INSTRUCTION MANUAL
MULTI-FUNCTION DIGITAL RELAY
DMR-Pro
DMR-FN
DMR-GN
DMR-BN
DMR-SN
DMR-212-006
Introduction
Thank you for your purchase of our product.
Read this instruction manual carefully before installation, wiring, and using this product.
This product is a product with the guard relay function for carrier transformation equipment.
Before use, please read this instruction manual and use it correctly.
Please keep it at hand to see always after reading.
If this instruction manual is lost or damaged, please ask our company or a distributing agent.
The detailed specification of a communication output (option), a communication step, and a communications protocol are
not indicated by this instruction manual. Please refer to the communication specification of a separate volume.
In addition, if a communication specification is necessary, please require of our company or a distributing agent.
<Caution>
Have a contact with us when you have any questions or are aware of missing article.
Safety precaution
Important contents are mentioned in this instruction manual to prevent any damage / use this product appropriately.
Keep the following safety precaution in mind after understanding each sign.
Improper use may lead to death or severe injury.
【About a disclaimer】
We are not responsible for the damage caused by following condition (earthquake / fire which is not caused by
us, action by third party, other accident, damage caused by our customer, misuse, product usage under abnormal condition).
We are not responsible for secondary damage caused by product use / product malfunction (loss of profit, halt of
business operation).
We are not responsible for damage produced depending on the usage which is not indicated by the instruction manual.
We are also not responsible for damage caused by false operation in combination with connecting equipment which is beyond
our control.
Do not use this product in a environment of high temperature and high humidity to prevent any damage.
Do not touch the terminal during operation to prevent electric shock.
Please do not pull a connection line by force or do not bend it by force. Damage of codes causes generation of heat
and a burn. And, apparatus breaks down by the loose connection.
Please do not perform connection or inspection of apparatus by the wet hand.
Please wire in applied voltage and the electric wire size suitable for power distribution current.
1
DMR-212-006
Other precaution
If control power supply voltage uses this product in the same input as a voltage measurement circuit by AC.
Please provide a power supply from an uninterruptible power system or dedicated AC power supply backup unit (type:
PBU-93. Option, Refer to 9 section).
If these are not used and control power supply voltage is less than the fluctuation range (AC100/110V±15%) in blackout
etc., it becomes impossible to perform ON / OFF control (any condition of REMOTE/LOCAL), and the relay output by protection
detection.
The abnormal output of equipment (relay break contact output).
The equipment abnormal output of this product is relay b contact output. (At the case of normal, a relay is excited
and the contact is OFF)
For this reason, it takes about 800ms by the contact OFF of an equipment abnormal output from control power supply input
(after the control power supply voltage was settled within ranges).
Please use a timer etc., in order to prevent false detection.
About an initial processing time.
The initial processing time of this product is necessary for about 1 second after control power supply input (after the
control power supply voltage was settled within ranges).
About an protection function stop mode.
This product is equipped with various test modes as a maintenance function.
While performing this mode, all original protection functions are suspended.
The details in each mode, please refer to "8. maintenance and the inspection".
• Sequence test mode.
It is the mode which checks protection detection operation, without applying an input.
Only arbitrary time can make protection detection condition by switch operation.
• Relay test mode.
This mode actually applies an input and confirms protection detection operation.
It outputs the relay contact only for these modes (test).
• Self check mode.
They are an internal memory, display, DI, and the mode that checks whether various option outputs are operating
normally.
Mercury component and Nickel-cadmium battery are not used in this product.
Please dispose of this product as industrial waste (noncombustible).
2
DMR-212-006
4. Setting
This product needs setting and a check of a measurement range or protection detection before use.
In wrong setting, it may cause a malfunction to protection detection. And, measurement display may become abnormal.
5. Operation
Please be careful of the following item at the case of operation.
Use the input within the rated range. Be careful since negligence of this caution may cause troubles of the unit.
Please shut a switch cover, if it is not operated.
• Be careful not to touch any terminal when power is applied to the unit.
• It is not warranted if this product is disassembled and converted without notice.
Also, modifications may cause troubles, a fire, or other accidents.
For specifications change, etc., please contact us.
If a question has arisen or if the unit seems to be defective, please contact us.
3
DMR-212-006
1. Warranty period
It is for one year after product delivery.
2. Warranty scope
In the state of the normal use of product-specification within the range according to this instruction manual,
the trouble within the warranty period performs exchange or repair gratuitously.
However, the shipping expenses and the packing cost in the case of shipping obtain as payment on a customer.
And, if it corresponds to the next, it does not warrant.
(1) If it breaks down when converted or repaired except our company.
(2) If it breaks down by use outside the specification range.
(3) If the cause of trouble is based on cause other than this product.
(4) Transportation, movement, damage by falling, and trouble.
(5) A natural disaster, disaster, etc., if it is the trouble which is irresponsible for a payment side (our company
or distributing agent).
Only a product simplex is applied with a warranty. We cannot bear the responsibility such as the damage and the loss
that occurred by the use of this product and trouble or the loss of profits.
3. Service
The following service expense is not contained in the price of this product.
(1) Dispatch of an artificer (Test run presence, maintenance inspection).
(2) The trouble investigation of possible cause and repair by cause besides a warranty scope.
(3) The trouble investigation of possible cause and repair in an out of warranty.
Please use this product within the limits of the following normal service condition about the environment by which
use is done.
1. The fluctuation range of control power supply voltage, +30...-20%(DC) and ±15% (AC) of rated voltage.
2. Fluctuation of frequency is within ±5% of a rated frequency.
3. Ambient temperature is 0...40℃. However, it permits -10℃ to +50℃ for several hours (condition that neither
dew condensation nor freezing occurs).
