm
Diameter 90 mm, wall thickness 2.3-6.1 mm* 50 x 5.0 mm
Diameter 110 mm, wall thickness 2.7-6.3 mm 50 x 6.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 61 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.4.1.3.5
Services Collar Inlay Classification
PP pipe according to EN 1451-1
Diameter 110 mm, wall thickness 2.7-10.0 mm* 60 x 6.0 mm
Diameter 125 mm, wall thickness 33-11.4 mm* 60 x 8.8 mm E 240 U/U, E 240 C/U,
EI 60 U/U, EI 60 C/U
Diameter 140 mm, wall thickness 4.0-12.8 mm* 60 x 11.5 mm
Diameter 160 mm, wall thickness 4.9-14.6 mm* 60 x 15.0 mm E 240 U/U, E 240 C/U,
E 240 U/C, E 240 C/C
EI 180 U/U, EI 180 C/U,
EI 180 U/C, EI 180 C/C
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 62 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
Construction details:
A.4.2.1
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 32 mm, wall thickness 2.4-3.7 mm
E 240 U/C, E 240 C/C
Diameter 40 mm, wall thickness 2.4-3.7 mm 50 x 3.0 mm
EI 180 U/C, EI 180 C/C
Diameter 50 mm, wall thickness 2.4-3.7 mm*
Diameter 55 mm, wall thickness 2.5-3.9 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.6-4.3 mm* 50 x 3.6 mm
Diameter 75 mm, wall thickness 2.7-4.9 mm* 50 x 4.2 mm E 180 U/C, E 180 C/C
Diameter 82 mm, wall thickness 2.8-5.2 mm* 50 x 4.6 mm EI 120 U/C, EI 120 C/C
A.4.2.2
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes made
from SAN+PVC according to EN 1565-1
Diameter 32 mm, wall thickness 3.0-4.6 mm
E 180 U/C, E 180 C/C
Diameter 40 mm, wall thickness 3.0-4.6 mm 50 x 3.0 mm
EI 120 U/C, EI 120 C/C
Diameter 50 mm, wall thickness 3.0-4.6 mm
Diameter 55 mm, wall thickness 3.1-4.5 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 3.1-4.3 mm* 50 x 3.6 mm
Diameter 75 mm, wall thickness 3.2-4.1 mm* 50 x 4.2 mm
EI 90 U/C, EI 90 C/C
Diameter 82 mm, wall thickness 3.2-3.9 mm* 50 x 4.6 mm
Diameter 90 mm, wall thickness 3.3-3.8 mm* 50 x 5.0 mm
Diameter 110 mm, wall thickness 3.4 mm* 50 x 6.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 65 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.4.2.3
Services Collar Inlay Classification
PP pipe according to EN 1451-1
Diameter 32 mm, wall thickness 2.0-4.6 mm
Diameter 40 mm, wall thickness 2.0-4.6 mm 50 x 3.0 mm EI 90 U/C, EI 90 C/C
Diameter 50 mm, wall thickness 2.0-4.6 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 66 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.1.1
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 32 mm, wall thickness 1.9-3.7 mm* 30 x 3.0 mm
E 90 U/U, E 90 C/U,
Diameter 40 mm, wall thickness 1.9-3.7 mm*
E 90 U/C, E 90 C/C
Diameter 50 mm, wall thickness 2.0-3.7 mm* EI 60 U/U, EI 60 C/U,
EI 60 U/C, EI 60 C/C
Diameter 55 mm, wall thickness 2.1-3.9 mm* 30 x 3.2 mm
Diameter 63 mm, wall thickness2.2-4.3 mm* 30 x 3.6 mm
Diameter 75 mm, wall thickness 2.5-4.9 mm* 30 x 4.2 mm
EI 60 U/U, EI 60 C/U,
Diameter 82 mm, wall thickness 2.6-5.2 mm* 30 x 4.6 mm EI 60 U/C, EI 60 C/C
Diameter 90 mm, wall thickness 2.8-5.6 mm* 30 x 5.0 mm
Diameter 110 mm, wall thickness 3.2-6.6 mm* 30 x 6.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 68 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.1.1.1
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 32 mm, wall thickness 2.0-3.7 mm
A.5.1.1.2
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 50 mm, wall thickness 2.0-3.7 mm* 50 x 3.0 mm
Diameter 90 mm, wall thickness 2.5-5.8 mm* 50 x 5.0 mm E 120 U/C, EI 90 U/C
A.5.1.1.3
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 110 mm, wall thickness 6.3 mm* 60 x 6.0 mm
Diameter 125 mm, wall thickness 5.6-7.3 mm* 60 x 9.0 mm
Diameter 140 mm, wall thickness 5.0-8.2 mm* 60 x 11.5 mm EI 120 U/C, EI 120 C/C
A.5.1.1.4
