Professional Documents
Culture Documents
E-403 - Construction Specification - Electrical Heat Tracing Requirements
E-403 - Construction Specification - Electrical Heat Tracing Requirements
E-403 - Construction Specification - Electrical Heat Tracing Requirements
Master Specification E-403 is proprietary and the property of the Owners of the Trans Alaska Pipeline System.
Its sole use is for Alyeska Pipeline Service Company (Alyeska), and the state and federal regulatory agencies
with authority to view the information. It may not be used for commercial or any other use. Any other use must
be expressly permitted in writing by Alyeska as Agent for the Trans Alaska Pipeline System Owners. This use
restriction includes reproduction or redistribution of this document or any portion of this document.
Master Specification E-403
Construction Specification - Electrical Heat Tracing
Requirements
Revision History
Master Specification E-403
Administrative Change
Rev. No. Date Comments
6 01/29/20 • Replaced reference to cancelled E-122 Bulk Materials Specification with
reference to E-102 Procurement Specification – General Purpose
Transformer (Dry Type) 300 kVA and Below
Approved by: David Heimke, Engineering Standards and Programs Manager
5 09/25/15 • The ownership statement on the title page of the document was replaced
with the Express Statement Marking, no.6 from AMS-006-01, Business or
Security Sensitive Information Procedure, Appendix B, “Express Language
Matrix.”
• Updated Records Section.
• Updated References throughout document.
• Minor wordsmithing throughout document, i.e. Section 1.6.6, Arctic Duty,
2.1.2 Basic Design, 2.2.1, Type and Thickness.
• Added reference to N-502, Aboveground and Transition Insulation for
Facility Piping, Valves, Vessels and Equipment Tanks.
• Deleted reference to EE-14 in Appendix A. Test Reports Index, EE-14
consolidated with EE-15 under MDR 32751.
• Added N-502, Construction Specification – Aboveground and Transition
Insulation for Facility, Valves, Vessels and Equipment Tanks to Appendix
B. Reference Publications.
• Deleted Old Sections 2.2.2 Type and Thickness through Section 2.2.13
Thermal Insulations.
4 02/03/10 • Updated Section 2.4.5, Division 1 Designs.
3 10/27/04 • Updated references throughout, including change to EE forms unique ID.
2 09/17/04 • Reformatted throughout. Complete rewrite.
1 N/A • N/A
0 N/A • Initial publication of master specification.
Records
• All documents as stated in All submittals (records) generated as a result of this document will be
Appendix A. retained in accordance with CW-200, Records Retention Schedule.
1.0 General
1.1 Scope
This specification together with the associated data sheets, E-403-DAS-001 and E-403-DAS-002, covers
the design, manufacturing, testing, and supply of an electrical resistance heat tracing system for
mechanical piping and equipment installations for installation at Alyeska facilities located in Alaska.
1.6.1 Location
North Slope and the Interior of Alaska.
1.6.4 Elevation
50 to 2400 Feet Above Sea Level
2.4.2 Classification
The Data Sheets shall define the area electrical classification.
1. Unclassified (Non-hazardous) areas.
2. Classified Areas
a. Class I, Division 1, Groups C and D
Class I, Division 2, Groups C and D
Minimum Auto-Ignition 320F (160C)
b. Class I, Zone 1, Groups IIA and IIB
Class I, Zone 2, Groups IIA and IIB
Minimum Auto-Ignition 320F (160C)
2.4.7 NRTL
All equipment must be Approved, Certified, Labeled or Listed by a Nationally Recognized Testing
Laboratory (NRTL). Refer to Appendix I, Nationally Recognized Testing Laboratories.
2.7 Grounding
2.7.1 Ground Wire
Each power circuit shall contain a green insulation ground wire for grounding of all heater power
connection boxes. The ground wire shall be sized per NEC requirements, and shall be grounded to the
control panel ground bus.
2.8.4 RTD
The resistance-monitoring device shall be a 3-wire 100 ohm platinum resistance temperature device
(RTD). The alpha shall be .00385 ohm/ohm C.
