WARNING: If the information in this manual is not followed exactly, a fire or explosion
may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch. Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or
the gas supplier.
CAUTION: Do not use automotive anti-freeze in the boiler waterways. If the use of antifreeze is necessary an
anti-freeze specifically formulated for hydronic heating systems must be used or damage to the boiler may
occur voiding the warranty!
IN UNITED STATES: 260 NORTH ELM ST. • WESTFIELD, MA 01085 • (413) 564-5515 • FAX (413) 568-9613
IN CANADA: 7555 TRANMERE DRIVE • MISSISSAUGA, ONT. L5S 1L4 • (905) 672-2991 • FAX (905) 672-2883
www.hydrothermkn.com
Page 2 KN INSTALLATION AND OPERATION INSTRUCTIONS
RATINGS & CAPACITIES 5. DO NOT place this boiler in a location that would
Before installing the KN boiler check the rating plate to restrict the introduction of combustion air into the
ensure that the unit has been sized properly for the job. unit or subject it to a negative pressure unless the
Also ensure that the unit has been set up for the type combustion air is piped from the outside, see the
of gas available at the installation site. Other important COMBUSTION AIR & VENTILATION section.
considerations are the availability of an adequate
electrical supply, fresh air for combustion and a suitable 6. NEVER place this boiler in a location that would
vent system. subject it to temperatures at or near freezing.
NOTE: Service clearances are not mandatory, but COMBUSTION AIR & VENTILATION
are recommended to ensure ease of service should
it be required. WARNING: This boiler must be supplied with
combustion air in accordance with Section 5.3,
Table 1 - Clearances Air for Combustion & Ventilation, of the latest
revision of the National Fuel Gas Code, ANSI
Clearance to Service Z223.1/NFPA 54 and all applicable local building
Combustibles Clearance codes. Canadian installations must comply with
in mm in mm CSA B149.1 or .2 Installation Code for Gas
Top 6 153 24 610 Burning Appliances and Equipment, or
Back 6 153 24 610 applicable provisions of the local building codes.
Left Side 6 153 6 152 Failure to provide adequate combustion air for
Right Side 6 153 6 152 this boiler/water heater can result in excessive
Front 6 153 36 914 levels of carbon monoxide which can result in
Flue 6 153 severe personal injury or death!
2. An optimum site will be level, central to the piping To operate properly and safely this boiler requires a
system, close to a chimney or outside wall and have continuous supply of air for combustion. NEVER store
adequate fresh air for combustion. Ensure that the objects on or around the boiler!
unit is level from front to back and from side to side.
Use metal shims if leveling is required. Electrical and CAUTION: Combustion air contaminated with fluoro-
electronic components must be protected from carbons or other halogenated compounds such as
exposure to water during operation and maintenance. cleaning solvents and refrigerants will result in the
DO NOT install this boiler in a location that would formation of acids in the combustion chamber.
subject any of the gas ignition and other electronic These acids will cause premature failure of the
components to direct contact with water or excessive boiler voiding the warranty!
moisture during operation or servicing.
CAUTION: If the boiler is operated while the building
3. Ensure that the floor is structurally sound and will is under construction it must be protected from
support the weight of the boiler. wood, concrete, sheet rock and other types of
dust. Failure to properly protect the unit from
NOTE: The KN may be installed directly on construction dust will damage the unit voiding the
combustible flooring, but never on carpeting. warranty!
Buildings will require the installation of a fresh air duct Where communicating with the outdoors through hori-
or other means of providing make-up air if the intake zontal ducts, each opening shall have a minimum free
air option isn't used. Any building utilizing other gas area of 1 in2/2000 Btu/hr, 1100 mm2/kW of the total
burning appliances, a fireplace, wood stove or any type input rating of all of the equipment in the enclosure.
of exhaust fan must be checked for adequate
combustion air when all of these devices are in When ducts are used, they must have the same cross-
operation at one time. Sizing of an outside air duct must sectional area as the free area of the opening to which
be done to meet the requirements of all such devices. they connect.
WARNING: Never operate the KN in an environ- Table 2 - Make-up Air Duct Sizing
ment subjected to a negative pressure unless it Required Cross Sectional Duct Area
is Direct Vented. Failure to comply with this Input 1/4 in, 6.4 mm Metal Wooden
warning can result in excessive levels of carbon (MBH) Wire Screen Louvers Louvers
monoxide causing severe personal injury or in2 cm2 in2 cm2 in2 cm2
death! 600 150 967 200 1292 600 3869
1000 250 1612 334 2154 1000 6448
All Air From Inside The Building 2000 500 3224 668 4308 2000 12,896
If the boiler is to be located in a confined space the 3000 750 4836 1002 6462 3000 19,344
minimum clearances listed in Table 1 must be
maintained between it and any combustible construction. When calculating the free area necessary to meet the
When installed in a confined space without the intake make-up air requirements of the enclosure,
air option two permanent openings communicating with consideration must be given to the blockage effects of
an additional room(s) are required. The combined louvers, grills and screens.
volume of these spaces must have sufficient volume to
meet the criteria for an unconfined space. The total air Screens must have a minimum mesh size of 1/4 in,
requirements of all gas utilization equipment, fireplaces, 6.4 mm. If the free area through a louver or grill is not
wood stoves or any type of exhaust fan must be known ducts should be sized per Table 2 above.
considered when making this determination. Each
opening must have a minimum free area of 1 in2/1000 Direct Intake Air Option - General
Btu/hr, 2200 mm2/kW based on the total input rating of This configuration provides combustion air directly to the
ALL gas utilization equipment in the confined area. Each boiler’s air intake using a dedicated pipe when using the
opening must be no less than 100 in2, 64,516 mm2 in direct vent option. Combustion air can be drawn in
size. The upper opening must be within 12 in, 300 mm horizontally through an outside wall or vertically through
of, but not less than 3 in, 80 mm from, the top of the the roof, see Figures 1, 2, 3 & 4. It must be sized per
enclosure. The bottom opening must be within 12 in, Table 3.
300 mm of, but not less than 3 in, 80 mm from, the
bottom of the enclosure. Single wall galvanized smoke pipe, single wall aluminum
pipe, flexible aluminum pipe, PVC or CPVC pipe can be
All Air From Outside The Building used for the intake air pipe.
