Technical Offer
Customer
PCV for Project EE-19004 / Kiekens-DSH 19129
Enquiry Ref.
Scope ControlValve
14.02.2021
SRG/AKV
Sr. I&C Engr
Refer TBE Query Log sheet for additional comments
Technical Offer
Yours Truely,
For KOSO India Pvt Ltd, Nashik
Mahesh Patil
Sr.Engineer-Sales Applications
Tel: 02532408724
Annexure I
Control Valve Datasheet
Koso India Private Limited, CONTROL VALVE TECHNICAL SPECIFICATION
H-33&34, MIDC Ambad,
Nashik, Approver
Trim Specification
T.1 Trim Design HF No. of Stages 1
T.2 Guide Material 410 ST.ST. Guide Finish/Overlay colmonoy
T.3 Plug Material 410 ST.ST. Plug Finish/Overlay colmonoy
T.4 Seat Material 410 ST.ST. Seat Finish/Overlay colmonoy
T.5 Stem Material 410 ST.ST. Stem Finish/Overlay None
T.6 Plug Type Balanced Plug Seal Carb/PTFE U Seal
T.7 Design CV 400 Trim Size Ref. 8
T.8 Flow Direction Flow Under Flow Characteristic Eq%
T.9 Valve Travel 4 inch Bonnet Mounting Dia. 3.56 inch
T.10 Stem Protection None Stem Diameter 1 inch
Additional Trim Features:
Actuator - Pneumatic
A.1 Model Number G300R-XS0SCE3-B Actuator Type Diaphragm Spring Return
A.2 Fail Mode Plug Type Stay Put Actuator Action Reverse
A.3 Manual Override Side Mounted Handwheel Min. Operating Pressure 3.40 barG
A.4 Limit Stop None Inc. Actuator Pressure Opens Valve
A.5 Material Standard Max. Operating Pressure 3.40 barG
A.6 Yoke/Distance Piece Mat Carbon Steel
A.7 Paint System S Actuator Area 300 in²
A.8 Thrust (Max) Nm Spring Setting 1.0-2.3 bar
A.9 Description
Additional Actuator Features:
Instrumentation
I.1 Instrument Piping 3/4" St.St. Pneumatic Connection NPT
I.2 Instrument Fittings St.St. Electrical Connections M20 x 1.5 mm
I.4 Air Set (Qty: 1) KOSO Air Set Model PRS Series, SS MOC , Manual Drain
I.5 Volume Booster (Qty: 1) KOSO Volume Booster Model VB3000 (St. St)
I.6 Air Lock (Qty: 1) KOSO Air Lock Model PA 231211 (St.St.)
Additional Instrumentation Features:
Technical Comments
1) Expander and reducer are not KOSO scope of supply.
2) Valve external body/actuator shall be painted as per QP-SPC-L002 Standard.
3) Stroke Time: <30 Seconds.
4) The Opening in condition 4 is very low since the flow for this condition is very low i.e. 240Kg/hr please review and confirm.
5) RT required on Critical Area .
6) Minimum flow value 240Kg/hr as per the process condition is to be non controllable since flow value is very less.
Process Conditions
Description UOM Condition 1 Condition 2 Condition 3 Condition 4 Condition 5
Steam Flow Rate Kg/Hour 35000 34000 19322 240 34388
Inlet Pressure barg 13.9 13.9 13.9 13.9 13.9
Outlet Pressure barg 6.9 6.9 6.9 6.9 6.9
Pressure Drop bar 7 7 7 7 7
Inlet Temperature °C 198 198 198 198 198
Calculated Values
Description UOM Condition 1 Condition 2 Condition 3 Condition 4 Condition 5
Expansion Factor 1.3 1.3 1.3 1.3 1.3
Inlet Spec Volume m³/kg 0.1357 0.1357 0.1357 0.1357 0.1357
Calculated CV US Units 229.9 223.3 126.3 1.556 225.9
Valve Opening % 77.2 76.1 55.6 3 76.5
Gas Recovery Factor 0.746 0.746 0.755 0.776 0.746
Fluid State Normal Normal Normal Normal Normal
Predicted Noise Level dBA 76 75.9 71.8 70 75.9
Body Inlet Velocity m/sec 40.7 39.5 22.5 0.3 40
Body Outlet Velocity m/sec 76 73.9 42 0.5 74.7
Body Outlet Mach No. 0.1463 0.1421 0.0808 0.001 0.1437
Mach No. Condition OK OK OK OK OK
Sys. Outlet Velocity m/sec 76 73.9 42 0.5 74.7
Sys. Outlet Mach No. 0.1463 0.1421 0.0808 0.001 0.1437
Sys Mach No. Condition OK OK OK OK OK
Pipework Correction Factor 1 1 1 1 1
Energy Conversion MW 1.1602 1.127 0.6405 0.008 1.1399
Specific Volume In m³/kg 0.1357 0.1357 0.1357 0.1357 0.1357
Specific Volume Out m³/kg 0.2536 0.2536 0.2536 0.2536 0.2536
Min DP 100% Open 2.305 2.175 0.6974 0.0001 2.225
Max Flow 100% Open 60888.1 60893.8 61183.5 61686.7 60891.6
Outlet Temperature 177.07 177.07 177.07 177.07 177.07
Inlet Saturated Temp 196.7 196.7 196.7 196.7 196.7
Outlet Saturated Temp 169.6 169.6 169.6 169.6 169.6
Dryness Fraction 1 1 1 1 1
1,294.41 lbf 1,241.87 lbf 4 in 3.56 in 49.09 in² 50.27 in² 0.79 in²
REV : 01
Since offered Valve design is proven design & the Cv offered are published Cv's , so please waive off this requirement. As
off now KOSO has not considered the Cv testing (Capacity Test). Though if you still insists on same, we shall perform the
2 51‐PV‐022B Capacity test
same at our facility. Kindly confirm. KOSO has provided the mandatory test applicable as mentioned in the DEP standard.
Supplymentary test are not considered.