PIPE SIZE 2" 3" 4" 6" 8" 10" 12" 14"
150# VALVE 9 FT 10 FT 12 FT 15 FT 18 FT 20 FT 23 FT 25 FT
300# VALVE 9 FT 11 FT 13 FT 16 FT 19 FT 22 FT 25 FT 27 FT
600# VALVE 9 FT 11 FT 14 FT 18 FT 21 FT 24 FT 26 FT 28 FT
900# VALVE 11 FT 12 FT 14 FT 19 FT 23 FT 26 FT 29 FT 30 FT
1500# VALVE 11 FT 13 FT 15 FT 20 FT 23 FT 27 FT 31 FT 34 FT
2500# VALVE 12 FT 16 FT 17 FT 23 FT 26 FT 31 FT 35 FT N/A
FLANGES 6 IN 7 IN 9 IN 14 IN 18 IN 22 IN 26 IN 28 IN
DEAD LEGS 12 IN 14 IN 18 IN 28 IN 36 IN 44 IN 52 IN 56 IN
3.2 Wiring
3.2.1 Accessibility
All power cable terminations shall be easily accessible.
3.2.16 CT Terminals
The terminal blocks to be supplied for all current transformer secondary wiring shall be of the short
circuiting type.
3.2.17 CT Grounding
The ground connection for current transformers shall be made at the first terminal block and not at the
CT.
3.2.20 No Splices
Wire and cable circuits shall be installed continuous from point to point without splices, unless
connections are made at junction boxes with terminal blocks per applicable Vendor drawings that have
been approved by the Purchaser and the Owner.
3.3 Conduit
3.3.1 Copper-Free Aluminum
The electrical conduit fittings shall be copper-free aluminum or non-corrosive, non-metallic materials
specifically approved for the purpose. All components shall be approved, listed and labeled. Pipe fittings
or brass fittings are not acceptable.
3.3.4 Reducers
The use of reducers at conduit connections to junction boxes is not allowed.
3.3.5 Drains
Conduit low points shall be provided with drains.
3.4.2 Painting
1. Each heat trace panel shall be cleaned, primed and painted, in accordance with the Manufacturer’s
standard practice, with a minimum of two coats of paint. Final exterior finish shall be the
Manufacturer's standard light grey. No. 61 light grey is preferred, per ANSI Z55.1.
2. With the exception of galvanized items, all surfaces shall be painted and no raw metal shall be
exposed. All surfaces under or behind electrical panels shall be painted, even if not exposed.
3. The inside of all NEMA 1, 4 and 12 junction boxes, control panels, etc. shall be painted white.
4. Nameplates shall be affixed only to pre-painted surfaces.
3.4.4 Grounding
1. A copper ground bus shall be installed at the bottom of each control panel assembly and shall be
solidly bound to the panel enclosure.
2. The ground bus shall be minimum 1/4" x 1" copper and shall extend across the entire width of the
enclosures. The ground bus shall be provided with two main compression type lugs (one at each end)
for connection of No. 2/0 AWG copper cables to the facility grounding grid.
3. All instrument cable shields and all equipment ground wires entering the control panel shall be
connected to the ground bus using bolt-on grounding lugs.
3.4.5 Labeling
1. All control panel instruments, electrical components and control devices shall be labeled in
accordance with the Vendor’s drawings. Descriptions shall be coordinated with the Purchaser's
requirements.
2. Power distribution panelboards shall be provided with typed directories and all breakers shall be
individually identified showing circuit numbers.
3.5.5 Accessories
The accessories may be metallic or non-metallic. They shall be Approved/Listed for the Division where
they shall be installed and with the heating device that they are connecting.
3.7.4 Start-Up
1. Initial startup of heat traced system shall be done under the supervision of a trained technician to
ensure proper system operation.
2. All control and safety devices shall be operated and the system operating data shall be checked
against design calculations. Detailed operating instructions shall be provided.
3.8.11 Location
Heating panels shall be attached to the tank wall and connected to power per the Manufacturer's
recommended procedures.
3.9.3 Contact
The process tube(s) and electric heating cable shall be cabled together to ensure contact is maintained
throughout the length of the product.
3.9.7 Labeling
The finished product shall be labeled its entire length with a minimum of the Manufacturer’s name,
catalog number, and country of origin. Product containing electric heating cables shall also be labeled
"caution electric" for its entire length. Long lengths of product shall be coiled and level wound on a
wooden spool. Lengths less than 25' may be straight lengths in a wooden crate.
3.10.4 Venting
Vent extensions for liquid pressure sensing instrument shall be available when venting must be done
outside the enclosure.