When installed in a confined space without the intake
air option two permanent openings communicating Table 3 - Intake Air Pipe Sizing
directly with, or by ducts to, the outdoors or spaces that Model Pipe Diameter
freely communicate with the outdoors must be present. Size in2 mm2
The upper opening must be within 12 in, 300 mm of, 600 5 127
but not less than 3 in, 80 mm from, the top of the 1000 6 152
enclosure. The bottom opening must be within 12 in, 2000 9 229
300 mm of, but not less than 3 in, 80 mm from, the 3000 8 203
bottom of the enclosure.
NOTE: All joints in metal intake air systems must be
Where directly communicating with the outdoors or secured using corrosion resistant fasteners and
communicating with the outdoors through vertical ducts, sealed using a suitable Silicone caulk. If PVC or
each opening shall have a minimum free area of 1in2/ CPVC is used, the joints must be cleaned with a
4000 Btu/hr, 550 mm2/kW of the total input rating of all suitable solvent and connected using a solvent
of the equipment in the enclosure. based PVC cement. The intake air system MUST be
supported by the building structure not the boiler.
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 5
Direct Intake Air Option - Vertical Table 5 - Horizontal Intake & Vent System
The maximum equivalent length for the vertical intake Components
air pipe is 80 ft, 19.7 m. Each 90° mitered elbow and Company Description Part Number Dia., in
the intake air cap are equal to 10 ft, 3.3 m of straight Flex-L Vent Adapter 5
pipe. If 90° long sweep elbows are installed use the Flex-L Vent Adapter 6
manufacturers recommended equivalent length. Flex-L Vent Adapter 8
Termination T
A listed, nonrestrictive intake air cap must be used. The Termination T
intake air cap must terminate as shown in Figure 3. The Termination T
penetration point in the roof must be properly flashed Termination EL
and sealed. Approved caps are listed in Table 4. Termination EL
Termination EL
Direct Intake Air Option - Horizontal Heat Fab Vent Adapter 9501KN10 5
The maximum equivalent length for the horizontal intake Heat Fab Vent Adapter 9601KN10 6
air pipe is 80 ft, 19.7 m. Each 90° mitered elbow and Heat Fab Vent Adapter 90801KN10 8
the intake air terminal are equal to 10 ft, 3.3 m of Termination T 9590TEE 5
straight pipe. If 90° long sweep elbows are installed use Termination T 9690TEE 6
the manufacturers recommended equivalent length. Termination T 90890TEE 8
Termination EL 7514TERM 5
Horizontal runs that exceed 5 ft, 1.5 m must be Termination EL 9614TERM 6
supported at 3 ft, 0.98 m intervals with overhead Termination EL 90814TERM 8
hangers. The intake air terminal must terminate as Pro Tech Vent Adapter 5
shown in Figures 1, 2 or 4. Approved terminals are listed Pro Tech Vent Adapter FSA-HFAG 6
in Table 5. Pro Tech Vent Adapter 8
Termination T 300313 5
Table 4 - Vertical Intake & Vent System Components Termination T 300314 6
Company Description Part Number Dia., in Termination T 8
Flex-L 5 Termination EL 5
Flex-L 6 Termination EL 6
Flex-L 8 Termination EL 8
Heat Fab Rain Cap 5500CI 5 Z Flex Vent Adapter 5
Heat Fab Rain Cap 5600CI 6 Vent Adapter 6
Heat Fab Rain Cap 51000CI 8 Vent Adapter 8
Pro Tech Rain Cap FSRC5 5 Termination T 02SVSTTX05 5
Pro Tech Rain Cap FSRC6 6 Termination T 6
Pro Tech Rain Cap FSRC8 8 Termination T 8
Z Flex 5 Termination EL 5
Z Flex 6 Termination EL 6
Z Flex 8 Termination EL 8
When running horizontal combustion air and venting for The maximum equivalent length for the vertical vent pipe
single or multiple units, exhaust and combustion air is 80 ft, 19.7 m for KN-6, 10, 20, 120 ft for KN-30.
terminals must be installed on the same plane (outside Each 90° elbow and the intake air cap are equal to
wall) in order to prevent pressure differences due to 10 ft, 3.3 m of straight pipe. If any part of a single wall
prevailing winds. In cold climates, double-wall or insulated metal vent system passes through an unheated space
inlet pipe recommended to prevent condensation. it must be insulated with insulation rated for 400°F, 204°C.
Structural penetrations must be made using approved
Vertical Direct Vent Systems - see Figure 3 fire-stops.
The vent materials used in positive pressure vent
systems must be certified to UL 1738 for installations in The top of a vertical vent system must extend at least
the United States, ULC S636 for installations in Canada. 51/2 ft, 1.8 m above the roof surface that it passes
through, 4 ft, 1.3 m above the intake air cap, see Figure
The vent terminals listed in Table 4 must also be used. 3. In addition the vent system must conform to the
Below is a list of some of the manufactures that have dimensions shown in Figure 3. The penetration point in
systems that meet these requirements. Others manu- the roof must be properly flashed and sealed.
facturers that have UL certified systems may be used.
Heat-Fab, Inc. The vent system must be gas tight. All seams and joints
38 Hayward Street in metal pipes must be joined and sealed in accordance
Greenfield, MA 01301, (800) 772-0739. with the vent system manufacturer's instructions.
"B"
ALL CONNECTIONS
TO BE "T-WYE"
DOUBLE ACTING "C"
BARAMETRIC DAMPER
"A"
THERMAL SPILL
SWITCH
"D"
5" AIR
INLET
"B"
ALL CONNECTIONS
DOUBLE ACTING TO BE "T-WYE"
BARAMETRIC DAMPER
"C"
"A"
THERMAL SPILL
SWITCH
"D"
6" AIR
INLET
*
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 9
Figure 1 - Horizontal Air Intake and Venting for a Single Direct Vent System
Figure 2 - Horizontal Air Intake and Venting for Multiple Direct Vent Systems
Page 10 KN INSTALLATION AND OPERATION INSTRUCTIONS
Figure 3 - Vertical Air Intake and Venting for Direct Vent System
SIDE WALL VENT The air for combustion is taken from the space in which
the unit is installed. The applicable instructions under
POSITIVE PRESSURE, CATEGORY IV the COMBUSTION AIR & VENTILATION SECTION
In this configuration the boiler blower is used to push the must be followed! The vent guidelines under the
flue products horizontally to the outdoors, see Figure 5. HORIZONTAL DIRECT VENT SYSTEMS section must
also be followed.
VERTICAL VENT (Optional) vent connector of the same diameter as the flue collar
to connect the boiler to a listed metal chimney system.
