Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

SCHEDULE OF DATA FOR THREE COLUMN DOUBLE BREAK DISCONNECTOR

FOR CONVENTIONAL SWITCHYARDS

(i) GENERAL
Disconnector type eDB72.5
Number of poles 3
Max. Altitude < 1000 m A.S.L.
Min. Temperature -5º C
Max. Temperature 50°C

(ii) RATINGS AND GUARANTEED PERFORMANCE IN ACCORDANCE WITH IEC 62271-102

Disconnector eDB72.5

No. of Built-on earth switch One

 Rated voltage kV 72.5

 Rated normal current (@ 50deg C) A 630

 Rated short-time current for


disconnector and earthing switch kA(rms) / s 31.5 / 3

 Rated peak withstand current for


disconnector and earthing switch kA(peak) 79

 Rated 1 min power-frequency


withstand voltage (50 Hz)
to earth and between poles kV(rms) 140
across isolating distance kV(rms) 160

 Rated lightning impulse withstand


Voltage 1.2/50 µs
to earth and between poles kV(peak) 325
across isolating distance kV(peak) 375

 Rated switching impulse withstand


Voltage 1.2/50 µs
to earth kV(peak) N.A.
between poles kV(peak) N.A.
across isolating distance kV(peak) N.A.

 Radio interference voltage at 1.13Ur/√3 µV N.A.

 Induced Current Switching by Earthing Switch Class B

Page 1 of 2
 Insulator design:
Color & Type Brown Porcelain
minimum failing load kN 6
minimum creepage distance mm/kV 31
overall height mm 770

 Admissible mechanical terminal load


static and dynamic kN 4.5
static portion kN 1.5

 Operating Mechanism
For Main Blade Motor
For Earth Switch-1 Motor
For Earth Switch-2 -

 Control Voltage V d.c. 110

 Motor Voltage (if applicable) V d.c. 110

 Heater Voltage V a.c. 230

 Spare Auxiliary Contacts


For Main Blade 8 NO + 8 NC
For Earth Switch-1 4 NO + 4 NC
For Earth Switch-2 -

 Tyical Dimension Drawing 1HYD990301-031

Page 2 of 2

You might also like