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 110 mm, wall thickness 2.7-6.3 mm* 60 x 6.0 mm
Diameter 125 mm, wall thickness 2.8-7.2 mm* 60 x 8.7 mm
EI 60 U/C
Diameter 140 mm, wall thickness 3.0-8.2 mm* 60 x 11.4 mm
Diameter 160 mm, wall thickness 3.2-9.5 mm* 60 x 15.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 72 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.1.1.5
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 110 mm, wall thickness 3.2-6.6 mm* 60 x 6.0 mm
Diameter 125 mm, wall thickness 3.2-7.4 mm* 60 x 8.7 mm
EI 60 U/U
Diameter 140 mm, wall thickness 3.2-8.3 mm* 60 x 11.4 mm
Diameter 160 mm, wall thickness 3.2-9.5 mm* 60 x 15.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 73 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.1.1.6
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1
and EN 1453-1 and PVC-C according to EN 1566-1
Diameter 110 mm, wall thickness 2.7-6.6 mm* 50 x 6.0 mm
Diameter 125 mm, wall thickness 2.8-7.4 mm* 60 x 8.7 mm
EI 60 C/U
Diameter 140 mm, wall thickness 3.0-8.3 mm* 60 x 11.4 mm
Diameter 160 mm, wall thickness 3.2-9.5 mm* 60 x 15.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 74 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.1.2
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes
made from SAN+PVC according to EN 1565-1
Diameter 32 mm, wall thickness 3.0-4.6 mm*
EI 60 U/U, EI 60 C/U,
Diameter 40 mm, wall thickness 3.0-4.6 mm* 30 x 3.0 mm
EI 60 U/C, EI 60 C/C
Diameter 50 mm, wall thickness 3.0-4.6 mm*
Diameter 110 mm, wall thickness 10.0 mm 30 x 6.0 mm EI 180 U/C
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 75 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.1.2.1
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes
made from SAN+PVC according to EN 1565-1
Diameter 50 mm, wall thickness 3.0-4.6 mm* 30 x 3.0 mm
EI 60 U/U, EI 60 C/U,
Diameter 55 mm, wall thickness 3.0-5.2 mm* 30 x 3.2 mm EI 60 U/C, EI 60 C/C
A.5.1.2.2
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes
made from SAN+PVC according to EN 1565-1
Diameter 32-40 mm, wall thickness 3.0-4.6 mm 50 x 3.0 mm
EI 240 U/C
Diameter 50 mm, wall thickness 3.0-4.6 mm 50 x 3.2 mm
Diameter 32-40 mm, wall thickness 3.0 mm 50 x 3.0 mm
EI 240 U/U
Diameter 50 mm, wall thickness 3.0 mm 50 x 3.2 mm
Diameter 50 mm, wall thickness 3.0-4.6 mm* 50 x 3.0 mm
Diameter 55 mm, wall thickness 3.1-5.1 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 3.1-5.8 mm* 50 x 3.6 mm
Diameter 75 mm, wall thickness 3.2-6.9 mm* 50 x 4.2 mm EI 60 U/U, EI 60 C/U
Diameter 82 mm, wall thickness 3.3-7.5 mm* 50 x 4.6 mm
Diameter 90 mm, wall thickness 3.3-8.2 mm* 50 x 5.0 mm
Diameter 110 mm, wall thickness 3.4-10.0 mm* 50 x 6.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 77 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.1.2.3
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes
made from SAN+PVC according to EN 1565-1
Diameter 110 mm, wall thickness 3.4-10.0 mm* 60 x 6.0 mm
Diameter 125 mm, wall thickness 3.9-11.3 mm* 60 x 8.8 mm
Diameter 140 mm, wall thickness 4.3-12.7 mm* 60 x 11.5 mm EI 60 U/U, EI 60 C/U
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 78 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.1.2.4
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes
made from SAN+PVC according to EN 1565-1
Diameter 32 mm, wall thickness 3.0-4.6 mm
Diameter 40 mm, wall thickness 3.0-4.6 mm 50 x 3.0 mm
Diameter 50 mm, wall thickness 3.0-4.6 mm
Diameter 55 mm, wall thickness 3.1-5.0 mm 50 x 3.2 mm
A.5.1.3
Services Collar Inlay Classification
Page 79 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.1.3.1
Services Collar Inlay Classification
PP pipe according to EN 1451-1