NEGATIVE PRESSURE - CATEGORY II Follow the chimney system manufacturer’s instructions
The KN is listed as a Category II appliance when vented for proper assembly.
vertically into a listed metal AL294C S.S. chimney
system, Figure 7. The chimney system must provide a The vent system should be sloped up toward the
negative pressure of 0.02 to 0.2 in, 0.51 to 5.08 mm chimney at a minimum rate of 1/4 in/ft, 2 cm/m.
W.C. at the boiler flue collar with the unit running.
WARNING: Never install a vent pipe of a
NOTE: When using a listed metal chimney system diameter different than that specified in Table 7.
the chimney system manufacturer’s instructions Failure to comply with this warning can result in
must be followed. excessive levels of carbon monoxide which can
cause severe personal injury or death.
Multiple KN’s can be vented into a single vertical
chimney system. Refer to HydroTherm KN-10 Venting Always provide a minimum clearance of 6 in, 152 mm
page 7. Refer to page 8 for multiple KN-6 and KN-20 between single wall vent pipe and any combustible
venting applications. Consult with vent manufacturer on materials.
KN-30 sizing: based on maximum .2 negative at boiler
outlet. See recommendations on page 6. WARNING: Failure to maintain minimum
clearances between vent connectors and any
WARNING: Multiple boiler vent systems must be combustible material can result in a fire causing
designed and verified by a qualified professional extensive property damage, severe personal
and stack manufacturer. The vent system must injury or death!
prevent backflow of exhaust gas through idle
boilers.
Figure 7 - Vertical Venting with a Metal Chimney System
When more than one appliance is connected to the same
chimney system the system must be large enough to
safely vent the combined output of all of the appliances.
Vent Connections
Locate the boiler as close to the chimney system as
possible. Use the shortest, straightest vent connector
possible for the installation. If horizontal runs exceed
5 ft, 1.5 m they must be supported at 3 ft, 0.9 m
intervals with overhead hangers. Use the appropriate
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 13
COMMON VENT SYSTEMS Dans la mesure du possible, fermer toutes les portes
If an existing boiler is removed from a common venting et les fenêtres du bâtiment et toutes les portes entre
system, the common venting system may then be too l'espace où les appareils toujours raccordés du
large for the proper venting of the remaining appliances système d'évacuation sont installés et les autres
connected to it. At the time of removal of an existing espaces du bâtiment. Mettre en marche les
boiler, the following steps shall be followed with each sécheuses, tous les appareils non raccordés au
appliance remaining connected to the common venting système d'évacuation commun et tous les
system placed in operation, while the other appliances ventilateurs d'extraction comme les hottes de
remaining connected to the common venting system are cuisinère et les ventilateurs des salles de bain.
not in operation. S'assurer que ces ventilateurs fonctionnent à la
vitesse maximale. Ne pas faire fonctionner les
Au moment du retrait d'une chaudière existante, les ventilateurs d'été. Fermer les registres des
mesures suivantes doivent être prises pour chaque cheminées.
appareil toujours raccordé au système d'évacuation
commun et qui fonctionne alors que d'autres appareils d) Place in operation the appliance being inspected.
toujours raccordés au système d'évacuation ne fonction- Follow the lighting instructions. Adjust thermostat so
nent pas: système d'évacuation appliance will operate continuously.
a) Seal any unused openings in the common venting Mettre l'appareil inspecté en marche. Suivre les
system. instructions d'allumage. Régler le thermostat de
façon que l'appareil fonctionne de façon continue.
Sceller toutes les ouvertures non utilisées du sys-
tème d'évacuation. e) After it has been determined that each appliance
remaining connected to the common venting system
b) Visually inspect the venting system for proper size properly vents when tested as outlined above, return
and horizontal pitch and determine there is no doors, windows, exhaust fans, fireplace dampers
blockage or restriction, leakage, corrosion and other and any other gas-burning appliance to their
deficiencies which could cause an unsafe condition. previous condition of use.
Inspecter de façon visuelle le système d'évacu-ation Une fois qu'il a été d éterminé, selon la métode
pour déter miner la grosser et l'inclinaison indiquée ci-dessus, que chaque appareil raccordé
horizontale qui conviennent et s'assurer que le au système d'évacuation est mis à l'air libre de façor
système est exempt d'obstruction, d'étranglement adéquate. Remettre les portes et les fenêtres, les
de fruite, de corrosion et autres défaillances qui ventilateurs, les registres de cheminées et les
pourraient présenter des risques. appareils au gaz à leur position originale.
c) Insofar as is practical, close all building doors and f) Any improper operation of the common venting
windows and all doors between the space in which system should be corrected so the installation
the appliances remaining connected to the common conforms with the National Fuel Gas Code, ANSI
venting system are located and other spaces of the Z223.1/NFPA 54. When resizing any portion of the
building. Turn on clothes dryers and any appliance common venting system, the common venting
not connected to the common venting system. Turn system should be resized to approach the minimum
on any exhaust fans, such as range hoods and size as determined using the appropriate tables in
bathroom exhaust, so they will operate at maximum Appendix F in the National Fuel Gas Code, ANSI
speed. Do not operate a summer exhaust fan for a Z223.1/ NFPA 54 and or CSA B149 Installation
boiler installation. Close fireplace dampers. Codes.
GENERAL PIPING REQUIREMENTS Upon reviewing different types of glycol, we have found
that Dow Frost HD glycol when used in conjunction with
CAUTION: Improper piping of this boiler will void the Dow Corning Antifoaming Agent part #1410 results in a
manufacturer’s warranty and can cause boiler failure mix with heat transfer characteristics nearly identical to
resulting in flooding and extensive property damage! that of pure water. The higher operating temperature
range offered by Dow Frost HD when combined with the
NOTE: Shut off valves and unions should be greatly reduced foam formation allowed by the antifoaming
installed at the inlet and outlet connections of the agent provides an ideal solution to ensure the long life of
boiler to provide for isolation of the unit should low mass/high rate of heat transfer KN Series boilers.
servicing be necessary.
On those jobs where glycol is necessary for freeze
protection, we highly recommend use of this mixture at
Relief Valve
a ratio of one gallon of the antifoaming agent per 5,000
Pipe the discharge of the pressure relief valve as shown
gallons of system volume.
in Figure 8. Mount on rear section or vertically on supply
nipple.
Figure 8 - Relief Valve Piping
WARNING: Never install any type of valve
between the boiler and the relief valve or an
explosion causing extensive property damage,
severe personal injury or death may occur!
Flow Switch
The flow switch (optional on KN-6, 10, and 20; standard
on KN-30) is wired to prevent the boiler from firing
unless there's adequate water flow through the unit.
