1.

THE COPYRIGHT OF THIS DRAWING IS VESTED IN


General Construction Notes and Guidance: 12. Wall ties to be Austenitic Stainless Steel complying with BS EN 845-1. "AC DESIGN SOLUTIONS LTD." AND IT MAY NOT BE REPRODUCED IN WHOLE
OR PART OR USED FOR THE MANUFACTURE OF ANY ARTICLE WITHOUT THE
EXPRESS PERMISSION OF THE COPYRIGHT HOLDERS.
1. Calculations are not to be used for the purpose of ordering materials and should 13. Masonry walls to be properly bonded and solidly put together with mortar and
2. DO NOT SCALE THE DRAWINGS. WORK TO FIGURED DIMENSIONS ONLY.
only be used for Building Regulations submissions. All dimensions should be checked constructed of masonry unites conforming to: ANY MISSING OR NEEDED DIMENSIONS MUST BE REPORTED BACK TO THE
ENGINEER. NO ENGINEERING RESPONSIBILITY IS HELD IF THIS OR ANY OF THE
by the contractor on site. · Clay Bricks or blocks to BS EN 771-1;
NOTES ARE NOT FOLLOWED.

3. ALL DIMENSIONS ARE IN mm UNLESS NOTED OTHERWISE.


2. All steelwork to be mechanically wire brushed and painted two coats of red oxide. · Calcium Silicate bricks or blocks to BS EN 771-2; 4. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL RELEVANT
Steelwork located in the cavity or below DPC to be suitably protected with 2 coats of ARCHITECTURAL AND STRUCTURAL DRAWINGS AND SPECIFICATIONS.

bituminous paint. · Concrete Bricks or blocks to BS EN 771-3 or BS EN 771-4; 5. THE CONTRACTOR IS TO ACCEPT FULL RESPONSIBILITY FOR THE STABILITY
AND STRUCTURAL INTEGRITY OF THE EXISTING OR PROPOSED STRUCTURES
WITHIN AND ADJACENT TO THE WORKS.
3. All steelwork connections to use grade 8.8 bolts unless stated otherwise. These are 14. Mortar is to be Mortar designation (iii) according to BS EN 1996-1-1:2005 with it's UK
6. NO VARIATION IN THE STRUCTURAL DETAILS SHOWN ON THESE DRAWINGS
to be spanner tightened using the appropriate podger spanner (min length 460mm) National Annex. WILL BE PERMITTED WITHOUT THE WRITTEN APPROVAL OF THE ENGINEER.

7. ALL FABRICATION/CONSTRUCTION DRAWINGS AND TEMPORARY WORKS


or suitable power tools in accordance with BS2583. If a torque wrench is used the 15. Compressive Strength of Concrete blocks to be not less than 7.3N. DESIGN ARE TO BE PREPARED AND CARRIED OUT BY THE CONTRACTOR.

torque applied should be around 90Nm for M16 bolts, 110Nm for M20 & 130Nm for 8. CONTRACTOR TO CHECK EXISTING/PROPOSED BUILDING DETAILS AND

M24. 16. Walls to be strapped to floors above ground level at intervals not exceeding 2m as DIMENSIONS ON SITE PRIOR TO ORDERING ANY MATERIALS AND
COMPONENTS SPECIFIED BY THE STRUCTURAL ENGINEER. THIS IS NECESSARY
shown in Construction Details Drawings. Tension straps to be Austenitic Stainless TO ENSURE THAT ANY ANOMALIES ARE REPORTED TO THE STRUCTURAL
ENGINEER PRIOR TO ORDERING ANY MATERIALS OR COMPONENTS SO AS
4. All timber to be grade C24 (SC4), unless stated otherwise. Preservative treated to steel conforming to BS EN 845-1 and of tensile strength not less than 8kN. Tension TO ALLOW THE SPECIFIED DETAILS TO BE ALTERED ACCORDINGLY TO SUIT
THE NEWLY UNCOVERED BUILDING DETAILS.
Architects details. straps to be provided in the longitudinal direction of joists as well as Perpendicular 9. POCKETS IN BRICKWORK TO RECEIVE BEAM ENDS ARE TO BE FORMED

5. To be read in conjunction with Architects drawings, any inconsistencies between the direction to joists. NEATLY AND ONLY AS BIG AS REQUIRED FOR CASTING/PLACING OF
REQUIRED PAD STONE -IF ANY- AND FITTING OF BEAM. ALL RESULTING
VOIDS AROUND BEAM ENDS ARE TO BE FREE OF ALL LOOSE DUST AND
drawings should be reported. If any site conditions or existing details are found that 17. Where an opening in a floor or roof for a stairway or the like adjoins a supported MORTAR AND ARE TO BE BRICKED UP OR WETTED THOROUGHLY AND
CONCRETE ENCASED APPROPRIATELY. FOLLOWING BEAM INSTALLATION,
may affect the structural design, Engineer to be notified immediately. wall and interrupts the continuity of lateral support, the following conditions to be BRICKWORK IS TO MATCH EXISTING SURROUNDING BRICK.