Diameter 50 mm, wall thickness 2.9 mm 50 x 3.2 mm EI 240 U/U
EI 120 U/U, EI 120 C/U,
Diameter 50 mm, wall thickness 1.8-4.6 mm* 50 x 3.0 mm
EI 120 U/C, EI 120 C/C
Diameter 55 mm, wall thickness 1.9-4.8 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.0-5.0 mm* 50 x 3.6 mm
Diameter 75 mm, wall thickness 2.2-5.4 mm* 50 x 4.2 mm
EI 60 U/U, EI 60 C/U
Diameter 82 mm, wall thickness 2.3-5.6 mm* 50 x 4.6 mm
Diameter 90 mm, wall thickness 2.4-5.9 mm* 50 x 5.0 mm
Diameter 110 mm, wall thickness 2.7-6.6 mm* 50 x 6.0 mm
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 82 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.1.3.2
Services Collar Inlay Classification
PP pipe according to EN 1451-1
EI 120 U/U, EI 120 C/U,
Diameter 50 mm, wall thickness 1.8-4.6 mm* 50 x 3.0 mm
EI 120 U/C, EI 120 C/C
Diameter 55 mm, wall thickness 1.9-4.8 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.0-5.0 mm* 50 x 3.6 mm
A.5.1.3.3
Services Collar Inlay Classification
PP pipe according to EN 1451-1
Diameter 50 mm, wall thickness 1.8-4.6 mm* 30 x 3.0 mm
Diameter 55 mm, wall thickness 1.9-5.1 mm* 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.0-5.8 mm* 50 x 3.6 mm
A.5.1.3.4
Services Collar Inlay Classification
PP pipe according to EN 1451-1
Diameter 110 mm, wall thickness 2.7-6.6 mm* 60 x 6.0 mm
Diameter 125 mm, wall thickness 3.4-8.9 mm* 60 x 8.8 mm EI 120 U/C, EI 120 C/C
Diameter 140 mm, wall thickness 4.1-11.2 mm* 60 x 11.5 mm
Diameter 160 mm, wall thickness 4.9-14.6 mm* 60 x 15.0 mm EI 180 U/C, EI 180 C/C
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 85 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.1.3.5
Services Collar Inlay Classification
PP pipe according to EN 1451-1
Diameter 110 mm, wall thickness 2.7-6.6 mm* 50 x 6.0 mm
Diameter 125 mm, wall thickness 3.6-8.9 mm* 60 x 8.8 mm
60 x 11.5 mm EI 60 U/U
Diameter 140 mm, wall thickness 4.7-11.3 mm*
Diameter 160 mm, wall thickness 6.2-14.7 mm* 60 x 15.0 mm
A.5.1.4
Services Collar Inlay Classification
Wavin SiTech + PP-M B according to EN 13501-1
32-40 mm diameter/ 1.8 mm wall thickness 50 x 3.0 mm
EI 240 U/U
50 mm diameter/ 1.8 mm wall thickness 50 x 3.2 mm
A.5.1.4.1
Page 87 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.2.1
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1 and EN
1453-1 and PVC-C according to EN 1566-1
Diameter 32 mm, wall thickness 2.0-3.7 mm*
Diameter 63 mm, wall thickness 2.2-4.3 mm* 50 x 3.6 mm EI 120 C/C, EI 60 C/U
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 89 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
Page 90 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.2.1.1
A.5.2.2
A.5.2.3
Services Collar Inlay Classification
PP pipe according to EN 1451-1
Up to 200 mm diameter / 4.9-18.2 mm wall thickness* 60 x 18 mm EI 120 C/C
Up to 250 mm diameter / 15.1-22.7 mm wall thickness* 75 x 24 mm
EI 60 C/C
Up to 315 mm diameter / 28.6 mm wall thickness* 75 x 30 mm
Up to 400 mm diameter / 9.8-22.7 mm wall thickness* 100 x 39 mm EI 30 C/C
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 93 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.3.1
Services Insulation Collar Classification
Copper pipe or mild steel
9 mm thick Elastomeric Up to 63 mm
Maximum diameter 42 mm, wall
insulation minimum collar at 50 mm EI 120 C/C
thickness 0.7-14.2 mm*
class D-s3, d0 height
Up to 110 mm
10-50 mm thick collar at 50 mm
Maximum diameter 42 mm, wall
Elastomeric insulation height, 125-160 EI 60 C/C
thickness 0.7-14.2 mm*
minimum class D-s3, d0 mm at 60 mm
height
19 mm thick Up to 110 mm
Maximum diameter 54 mm, wall
Elastomeric insulation collar at 50 mm E 120 C/C, EI 60 C/C
thickness 0.7-14.2 mm*
minimum class B-s3, d0 height
Alupex pipe