4. Storage conditions are the same as an operating condition. Storage temperature is -25℃ to +60℃.
5. Relative humidity is a one day average and is 30% to 80%.
6. Altitude is 2000m or less.
7. Condition of not receiving an abnormal vibration (exceeds the 16.7Hz and double amplitude of 0.4mm), a shock
(exceeds the 294m/s2), an inclination (exceeds the 5° from front to back and from side to side), and a magnetic
field (exceeds the 400A/m).
8. Condition which is not exposed to the next conditions.
Harmful smoke or gas. Gas including salt. Waterdrop or steam. Too much dust or powder.
Explosive gas or an explosive powder. Weather.
4
DMR-212-006
Content
3. Specification ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 9
3.1 Rating ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 9
3.2 The function list according to models ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 9
3.3 Protection factor Specification ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 11
3.3.1 Overcurrent [51] inverse time characteristics ・・・・・・・・・・・・・・・・・・・・・・ 14
3.3.2 Overcurrent [51] calculation formula ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 19
3.3.3 Directional earth-fault [67] phase characteristic ・・・・・・・・・・・・・・・・・・ 19
3.4 Measurement specification ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 20
3.5 Option specification ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 23
3.6 Performance (Strength) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 24
5. Preparation ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 30
5.1 Installation ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 30
5.2 Wiring ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 31
6. Control ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 42
6.1 External sequence ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 42
6.1.1 Kind and function of input ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 42
6.1.2 Kind and function of output ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 42
6.2 Control in control output 「ON」 「OFF」 「TRIP」 specification ・・・・・・・・・・・・・・ 43
6.2.1 ON/OFF control ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 43
6.2.2 Control by protection detection ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 44
6.2.3 Block diagram of control ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 45
6.2.4 Timing of control action ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 46
7. Operation・Setting ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 47
《Default setting value》・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 48
7.1 Display change ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 51
7.1.1 Measurement setting value display ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 52
7.1.2 Protection setting value display ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 53
7.1.3 Protection detection history display ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 57
7.1.4 Error code display ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 58
7.2 Measurement factor display change ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 59
7.2.1 Main monitor measurement display factor change ・・・・・・・・・・・・・・・・・・・・・ 59
7.2.2 Phase, line display change ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 59
7.2.3 Integrated value expansion display change ・・・・・・・・・・・・・・・・・・・・・・・・・・ 59
7.3 Measurement value reset ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 60
7.3.1 Maximum value and minimum value reset ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 60
7.3.2 Integrated value reset ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 60
7.4 Setting ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 61
7.4.1 Measurement factor setting ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 61
7.4.2 Protection factor setting ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 76
7.5 LOCAL-REMOTE cahnge ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 94
7.6 ON/OFF control ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 94
7.7 Test mode ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 95
7.7.1 Sequence test mode (STM) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 95
7.7.2 Relay test mode (RTM) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 96
7.7.3 Self check mode ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 97
7.8 Version check ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 98
7.9 Reset operation at the case of protection detection ・・・・・・・・・・・・・・・・・・・・ 99
7.10 Reset operation at the case of fail-safe error occurrence ・・・・・・・・・・・・・・ 100
7.11 Zero phase current input correction ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 101
5
DMR-212-006
9. Related product
9.1 AC power supply backup unit (TYPE:PBU-93) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 121
9.1.1 Specification ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 121
9.1.2 Block diagram ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 121
9.1.3 The name and function of each part ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 122
9.1.4 Preparation ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 122
9.1.5 Connection ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 124
9.1.6 Compulsive electric discharge ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 124
9.1.7 Cautions on handling ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 124
9.1.8 Check ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 125
9.1.9 Maintenance ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 125
9.1.10 Storage ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 125
9.1.11 Design expected life ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 125
9.1.12 Troubleshooting ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 125
9.1.13 Warranty ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 125
6
DMR-212-006
1. Product outline
1.1 Usage of product
This product is a guard relay for carrier transformation equipment.
This one product performs a protection function and various measurement displays.
The direct control from a built-in switch is possible. And, circuit breaker ON/OFF control is possible by outside
DI and the remote control from communication.
Analog output, an watt-hour pulse output, and a communication output are possible as an option.
Main transformer
9 DMR-SN-A1100□1-□□□□□ AC110V AC5A - -
secondary
Main transformer
10 DMR-SN-A1200□1-□□□□□ AC110V AC1A - -
secondary
7
DMR-212-006
DMR-FN-□ □ □ □ □ □ □ -□ □ □ □ □
ON/OFF display color(Switch,LED)
1:「ON」 - Red,「OFF」 - Green
2:「ON」 - Green,「OFF」 - Red
Priority control
1:REMOTE / LOCAL switch priority
2:「OFF」control priority
Installation position
1:For high position installation (LCD visual angle direction:Lower view)
2:For low position installation (LCD visual angle direction:Upper view)
Communication output
0:Nothing
2:Modbus (RS-485)
Control output〔Fixation〕
1:「ON」「OFF」「Trip」
Type
F:Feeder (For directional earth-fault【67】)
G:Feeder (For earth-fault overcurrent【51G】)
B:Bus
S:Main transformer secondary
8
DMR-212-006
3. Specification
3.1 Rating
Item Rating
Three-phase three-wire:AC110V,AC5A or 1A [Designation],50/60Hz,
2VT・3CT method (or 2VT・2CT method)
DMR-FN Zero-phase voltage:AC110V,190V common use (EVT) or AC1V (ZPD:AC190V/50mV)
[Designation],50/60Hz
Zero phase current:AC4A/30mA (ZCT:AC200mA/1.5mA), 50/60Hz
Input Three-phase three-wire:AC110V,AC5A or 1A [Designation],50/60Hz, 2VT・3CT method
DMR-GN
( 3) Zero phase current:AC5A or 1A (CT residual circuit) [Designation], 50/60Hz
Three-phase three-wire:AC110V,50Hz/60Hz,2VT method
DMR-BN Zero-phase voltage:AC110V,190V common use(EVT) or AC1V(ZPD:AC190V/50mV)
[Designation],50/60Hz
Three-phase three-wire:AC110V,AC5A or 1A [Designation],50/60Hz,
DMR-SN
2VT・3CT method (or 2VT・2CT method)
Input
Voltage circuit:0.5VA or less, Current circuit:0.1VA or less
consumption VA
Control power
DC100/110V(-20…+30%) or AC100/110V(±15%) [Designation]
supply
3
Note( ) Please use the following in the case of use of CT, ZPD, and ZCT.