Water
Flow Rates ΔT Across
(GPM) Heat Exchanger
Min. Max. Min. Max.
KN-6 10 100 20°F 100°F HEATING SYSTEM PIPING
KN-10 15 150 20°F 100°F
KN-20 30 300 20°F 100°F General Piping Requirements
KN-30 45 450 20°F 100°F All heating system piping must be installed by a qualified
technician in accordance with the latest revision of the
Increase flow rates approximately 30% for glycol ANSI/ASME Boiler and Pressure Vessel Code, Section IV.
mixtures.
Where required, the piping must comply with ANSI/
We have been informed of a small number of jobs on ASME CSD-1, Standard for Controls and Safety Devices
which the particular glycol/water mix results in foaming for Automatically Fired Boilers.
within the sections. The air entrapment within this foam
significantly decreases heat transfer and could potentially All applicable local codes and ordinances must also be
result in damage to the boiler sections. The formation of followed. A minimum clearance of 1in, 25 mm must be
this foam can be controlled rather simply by introducing maintained between heating system pipes and all
an anti-foaming agent to the water/glycol mix. combustible construction. All heating system piping must
be supported by suitable hangers not the boiler. The
thermal expansion of the system must be considered
when supporting the system. A minimum system
pressure of 12 psig, 84 kPa must be maintained at the
highest point in the system piping. A minimum system
pressure of 25 psig, 172 kPa fill pressure is required
on glycol mixtures within a closed loop.
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 15
Table 8 - Supply & Return Pipe Sizing Reverse Return Piping (RECOMMENDED)
Model Supply Return Systems using multiple boilers can also be installed
Size Size Size using a reverse return system, Figure 10.
600 2" NPT 2" NPT
1000 3" NPT 3" NPT Primary/Secondary Piping
2000 3" NPT 3" NPT Although acceptable, the system is not as cost effective
3000 4" NPT 4" NPT as reverse return piping. Figure 11 shows a typical
primary/secondary piping system. A dedicated pump is
Water Treatment used to maintain a constant water flow through the
This boiler was designed to operate in a closed loop boiler. Systems using multiple boilers can be installed
heating system. Water treatment is required when fill or using a primary/secondary manifold system, Figure 12.
make-up water contains dissolved solids greater than
200 ppm or if PH level is not within the 6.5-11 range. Piping For Use With Cooling Units
The boiler, when used in connection with a refrigeration
Pump Requirements system, must be installed so the chilled medium is piped
This boiler requires a continuous minimum water flow in parallel with the boiler. Appropriate valves must be used
for proper operation. The system pump must be sized to prevent the chilled water from entering the boiler.
to overcome the head loss of the boiler and the heating
system in order to achieve the required temperature rise. When a boiler is connected to a heating coil that may
If the system contains hydronic antifreeze this must be be exposed to refrigerated air from an air handling
considered when sizing the pump. The temperature rise device, the piping system must be equipped with flow-
across the boiler must never exceed 100°F, 55.6°C. control valves or some other automatic means of
preventing gravity circulation of the boiler water during
Low Water Cutoff the cooling cycle.
Each KN boiler comes equipped with a factory installed
low water cutoff. NOTE: It is essential that following boiler shut off,
t h e b o i l e r p u m p c o n t i n u e t o o p e r a t e fo r
approximately (5) minutes to dissipate the heat away
from the heat exchanger.
Figure 9 - Typical Single Boiler Piping (RECOMMENDED)
(Circulator pump must be sized for minimum water flow rate of boiler, including system pressure drop)
HIOM-64
Page 16 KN INSTALLATION AND OPERATION INSTRUCTIONS
Motorized
Valve
NOTE: Not all system valves may be shown. Consult local codes for additional system
components which may be necessary. HIOM-11 REV .3
NOTE: Not all system valves may be shown. Consult local codes for additional system
components which may be necessary. HIOM-9 REV .2
NOTE: Not all system valves may be shown. Consult local codes for additional system
components which may be necessary. HIOM-10 REV .3
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 17
DOMESTIC WATER SUPPLY PIPING NOTE: The storage tank must be located as close
to the boiler as possible to prevent excessive head
CAUTION: Proper controls must be used to prevent loss which will reduce flow.
water supplied for domestic use from exceeding
130°F, 54°C or a scald injury will occur! When Expansion Tank
higher water temperatures are required for An expansion tank or other means to control thermal
appliances such as a dishwasher, a mixing valve or expansion must be installed in the water heating system
some other tempering means must be installed. if back flow prevention devices are installed.
Households with small children may require water
temperatures less than 120°F, 49°C. Local codes Two typical water heating systems are shown in Figures
must be complied with! 13 & 14.
General Piping Requirements Thermostatic Mixing Valve- Water Above 140°F, 60°C
The KN boiler can be use in combination with an indirect Water can be stored a temperatures above 140°F,
tank to provide hot water for domestic use. Piping and 60°C provided that a thermostatically controlled mixing
components must be suitable for use with potable water. valve is used to temper the hot water to an acceptable
The indirect storage tank must be equipped with a temperature before it's supplied for domestic use. The
temperature and pressure relief valve that complies with mixing valve MUST be set to prevent a scald injury from
ANSI Z21.22 or CAN-4.4 and CAN-4.6. occurring, see the caution against scalding above.
Storage of water for domestic use above 140°F, 60°C
will provide an increased quantity of tempered water and
help prevent the growth of water born bacteria.
Table 10 - Equivalent Pipe Length Chart Whenever the gas supply piping is pressure tested
Type of pipe fitting the boiler gas controls must be protected. If the test
Nominal pressure is equal to, or less than 1/2 psig, 3.5 kPa
Iron Pipe 90° Elbow Tee1 Gas Valve2 Gas Cock2
Size, (in)
isolate the boiler by closing its' manual shut off valve,
Equivalent pipe length, (ft) see Figure 15. If the test pressure is greater than, or
1″ 2.6 5.2 0.6 1.5 equal to 1/2 psig, 3.5 kPa, disconnect the boiler and its
11/4″ 3.5 6.9 0.8 1.9 individual shut-off valve.
11/2″ 4.0 8.0 0.9 2.3
2″ 5.2 10.3 1.2 3.0
ELECTRICAL WIRING
Notes: 1. For flow through branch.
2. For flow at full open.
Electrical Power Connections
4. Remove the front cover. 18. Remove the manometer fitting from the pilot tee and
replace the plug. Close manual main shut-off valve
5. Close manual main shut-off valves 1 and 2 and the 2 and the pilot gas shut-off valve, Figure 15.
pilot gas shut-off valve, Figure 15.
