Professional Documents
Culture Documents
Mistakes and Improvements in Datacenter Earthing 1691489455
Mistakes and Improvements in Datacenter Earthing 1691489455
EARTHING
MISTAKES
(100’s of earth electrodes (plate/rod/pipe) all around the DC /
Large earth grid in soil (under the building) are the mistakes)
&
IMPROVEMENTS
By S. Gopa Kumar
Member
Page 1 of 18
EARTHING SYSTEM
DATA CENTER
1 Introduction
Earthing plays the major role in safety and reliability in any electrical system. A good earthing arrangement
ensures reliable and long life for the connected electrical installation. For electrical system including LV
and HV installations, the IEC 60364 (IS732 / NEC of India 2023) and IS/IEC 61936-1 laydown the
mandatory requirements. These IEC standards are followed globally.
Eg. in UK the IEC 60364 is adopted as BS7671 called wiring Regulations. Similarly in USA as NFPA 70 (NEC). In India the
IEC 60364 has been adopted as IS732 and NEC of India.
A good and reliable earthing arrangement is necessary to fulfil the following functions.
• Limit touch and step potentials inside and outside the building during faulty conditions, including
lightning.
• Thermal effects (e.g., fire due to short circuits) is avoided satisfying various requirements in the
standard.
• Temporary overvoltage (e.g., TOV in LV during a fault in HV system) is limited to less than the
tolerable limits.
1. NEC 2023(SP30) – National Electrical Code of India 2023. (Adopted from IEC 60364-all parts)
6. ISO 30129: Information technology – Telecommunications bonding networks for buildings and
other structures. (e.g., TIA/ANSI/BICSI 607 in USA)
Subject of the standard: Requirements and recommendations for the design and installation of connections (bonds)
between various electrically conductive elements in buildings and other structures, during their construction or
refurbishment, in which information technology (IT) and, more generally, telecommunications equipment is intended to be
installed in order to minimise the risk to the correct function of that equipment and interconnecting cabling from electrical
Page 2 of 18
hazards, provide the telecommunications installation with a reliable signal reference – which may improve immunity from
EMI.
8. ITU (various)
The below standards (sl. no 10 to 12) can be referred to but are not a legal obligation as the subjects are
already covered in the standards in sl. no 1 to 8 and in the National Regulation.
9. IEEE 1100: IEEE Recommended Practice for Powering and Grounding Electronic Equipment
10. IEEE 142: IEEE Recommended Practice for Grounding of Industrial and Commercial Power
Systems.
The concept of independent earth electrodes as shown in fig.1 & 2, is not only wrong but is the reason for
major electrical accidents. This wrong method also creates and accelerates EMI there by reduces the life
of electrical installation and connected equipment.
Myth: Earth grid as per IEEE80 is required for Transformers feeding to LV system.
Note: Due to this misinterpretation, large grids are made under soil for 11000/433 V application considering expected fault current of
50/65 kA at LV.
Fact: IEEE 80 is a guide, which can be used as an alternate method for making earth grid in
EHV substations
(not GIS). Detailed information can be found in https://www.vidyutsuraksha.com/post/misuse-of-ieee80.
Note: Refer clause 7 for some explanations from IEEE80.
Page 3 of 18
3.3 Violation of ANSI/BICSI/TIA/NECA 607 Standards.
The “conventional earthing methods” followed in India is a violation of requirements in 607 standards.
Professionals working in datacentre ensure compliance to 607 standards, but the basic requirements as
explained in clause 8 is violated.
Myths in earthing: The words “earth” and “earthing” is understood as an electrode in soil. Other myths are
the derivations from this concept.
Myth: Standards and regulation recommend connection to two separate earth pit for transformer neutral,
transformer body, DG neutral, DG body, UPS neutral, UPS body, Panel body, elevator, each and every
electrical appliance. All earth electrodes under soil need interconnection under soil as a grid.
Fact:NO standards or regulations recommend the above. The subject of earthing is about achieving safety
during an earth fault by implementing various electrical safety rules. The most common rule is “protective
equipotential bonding and automatic disconnection of supply ”.
Making separate connections to earth pit from every equipment (as shown in fig 1 and 2) is not
only wrong practice, but the primary reason for electrical accidents and equipment failures.
Myth:Attractive names for earthing such as “Chemical earth, digital earth, pipe in pipe, plate in pipe, NCE
charge electrode, earth enhancing compound, chemical compound, granule backfill compound, carbon
earth, gel earthing electrode”. Some of them claim that they can absorb lightning, fault current and solve
major electrical problems. They are capable of providing an earth pit resistance close to 1 ohm in any soil.
Fact:Resistance of an earth electrode in soil does not have a role in a LV system (including neutral of the
source, UPS, electronics etc). The compounds used are fly ash, bentonite, carbon flakes, graphite, cement
etc. Except conductive cement, others seem to be creating corrosion problem to earth electrode in long
run.
Myth: Neutral requires two separate and distinct connections to earth electrode in soil as per IE rule 1956.
Fact: The IE rule is replaced with CEA regulations. The new regulations
replaced the requirement of earthing
from definition onwards. Refer CEA MEASURES RELATING TO SAFETY AND ELECTRIC SUPPLY
REGULATIONS 2023. The recommendation of the regulations is explained in Sl., no 4 onwards.
Myth: Earth pit of ONE OHM is required for safety and operation of electronics.
Fact:Resistance of an earth electrode (such as a plate / rod / pipe) in soil does not influence a LV electrical
installation. No standards recommend a maximum value of 1 ohm for an earth electrode.
Page 4 of 18
4.1 Safety requirements
2. Disconnection times: Fault disconnection times as per IS3043 / NEC / IS732 / IEC 61936.
3. TN-S system (separate protective conductor) with PME for the LV system (only for India).
4. Double earthing of all major class 1 equipment as per IS 3043 and the neutral of the source.
5. CBN (Common Bonding Network) as per ISO 30129 for the electronic system.
6. Global Earthing for EHV/HV/LV/ELV.
7. Temporary Over Voltage, limited to less than the tolerable limit as per table 5 of IS732.
8. Protective overvoltage control for the complete installation.
9. Integrated lightning protection system as per IS/IEC 62305.
10. Effective shielding against conducted and radiated EMP (at least protective concept 3 explained
in IEC 61000).
EMI/EMC and the effects of EMP on electronics also shall be considered in a DATACENTER. Equipotential
bonding and shielding play major role in protecting the electronics from EMP.
An example is, where a Data Centre is co-sited with a high-voltage line or substation, effects of EMI shall
be reduced below the tolerable limit to safeguard from the loss of vital data due to EMI.
Page 5 of 18