This product can also be used by single phase load.
The connection number of this product per ZPD becomes to eight sets at the maximum.
CT :Overcurrent constant n>10.
ZPD:HIKARI TRADING CO.,LTD. ZPC-9B
ZCT:JEC-1201 compliance product (200mA/1.5mA)
9
DMR-212-006
10
DMR-212-006
11
DMR-212-006
12
DMR-212-006
13
DMR-212-006
10000
1000
100
Operating
time
(Second)
Time multiplier:U
10 30
Time multiplier:U
25
30 20
25
20 15
15 10
10 5
1 4
5 3
4
2
3
1.5
2
1.5 1.1
1.1 1
1
0.1
0.01
100% 1000% 10000%
Current (% of the input current to a setting value)
14
DMR-212-006
10000
1000
100
Operating
time
(Second)
Time multiplier:U
10 30
25
20
15
10
1 4
3
Time multiplier:U
2
1.5
30
1.1
25
20 1
15
0.1
10
1.5 2 3 4 5
1 1.1
0.01
100% 1000% 10000%
15
DMR-212-006
10000
1000
100
Operating
time
(Second)
Time multiplier:U
10
30
25
20
15
10
Time multiplier:U
5
1 4
30
25 3
20 2
15
1.5
10 1.1
1
5
0.1 4
3
2
1 1.1 1.5
0.01
100% 1000% 10000%
Current (% of the input current to a setting value)
16
DMR-212-006
10000
1000
100
Operating
time
(Second)
Time multiplier:U
10 30
Time multiplier:U 25
20
30
15
25
20 10
15
5
10
1 4
3
5
4 2
3 1.5
2 1.1
1.5 1
1.1
0.1 1
0.01
100% 1000% 10000%
17
DMR-212-006
10000
1000
100
Operating
time
(Second)
Time multiplier:U
10
30
Time multiplier:U 25
20
30
15
25
20 10
15
5
1 10 4
3
5 2
4
1.5
3
1.1
2
1
1.5
1.1
0.1 1
0.01
100% 1000% 10000%
Current (% of the input current to a setting value)
18
DMR-212-006
LEAD V0 LAG
Operating angle:40°
90° 270°
100% 200% 300% 400% 500%
An operation phase angle in case operating
Magnification to current
setting value angle is 0°.
19
DMR-212-006
20
DMR-212-006
Item Specification
Bar graph Bar graph display (Watt-hour and var-hour exclude) of the main monitor factor.
display A sub monitor factor can also be indicated by setting.
Current / Maximum current (L1,L2,L3),
Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1), Power, Reactive power,
Main monitor Power factor, Frequency, Watt-hour, var-hour,
Zero phase current / Maximum zero phase current,
Zero phase voltage / Maximum zero phase voltage
Current / Maximum current (L1,L2,L3),
Sub monitor Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1),
(Left) Power, Reactive power, Power factor, Zero phase current / Maximum zero phase current,
Display Zero phase voltage / Maximum zero phase voltage
setting Current / Maximum current (L1,L2,L3),
possible Sub monitor Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1), Power, Reactive power,
factor (Center) Frequency, var-hour, Zero phase current / Maximum zero phase current,
(11) Zero phase voltage / Maximum zero phase voltage
Current / Maximum current (L1,L2,L3),
Sub monitor Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1), Power, Power factor,
(Right) Frequency, Watt-hour, Zero phase current / Maximum zero phase current,
Zero phase voltage / Maximum zero phase voltage
Current / Maximum current (L1,L2,L3),
Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1), Power, Reactive power,
Bar graph
Power factor, Frequency, Zero phase current / Maximum zero phase current,
Zero phase voltage / Maximum zero phase voltage
Note(11) It is based on the measurement factor of each model.