6. For details of fire protection to steelwork, see Architects drawings. satisfied: 10. ALL TIMBER MEMBERS IN CONTACT WITH MASONRY WALL TO BE
WRAPPED IN DPM.

7. The Contractor is to ensure that all existing construction is adequately supported, · The maximum permitted length of the opening is to be 3m, measured parallel 11. ALL SCREWS, NAILS, TIMBER CONNECTORS, JOIST HANGER, STEEL
STRAPS, ETC. ARE TO BE AUSTENITIC STAINLESS STEEL OR GALVANIZED STEEL.

using needles and props as required. Where a new beam supports the existing to the supported wall, and 12. ALL STEEL BEAMS AND PLATES TO BE OF GRADE S275.

construction, adequate pre-load is to be applied and suitable packs such as driven · Where a connection is provided by means other than by anchor, this is to be 13. GIVEN STEEL BEAMS SPANS ARE CLEAR SPANS ONLY, WHEN ORDERING
ALLOW FOR ADDITIONAL 300mm FOR BEARING ON EACH BEAM END.
dry-slate introduced, then pointed up with mortar. provided throughout the length of each portion of the wall situated on each 14. STEEL BEAMS SUPPORTED ON MASONRY WALLS TO REST ON S275
SPREADER PLATE (600mm Length X 100mm Width X 25mm Thickness)
8. All blockwork to be 7.3 N/mm2 in class III mortar below DPC in accordance with BS side of the opening, and or PAD STONE (300mm Length X100mm Width X 215mm Height).

5628: Part 3: 2005 or suitable 7.0 N/mm2 foundation quality blocks in class II mortar · where a connection is provided by mild steel anchors, these are to be spaced 15. ALL STEEL BEAMS CARRYING A MASONRY WALL ABOVE TO BE STITCH
WELDED TO S275 STEEL BOTTOM PLATE 300mm WIDTH x 20mm THICK.
in accordance with the manufacturer's instructions. All brickwork below DPC to be closer than 2m on each side of the opening to provide the same number of
Engineering Bricks DPC in accordance with BS 5628: Part 3: 2005. anchors as if there were no opening, and
9. The project requires the introduction of heavy structural elements such as steel · there should be no other interruption of lateral support.
beams or concrete lintels. Although the Construction (Design and Management)
Regulation 2015 would not normally apply to this type of construction, the designer
still has an obligation to foresee risks and bring to the attention of the builder such 18. Wall ties to have a horizontal spacing of 900mm and a vertical spacing of 450mm, or
risks. In consequence, the builder is to take into consideration the placement of all alternatively should be spaced such that the number of wall ties per square metre is
structural elements, ensuring that the method of lifting and placement is safely not less than 2.5 ties/m2. Wall ties also to be provided, spaced not more than
carried out. Responsibility for this element lies with the Contractor. As the existing 300mm apart vertically, within a distance of 225mm from the vertical edges of all
walls need to be propped in order to introduce some of the lintels, this should also openings, movement joints and roof verges. Wall tie length to be 225mm.
03
be considered in relationship to the risk assessment of the Contractor. Safe working
19. All ordered Construction material to be CE Marked and conforming to relevant 02
procedures must be adopted. Responsibility for this element lies with the
British Standards. 01
Contractor. Splice details for long-span beams can often be accommodated if
required.
CONSTRUCTION ISSUE
10. All construction products should be CE marked in accordance current legislation.
This includes all fabricated structural steelwork in accordance with BS EN 1090-1 and Party Wall etc. Act 1996:
BS EN 1090-2. The consequence class is CC2 unless noted otherwise. The service If part of the work is adjacent to the boundary, the adjacent neighbors right to support
class is SC1 for all buildings, SC2 for all lifting beams, sculptures & fall arrest systems. could be affected; the issues associated with Party Wall Act may need to be considered.
Production category will be PC1 unless noted otherwise. All site welded items, S355 This may include providing information to the adjoining owner, giving sufficient notice of
steelwork & CHS lattice girders will be PC2. As such the execution class for buildings works in compliance with the Act. If the following list applies to this project then the Party
will be EXC2. Wall Act will apply.
11. CLIMATE CHANGE: The Building Research establishment have produced a document Installing a new beam into the shared wall between properties
AC DESIGN SOLUTIONS Ltd.
CBG 63 “Climate Change: impact on building design and construction”. Part of their
Demolishing, building or under-pinning an existing shared wall
recommendations are that designers and builders should give consideration to:
Building a new wall at or on the boundary or junction of two properties
a. Increased wind loading by providing additional laps and fixings to roof
coverings Damp-proofing all the way through a party wall
b. Consider foundation depth on shrinkable clays and to avoid future problems, Digging foundations that are within 3m of a Party Wall, where the new foundations are
3 Wolsey Drive, KT12 3AY
increase the depth above standard requirements if there is a risk. This should deeper than the existing ones
be in accordance with the NHBC Standards, Chapter 4.2 Guidance on Building
Where the new foundations are within 6m and lower than a 45° line from the bottom of
near Trees. If the calculations do not specifically design the depths of the General Notes
the existing foundations
foundations to take into account any local trees, then this should be checked
and agreed with the Building Inspector on site. N/A 04/05/2022 M.SALAM YASSER

