Professional Documents
Culture Documents
SCH 3W RMU GD
SCH 3W RMU GD
PAGE NOS: RATED CURRENT AT BUSBAR 630 A (ALL RATINGS AT BELOW MENTIONED AMBIENT CONDITIONS)
STC 21 kA/3s
LIST OF CONTENTS PAGE NO. INTERNAL ARC AFLR 21kA/0.2s
INFORMATION SHEET 1- 1 DIELECTRIC WITHSTAND 28 kV AC/1 MINUTE
GENERAL ARRANGEMENT 2- 6 IMPULSE WITHSTAND 75 kVP
SINGLE LINE DIAGRAM 7- 8 RATED PEAK CURRENT 52.5 kAP
SCHEMATIC DIAGRAM 9- 13 RATED FREQUENCY 50 Hz
BILL OF MATERIAL 14- 14 C-FUNCTION LOAD BREAK SWITCH- 12kV, 3 PHASE,630 A,21 kA/3s
FOUNDATION DRAWING 15- 16 T2-FUNCTION CIRCUIT BREAKER- 12kV, 3 PHASE,630 A,21 kA/3s
NOTE:
1. CT suitable for Transformer rating : DEGREE OF PROTECTION
11kV, 500kVA to 11kV,2.4MVA TANK IP 67 SS TANK THICKNESS: 2 MM
2. Cable Sizes considered for ALL functions: MECHANISM CHAMBER IP 2X IN CANOPY DOOR OPEN CONDITION
1RX3C- AL XLPE 11kV(E) cable having size 185 to 400 sq. mm CABLE CHAMBER IP 3X IN CANOPY DOOR OPEN CONDITION
Suitable Bushing studs of M16 size for above cable sizes OUTDOOR IP 54 IN CANOPY DOOR CLOSED CONDITION
will be provided. PAINT SHADE
OUTDOOR RAL7032 THICKNESS: MIN 100 MICRONS
LV CHAMBER RAL 7032 THICKNESS: MIN 60 MICRONS
MIMIC (STICKER) RAL 9003
MATERIAL (CRCA/Aluzinc) LOAD BEARING: 2 to 2.5 mm thick
NON LOAD BEARING: 1 to 1.6 mm thick
OPERATING CONDITIONS
AMBIENT TEMPERATURE -5 TO +40 DEG C
ALTITUDE UPTO 1000 METRES ABOVE SEA LEVEL
RMU PARAMETERS
GAS PRESSURE OPERATING: 1.3 BAR (ABSOLUTE) OR 0.3 BAR (RELATIVE) AT 20 DEG C
BUSBAR ALUMINIUM
AUX. SUPPLY 230V AC (NOT IN RMU SCOPE OF SUPPLY)
2 Q11 Load Break Switch SEIL 12 kV, 21 kA/3s 3 Pole Load Break Switch with 3 Pole Manual Earth Switch & counter. FBX 2
LBS Operation: Manual
3 A01 Voltage Presence Indicator SEIL LED type as per IEC 62271-206 (old ref. IEC61958) VPIS-V2 3
Range: To cover 1.3 Bar (absolute) or 0.3 Bar (relative) @20 deg C
Regency/Konly/Electron System/Schneider
4 Manometer Manometer Remote contacts : Not available 1
approved make
Temperature Scale: Multiscale
Manual operating handle For manual operation 1
5 Handle Operating handle SEIL
SUT4/KU2D4/KUDD4/MSTB/eq.
Screw type - (Single T.B or double deck type) For Control Circuit LOT
6 T.B Terminal blocks Elmex/ Phoenix/ Connectwell/ eq KUTSD6/KLTDM4/eq.
Disconnecting type For Instrument Trafo Circuit LOT
KLTDM4/eq.
Disconnecting type For Protection CT LOT
7 Cable boots Cable boots Raychem Suitable for XLPE Al cable Push-on type 3 Sets
1R X 3C upto 400 sq mm
2.5 Sq.mm, PVC Multistrand Cu Wire, 660V Grade For Instrument Trafo Circuit Colour Coded LOT
Finolex/ Polycab/ KEI/ Relicab/ Ultracab/
1.5 Sq.mm, PVC Multistrand Cu Wire, 660V Grade For Control Circuit Black colour LOT
8 Wires Wires Gemtech/ SBEE/ Schneider Approved
make 1.0 Sq.mm, PVC Multistrand Cu Wire, 660V Grade For Remote/ Aux. Contacts Black colour LOT
1 to 2.5 Sq.mm, PVC Multistrand Cu Wire, 660V Grade For Earthing Green/Yellow-green colour LOT
Suitable for XLPE Al cable
9 Cable Clamp Cable Clamps SEIL/eq. Metal 3
1R X 3C upto 400 sq mm
3 Pole over current + earth fault relay with selectable characteristics For breaker feeder
Mounting: Base Mounted
Display: LCD
Settings Range:
10 Relay Protection Relay SEIL I>:0.2 to 2.5, t>:0.1-150s in steps of 0.01s & ti>: 0.01-1.500 in steps of 0.005; I>>:0.5 to DPX-V5 1
30,t>>: 0.03-20s in steps of 0.01s
Ie>:0.05 to 2.5,te>:0.05-150s in steps of 0.01s & tie>:0.01-1.500 in steps of 0.005;Ie>> : 0.5
to 15,te>>:0.04-20s in steps of 0.01s
RS485 port on MODBUS protocol
CTR: 50-100-150/1A,5P10, 2.5VA
11 CT Current transformer NPT/ECS (Protection) 1 set
Resin Cast
Rev. No. Date Revision Details Revised By