9 mm thick Elastomeric Up to 110 mm
insulation minimum collar at 50 mm EI 120 C/C
class D-s3, d0 height
Maximum diameter 75 mm, wall Up to 110 mm
thickness 2.25-4.6 mm 10-50 mm thick collar at 50 mm
Elastomeric insulation height, 125-200 E 120 C/C, EI 90 C/C
minimum class B-s3, d0 mm at 60 mm
height
PE pipe according to EN 1519-1, EN 12201-2 and EN 12666-1, ABS according to EN 1455-1 and pipes made from
SAN+PVC according to EN 1565-1
Up to 110 mm
9 mm thick Elastomeric
collar at 50 mm
insulation minimum
height, 125-200 EI 180 C/C
class
mm at 60 mm
BL-s3, d0
height
Maximum diameter 160 mm, wall Up to 110 mm
thickness 3.0-9.5 mm collar at 50 mm
10-50 mm thick
height, 125-200
Elastomeric insulation
mm at 60 mm EI 120 C/C
minimum class
height, 250-315
B-s3, d0
mm at 75 mm
height
PP pipe according to EN 1451-1
Up to 110 mm
9 mm thick Elastomeric
collar at 50 mm
insulation minimum
height, 125-200 E 180 C/C, EI 120 C/C
class
mm at 60 mm
BL-s3,d0
height
Maximum diameter 160 mm, wall Up to 110 mm
thickness 1.8-9.1 mm collar at 50 mm
10-50 mm thick height, 125-200
Elastomeric insulation mm at 60 mm EI 60 C/C
minimum class B-s3,d0 height, 250-315
mm at 75 mm
height
* Typical pipe diameters shown, see below graph for intermediate sizes
Page 95 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
Page 96 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
Page 97 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.4.1
Services Collar Classification
A.5.5.1
Services Collar Inlay Classification
PVC-U pipe according to EN 1329-1, EN 1452-1 and EN
1453-1 and PVC-C according to EN 1566-1
Diameter 32 mm, wall thickness 1.9-3.7 mm 50 x 3.0 mm
Diameter 40 mm, wall thickness 1.9-3.7 mm 50 x 3.0 mm EI 240 U/C
Diameter 50 mm, wall thickness 1.9-3.7 mm 50 x 3.2 mm
Diameter 55 mm, wall thickness 2.0-4.0 mm 50 x 3.2 mm
Diameter 63 mm, wall thickness 2.1-4.4 mm 50 x 3.6 mm
Diameter 75 mm, wall thickness 2.4-5.0 mm 50 x 4.2 mm
EI 120 U/C
Diameter 82 mm, wall thickness 2.5-5.3 mm 50 x 4.6 mm
Diameter 90 mm, wall thickness 2.7-5.7 mm 50 x 5.0 mm
Diameter 110 mm, wall thickness 3.2-6.6 mm 50 x 6.0 mm
Diameter 125 mm, wall thickness 5.0-7.5 mm 60 x 8.8 mm
Diameter 140 mm, wall thickness 6.9-8.3 mm 60 x 11.5 mm E 240 U/C, EI 180 U/C
Diameter 160 mm, wall thickness 9.5 mm 60 x 15 mm
Diameter 125 mm, wall thickness 4.1-7.5 mm 60 x 8.8 mm
Diameter 140 mm, wall thickness 5.0-8.3 mm 60 x 11.5 mm E 180 U/C, EI 90 U/C
Diameter 160 mm, wall thickness 6.2-9.5 mm 60 x 15 mm
Page 99 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
Page 100 of 103 of European Technical Assessment ETA-21/0551 issued on 2021-06-16
A.5.5.2
Services Collar Inlay Classification
PE pipe according to EN 1519-1, EN 12201-2 and EN
12666-1, ABS according to EN 1455-1 and pipes made
from SAN+PVC according to EN 1565-1
Diameter 32 mm, wall thickness 3.0-4.6 mm 50 x 3.0 mm
A.5.5.3
Services Collar Inlay Classification
PP pipe according to EN 1451-1
Diameter 32 mm, wall thickness 2.9-4.6 mm 50 x 3.0 mm
Diameter 40 mm, wall thickness 2.9-4.6 mm 50 x 3.0 mm E 240 U/C, EI 180 U/C
Diameter 140 mm, wall thickness 12.7 mm 60 x 11.5 mm E 240 U/C, EI 60 U/C
Product tested 110mm Bostik FP 330 Pipe Collar each face fixed with plasterboard anchors
Summary of testing procedure Result
3
Pressure (Pa) Leakage (m /h) Leakage (m3/m2/h)
25 0.23 N/A
50 0.43 N/A
100 0.72 N/A
Results under negative
200 1.17 N/A
chamber pressure
300 1.63 N/A
450 1.9 N/A
600 2.34 N/A
25 0.2 N/A
50 0.29 N/A
100 0.49 N/A
Results under positive
200 1.13 N/A
chamber pressure
300 1.75 N/A
450 2.34 N/A
600 3.01 N/A
BOSTIK BENELUX B.V.
P: + 31 (0)162 491 000
Denariusstraat 11, 4903 RC, Oosterhout The Netherlands
E: info.benelux@bostik.com