UK22057 UK22057-S-000 00
1. THE COPYRIGHT OF THIS DRAWING IS VESTED IN
"AC DESIGN SOLUTIONS LTD." AND IT MAY NOT BE REPRODUCED IN WHOLE
OR PART OR USED FOR THE MANUFACTURE OF ANY ARTICLE WITHOUT THE
EXPRESS PERMISSION OF THE COPYRIGHT HOLDERS.

2. DO NOT SCALE THE DRAWINGS. WORK TO FIGURED DIMENSIONS ONLY.


ANY MISSING OR NEEDED DIMENSIONS MUST BE REPORTED BACK TO THE
ENGINEER. NO ENGINEERING RESPONSIBILITY IS HELD IF THIS OR ANY OF THE
NOTES ARE NOT FOLLOWED.

3. ALL DIMENSIONS ARE IN mm UNLESS NOTED OTHERWISE.

4. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL RELEVANT


ARCHITECTURAL AND STRUCTURAL DRAWINGS AND SPECIFICATIONS.

5. THE CONTRACTOR IS TO ACCEPT FULL RESPONSIBILITY FOR THE STABILITY


AND STRUCTURAL INTEGRITY OF THE EXISTING OR PROPOSED STRUCTURES
WITHIN AND ADJACENT TO THE WORKS.
Use C50 PADSTONE 300mm Length X 100mm 6. NO VARIATION IN THE STRUCTURAL DETAILS SHOWN ON THESE DRAWINGS
Width X 215mm Height WILL BE PERMITTED WITHOUT THE WRITTEN APPROVAL OF THE ENGINEER.

7. ALL FABRICATION/CONSTRUCTION DRAWINGS AND TEMPORARY WORKS


DESIGN ARE TO BE PREPARED AND CARRIED OUT BY THE CONTRACTOR.
TRENCH FOOTING 600mmX1000mm
8. CONTRACTOR TO CHECK EXISTING/PROPOSED BUILDING DETAILS AND
TO BE APPROVED BY BUILDING WELDED TO DIMENSIONS ON SITE PRIOR TO ORDERING ANY MATERIALS AND
CONTROL OFFICER ON SITE. 12X300MM BOTTOM PLATE COMPONENTS SPECIFIED BY THE STRUCTURAL ENGINEER. THIS IS NECESSARY
5400 TO ENSURE THAT ANY ANOMALIES ARE REPORTED TO THE STRUCTURAL
ENGINEER PRIOR TO ORDERING ANY MATERIALS OR COMPONENTS SO AS

600
BEAM B10 UC203X203X46
TO ALLOW THE SPECIFIED DETAILS TO BE ALTERED ACCORDINGLY TO SUIT
THE NEWLY UNCOVERED BUILDING DETAILS.