270°
(var=100%,PF=0%)
21
DMR-212-006
● Measurement range
Measurement Input Measurement range
Note
factor ( ) is 1A rating Display Analog output
Current AC0…5A (AC0…1A) 120% of input rating DC4…23.2mA Maximum, Instant
Maximum,
Voltage AC0…150V 101% of meter full-scale DC4…20.16mA
Minimum, Instant
0…1kW (0…200W) DC3.84…23.2mA
Power 120% of input rating
-1…0…+1kW (-200…0…+200W) DC3.84…21.6mA
Reactive LEAD 1…0…LAG 1kvar
120% of input rating DC3.84…21.6mA
power (LEAD 200…0…LAG 200var)
LEAD 0…1…LAG 0 LEAD 0.00…1.00…LAG 0.00 DC4…20mA
Power factor
LEAD 0.5…1…LAG 0.5 LEAD 0.49…1.00…LAG 0.49 DC3.84…20.16mA
45…55Hz 44.9…55.1Hz
Frequency DC3.84…20.16mA
55…65Hz 54.9…65.1Hz
ZCT AC0…4A ( /30mA) 120% of input rating -
Zero phase
CT residual Maximum, Instant
current AC0…5A (AC0…1A) 120% of input rating -
circuit
AC0…110V Maximum, Instant
EVT
AC0…190V DC4…23.2mA or Analog output is
Zero phase
120% of input rating DC4…18.08mA only for maximum
voltage
ZPD AC0…1V (15) (16) zero-phase
voltage.
Note(15) If it uses ZPD by primary rating 3300V, a measuring range is AC0…0.5V. (if voltage range setting is
3300V or 3.3kV setting)
Note(16) A measuring range changes by setting of a zero phase voltage output range.
Example) In case of EVT specification, and secondary rating 110V.
・0…150V/DC4…20mA setting:Measurement range 0…132V(1.2 times 110V)/DC4…18.08mA
・0…110V/DC4…20mA setting:Measurement range 0…132V(1.2 times 110V)/DC4…23.20mA
In case of EVT primary rating 6600V, 150V is 9000V equivalency, and 110V is 6600V equivalency.
22
DMR-212-006
23
DMR-212-006
24
DMR-212-006
* Communication error:If transmission and reception are not correctly performed even if it
performed the continuation retry 3 times.
25
DMR-212-006
26
DMR-212-006
Bar graph
Indicate the measurement ・Operation switch
value of the main monitor. Use it for reset and various
(Exclude Watt-hour and settings of the change of the
var-hour) display mode of a LCD, the
And, the measurement value change of the phase (line) of
of sub-monitor can be a measurement factor or a
displayed on bar graph. measurement factor, and a
In this case, a bar is measurement value.
indicated on the bottom of
the set sub monitor digital
display.
・Operation switch
(Inside of switch cover)
Use it for the change of
Switch cover REMOTE/LOCAL control, ON/OFF
control of a circuit breaker,
and the test mode of apparatus.
Termination register
ON-OFF switch
27
DMR-212-006
28
DMR-212-006
29
DMR-212-006
5. Preparation
5.1 Installation
Refer to an outline dimension drawing, a panel cutout, and the mounting instruction for a mounting instruction.
And, please install in a panel with an attached installation tool and an attached installation screw.
● Outline dimension drawing
● Caution on handling
The contrast of LCD changes with the angle to see. Please install in the position used as an optimum angle.
(1) For upper case installation. (2) For lower case installation.
● Installation
(1) Insert a product in the cut hole of a panel from the front.
(2) Install an attached installation tool in the mounting hole
of a product side from a back of panel. (Two points of right
and left. Total of four points.)
(3) Put the nail of an installation tool into the hole of a
product, draw it into the back side and insert it.
(4) Perform the screw bundle of an installation tool in a cross
slot screwdriver, and fix a product. (Two points of right
and left. Total of four points.) Please give a tightening
torque as 0.59 to 1.08N・m (6 to 11 kg・cm).
Recommendation tightening torque:0.88N・m(9kg・cm).
When you tighten a screw, please tighten by turns.
And, if it installs in the place where vibration is added,
please use a screw lock etc.
30
DMR-212-006
5.2 Wiring
If it wires this product, please perform connection with reference to the following.
● Wiring step
(1) Wiring of a terminal block.
A terminal block is screw stop structure. Please be sure to use a solderless contact. In that case, please protect
a tightening torque and press a screw correctly.
The short bar is beforehand installed in the current input terminal. If this short bar is removed and it wires,
there is a possibility of damaging a product. Please be sure to wire, with a short bar installed.
・Terminal block (Manufacturer:FUJICON CO.,LTD.)
Compatibility Compatibility Terminal Tightening
No. Application
electric wire solderless contact screw torque
AWG22(0.25mm2 ) to
Terminal block for control 1.25-3.5
16(1.65mm2 ) 0.8…1.0N・m
TB power supply, AC input M3.5×8×8L
AWG16(1.04mm2 ) to (8…10kg・cm)
(connecting terminal) 2-3.5
14(2.63mm2 )
31
DMR-212-006
E 1S 1L 2S 2L 3S 3L
CN3 1 3 5 7 9 11 13 15 17 19 21 23 25
2 4 6 8 10 12 14 16 18 20 22 24 26
CN1 P N P1 P2 P3 V0 Z1 Z2
AUX.SUPPLY (24) I0
CN2
TB
CN1:DO
No. Terminal name No. Terminal name
A1 CB-ON B1 CB-ON
A2 CB-OFF B2 CB-OFF
A3 CB-Trip B3 CB-Trip
A4 NC B4 NC
A5 Fault 1 B5 Fault 1
A6 Fault 2 B6 Fault 2
A7 Fault 3 B7 Fault 3
A8 REMOTE/LOCAL B8 REMOTE/LOCAL
A9 TEST B9 TEST
A10 Equipment malfunction B10 Equipment malfunction
CN2:DI
No. Terminal name No. Terminal name
A1 CB-ON answer (+) B1 CB-ON answer (-)
A2 CB-OFF answer (+) B2 CB-OFF answer (-)
A3 REMOTE-ON (+) B3 REMOTE-ON (-)
A4 REMOTE-OFF (+) B4 REMOTE-OFF (-)
A5 External trip (+) B5 External trip (-)
Note(21) In the case of DMR-BN, there are no three phase current (1S, 1L, 2S, 2L, 3S, 3L) and zero phase current
(Z1, Z2) input. In the case of DMR-SN, there are no zero phase voltage (V0) and zero phase current (Z1,
Z2) input. In the case of DMR-GN, there is no zero phase voltage (Vo) input. And, wiring of Io changes.