19. Switch the Honeywell 7800 back to “run”.
6. Purge the gas piping up to the manual valve ahead
of the main gas control of air. When the bleeding is 20. Create a min (TI) input demand as before. The boiler
complete, check all gas joints up to the gas valve will begin the start sequence.
for leaks.
21. Monitor the flame current on the 7800. No flame
7. Install a fitting at the bleed point and connect current should be detected and the 7800 should
a manometer having a minimum range of 20 in, lock out. If flame current is detected at any time up
508 mm WC to it, Figure 15. to the 7800 locking out, the 120V wiring on the
ignition transformer must be reversed and the test
8. Remove the 1/8" pipe plug from the pilot tee and run again to insure that no flame is detected.
connect a manometer having a minimum range of
6 in, 154 mm WC to it. WARNING: Improper wiring of the ignition
transformer can result in an explosion causing
9. Wait five (5) minutes to clear out any gas. extensive property damage, severe personal
injury or death!
10. Open the manual main shut-off valves 1 and 2 and
the pilot gas shut-off valve, Figure 15. 22. Open both manual main shut-off valves and the pilot
gas shut-off valve.
11. Place the “Remote/Local” switch to Remote.
23. Reset the Honeywell 7800. The boiler will start and
12. Turn the power switch on the front of the boiler to will run at minimum input rate.
“on”. It will light up when the power is on. If all
interlocks are properly closed, the display will say 24. Setting the low fire: Allow the low fire to settle
“Standby”, Figure 16. out for a few minutes and observe the combustion
reading. They should be as follows:
13. Create a min input demand by jumping the TI
terminals, Figure 22. CO2 O2
KN-6, 10, 20 Low Fire 7.4-8.8% 7.6-5.2%
14. The boiler will begin the start sequence. KN-30 Low Fire 6.7-8.1% 8.6-6.8%
15. When the main display reads “PILOT RUNNING” The low fire O2-CO2 can be adjusted in the field by
and the flame current is 5VDC, switch the Honey- opening the low fire adjustment door located on the
well 7800 to the “test” position, Figure 16. This will forward facing side of the main gas valve. Inserting
hold the Honeywell 7800 in its ignition state. an allen wrench and rotating the allen screw clock-
wise will increase the CO2 and lower the O2, rotating
16. Adjust the pilot pressure per the CHECKING, counter clock-wise will decrease the CO 2 and
ADJUSTMENT & OPERATION section below. increase the O2. In low fire you should see a red and
blue striped pattern on the burner. If the mesh is
17. Remove the demand from the 7800 control by entirely red decrease low fire CO2.
opening the TI terminals, allowing the boiler to stop.
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 23
25. Jumper the "AA" terminals. The boiler input will rise COMMENT COUPER L'ADMISSION DE GAZ DE
to its maximum input, "Run 100%", see Fig. 22. L'APAREIL
1. Réglez le thermostat à la température la plus basse.
26. Allow the boiler to stabilize and adjust the input rate
per the CHECKING, ADJUSTMENT & OPERATION 2. Coupez l'alimentation électrique de l'appareil s'il faut
section below. procéder à l'entretien.
27. When all adjustments are finished, remove jumpers 3. Fermer la vanne manuelle d'arrêt d'alimintation de
on terminals "TI" and "AA", see Fig. 22. gaz.
28. Boiler allows for many modes of operation and SEQUENCE OF OPERATION
control methods. Reference the "Model KN-Series
Control-IOM" and the "Model KN-Series Control- NO DEMAND
Programming Examples" for instruction. Standby
1. The boiler is idle with no interlocks in the fault
Instructions De Mise En Marche condition.
1. ARRÊTEZ! Lisez les instructions de sécurité sur la
portion supérieure de cette étiquette. DEMAND
Pre-Purge
2. Réglez le thermostat à la température la plus basse. 1. The blower operates at purge RPM. The water flow
interlock must ‘make’ within 15 seconds after the
3. Coupez l'alimentation électrique de l'appareil. demand signal is initiated.
4. Cet appareil est muni d'un dispositif d'allumage qui 2. The Honeywell 7800 starts a 10 second purge delay
allume automatiquement la veilleuse. Ne tentez pas once the air prove switch contacts close.
d'allumer la veilleuse manuellement.
Pilot Run - %Input
5. Fermer la vanne manuelle d'arrêt d'alimintation de 1. The blower operates at minimum ignition setting.
gaz. See the calibration section in the "KN-Series
Control-IOM" to enter the calibration menus.
6. Attendre cinq (5) minutes pour laisser échapper tout
le gaz. Reniflez tout autour de l'appareil, y compris 2. The ignition transformer is energized. The pilot
près du plancher, pour déceler une odeur de gaz. solenoid valve opens for the 10 second pilot ignition
Si vous sentez une odeur de gaz, ARRÊTEZ! trial.
Passez à l'étape B des instructions de sécurité sur
la portion supérieure de cette étiquette. S'il n'y a pas Main Run %Input
d'odeur de gaz, passez à l'étape suivante. 1. The main gas valve opens.
7. Ouver la vanne manuelle d'arrêt d'alimintation de 2. The ignition transformer is de-energized.
gaz.
3. The pilot solenoid valve closes.
8. Mettez l'appareil sous tension.
4. The blower stays at the minimum input setting for
9. Réglez le thermostat à la température désirée. 3 seconds then operates at demand % input. See
the calibration section in the "KN-Series Control-
10. Si l'appareil ne se met pas en marche, suivez les IOM" to enter the calibration menus.
instructions intitulées couper l'admission de gaz de
l'appareil et appelez un technicien qualifié ou le NO DEMAND
fournisseur de gaz. Post-Purge
1. The main gas valve closes.
TO TURN OFF GAS TO APPLIANCE
1. Set the operating control to its lowest setting. 2. The blower operates at purge RPM for 10 seconds.
2. Turn off all electric power to the boiler if service is 3. The boiler is idle with no interlocks in the fault
to be performed. condition.
3. Close the manual main and pilot gas shut-off valves.
Page 24 KN INSTALLATION AND OPERATION INSTRUCTIONS
Setpoint - 1/2
Are we below the
Heat Band
Temp Band?
NO
J5 Pin 3
Have We
NO "BLOWER"
Operate Blower J4 Pins 4 & 8 received the Send 120 VAC
BLOWER
Motor @ 0% < .5 volts DC "BLOWER" BLOWER signal
signal?