REAR FLAT ROOF JOISTS 9. POCKETS IN BRICKWORK TO RECEIVE BEAM ENDS ARE TO BE FORMED
47X195@350 C24 C/C NEATLY AND ONLY AS BIG AS REQUIRED FOR CASTING/PLACING OF
REQUIRED PAD STONE -IF ANY- AND FITTING OF BEAM. ALL RESULTING
VOIDS AROUND BEAM ENDS ARE TO BE FREE OF ALL LOOSE DUST AND
MORTAR AND ARE TO BE BRICKED UP OR WETTED THOROUGHLY AND
CONCRETE ENCASED APPROPRIATELY. FOLLOWING BEAM INSTALLATION,
Timber Trimmer T2 3No. 47X195 C24 BRICKWORK IS TO MATCH EXISTING SURROUNDING BRICK.
FLITCH BEAM B12 3NO. 47X195 C24 + 2NO. STEEL PLATES
600 PROPOSED GROUND FLOOR TO 600
190X8MM THICK STRENGTH ( 165 N/MM2),
10. ALL TIMBER MEMBERS IN CONTACT WITH MASONRY WALL TO BE
MATCH EXISTING GROUND FLOOR. USING M12 BOLTS AT 400MM SPACING WRAPPED IN DPM.
FLITCH BEAM B11 3NO. 47X195 C24 + 2NO. STEEL PLATES
190X8MM THICK STRENGTH ( 165 N/MM2), 11. ALL SCREWS, NAILS, TIMBER CONNECTORS, JOIST HANGER, STEEL
Timber Trimmer T2 3No. 47X195 C24 USING M12 BOLTS AT 400MM SPACING STRAPS, ETC. ARE TO BE AUSTENITIC STAINLESS STEEL OR GALVANIZED STEEL.

12. ALL STEEL BEAMS AND PLATES TO BE OF GRADE S275.

13. GIVEN STEEL BEAMS SPANS ARE CLEAR SPANS ONLY, WHEN ORDERING
ALLOW FOR ADDITIONAL 300mm FOR BEARING ON EACH BEAM END.
600

14. STEEL BEAMS SUPPORTED ON MASONRY WALLS TO REST ON S275


SPREADER PLATE (600mm Length X 100mm Width X 25mm Thickness)
BEAM B9 UC203X203X71 or PAD STONE (300mm Length X100mm Width X 215mm Height).

WELDED TO 15. ALL STEEL BEAMS CARRYING A MASONRY WALL ABOVE TO BE STITCH
12X300MM BOTTOM PLATE WELDED TO S275 STEEL BOTTOM PLATE 300mm WIDTH x 20mm THICK.
USE CONCRETE LINTEL
1NO. 100X215

USE CONCRETE LINTELS


2NO. 100x215

600

Steel Beam B8 UB203X102X23

03
02
UP UP
01
CATNIC LINTEL CG90/100

CONSTRUCTION ISSUE
BEAM B7 UC152X152X23
600

CATNIC LINTEL WELDED TO


CG90/100 12X300MM BOTTOM PLATE
600 600
600

PROPOSED GROUND FLOOR PLAN


PROPOSED FOUNDATION PLAN AC DESIGN SOLUTIONS Ltd.

3 Wolsey Drive, KT12 3AY

Structural Floor Plans (1/2)


1:50 05/04/2022 M.SALAM YASSER

UK22057 UK22057-S-101 00
1. THE COPYRIGHT OF THIS DRAWING IS VESTED IN
"AC DESIGN SOLUTIONS LTD." AND IT MAY NOT BE REPRODUCED IN WHOLE
OR PART OR USED FOR THE MANUFACTURE OF ANY ARTICLE WITHOUT THE
EXPRESS PERMISSION OF THE COPYRIGHT HOLDERS.

2. DO NOT SCALE THE DRAWINGS. WORK TO FIGURED DIMENSIONS ONLY.


ANY MISSING OR NEEDED DIMENSIONS MUST BE REPORTED BACK TO THE
ENGINEER. NO ENGINEERING RESPONSIBILITY IS HELD IF THIS OR ANY OF THE
NOTES ARE NOT FOLLOWED.

3. ALL DIMENSIONS ARE IN mm UNLESS NOTED OTHERWISE.

4. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL RELEVANT


ARCHITECTURAL AND STRUCTURAL DRAWINGS AND SPECIFICATIONS.

5. THE CONTRACTOR IS TO ACCEPT FULL RESPONSIBILITY FOR THE STABILITY


AND STRUCTURAL INTEGRITY OF THE EXISTING OR PROPOSED STRUCTURES

USE S275 SPREADER PLATE 600MM LENGTH X USE S275 SPREADER PLATE 600MM LENGTH X WITHIN AND ADJACENT TO THE WORKS.

