Professional Documents
Culture Documents
Evaluation of Load Generated Harmonics o
Evaluation of Load Generated Harmonics o
ATTILA BUCHMAN, CLAUDIU LUNG, MIRCEA HORGOS, ALIN TISAN, STEFAN ONIGA
Electronic and Computer Engineering Department
North University
Victor Babes str., 62/A, 430083, Baia Mare
ROMANIA
abuchman@ubm.ro http://www.ece.ubm.ro
Abstract: Electronic appliances connected to the low voltage alternating current network draw non sinusoidal current.
Due to the huge number of such consumers, the mains voltage is more or less distorted. In order to protect to the public
network from polluting consumers, a figure of merit to evaluate the harmonic generating behavior of the loads is
needed. Power factor is often used in this purpose but as we will prove in this paper this parameter is not suitable
under non sinusoidal voltage condition. Another parameter, total harmonic distortion of current is applicable but it
includes all harmonics not only those produced by the load under test. A third parameter, load generated harmonic, is
introduced in this paper to accurately evaluate the polluting effect of a certain load.
Key Words: power theory, power factor, active power, apparent power, harmonic distortion, load generated
harmonics.
Increasing use of electronic devices in daily life has The shape of the mains voltage, as measured at the
reinforced the stress caused by harmonic currents on wall outlet is presented in fig.1 along with the current
low6voltage alternating6current (LVAC) public networks drawn by a TV set. One can see that not only the load is
[1]. Indeed, most domestic electrical and electronic harmonic generating [3] but is already fed by non
equipment needs direct current to operate. All of them sinusoidal voltage.
use rectifiers to connect to the LVAC network. Common Distorted mains voltage affects power components
rectifiers have bulk capacitors to reduce voltage ripple. such as phase6correction capacitors and electric motors
These capacitors charges for a very short period of time which experience an increase in temperature and hence a
close to the moment when the AC voltage reaches its reduction in lifetime [2]. The conclusion to be drawn is
maximum value. One can say that all rectifiers that mains connected equipment should be subjected to
connected to the same phase of the LVAC network harmonic emission control. For that purpose harmonic
charge their capacitors at the same time. emission of all LVAC connected loads must be
The LVAC network has finite valued impedance quantified.
that varies from location to location and from country to
country [2]. By consequence large current peaks will
produce a clamping of the mains voltage (fig.1).
When it comes to harmonic emission two figures of
merit are widely used: power factor (PF) and total
harmonic distortion of current (THDI). Under sinusoidal
voltage condition (which was applicable to LVAC
networks not so long time ago) these figures are closely
related and any of them would be adequate. Power factor
correction was in fact similar to harmonic emission
reduction. But when the voltage itself is already
distorted even a purely resistive load (PF=1) will draw a
non sinusoidal current (THDI > 0). So, the applicability
of theses parameters to harmonic emission evaluation
deserves to be investigated.
Several power theories exist. The first was proposed
by Budeanu [4] and perfected by the so called IEEE
Fig.1. Voltage applied to and current drawn by a TV set group [5],[6]. In this paper PF and THDI are computed
according to this theory. The newest power theory results prove it, PF can give erroneous evaluation of
proposed by Czarnecki [7],[8], is the first to give harmonic emission in these situations.
practical means to identify load generated harmonics. In
this paper, load generated harmonic distortions (LGHD)
will be defined according to this theory. # $ % "
"
In order to compute THDI a frequency domain analysis
! " is required. In this case dedicated signal processing or
circuit analysis software is required to perform a Fourier
If u(t) and i(t) are the instant values of voltage applied to series decomposition of i(t). For THDI computation only
and current flowing thru a load then the instant power the amplitudes (In) of the harmonic components are
(p) is given by equation (1). required (eq. 7).
& $
Their product is the apparent power (S) as defined by '
eq.(5). Based on Czarnecki’s power theory [3],[7],[8], it is
possible to identify not only if the load is harmonics
generating but also the frequency of those harmonics. As
Knowing P and S one can compute PF using eq.(6). stated in [3] the active power of the nth order harmonic
As one can see from eq. (1)6(6) computation of PF is Pn is positive if the power flows from the source to the
fairly simple and is all done in time domain. More than load. If Pn is negative the power flows from load to
that U, I and P can be directly measured so it takes only source. If that is the case, that particular harmonic is
one multiplication (eq.5) and one division (eq.6) to generated by the load itself. Since Un and In are always
compute PF. That is one more reason for its extended positives, Pn is negative if and only if cos(φn) is
use. negative. Identifying load generated harmonics is thus a
But regarding harmonic emission PF gives only an simple task in frequency domain.
indirect evaluation under non sinusoidal condition. If In order to define a figure of merit similar to THDI
PF=1 all the power originating from the source is we would suggest the use of load generated harmonic
absorbed by the load so no harmonic current is distortion (LGHD), defined as in eq. (9).
generated by the load itself. But if PF < 1 then there is
also non active power in the system and the load is
susceptible of harmonic emission. As our experimental
#
Six loads (monitors, PCs, TVs)
s) were
wer tested. One of them
*+ ! , -
(SMPS1) had no power factor or correction
cor (PFC) at all,
three of them (TV, monitor1, PC)) had passive PFC and
the last two (monitor2, SMPS2) had different type of
active PFC. For each one of them PF, THDI, THDU and
The values of h in eq. (9) are those values of n that LGHD were computed. Table 1 summarizes
sum the results.
./0(" 1 2
satisfy eq. (10).
Obviously THDU is not expected
ected to be altered by one
(10) particular load but its value depe
depends on the location
were the measurement is takenn and the global load of the
According to this definition, strictly the harmonics
LVAC network. SMPS1 and SMPS2 were measured in
contributed by the load will degrade its figure of merit.
the same place, one after the other,
other and that is why the
THDU value is the same forr them
them. The same goes for
monitors 1 and 2. A more compreh
mprehensive representation
& ( of these results appears in fig.3, where the graph of
In order to test the ability of PF, THDI and LGHD to THDI and LGHD versus PF iss presented.
prese
evaluate harmonic emission related performa
rformances some
experimental work was done. The voltagege applied
app to and
the current passing through six different
erent loads was
recorded using the setup in fig.2. Each record
recor contains
20,000 values sampled at a rate off 100kHz,
100 thus
covering a 200ms time window.