Professional Documents
Culture Documents
Cap 4. Industrial-Motor-Control-7th-Edition-by-stephen-L-Herman
Cap 4. Industrial-Motor-Control-7th-Edition-by-stephen-L-Herman
Cap 4. Industrial-Motor-Control-7th-Edition-by-stephen-L-Herman
OBJECTIVES
Most industrial motors operate on voltages that the two primary windings are connected parallel
range from 240 to 480 volts. Magnetic control to each other as shown in Figure 6–1. Notice that
systems, however, generally operate on 120 volts. in Figure 6–1 the H1 and H3 leads are connected
A control transformer is used to step the 240 or together, and the H2 and H4 leads are connected
480 volts down to 120 volts to operate the con- together. Because the voltage applied to each pri-
trol system. There is really nothing special about mary winding is the same, the effect is the same as
a control transformer except that most of them having only one primary winding with 200 turns of
are made with two primary windings and one sec- wire in it. This means that when the transformer
ondary winding. Each primary winding is rated at is connected in this manner, the turns ratio is 2:1.
240 volts, and the secondary winding is rated at When 240 volts are connected to the primary wind-
120 volts. This means there is a turns ratio of 2:1 ing, the secondary voltage is 120 volts.
(2 to 1) between each primary winding and the sec- If the transformer is to be used to step 480 volts
ondary winding. For example, assume that each down to 120 volts, the primary windings are con-
primary winding contains 200 turns of wire, and nected in series as shown in Figure 6–2. With the
the secondary winding contains 100 turns. There windings connected in series, the primary winding
are two turns of wire in each primary winding for now has a total of 400 turns of wire, which makes
every one turn of wire in the secondary. a turns ratio of 4:1. When 480 volts is connected
One of the primary windings of the control to the primary winding, the secondary winding has
transformer is labeled H1 and H2. The other pri- an output of 120 volts.
mary winding is labeled H3 and H4. The secondary Control transformers generally have screw
winding is labeled X1 and X2. If the transformer terminals connected to the primary and second-
is to be used to step 240 volts down to 120 volts, ary leads. The H2 and H3 leads are crossed to
76
Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
77
Chapter 6 The Control Transformer
H1 H3 X1
Figure 6–1
Primaries connected in parallel for 240-volt operation.
H1
H2 X1
Figure 6–2
Primaries connected in series for 480-volt operation.
Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
78
Chapter 6 The Control Transformer
H1 H2 H3 H4
H4 H2 H3 H1
208 V
277 V
0V
380 V
© Cengage Learning 2014
X1 X2
Figure 6–4
Metal links used to make a 240-volt connection. 120 V
H4 H2 H3 H1 Figure 6–6
Control transformer.
X1 X2
Figure 6–5
Metal link used to make a 480-volt connection.
Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
79
Chapter 6 The Control Transformer
L1 L2 L3
M OL
M OL
MOTOR
M OL
CONTROL TRANSFORMER
OL OL OL
© Cengage Learning 2014
Figure 6–9
One side of the transformer has been grounded.
Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
80
Chapter 6 The Control Transformer
L1 L2 L3
M OL
M OL
MOTOR
M OL
CONTROL TRANSFORMER
OL OL OL
M
M
VOLTMETER
Figure 6–10
Voltage can be measured by connecting one meter probe to any grounded point.
grounded system. Many industries prefer to ground and induced voltage produced by surrounding
the control system, and it is a very common prac- magnetic fields. These are generally referred to as
tice. Some technicians believe that it is an aid when ghost voltages. A low-impedance meter such as a
troubleshooting a problem. Grounding one side plunger-type voltage tester would indicate no volt-
of the control transformer permits one lead of a age. Accurate voltage measurement can be made in
voltmeter to be connected to any grounded point a float control system, however, by connecting one
and the other voltmeter lead to be used to test voltmeter probe directly to one side of the control
voltage at various locations throughout the circuit transformer (Figure 6–12). Because both grounded
(Figure 6–10). and floating control systems are common, both are
However, it is also a common practice to illustrated throughout this text.
not ground one side of the control transformer.
This is generally referred to as a floating system.
If one voltmeter probe were to be connected to a Transformer Fusing
grounded point, the meter reading would be erro- Control transformers are generally protected
neous or meaningless because there would not be by fuses or circuit breakers. Protection can be
a complete circuit (Figure 6–11). High-impedance placed on the primary or secondary side of the
voltmeters would probably indicate some amount transformer, and some industries prefer protec-
of voltage caused by the capacitance of the ground tion on both sides. NEC Section 430.72(C) lists
Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
81
Chapter 6 The Control Transformer
L1 L2 L3
M OL
M OL
MOTOR
M OL
CONTROL TRANSFORMER
OL OL OL
M
M
VOLTMETER
Figure 6–11
Floating control systems do not ground one side of the control transformer. Connecting a voltmeter probe to a
grounded point would provide meaningless readings because a complete circuit would not exist.
Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
82
Chapter 6 The Control Transformer
L1 L2 L3
M OL
M OL
MOTOR
M OL
CONTROL TRANSFORMER
VOLTMETER
OL OL OL
Figure 6–12
Connecting one meter probe directly to one side of the transformer provides accurate readings on a floating
control system.
fuses protecting a transformer secondary with a The nearest standard fuse size listed in 240.6
current of less than 9 amperes. Assuming a con- without going over this value is 3 amperes. The sec-
trol voltage of 120 volts, the rated secondary cur- ondary fuse size can be set at a lower percentage of
rent of the transformer in the previous example the rated current because the secondary does not
would be 2.5 amperes (300/120). The fuse size experience the high inrush current of the primary.
would be: Because primary and secondary fuse protection is
2.5 3 1.67 5 4.175 A common throughout in dustry, control circuits pre-
sented in this text illustrate both.
Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.
83
Chapter 6 The Control Transformer
●● Review Questions
1. What is the operating voltage of most magnetic that contains six motor starters and six pi-
control systems? lot lamps. All control components operate
2. How many primary windings do control trans- on 120 volts AC. Two of the motor starters
formers have? have coil currents of 0.1 amperes each and
four have coil currents of 0.18 amperes each.
3. How are the primary windings connected when The six pilot lamps are rated at 5 watts each.
the transformer is to be operated on a 240-volt The supply room has control transformers
system? with the following rating (in volt-amperes):
4. How are the primary windings connected when 75, 100, 150, 250, 300, and 500. Which of
the transformer is to be operated on a 480-volt the available control transformers should
system? you choose to supply the power for all the
5. Why are two of the primary leads crossed on a control components in the cabinet? (Choose
control transformer? the smallest size that will supply the power
needed.)
6. You are an electrician working in an industrial
plant. You are building a motor control cabinet
Copyright 2012 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part.