6. NO VARIATION IN THE STRUCTURAL DETAILS SHOWN ON THESE DRAWINGS

100MM WIDTH X 25MM THICKNESS 100MM WIDTH X 25MM THICKNESS WILL BE PERMITTED WITHOUT THE WRITTEN APPROVAL OF THE ENGINEER.

7. ALL FABRICATION/CONSTRUCTION DRAWINGS AND TEMPORARY WORKS


DESIGN ARE TO BE PREPARED AND CARRIED OUT BY THE CONTRACTOR.

USE 2NO. 47X195 C24 USE 2NO. 47X195 C24 8. CONTRACTOR TO CHECK EXISTING/PROPOSED BUILDING DETAILS AND
DIMENSIONS ON SITE PRIOR TO ORDERING ANY MATERIALS AND
COMPONENTS SPECIFIED BY THE STRUCTURAL ENGINEER. THIS IS NECESSARY
ABOVE WINDOW ABOVE WINDOW TO ENSURE THAT ANY ANOMALIES ARE REPORTED TO THE STRUCTURAL
ENGINEER PRIOR TO ORDERING ANY MATERIALS OR COMPONENTS SO AS
TO ALLOW THE SPECIFIED DETAILS TO BE ALTERED ACCORDINGLY TO SUIT
THE NEWLY UNCOVERED BUILDING DETAILS.

BEAM B4 UC203X203X71 9. POCKETS IN BRICKWORK TO RECEIVE BEAM ENDS ARE TO BE FORMED


NEATLY AND ONLY AS BIG AS REQUIRED FOR CASTING/PLACING OF
REQUIRED PAD STONE -IF ANY- AND FITTING OF BEAM. ALL RESULTING
VOIDS AROUND BEAM ENDS ARE TO BE FREE OF ALL LOOSE DUST AND
MORTAR AND ARE TO BE BRICKED UP OR WETTED THOROUGHLY AND
CONCRETE ENCASED APPROPRIATELY. FOLLOWING BEAM INSTALLATION,
BRICKWORK IS TO MATCH EXISTING SURROUNDING BRICK.

10. ALL TIMBER MEMBERS IN CONTACT WITH MASONRY WALL TO BE


WRAPPED IN DPM.

LOFT FLOOR JOISTS 11. ALL SCREWS, NAILS, TIMBER CONNECTORS, JOIST HANGER, STEEL
STRAPS, ETC. ARE TO BE AUSTENITIC STAINLESS STEEL OR GALVANIZED STEEL.
47X195@400 C24 C/C 12. ALL STEEL BEAMS AND PLATES TO BE OF GRADE S275.

13. GIVEN STEEL BEAMS SPANS ARE CLEAR SPANS ONLY, WHEN ORDERING
FLAT ROOF JOISTS ALLOW FOR ADDITIONAL 300mm FOR BEARING ON EACH BEAM END.

47X195@400 C24 C/C 14. STEEL BEAMS SUPPORTED ON MASONRY WALLS TO REST ON S275
SPREADER PLATE (600mm Length X 100mm Width X 25mm Thickness)
or PAD STONE (300mm Length X100mm Width X 215mm Height).

BEAM B3 UC203X203X46 15. ALL STEEL BEAMS CARRYING A MASONRY WALL ABOVE TO BE STITCH
WELDED TO S275 STEEL BOTTOM PLATE 300mm WIDTH x 20mm THICK.
DN

FLITCH BEAM B5 2NO. 47X195 C24 + 1NO. STEEL PLATE


190X10MM THICK STRENGTH ( 165 N/MM2),
TIMBER TRIMMER T1 DN STEEL BEAM B6
USING M12 BOLTS AT 400MM SPACING
2NO. 47X195 C24 UC152X152X23 BEAM B1 UC152X152X37
WELDED TO 12X300MM
LOFT FLOOR JOISTS
BOTTOM PLATE
47X195@400 C24 C/C
UP
Timber Post 100X200 C24 03
02
01
ROOF RAFTERS
BEAM B2 UC203X203X46 TO MATCH EXISTING RAFTERS
CONSTRUCTION ISSUE

LOFT FLOOR JOISTS


47X195@400 C24 C/C

AC DESIGN SOLUTIONS Ltd.

PROPOSED ROOF PLAN PLAN AND JOISTS LAYOUT 3 Wolsey Drive, KT12 3AY
PROPOSED LOFT FLOOR JOISTS LAYOUT
Structural Floor Plans (2/2)
1:25 05/04/2022 M.SALAM YASSER

UK22057 UK22057-S-102 00