CBD-Switchgear

Date:5/21/2020
EMAS
Egyptian Co. For Manufacturing
And Advanced Systems

Replies to the comments of Switchboards general submittals of CBD no. MAT-CSCEC-00-EL-LV-


0101-01
Point EMAS Reply
2 Attached new compliance sheet
3 Attached Technical offer of tower C01 & D01 with all material used
4 Attached data sheet
Confirm, according to specs "otherwise enclosure thickness shall not be less than
5
1.5mm"
6 attached data sheet of the contactor
Sorry for conflict, kindly cancel the last reply, EMAS confirm that each outgoing circuit
8 in Panelboards is protected against earth fault current, in addition to over current and
short circuit protection
9 attached data sheet of adj. inst. MCCB 160A
10 Confirm according to recived drawing E18066-0102D-FD-02-C01-MH-8-00-014-1
12 Attached type test certificate
13 Complete short circuit and selectivity studies will be submitted in the shop DWGs stage
15 Confirm
20 Spare parts attached in Technical offer of each building
21 attached SAT procedures

1/2
CBD-Switchgear

Date:5/21/2020
EMAS
Egyptian Co. For Manufacturing
And Advanced Systems

Comments on MCCB
Point EMAS Reply
1 feeders with ampere rating equal to or more than 800A will be ACB Category B
Comments on MCB
1 Data sheet of all MCB is attached
Comments on contactors
1 Contactors is attached in material list & data sheet
Comments on Disconnector switch (MCS)
Switch disconnector is molded case switch can make-break-isolate current
1
attached technical data of switch disconnector
Comments on Meters
Schedules of the project don't specified anything in case of using metering it will be as
1
attached metering datasheet
Comments on Rev.01
Confirm panel boards comply with IEC 61439-1 & IEC 61439-3 as per attached
1
certifacte & catalogue
2 Confirm according to new compliance sheet
3 Detailed shop drawings will be submitt in design stage
4 Confirm.
5 In design stage
6 Noted
Comments on MCCB
7 Confirm
8 MCCB comply with IEC 60947 as mentioned in data sheet
9 Siemens MCCB trip unit are not interchangeable as per attached
10 Confirm according to recived drawing E18066-0102D-FD-02-C01-MH-8-00-014-1
11 Data sheet is attached
12 Contractor scope
Detailed shop drawings will be submitt in design stage with panel dimension for
13
approval
Comments on MCB
14 Attached MCB data sheet
15 Attached MCB data sheet
Comments on MCB
16 Confirm new data sheet attached
17 Confirm RCCB will be type A according to IEC tandard

2/2