Note(22) If there is no option, there is no CN3.
Note(23) In the case of DMR-BN, analog output becomes to three factors. And, a pulse output cannot be performed.
Therefore, these terminals are non-connected (NC) terminals.
Note(24) As for the zero phase voltage Vo input, polarity of the wiring changes in ZPD and EVT.
32
DMR-212-006
● Block diagram
(1) DMR-FN
P1 Input DO1
circuit (CB-ON)
P2
Input DO2
circuit (CB-OFF)
P3
1S Input DO3
circuit (CB-TRIP)
1L
2S Input DO4
circuit (50)
2L S/H
+ I/O
3S Input DO5
ADC (51)
3L circuit
Input
DO6
Vo (67)
circuit
DO7
Input (LOCAL/REMOTE)
Io circuit
DO8
(TEST)
Vref
DO9
[b contact]
(Equipment
malfunction)
S1 Power
supply
circuit WDT
S2
E RESET
DI1 CLK
(CB-ON answer)
DI2 LCD
(CB-OFF answer)
DI3 I/O
(REMOTE-ON)
CPU (+)
DI4 T/D AO1
(REMOTE-OFF) (-)
(+)
DI5 T/D AO2
(External trip) (-)
(+)
T/D AO3
(-)
NVSRAM (+)
T/D AO4
(-)
LED I/O
Photo MOS
relay WHP
Switch I/O
+
SCI
TX/RX -
SG
Ter.
33
DMR-212-006
(2) DMR-GN
P1 Input DO1
circuit (CB-ON)
P2
Input DO2
circuit (CB-OFF)
P3
1S Input DO3
circuit (CB-TRIP)
1L
2S Input DO4
circuit (50)
2L S/H
+ I/O
3S Input DO5
ADC (51)
3L circuit
DO6
(51G)
DO7
Input (LOCAL/REMOTE)
Io circuit
DO8
(TEST)
Vref
DO9
[b contact]
(Equipment
malfunction)
S1 Power
supply
circuit WDT
S2
E RESET
DI1 CLK
(CB-ON answer)
DI2 LCD
(CB-OFF answer)
DI3 I/O
(REMOTE-ON)
CPU (+)
DI4 T/D AO1
(REMOTE-OFF) (-)
(+)
DI5 T/D AO2
(External trip) (-)
(+)
T/D AO3
(-)
NVSRAM (+)
T/D AO4
(-)
LED I/O
Photo MOS
relay WHP
Switch I/O
+
SCI
TX/RX -
SG
Ter.
34
DMR-212-006
(3) DMR-BN
P1 Input DO1
circuit (CB-ON)
P2
Input DO2
circuit (CB-OFF)
P3
DO3
(CB-TRIP)
DO4
(27)
S/H
+ I/O
ADC
DO5
(59)
Input
DO6
Vo (64)
circuit
DO7
(LOCAL/REMOTE)
DO8
(TEST)
Vref
DO9
[b contact]
(Equipment
malfunction)
S1 Power
supply
circuit WDT
S2
E RESET
DI1 CLK
(CB-ON answer)
DI2 LCD
(CB-OFF answer)
DI3 I/O
(REMOTE-ON)
CPU (+)
DI4 T/D AO1
(REMOTE-OFF) (-)
(+)
DI5 T/D AO2
(External trip) (-)
(+)
T/D AO3
(-)
NVSRAM
LED I/O
Switch I/O
+
SCI
TX/RX -
SG
Ter.
35
DMR-212-006
(4) DMR-SN
P1 Input DO1
circuit (CB-ON)
P2
Input DO2
circuit (CB-OFF)
P3
1S Input DO3
circuit (CB-TRIP)
1L
2S Input DO4
circuit (50)
2L S/H
+ I/O
3S Input DO5
ADC (51)
3L circuit
DO6
(27)
DO7
(LOCAL/REMOTE)
DO8
(TEST)
Vref
DO9
[b contact]
(Equipment
malfunction)
S1 Power
supply
circuit WDT
S2
E RESET
DI1 CLK
(CB-ON answer)
DI2 LCD
(CB-OFF answer)
DI3 I/O
(REMOTE-ON)
CPU (+)
DI4 T/D AO1
(REMOTE-OFF) (-)
(+)
DI5 T/D AO2
(External trip) (-)
(+)
T/D AO3
(-)
NVSRAM (+)
T/D AO4
(-)
LED I/O
Photo MOS
relay WHP
Switch I/O
+
SCI
TX/RX -
SG
Ter.
36
DMR-212-006
● Connecting diagram
(1) DMR-FN
● 2CT,EVT ● ZPD
ON B1
OFF B2
TRIP B3
Fault 1 (50)
Fault 2 (51) ● 3CT
Fault 3 (67)
REMOTE/LOCAL
Test
Equipment malfunction
REMOTE-ON
REMOTE-OFF
External trip
Communication
output
● If single phase load is taken ● If single phase load is taken ● If single phase load is taken
from between L1 and L2. from between L2 and L3. from between L3 and L1.
