Fire Alarm System

Testing Procedure
Contractor :
Project :
Date :

SN Test Result on FACP Information Technical Message Isolation Fault Fire


1 Activation of any Automatic Detector Fire Alarm
2 Activation of any Manual Call point Fire Alarm
3 Activation of ANY Manual Discharge Signal Fire Alarm
4 Activation of ANY First Stage Alarm Fire Alarm
5 Activation of ANY Second Stage Alarm Fire Alarm
Panel Buzzer is activated
FIRE LED IS ON
6 Fire Alarm
All Sounders and Flasher activated
All Control module activation
7 Activation of Pressure Low Alarm Switch Technical Message
8 Activation of Tamper Switch Technical Message
9 Activation of Flow Switch Technical Message
10 Technical Message Panel Buzzer is activated
11 Open fire alarm loop at any place Open Loop Fault
12 Any device missing from the system Device missing Fault
13 Battery is low veltage or disconnected Battery Failure Fault
14 AC220 is lost Mains Failure Fault
15 Panel Buzzer is activated
Fault
16 Fault LED IS ON
17 Any detector is dirty Change recommended -information
18 Information Message Panel Buzzer is activated
19 Execute Device OFF from panel Isolation
20 ISOLATION ISOLATION LED is ON
Site Engineer
Name :
Signature :