* Maximum outside temperature: For transport and storage of the 30RB/RQ units the minimum and maximum allowable temperatures are -20℃
and +48℃. It is recommended that these temperatures are used for transport by container.
Heating mode
50 60
40 55
Leaving water temperature, ℃
Outside air temperature, ℃
50
30
45
20
40
10
35
0
30
-10
25
-20
20
0 5 10 15 20 25 -20 -10 0 10 20 30 40 50
10
Operating Range, 30RB039S~160S
Cooling mode
* Maximum outside temperature: For transport and storage of the 30RB/RQ units the minimum and maximum allowable temperatures are -20℃
and +48℃. It is recommended that these temperatures are used for transport by container.
Operating range
50
45
40
35
30
Outside air temperature,oC
25
20
15
10
-5
-10
-15
0 5 10 15 20 25
Full load
Minimum load
9
Options & accessories
015LS Super low noise Acoustic compressor enclosure and low speed fans Super low operating noise
025 Soft starter Electronic compressor starter Reduced compressor start-up current
012 High static pressure* High static pressure fan (80Pa) Additional static pressure up to 80pa
11
Dimensions/Clearances
30RB039S~080S/30RQ039S-078S
1330
419
222
519
1061
2050
1000
1000
1 2
2
1000
1000
Legend:
All dimensions are given in mm
Control box
Water outlet
Water inlet
12
Dimensions/Clearances
30RB100S~160S/30RQ100S-160S
1330
419
222
2258 2050 900
1000
1000
1
2 2
1
1000
1000
Legend:
All dimensions are given in mm
Control box
Water outlet
Water inlet
13
Multiple Chiller Installation
1000
Wall Wall
1000
2000
2000
2000
1000 1000
2000
50
P1 P2
250
Unit's footprint F
250
150
Section F - F
250
300
P3 P4
C Section F - F
A
Note: 4 foot screws M16x220
14
Hydronic Connections
17
13 2
12 10
14 16 1 4
25 5
3
19 18 17
7 6 11
8
14 16 15 9 12
25
7 6
20 5 8 9 2
21 12 3 24
23
22
4 1 26
15
Unit Internal Water Pressure Drop
180
160 5 6
3 4
140 2
100
80
60
40
20
0 1 2 3 4 5 6 7 8 9 10 11 12
270
250
Available static pressure, kPa
230
210
190
170
3 4
1 2
150
0 1 2 3 4 5 6 7 8 9 10 11 12
Water flow rate,l/s
1 30RB039S~060S/30RQ039S~060S 2 30RB080S/30RQ078S
3 30RB100S~120S/30RQ100S~120S 4 30RB160S/30RQ160S
16
Minimum Water Loop Volume
For better control of leaving water temperature, the water loop minimum capacity is given by the formula:
Capacity = CAP (kW) × N Liters
CAP: Unit’s nominal cooling capacity
Application N
Process cooling 30RB039S~160S/30RQ039S~160S Should be greater than 3.5 for better water temperature control
It is often necessary to add a buffer water tank to the circuit in order to achieve the required volume. The tank must itself be internally baffled
in order to ensure proper mixing of the liquid (water or brine). Refer to the examples below.
30RB039S~080S/30RQ039S~078S 30RB100S~160S/30RQ100S~160S
Water-side static pressure kPa 100 200 300 100 200 300
17
31B
Circuit B alarm
30B
20V M N
2.5mm2MAX
24VAC 48VDC MAX
38
Boiler control
37
Field Control Wiring
76
Demand limit #2
75
30RB100S~160S/30RQ100S~160S
30RB039S~080S/30RQ039S~078S
68
20V MIN
2.5mm2MAX
67
24VAC-48VDC MAX
1.5mm2 MAX
24VAC 20mA
31
Circuit A alarm
66
30
2 set points
65
38
Boiler control
37
20V M N
31A
Circuit A alarm
2.5mm2 MAX
35
30A
34
74
35
Customer control system
64
34
Remote cooling / heating switch
63
74
Demand limit #1
33
73
Remote On/Off
32
1.5mm2 MAX
24VAC 20mA
64
Remote cooling / heating switch
63
33
Remote On/Off
32
18
CAT_NGA-E-202005-03
CAT_NGA-E-1411_02