37
DMR-212-006
(2) DMR-GN
ON B1
OFF B2
TRIP B3
Fault 1 (50)
Fault 2 (51)
Fault 3 (51G)
REMOTE/LOCAL
Test
Equipment malfunction
REMOTE-ON
REMOTE-OFF
External trip
Communication
output
38
DMR-212-006
(3) DMR-BN
● EVT ● ZPD
B1
B2
B3
Fault 1 (27)
Fault 2 (59)
Fault 3 (64)
REMOTE/LOCAL
Test
Equipment malfunction
REMOTE-ON
REMOTE-OFF
External trip
Communication
output
39
DMR-212-006
(4) DMR-SN
● 3CT, EVT ● 2CT
ON B1
OFF B2
TRIP B3
Fault 1 (50)
Fault 2 (51)
Fault 3 (27)
REMOTE/LOCAL
Test
Equipment malfunction
REMOTE-ON
REMOTE-OFF
External trip
Communication
output
● If single phase load is taken ● If single phase load is taken ● If single phase load is taken
from between L1 and L2. from between L2 and L3. from between L3 and L1.
40
DMR-212-006
● Caution on handling
(1) Please install a terminal cover, if connection is finished.
(2) Please be sure to separate the wiring by the input and the output. Please do consideration (malfunction
prevention) to an exogenous noise.
(3) Please ground a earth terminal (E) in order to increase the shield effect.
And, please give the earthing resistance between a earth terminal and the ground as 100Ω or less.
(4) Please shorten wiring for this product from secondary of ZPD and ZCT, as much as possible.
In order to avoid the influence of noise sources, such as a main circuit, recommend a shielded twisted pair cable
line.
(5) In case analog output is sent at a distance, even if there is a possibility of receiving the influence of indirect
stroke serge etc. in a transmission line, protection is unnecessary for this product.
In addition, in order to protect the equipment by the receiver, please install an about 500V arrester etc. to
a receiver side between the line serge protector, and a transmission line and the ground.
(6) Wiring of analog output recommends a twisted pair cable line. (Normal mode noise abatement)
If the influence of an exogenous noise is large, recommend a shielded twisted pair cable line.
(Normal mode and common mode noise abatement) And, please ground a shield one point.
(7) Please use a shielded twisted pair cable line for a communication output. Please use the same cables including
the inside of a board.
And, please ground in the existing most operative place in a place with many inductive noises.
(8) If an inductive load is connected to a pulse output and an alarm output, recommend installation of a serge
killer to the outside. The life of a contact may become short if there is no serge killer.
(9) This product has the control output of three points. (Circuit breaker trip control by the protection function,
And contact output for circuit breaker "ON/OFF" control.)
In order to prevent the mistake trip of a circuit breaker, please connect these outputs correctly.
(Refer to the following figure.)
Please refer to "6. Control" about operation of an output.
(10) The indication for "ON" and "OFF" LED of this product, carry out by receiving the answer signal from a
circuit breaker by DI. Please connect wiring of DI to an answer from each circuit breaker. (Please refer
to the following figure.)
(DI1:CB-ON answer , DI2:CB-OFF answer)
Control 1 (CB-ON) B1
Control 2 (CB-OFF) B2
Control 3 (CB-TRIP) B3
CB-ON Answer
CB-OFF Answer
41
DMR-212-006
6. Control
6.1 External sequence
6.1.1 Kind and function of input
No. Factor Specification・Use Note
The answer of circuit breaker-ON status.
DI1 CB-ON answer
During an input, LED "ON" is lighted. Use it for LED
The answer of circuit breaker-OFF status. lighting.
DI2 CB-OFF answer
During an input, LED "OFF" is lighted.
By the input at the case of "REMOTE", "CB-ON" output is ON (OFF priority).
REMOTE-ON Invalid at the case of "LOCAL".
DI3
Command Trouble displaying "ON" control, setting of enable/disable is possible
according to a protection factor.
Valid in the input
"CB-OFF" output ON in the input at the case of "REMOTE."
for 100ms or more.
REMOTE-OFF Invalid at the case of "LOCAL".
DI4
Command However, the case of "OFF" control priority, it is not based on the status of
"REMOTE/LOCAL" but is "CB-OFF" output ON.
DI5 External trip “CB-trip” output ON. "CB-Trip" output ON while the input is continuing.
Number of inputs :5 points, Photo coupler insulation method
Input rating Input :DC100V/110V 0.6W,AC100V/110V 0.6VA
Minimum pulse width:100ms or more
42
DMR-212-006
(3) Control by DI
・ If the "LOCAL-REMOTE" switch is "REMOTE", control by DI is possible.
・ "CB-ON" output is ON in 100ms or more of "REMOTE-ON" inputs.
・ "CB-OFF" output is ON in 100ms or more of "REMOTE” OFF" inputs.
However, in "OFF" control priority, "CB-OFF" output is ON regardless of the status of "LOCAL-REMOTE".
43
DMR-212-006
44
DMR-212-006
ON
100ms
Delay
OFF circuit
ON/OFF
Switch PERMISSION 1s
Monostable
circuit CB-ON
LOCAL-REMOTE
[LOCAL] 1s
Monostable
CB-OFF DO
circuit
[REMOTE]
ON
REMOTE-ON
Control signal from CPU
(The command by protection OFF CB-Trip
detection and communication.)
DI REMOTE-OFF Trip
External
trip
Output lock by
Lock
fail-safe error
ON
100ms
Delay
OFF circuit
ON/OFF
Switch PERMISSION 1s
Monostable
circuit CB-ON
LOCAL-REMOTE
[LOCAL] 1s
Monostable
CB-OFF DO
circuit
[REMOTE]
ON
REMOTE-ON
Control signal from CPU
(The command by protection OFF CB-Trip
detection and communication.)
