Cap 4. Industrial-Motor-Control-7th-Edition-by-stephen-L-Herman

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Chapter 6

The Control Transformer

OBJECTIVES

After studying this chapter, the student will be able to


●● Discuss the use of control transformers in a control circuit.
●● Connect a control transformer for operation on a 240- or 480-volt system.

Most industrial motors operate on voltages that the two primary windings are connected parallel
range from 240 to 480 volts. Magnetic control to each other as shown in Figure 6–1. Notice that
systems, however, generally operate on 120 volts. in Figure 6–1 the H1 and H3 leads are connected
A control transformer is used to step the 240 or together, and the H2 and H4 leads are connected
480 volts down to 120 volts to operate the con- together. Because the voltage applied to each pri-
trol system. There is really nothing special about mary winding is the same, the effect is the same as
a control transformer except that most of them having only one primary winding with 200 turns of
are made with two primary windings and one sec- wire in it. This means that when the transformer
ondary winding. Each primary winding is rated at is connected in this manner, the turns ratio is 2:1.
240 volts, and the secondary winding is rated at When 240 volts are connected to the primary wind-
120 volts. This means there is a turns ratio of 2:1 ing, the secondary ­voltage is 120 volts.
(2 to 1) between each primary winding and the sec- If the transformer is to be used to step 480 volts
ondary winding. For example, assume that each down to 120 volts, the primary windings are con-
primary winding contains 200 turns of wire, and nected in series as shown in Figure 6–2. With the
the secondary ­winding contains 100 turns. There windings connected in series, the primary winding
are two turns of wire in each primary winding for now has a ­total of 400 turns of wire, which makes
every one turn of wire in the secondary. a turns ratio of 4:1. When 480 volts is connected
One of the primary windings of the control to the primary ­winding, the secondary winding has
transformer is labeled H1 and H2. The other pri- an output of 120 volts.
mary winding is labeled H3 and H4. The secondary Control transformers generally have screw
winding is ­labeled X1 and X2. If the transformer terminals connected to the primary and second-
is to be used to step 240 volts down to 120 volts, ary leads. The H2 and H3 leads are crossed to

76

Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
77
Chapter 6 The Control Transformer

H1 H3 X1

240 VOLTS AC 120 VOLTS AC

© Cengage Learning 2014


H2 H4 X2

Figure 6–1
Primaries connected in parallel for 240-volt operation.

H1

H2 X1

480 VOLTS AC 120 VOLTS AC


H3 X2

© Cengage Learning 2014


H4

Figure 6–2
Primaries connected in series for 480-volt operation.

make connection of the primary winding easier,


Figure 6–3. For example, if the transformer is to be
H4 H2 H3 H1 connected for 240 volt ­operation, the two primary
windings must be connected ­parallel to each other
as shown in Figure 6–1. This connection can be
made on the transformer by using one metal link to
connect leads H1 and H3, and another metal link
to connect H2 and H4 (Fig­ure 6–4).
© Cengage Learning 2014

If the transformer is to be used for 480 volt


­o peration, the primary windings must be con-
nected in series as shown in Figure 6–2. This con-
X1 X2
nection can be made on the control transformer by
using a metal link to connect H2 and H3 as shown
Figure 6–3 in Figure 6–5. A ­t ypical control transformer is
Primary leads are crossed. shown in Figure 6–6.

Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
78
Chapter 6 The Control Transformer

H1 H2 H3 H4
H4 H2 H3 H1

208 V

277 V
0V

380 V
© Cengage Learning 2014
X1 X2

Figure 6–4
Metal links used to make a 240-volt connection. 120 V

© Cengage Learning 2014


X2 X1

H4 H2 H3 H1 Figure 6–6
Control transformer.

480 277 240 208 C


© Cengage Learning 2014

X1 X2

Figure 6–5
Metal link used to make a 480-volt connection.

© Cengage Learning 2014


X2 120 X1

Some control transformers contain a multi- Figure 6–7


tapped primary instead of two separate windings Control transformer with a multi-tapped primary
(Figure 6–7). The transformer in this example is winding.
designed to step voltages of 480, 277, 240, or 208
down to 120.
operate inductive devices such as the coils of re-
Power Rating lays and motor starters (Figure 6–8). The volt-
The power rating of control transformers generally ampere rating indicates the amount of current
ranges from 0.75 kilovolt-ampere, or 75 volt-am- the transformer can supply to operate control de-
peres, to 1 kilovolt-ampere, or 1000 volt-amperes. vices. To determine the maximum output current
The rating is indicated in volt-amperes, not watts, of a transformer, divide the volt-ampere rating by
because transformers generally supply power to the secondary voltage. The transformer shown in

Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
79
Chapter 6 The Control Transformer

Figure 6–8 has a power rating of 250 volt-amperes.


If the secondary voltage is 120 volts, the maxi-
mum secondary current would be 2.08 amperes.
VA
I5
E
250
I5
120
I 5 2.08 A
A control transformer intended to operate a
single motor starter may have a rating of 75 to 100
volt-­a mperes. Transformers intended to supply
power to an entire relay cabinet have much higher
ratings, depending on the number of devices and

© Cengage Learning 2014


their current requirements.

