PROPOSED ASEANA BLDG

Electrical Load Estimate


Area Allowed VA Back Up
Building Total kVA Total kVA
m2 Lighting Power ACU & Vent. Equipment Power
16 60 35 55

LGF 10,637.10 170,194 638,226 372,298.64 585,040.72 1,765.76 100% 1,765.76

GROUND FLR 12,912.49 206,600 774,750 451,937.29 710,187.17 2,143.47 100% 2,143.47

SECOND FLR 11,937.05 190,993 716,223 417,796.89 656,537.97 1,981.55 100% 1,981.55

THIRD FLR 12,811.20 204,979 768,672 448,392.14 704,616.22 2,126.66 100% 2,126.66

FOURTH FLR 12,811.20 204,979 768,672 448,392.14 704,616.22 2,126.66 100% 2,126.66

FIFTH FLR 7,380.43 118,087 442,826 258,315.19 405,923.87 1,225.15 100% 1,225.15

SIXTH FLR 7,380.43 118,087 442,826 258,315.19 405,923.87 1,225.15 100% 1,225.15

SEVENTH FLR 7,380.43 118,087 442,826 258,315.19 405,923.87 1,225.15 100% 1,225.15

EIGHT FLR 7,380.43 118,087 442,826 258,315.19 405,923.87 1,225.15 100% 1,225.15

NINETH FLR 7,380.43 118,087 442,826 258,315.19 405,923.87 1,225.15 100% 1,225.15

ROOFDECK 1,888.77 30,220 113,326 66,106.95 103,882.35 313.54 100% 313.54

MACHINE ROOM 100.00 1,600 6,000 3,500.00 5,500.00 16.60 100% 16.60

Miscellaneous - - - - - -

100,000.00
PROPOSED ASEANA BLDG
Electrical Load Estimate
PROPOSED ASEANA BLDG -
EE Concept Report 980.71 Davis Langdon and Seah Philippines

ELECTRICAL SUMMARY
1,148 kW 1,148 kW
LGF
1,766 kVA 1,766 kVA
1,393 kW 1,393 kW
GROUND FLR
2,143 kVA 2,143 kVA
1,288 kW 1,288 kW
SECOND FLR
1,982 kVA 1,982 kVA
1,382 kW 1,382 kW
THIRD FLR
2,127 kVA 2,127 kVA
1,382 kW 1,382 kW
FOURTH FLR
2,127 kVA 2,127 kVA
796 kW 796 kW
FIFTH FLR
1,225 kVA 1,225 kVA
796 kW 796 kW
SIXTH FLR
1,225 kVA 1,225 kVA
796 kW 796 kW
SEVENTH FLR
1,225 kVA 1,225 kVA
796 kW 796 kW
EIGHT FLR
1,225 kVA 1,225 kVA
796 kW 796 kW
NINETH FLR
1,225 kVA 1,225 kVA
204 kW 204 kW
ROOFDECK
314 kVA 314 kVA
11 kW 11 kW
MACHINE ROOM
17 kVA 17 kVA

Estimated Load 10,790 kW 10,790 kW


Total Load 16,600 kVA 16,600 kVA
Demand Factor 0.65 0.65
Diversity Factor 1.30 1.30
Maximum demand after Diversity 8,300 kVA 8,300 kVA
Transformer capacity (kVA) 2,500 3,125
Transformer capacity (kW) 2,250 2,500
Number of Transfomer (Normal) 4 3
Number of Transfomer (Spare) 1 1
Total No. of Transformers 5 UNIT 4 UNIT

PROPOSED ASEANA BLDG


EE Concept Report Davis Langdon and Seah Philippines
10,000 kVA 9,375
Assumptions:
16VA/sqm for Lighting ASEANA N 10.00 MVA N 9.38
60VA/sqm for power 2N+1 12.50 MVA N+1 12.50
35VA/sqm for ACU/Ventilation
55VA/sqm for Equipment NHB N 7.5 MVA N+1 9.38