DI REMOTE-OFF Trip
External
trip
Output lock by
Lock
fail-safe error
45
DMR-212-006
Fault 1 input
Reset time Reset time
(Automatic reset
setting)
Fault 2 input
Reset time Reset time
(Hold setting)
OFF priority
ON 100ms
SW/DI/Communication or more 100ms or more 100ms or more
OFF 100ms
SW/DI/Communication or more
100ms
ON/OFF permission
or more
SW/DI/Communication
ON operation reset
(For an ON continuation input)
ON is off (with no input)
CB-ON DO 1 sec
min.
CB-OFF DO
Fault 2 DO
(Hold setting)
Fault 1 LED
(Automatic reset
setting)
Flicker Flicker
Fault 2 LED
(Hold setting)
Flicker Flicker
TRIP LED
Protection
detection display
LCD display Protection
detection display
Protection
detection display Protection detection
1 second 1 second display (Update)
or more or more 1 second or more
RESET SW
46
DMR-212-006
7. Operation・Setting
This product displays various measurement values on a LCD. And, a display and change of a protection setting value can
be performed. Perform a change and setting of a display by the front push switch.
MODE
47
DMR-212-006
《Default settings》(1)
This product is shipped with the following setting value. Please set according to an use conditions.
Feeder(For directional earth-fault)DMR-FN Feeder(For earth-fault overcurrent)DMR-GN
Setting
Default Default
No. Setting item Setting item
settings settings
1101 Display pattern Pattern 1 Display pattern Pattern 1
1102 Main monitor display factor Current (L2) Main monitor display factor Current (L2)
1103 Sub-monitor (left) display factor Voltage (L1L2) Sub-monitor (left) display factor Voltage(L1L2)
1104 Sub-monitor (center) display factor Power Sub-monitor (center) display factor Power
1105 Sub-monitor (right) display factor Watt-hour (Wh) Sub-monitor (right) display factor Watt-hour (Wh)
1106 Bar graph display factor Main monitor Bar graph display factor Main monitor
1201 Voltage measurement range 6600V Voltage measurement range 6600V
1202 Current measurement range 100.0A Current measurement range 100.0A
One-way One-way
1203 Power polarity Power polarity
deflection deflection
1204 Power measurement range 1200kW Power measurement range 1200kW
1205 Reactive power measurement range 600kvar Reactive power measurement range 600kvar
1206 Power factor measurement range 0.5-1-0.5 Power factor measurement range 0.5-1-0.5
1207 Frequency measurement range 45-55Hz Frequency measurement range 45-55Hz
1208 Zero phase voltage rating (EVT) (31) 110V
1209 Zero phase voltage output range (32) 9000V
1301 A display ON/OFF ON A display ON/OFF ON
1302 Amax. display ON/OFF ON Amax. display ON/OFF ON
1303 V display ON/OFF ON V display ON/OFF ON
1304 Vmax. display ON/OFF ON Vmax. display ON/OFF ON
1305 Vmin. display ON/OFF ON Vmin. display ON/OFF ON
1306 W display ON/OFF ON W display ON/OFF ON
1307 var display ON/OFF ON var display ON/OFF ON
1308 cosφ display ON/OFF ON cosφ display ON/OFF ON
1309 Hz display ON/OFF ON Hz display ON/OFF ON
1310 Wh display ON/OFF ON Wh display ON/OFF ON
1311 varh display ON/OFF ON varh display ON/OFF ON
1312 A0 display ON/OFF ON A0 display ON/OFF ON
1313 A0max. display ON/OFF ON A0max. display ON/OFF ON
1314 V0 display ON/OFF ON
1315 V0max. display ON/OFF ON
1401 L1 phase display ON/OFF ON L1 phase display ON/OFF ON
1402 L2 phase display ON/OFF ON L2 phase display ON/OFF ON
1403 L3 phase display ON/OFF ON L3 phase display ON/OFF ON
1404 L1L2 line display ON/OFF ON L1L2 line display ON/OFF ON
1405 L2L3 line display ON/OFF ON L2L3 line display ON/OFF ON
1406 L3L1 line display ON/OFF ON L3L1 line display ON/OFF ON
1501 Analog output 1 factor Current (L2) Analog output 1 factor Current (L2)
1502 Analog output 2 factor Voltage (L1L2) Analog output 2 factor Voltage (L1L2)
1503 Analog output 3 factor Power Analog output 3 factor Power
1504 Analog output 4 factor Power factor Analog output 4 factor Power factor
1505 Output intrinsic sensitivity (W) 100.0% Output intrinsic sensitivity (W) 100.0%
1506 Output intrinsic sensitivity (var) 50.0% Output intrinsic sensitivity (var) 50.0%
1601 Pulse output factor Watt-hour (Wh) Pulse output factor Watt-hour (Wh)
1602 Pulse unit 10kWh/pulse Pulse unit 10kWh/pulse
1701 Address 1 Address 1
1702 Transmission rate (33) 9600bps Transmission rate (33) 9600bps
33
1703 Parity ( ) Even Parity (33) Even
1704 Stop bit (33) 1 Stop bit (33) 1
48
DMR-212-006
《Default settings》(2)
Feeder(For directional earth-fault)DMR-FN Feeder(For earth-fault overcurrent)DMR-GN
Setting
Default Default
No. Setting item Setting item
settings settings
2101 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
2102 Operating value (34) 10A(2A) Operating value (34) 10A(2A)
2103 Operating time Instantaneous Operating time Instantaneous
2104 50 Reset method Hold 50 Reset method Hold
"ON" control within "ON" control within
2105 protection detection Permission protection detection Permission
display display
2201 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
2202 Characteristic Standard [SI] Characteristic Standard [SI]
2203 Operating value (34) 2.0A(0.40A) Operating value (34) 2.0A(0.40A)
2204 Time multiplier 1.0 times Time multiplier 1.0 times
51 51
2205 Reset method Hold Reset method Hold
"ON" control within "ON" control within
2206 protection detection Permission protection detection Permission
display display
2301 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
2302 Operating value (Current) 0.1A Operating value 0.25A(0.050A)
Operating value (Voltage) Instantaneous
2303 5V(0.025V) Operating time
(35) (50ms or less)
2304 Operating angle 40° 51G 2nd harmonic suppression OFF
2305 Operating time 0.1s Reset method Hold
"ON" control within
67
2306 Reset method Hold protection detection Permission
display
Zero phase current input
2307 100%
correction
"ON" control within
2308 protection detection Permission
display
2401 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
External "ON" control within External "ON" control within
2401 trip protection detection Permission trip protection detection Permission
display display
2501 Reset time 0.2s Reset time 0.2s
2601 Zero phase monitoring OFF Zero phase monitoring OFF
Note(31) It is a setting item of only a EVT specification. (It is skipped by ZPD specification.)