Grounded and Floating Control


Systems
Figure 6–8 One side of the secondary winding of a control
The power rating of a transformer is listed in transformer is often grounded (Figure 6–9). When
volt-amperes.
this is done, the control system, is referred to as a

L1 L2 L3

M OL

M OL
MOTOR
M OL

CONTROL TRANSFORMER

OL OL OL
© Cengage Learning 2014

Figure 6–9
One side of the transformer has been grounded.

Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
80
Chapter 6 The Control Transformer

L1 L2 L3

M OL

M OL
MOTOR
M OL

CONTROL TRANSFORMER

OL OL OL
M

M
VOLTMETER

© Cengage Learning 2014


GROUNDED POINT

Figure 6–10
Voltage can be measured by connecting one meter probe to any grounded point.

grounded system. Many industries prefer to ground and induced voltage produced by surrounding
the control system, and it is a very common prac- magnetic fields. These are generally referred to as
tice. Some technicians believe that it is an aid when ghost voltages. A low-impedance meter such as a
troubleshooting a problem. Grounding one side plunger-type voltage tester would indicate no volt-
of the control transformer permits one lead of a age. Accurate voltage measurement can be made in
­voltmeter to be connected to any grounded point a float control system, however, by connecting one
and the other voltmeter lead to be used to test voltmeter probe directly to one side of the control
­voltage at various locations throughout the circuit transformer (Figure 6–12). Because both grounded
(Figure 6–10). and floating control systems are common, both are
However, it is also a common practice to illustrated throughout this text.
not ground one side of the control transformer.
This is generally referred to as a floating system.
If one voltmeter probe were to be connected to a Transformer Fusing
grounded point, the meter reading would be erro- Control transformers are generally protected
neous or meaningless because there would not be by fuses or circuit breakers. Protection can be
a complete circuit (Figure 6–11). High-impedance placed on the primary or secondary side of the
voltmeters would probably indicate some amount transformer, and some industries prefer protec-
of voltage caused by the capacitance of the ground tion on both sides. NEC Section 430.72(C) lists

Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
81
Chapter 6 The Control Transformer

L1 L2 L3

M OL

M OL
MOTOR
M OL

CONTROL TRANSFORMER

OL OL OL
M

M
VOLTMETER

© Cengage Learning 2014


GROUNDED POINT

Figure 6–11
Floating control systems do not ground one side of the control transformer. Connecting a voltmeter probe to a
grounded point would provide meaningless readings because a complete circuit would not exist.

EXAMPLE: requirements for the protection of transformers


employed in motor control circuits. This section
What is the maximum fuse size permitted basically states that control transformers that have
to protect the primary winding of a control a primary current of less than 2 amperes shall be
protected by an overcurrent device set at not more
transformer rated at 300 volt-amperes and
than 500% of the rated primary current. This large
connected to 240 volts? percentage is necessary because of the high inrush
current associated with transformers. To deter-
I 5 VA
E mine the rated current of the transformer, divide
the volt-ampere rating of the transformer by the
I 5 300 primary voltage.
240 NEC Section 430.72(C)(2) states that fuse pro­
tection in accordance with 450.3 is permitted also.
I 5 1.25 A
This section states that primary protection for
Fuse size 5 1.25 3 5 transformers rated 600 volts or less is determined
Fuse size 5 6.25 A in NEC Table 430.3(B). The table indicates a rating
NEC Section 240.6 indicates that a standard of 300% of the rated current.
The secondary fuse size can also be determined
fuse size is 6 amperes. A 6 ampere fuse
from NEC Table 450.3(B). The table indicates a rat-
would be used. ing of 167% of the rated secondary current for

Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
82
Chapter 6 The Control Transformer

L1 L2 L3

M OL

M OL
MOTOR
M OL

CONTROL TRANSFORMER

VOLTMETER

OL OL OL

© Cengage Learning 2014


M

Figure 6–12
Connecting one meter probe directly to one side of the transformer provides accurate readings on a floating
control system.

fuses ­protecting a transformer secondary with a The nearest standard fuse size listed in 240.6
current of less than 9 amperes. Assuming a con- without ­going over this value is 3 amperes. The sec-
trol voltage of 120 volts, the rated secondary cur- ondary fuse size can be set at a lower percentage of
rent of the transformer in the previous example the rated current because the secondary does not
would be 2.5 amperes (300/120). The fuse size experience the high inrush current of the primary.
would be: Because primary and ­secondary fuse protection is
2.5 3 1.67 5 4.175 A common throughout in dustry, control circuits pre-
sented in this text illustrate both.

Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
83
Chapter 6 The Control Transformer

●● Review Questions
1. What is the operating voltage of most magnetic that contains six motor starters and six pi-
control systems? lot lamps. All control components operate
2. How many primary windings do control trans- on 120 volts AC. Two of the motor starters
formers have? have coil currents of 0.1 amperes each and
four have coil currents of 0.18 amperes each.
3. How are the primary windings connected when The six pilot lamps are rated at 5 watts each.
the transformer is to be operated on a 240-volt The supply room has control transformers
system? with the following rating (in volt-amperes):
4. How are the primary windings connected when 75, 100, 150, 250, 300, and 500. Which of
the transformer is to be operated on a 480-volt the available control transformers should
system? you choose to supply the power for all the
5. Why are two of the primary leads crossed on a control components in the cabinet? (Choose
control transformer? the smallest size that will supply the power
needed.)
6. You are an electrician working in an industrial
plant. You are building a motor control cabinet

Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.

You might also like