3.10.5 Windows
Windows for total enclosures shall be available in lexan and safety glass in 6" circular, 10" or 12" square.
3.10.6 Drains
Drains shall be installed to prevent water accumulation in the enclosure.
3.11.4 Insulation
Insulation shall be high density, 1200F Fiberglass or No. 8 density, 1900 F ceramic fiber. Thickness
shall be as required by application and temperature requirements.
3.11.9 Hardware
All hardware shall be 304 stainless steel.
3.11.10 Covers
Covers shall be constructed and installed to shed water. The closing seams shall be located at the
gravitational bottom.
3.11.11 Seams
All seams shall be sewn using a locked double stitch with a minimum of seven stitches per inch. The
thread must be able to withstand the full process temperature without degradation. Hog rings or staples
shall not be used as a method of seam closure. For holding the cover in place, cinch belts shall be used.
Belts shall be made of outer jacket materials and two stainless steel D-ring fasteners. Velcro hook and
loop fasteners shall be used to secure end of belt to cover after closing.
Notes:
1. Isolate braid from ground with heat shrinkable tubing.
2. Heat trace tape shall be dressed to minimize the amount of heater inside the box.
NOTES:
1. RTD, if required, shall be placed away from spiral.
2. Use 3M Scotch 69 fiberglass cloth tape.
GROUND BUS
MOTOR
THRU BOLT OR DRILL & TAP CONTROL
CENTER OR
7/16" DIA. HOLE CONTROL
CL PANEL
3-1/8 "
3/16"
5/8"
2 HOLES 9/64”
1-1/4"
1/32" BEVEL
SAMPLE
LETTERING
18 LETTERS OR SPACES
TOP OR BOTTOM ROWS
SAMPLE
LETTERING
REQUIRED
15 LETTERS OR SPACES
CENTER ROW
NOTES:
1. Dimensions are minimum, increase as required.
2. Material: Laminated Bakelite, 1/16" thick, white surface, black core.
3. Engraving: Engrave through white surface to expose black core. Lettering style shall be condensed
Gothic, 1/4" high, with 1/8” between lines.
4. Lettering: Arrange all lettering to the center of the plate. Use one, two or three lines of lettering as
shown on nameplate schedule.
5. Attachment to NEMA 7 Enclosures shall be in accordance with UL Standards for Safety 698, 886,
1203, and 1604.
Conduit Nipple
(Minim um Length) Explosion Pr oof
Term inal Box
(COUNTERBORE BOX
IF RE QUIRED P ER
UL STANDARD 886)
Fema le Union
Rigid
Alum inum
Conduit
APPLICATION
Crouse-Hinds LNR Non-Metallic Conduit Liner is a cylindrical plastic insert installed at the end of rigid and
intermediate metallic conduit to provide for the smooth entry of conductors into hazardous and non-
hazardous enclosures. No tools are required for installation.
A smooth entry is required under NEC Article 342.28, 344.28, UL 514B, and UL-886 to protect conductor
insulation from possible damage when being pulled through conduit into or out of enclosures.
INSTALLATION
Crouse-Hinds LNR conduit liner is used with rigid metallic conduit in the following installation conditions:
Conduit extends
into the enclosure.
Figure 1.
2. Push the liner into the conduit until the flange butts against the end of the conduit or box. See Figure
2.
Figure 2.
Figure 3.
Exception:
Recognized component terminal blocks may be installed in the field in a listed cabinet or listed junction
box by a licensed electrician when a copy of the terminal component directory information is installed in
the enclosure.
NOTES:
1. An approved certifier is one that complies with the American National Standard for Certification –
Third-Party Certification Program ANSI Z34.1. Any Nationally Recognized Testing Laboratory (NRTL)
that is recognized by the U.S. Department of Labor, Occupational Safety & Health Administration
(OSHA) is accepted by the State of Alaska, Department of Labor.
2. For a detailed list of the specific ANSI and other national standards that are recognized to evaluate
products by NRTL, refer to the U.S. Department of Labor, OSHA website at http://www.osha-
slc.gov/dts/otpca/nrtl/index.html
NOTE:
The above testing laboratories are acceptable for the product categories listed. The NRTL’s are
acceptable only if they evaluate the product in accordance with an ANSI approved standard. For
example, CSA is an acceptable NRTL but not for evaluating products to CSA standards.