Tech Article - Optimized Use of Power Supply Module
Tech Article - Optimized Use of Power Supply Module
1. It shall be possible to alter protection settings while ACB is in OFF condition through navigation keys.
2. If it is desired to see details of Fault/Event History after the ACB has tripped on Fault. However last trip
record will be available on display without auxiliary power through Query button in P&C Unit.
5. Necessary to build communication between P&C Unit and external modules like REL, TCS, DIO, AO, TM,
EF & REF
Note:
I. For point no.1, 2, 3 & 4 it is not necessary to use PS Module available with L&T only. Any continuous
source of controlled 24V DC can serve the purpose. (Applicable for versions–
MTX2.5/2.5G/3.5/3.5EC/3.5H/4.5)
II. For point no. 5, PS Module available with L&T is must to hardware each & all external module to get
desired features (Applicable in MTX3.5/3.5EC/3.5H/4.5). In this case each MATRIX release needs a PS
Module.
III. Before providing auxiliary power supply to MATRIX P&CU it is necessary to know the VA burden of
MATRIX P&C Unit & Modules for the calculation of total VA demand.
Power Supply Module have 3 sets of auxiliary power output. Set - 2 & 3’s combined VA
burden is 15.5VA & Set -1 with an additional VA burden of 4.8VA. So, total output power
available from PS Module is 20.3VA.
Note:-
Power output set -2 or 3, has to be loaded first, while connecting P&C Unit &
External Modules with Power Supply Module.
Recommended wire for connection of MATRIX release with PS
Module through AS+/AS- SIC port in ACB is 24AWG ( 7/0.2).
F. EXAMPLE
Let us consider a Panel Board having 5 nos. Omega ACBs of different MATRIX P&C Units
& auxiliary power has to be supplied through PS Module as there is no auxiliary power (24Vdc)
source available–
1. Incomer ACB is with MTX3.5EC + ZSI - 1 no.
2. Outgoing ACBs are with MTX3.5 + Modbus COM + ZSI – 3 nos.
Count
P&CU & Modules Total VA burden
(Nos.)
MTX3.5EC 1 3
MTX3.5+ Modbus COM 3 9
ZSI module 4 4
TOTAL VA 16
Connection:
Incomer ACB Outgoing ACBs
Device VA burden Device VA burden
MTX3.5EC : 1 No 3 VA MTX3.5 + COM : 3 Nos 9 VA
ZSI : 1 No 1 VA ZSI : 3 Nos 3 VA
Total 4 VA Total 12 VA
Connect to PS module O/P 1 Connect to PS module O/P 2
So, using only a single PS Module, the above set up can be powered ON.
However, above PS module quantity selection can vary depending on the location/distance of the
modules in the panel as well as the type of module used (refer Point A Note I, II, III)