TERM 4
"MOTOR"
YES
If Yes, do
not operate
YES
blower. "MAIN VALVE"
greater than 7 VAC
NO
J4 Pins 4 & 8
Operate Blower ~5.4 volts DC
PRE_PURGE
Motor @ ~55%
DISPLAY:
PRE PURGE TERM 8
J5 Pin 2 "PILOT"
NO "PILOT" After 10 Seconds
PILOT signal? PILOT send PILOT signal
YES
J4 Pins 4 & 8
Operate Blower ~3.2 volts DC FLAME?
PILOT Ignition
Motor @ ~32%
DISPLAY:
PILOT: YES
J5 Pin 1
NO After 10 Seconds
"MAIN"
MAIN signal? MAIN send MAIN
VALVE signal
TERM 9
YES
"MAIN"
Operate Blower J4 Pins 4 & 8
1. Minimum fire rate
Motor @ Min Fire, >2 volts DC
2. Hold for (x) secs.
then Modulate to DISPLAY: 3. Modulate to temp
maintain temp RUN % 25
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 25
Troubleshooting A Startup
An Interlock is tripped. 1. Is it a 24 VAC Interlock? 1. All 24 VAC Interlocks are 1.Use a multimeter and check
1. located on J11A and J11B. for 24 VAC on J11A,J11B to
Examples of 24 VAC Interlocks: identify which interlock has
1.SPARE3 tripped. Reset the Interlock or
2. V ariable Frequency Drive(VFD) check for disconnected wiring
3. Low Water Cutoff(LWCO), or shorts.
4. Gas Pressure
5. Spare 4 The Air Pressure from UV
6. Operator OPLIM Sensor interlock if displayed
7. Water Flow will allow the boiler to
8. Air Pressure from UV Sensor. function, but it needs to be
functional while the boiler is
running for it to clear.
2.
Proceed to Operation
Maual or Programming
examples manual for
more details and
problem resolution.
Page 26 KN INSTALLATION AND OPERATION INSTRUCTIONS
CHECKING, ADJUSTMENT & OPERATION CAUTION: Never force the regulator adjustment
screw beyond the stop limits or damage to the
Spark Gap regulator will occur!
The gap has to be measured and adjusted with the
igniter removed from the boiler. Observe the trial for Figure 18 - Pilot Flame
ignition to confirm that the spark is strong and
continuous. If not, allow the electrodes to cool. Check
and adjust the spark gap as shown in Figure 17.
Electrode tips should face slightly downward.
"A"
To confirm the input of the unit follow the instructions in STANDBY OPERATING LIMIT: Indicates that the
the INPUT RATE section below. operating limit if used is open.
Input Rate, Natural Gas HONEYWELL ALARM “flashing”: Indicates that there
1. Turn off all other gas appliances that use the same is a call for heat and the Honeywell 7895C is locked out.
gas meter as the boiler.
STANDBY START DEMAND: Indicates that there is a
2. Call your gas supplier and ask for the heating value call for heat and the Honeywell 7895C is not functioning
of the gas (Btu per cu/ft). or is locked out.
3. Start the boiler and let it run for 15 minutes. STANDBY WATER LIMIT: Indicates that either the high
limit, low water cut off, or both are open without a call
4. With the boiler operation clock the time that it takes for heat.
to burn 10 cu/ft of gas at full fire.
LOCKOUT WATER LIMIT: Indicates that either the high
5. Insert the heating value and the time, in seconds, limit, low water cut off, or both are open with a call for
into the formula below. heat.
6. Input = 10 / seconds (Btu per cu/ft)(3600). STANDBY GAS PRESSURE: Indicates that the low gas
pressure switch or the high gas pressure switch if used
7. If the computed rate exceeds the desired input rate is open without a call for heat.
or 1,000,000 Btu/hr reduce the input. To do this use
the maximum Btu adjustment pot located on the LOCKOUT GAS PRESSURE: Indicates that the low gas
face of the display, Figure 16. pressure switch or the high gas pressure switch if used
is open with a call for heat.
CAUTION: Never increase the input to the boiler
above that for which it is rated. Doing so can cause STANDBY FLOW SWITCH: Indicates that the water
premature failure of the boiler! flow switch is open without a call for heat.
MAINTENANCE Controls
Use the BOILER OPERATION and CHECKING AND
WARNING: Disconnect electrical power and ADJUSTMENT sections of this manual for reference.
close the manual gas shut off valve before 1. Check the operating controls for proper operation.
performing maintenance or severe personal
injury may result! 2. A float type low water cutoff device must be flushed
out per the manufacturers' instructions. The probe
CAUTION: Servicing, inspection and adjustment on a probe low water cut off must be removed,
must be done by a trained technician in accordance cleaned and inspected at least once a year. Ensure
with all applicable local and national codes. Improper that the low water cutoffs operate properly. In not,
servicing or adjustment can damage the boiler! replace them.
The boiler must be inspected at least once a year and 3. The flow switch contacts must be open when water
before each heating season. Make sure that the burner flow is not present.
and ignition components are free from dust, soot, dirt,
corrosion or other deposits that would impair the boiler’s 4. The relief valve should not weep or discharge water
performance. Visually inspect the burner through the site at normal system pressure. If it does contact a
glass. Refer to page 26 for component identification. qualified service technician to have it inspected.
NEVER try to clean or repair the relief valve! If the
CAUTION: Improper burner servicing can result in valve fails to operate properly, have it replaced!
premature burner failure voiding the warranty!
5. The aquastat high limit controls the maximum water
Burner Removal & Inspection temperature in the boiler. It is adjustable from 130°F,
54°C to 215°F, 102°C. If the water temperature
WARNING: Wear a tightly fitted dust mask when reaches the set temperature before the demand for
servicing the burner and gently handle the heat has been met, the aquastat high limit should
burner and its gasket to prevent inhalation of shut the boiler off. The water temperature should
airborne fibers. never exceed the maximum set point of 215°F,
102°C. The aquastat high limit cannot be repaired.
NOTE: Do not attempt to remove the burner without If it fails to function properly replace it.
having a burner gasket kit on hand.
6. Visually check the pilot and main burner flames to
Heat Exchanger Cleaning ensure proper operation, see Figures 18 & 19.
In the unlikely event that the heat exchanger becomes
blocked consult the factory for the proper cleaning WARNING: When performing a visual inspection
procedure. of burner operation you should note a striped
pattern of red and blue when operating at low
Air Intake & Vent System fire. This pattern will change to mostly blue with
Thoroughly inspect the air intake and vent systems red speckling during high fire operation. High
for any signs of blockage, corrosion or leakage. concentrations of red on high fire would require
Immediately replace any unsound vent system piping. burner adjustment to reduce CO2 value.
Inspect the air filter and replace when required.
Figure 19 - Main Burner Flame
KN-6, 10, 20 Condensate Pan
Remove the (4) bolt exhaust flange from the rear of the
boiler. Using a hose, flush out any residual material in
the base pan through the condensate drain opening.
Reseal the exhaust flange with a high temp silicone.
Flush the drain trap and refill with 50% water/glycol mix
to prevent evaporation in the trap.
TROUBLESHOOTING
OPERATIONAL PROBLEM CORRECTIVE ACTION
The "Power On" light doesn't illuminate. Ensure that proper voltage is being supplied to the unit
Inspect the circuit breaker for the boiler circuit
Check the light
Ensure that the power switch operates properly and is
wired correctly
Lockout water limit is displayed with a call for heat. Check both the high limit and low water cut off.
Ensure that the boiler has been completely purged
of air.
Ensure that all system valves are in the correct
position.
Lockout gas pressure is displayed with a call for heat. Ensure that the manual main gas valve is open.
Ensure that there is sufficient gas pressure supplying
the boiler.
Check pressure setting on the low gas pressure
switch.
Lockout flow switch is displayed with a call for heat. Ensure that there is sufficient water flow through the
boiler
UV scanner switch is displayed flashing along with Ensure the scanner-cooling pump is operating.
the normal running display. Make sure there are no obstructions in the tubing
supplying the air to the scanner.
S E
EA
R 2
ECCO
D
SE
EA
R
C O2
IN C
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 31
4
2
5
1
6
SEE SHEET 4
HIOM-95-A
Page 34 KN INSTALLATION AND OPERATION INSTRUCTIONS
18
17
16
18 A
18 B
15
14
12
11
10 13
19 SEE SHEET 3
9
21
20
HIOM-95-A
22
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 35
23
3.62
26
25 24
27
28
HIOM-95-A
29
33
32
31
30
HIOM-95-A
34
35
36
37
38
Page 36 KN INSTALLATION AND OPERATION INSTRUCTIONS
58 59
60
61
57
62
63
64
65
66
HIOM-95-A 46
67
NOTE: CONTROLS AND COMPONENTS
MAY BE LAID OUT IN DIFFERENT
LOCATIONS.
45 48
56
49
44
43
39 40 41 42
54
50
51
HIOM-95-A
53
55
52
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 37
SERVICE AND REPLACEMENT PARTS LIST
Item Description Part # KN-30 Item Description Part # KN-30
1 SUPPLY SENSOR 02-4283 1 34 FILTER SCREEN 03-1826 1
2 FS254 FLOW SWITCH 14-0205 1 35 O-RING 59-2034 1
3 RELIEF VALVE 35# 22-1820 1 36 THREADED BLOCK 01-1656 1
RELIEF VALVE 50# 22-1821 1 HELICAL SPRING LOCK
37 22H-1133618 1
RELIEF VALVE 75# 22-1822 1 WASHER
RELIEF VALVE 100# 22-1823 1 38 HEX BOLT - UNC 22H-110120302 1
4 AIR VENT 60-4257 1 39 LWCO 21-2061 1
AUTOMATIC RESET HIGH LIMIT 40 LWCO LOCAL/REMOTE SWITCH 58-1535 1
5 02-3204 1
AQUASTAT L4006A 41 LWCO ALARM RESET 58-1534 1
MANUAL RESET HIGH LIMIT 42 LIGHT SWITCH 58-1535 1
6 02-2800 1
AQUASTAT L4006E 43 DISPLAY MOUNT PLATE ASSEMBLY 70-1475 1
PRESSURE TEMPERATURE 44 POWER SWITCH 58-1536 1
7 20-1021 1
GAUGE (30 & 50 PSI) 45 HIDDEN PANEL WELDMENT 70-1480 1
PRESSURE TEMPERATURE 46 FRONT CONTROL PANEL WELDMENT 70-1486 1
7 20-1020 1
GAUGE (75 & 100 PSI) 48 FRONT JACKET PANEL 03-1854 1
8 RETURN SENSOR 02-4283 1 49 HONEYWELL SPARK GENERATOR 26-3207 1
9 FRONT COVER 03-1867 1 50 GAS BRACKET SUPPORT (RIGHT) 03-1842 1
10 FRONT GASKET 59-1146 1 51 GAS BRACKET SUPPORT (LEFT) 03-1843 1
11 FILTER ASSEMBLY 59-1074 1 52 GAS TRAIN SHROUD 03-1863 1
12 FILTER BOX ASSEMBLY 70-1487 1 53 FRONT CONTROL PANEL (DOOR) 03-1839 1
13 UV FLAME SCANNER 02-5206 1 54 LEFT FRONT PANEL 03-1856 1
14 BLOCK W/ BASE 70-1224 1 55 RIGHT FRONT PANEL 03-1855 1
15 JACKET ASSEMBLY SS 70-1937 1 56 BLOWER CONTROLLER 58-1826 1
16 BLOWER 70-1481 1 57 PC CONTROL 02-4299 1
17 SPOOL ADAPTER 70-1491 1 58 SPARK RESISTOR 58-1831 1
18 UPPER COVER ASSY 70-1227 1 59 TRANSFORMER, 50 VA 26-3211 1
18A MAIN BURNER ASSY 70-1228 1 60 TRANSFORMER, 250 VA 26-3025 1
18B CERAMIC CHAMBER 45-1275 1 61 BLOWER OVERLOAD RELAY 58-1828 1
19 DRAIN PAN ASSEMBLY 70-6701 1 62 CONTACTOR (1 1/2, 2, 3 HP) 58-1917 1
20 1 1/2" GAS TRAIN 70-1489 1 (Optional) CONTACTOR (5 HP) 58-1918 1
21 IGNITOR BLOCK ASSY 70-1345 1 OVERLOAD RELAY (4 - 6AMP) 1 1/2 HP 58-1821 1
22 CONDENSATE DRAIN KN 70-1338 1 OVERLOAD RELAY (5.5 - 8AMP) 2 HP 58-1822 1
23 1 1/2" GAS BALL VALVE 02-1578 1 OVERLOAD RELAY (9 - 13AMP) 3 HP 58-1823 1
24 MAXITROL REG RV12LT 23-1014 1 OVERLOAD RELAY (12 - 18AMP) 5 HP 58-1824 1
25 V4046C PILOT GAS VALVE 02-1749 1 PUMP FUSE (1 1/2 HP) 58-1934 3
26 1/8 GAS COCK 23-1016 1 PUMP FUSE (2 HP) 58-1931 3
27 1 1/2" GAS BALL VALVE 02-1578 1 PUMP FUSE (3 HP) 58-1935 3
28 DUNGS VALVE 02-1592 1 PUMP FUSE (5 HP) 58-1936 3
29 1/8 GAS COCK 23-1016 1 63 FLAME SAFEGUARD RM7895C 02-4012 1
30 1/4-20 NEX NUT 57-2600 1 64 SWITCH 4" 02-5208 1
31 CLEAN OUT COVER 03-1830 1 65 SWITCH 3" 02-5211 1
32 CLEAN OUT COVER GASKET 59-1119 1 66 HUBA SWITCH 02-4881 1
33 DRAIN PAN 03-1834 1 67 AIR PUMP 09-1518 1
Page 38 KN INSTALLATION AND OPERATION INSTRUCTIONS
Figure 22
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 39
Figure 23
Page 40 KN INSTALLATION AND OPERATION INSTRUCTIONS
START-UP REPORT
PRE-STA
T RTUP CHECK LIST
BOILER STA
T RTUP SEQUENCE
Note: Locate the AA terminals and minimum hold switch in the bottom-right of the electrical panel on the main
HeatNet board. Also locate the manometer test manifold in the bottom of the electrical panel.
1. Disable any external call for heat and toggle the remote/local switch to REMOTE.
2. Toggle the LOW FIRE switch to cycle the boiler then hold at trial for pilot ignition.
3. Set pressure to 2.5–3.5" w.c. (flame signal should read 5.0 VDC).
4. Release boiler to main flame trial for ignition.
5. Check for stable flame.
6. Record combustion and elbow pressure at minimum firing rate.
7. Jumper the AA terminals to force 100% input.
8. Record combustion and elbow pressure.
9. Remove the AA jumper to place the boiler at minimum rate.
10. Make any final adjustments on low fire.
11. Check all combustion results using a calibrated flue gas analyzer.
12. Release the LOW FIRE switch to place boiler in standby.
In addition to completing the KN Series start-up report, complete the control set-up information in the rear
of the HeatNet manual.
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 41
COMBUSTION ANALYSIS
L MINIMUM FIRING RATE
A 100% FIRING RATE
A
GAS INLET PRESSURE (W.C.) INCHES W.C. INCHES W.C.
CO2 % %
O2 % %
Load
O
54
ew
56 4-20 mA Input
57 TB Strip Status
58 Keypad Status
* These values can be adjusted in the field for precision tuning.
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 43
P1 P2 P3 P4
B
HIOM-097-REV. 0
DETAIL B
HIOM-097-REV. 0
P1 P2 P3 P4
INCREASE DECREASE INCREASE DECREASE DECREASE INCREASE INCREASE DECREASE
DECREASE BTU INPUT - TURN DECREASE BTU INPUT - TURN DECREASE RAMP SPEED - TURN DECREASE RAMP SPEED - TURN
CLOCKWSIE CLOCKWSIE COUNTER CLOCKWISE CLOCKWISE
Page 44 KN INSTALLATION AND OPERATION INSTRUCTIONS
MACODE-3
NOTICE!
Commonwealth of Massachusetts
Installation Requirements
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building
or structure used in whole or in part for residential purposes, including those owned or operated
by the commonwealth and where the side wall exhaust vent termination is less than seven (7) feet
above finished grade, in the area of the venting, including but not limited to decks and porches,
the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired
carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas
equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of
the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall
be the responsibility of the property owner to secure the services of qualified licensed professionals for
the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space
or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be
installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of
installation, the owner shall have a period of thirty (30) days to comply with the above requirements;
provided, however, that during said thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the
building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal
for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size
no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide
detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
WARNING: Improper venting can result in excessive levels of carbon monoxide which can
cause severe personal injury or death!
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 45
MACODE-3
NOTICE!
Commonwealth of Massachusetts
Installation Requirements
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most
current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or
structure separate from the dwelling, building or structure used in whole or in part for residential
purposes.
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a
venting system design or venting system components with the equipment, the instructions provided by
the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system
components; and
2. A complete parts list for the venting system design or venting system.
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does
not provide the parts for venting the flue gases, but identifies “special venting systems”, the following
requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or
equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that
system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented
gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all
venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
WARNING: Improper venting can result in excessive levels of carbon monoxide which can
cause severe personal injury or death!
Page 46 KN INSTALLATION AND OPERATION INSTRUCTIONS
Five-Year Warranty
The manufacturer further warrants to the original owner at the original installation site that the products Heat Exchanger (Cast
Iron Block) will be free from defects in material and workmanship for five (5) years from the date of shipment from the factory.
If upon examination by the manufacturer the product is shown to have a defect in material or workmanship during the warranty
period, the manufacturer will repair or replace, at its option the Heat Exchanger of the product, which is shown to be defective.
Water quality is important. As per ASME recommendations, dissolved solids must be less than 200 ppm. Also, PH levels must
be in the 6.5-11 range. Failure to follow these guidelines will void the warranty.
Repair or replacement of any part under this Limited warranty shall not extend the duration of the warranty with respect to such
repaired or replaced part beyond the stated warranty period.
THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, AND ALL SUCH
OTHER WARRANTIES, INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS
FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY. IN NO
EVENT SHALL THE MANUFACTURER BE LIABLE IN ANY WAY FOR ANY CONSEQUENTIAL, SPECIAL, OR INCIDENTAL
DAMAGES OF ANY NATURE WHATSOEVER, OR FOR ANY AMOUNTS IN EXCESS OF THE SELLING PRICE OF THE
PRODUCT OR ANY PARTS THEREOF FOUND TO BE DEFECTIVE. THIS LIMITED WARRANTY GIVES THE OWNER AT THE
ORIGINAL INSTALLATION SITE SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS, WHICH MAY VARY
BY EACH JURISDICTION.
KN INSTALLATION AND OPERATION INSTRUCTIONS Page 47
IN UNITED STATES: 260 NORTH ELM ST. • WESTFIELD, MA 01085 • (413) 564-5515 • FAX (413) 568-9613
IN CANADA: 7555 TRANMERE DRIVE • MISSISSAUGA, ONT. L5S 1L4 • (905) 672-2991 • FAX (905) 672-2883