Note(32) In the equipment for DMR-FN, it is a setting item in a case with a communication output option.
(It is skipped if there is no option.)
Note(33) It is the setting item of only a Modbus communication output.
Note(34) ( ) is the default value in rated current AC1A
Note(35) ( ) is the default value in zero-phase rated voltage AC1V (ZPD)
In the default value, each protection factor is OFF (unused). The zero phase monitoring
(voltage, current) of a fail-safe function is also OFF (monitoring stop).
If it uses these factors, please make it setting ON (used).
49
DMR-212-006
《Default settings》(3)
This product is shipped with the following setting value. Please set according to an use conditions.
Bus DMR-BN Main transformer secondary DMR-SN
Setting
Default Default
No. Setting item Setting item
settings settings
1101 Display pattern Pattern 1 Display pattern Pattern 1
1102 Main monitor display factor Voltage (L1L2) Main monitor display factor Current (L2)
Maximum zero-
1103 Sub-monitor (left) display factor Sub-monitor (left) display factor Voltage (L1L2)
phase voltage
Zero-phase
1104 Sub-monitor (center) display factor Sub-monitor (center) display factor Power
voltage
1105 Sub-monitor (right) display factor Frequency Sub-monitor (right) display factor Watt-hour (Wh)
1106 Bar graph display factor Main monitor Bar graph display factor Main monitor
1201 Voltage measurement range 6600V Voltage measurement range 6600V
1202 Frequency measurement range 45-55Hz Current measurement range 100.0A
36 One-way
1203 Zero phase voltage rating (EVT) ( ) 110V Power polarity
deflection
1204 Zero phase voltage output range (37) 9000V Power measurement range 1200kW
1205 Reactive power measurement range 600kvar
1206 Power factor measurement range 0.5-1-0.5
1207 Frequency measurement range 45-55Hz
1301 V display ON/OFF ON A display ON/OFF ON
1302 Vmax. display ON/OFF ON Amax. display ON/OFF ON
1303 Vmin. display ON/OFF ON V display ON/OFF ON
1304 Hz display ON/OFF ON Vmax. display ON/OFF ON
1305 V0 display ON/OFF ON Vmin. display ON/OFF ON
1306 V0max. display ON/OFF ON W display ON/OFF ON
1307 var display ON/OFF ON
1308 cosφ display ON/OFF ON
1309 Hz display ON/OFF ON
1310 Wh display ON/OFF ON
1311 varh display ON/OFF ON
1401 L1L2 line display ON/OFF ON L1 phase display ON/OFF ON
1402 L2L3 line display ON/OFF ON L2 phase display ON/OFF ON
1403 L3L1 line display ON/OFF ON L3 phase display ON/OFF ON
1404 L1L2 line display ON/OFF ON
1405 L2L3 line display ON/OFF ON
1406 L3L1 line display ON/OFF ON
1501 Analog output 1 factor Voltage (L1L2) Analog output 1 factor Current (L2)
1502 Analog output 2 factor Frequency Analog output 2 factor Voltage (L1L2)
Maximum zero-
1503 Analog output 3 factor Analog output 3 factor Power
phase voltage
1504 Analog output 4 factor Power factor
1505 Output intrinsic sensitivity (W) 100.0%
1506 Output intrinsic sensitivity (var) 50.0%
1601 Pulse output factor Watt-hour (Wh)
1602 Pulse unit 10kWh/pulse
1701 Address 1 Address 1
1702 Transmission rate (38) 9600bps Transmission rate (38) 9600bps
1703 Parity (38) Even Parity (38) Even
1704 Stop bit (38) 1 Stop bit (38) 1
2101 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
2102 Operating value 60V Operating value (39) 10A(2A)
2103 Operating time 0.1s Operating time Instantaneous
2104 27 Reset method Hold 50 Reset method Hold
"ON" control within "ON" control within
2105 protection detection Permission protection detection Permission
display display
50
DMR-212-006
《Default settings》(4)
Bus DMR-BN Main transformer secondary DMR-SN
Setting
Default Default
No. Setting item Setting item
settings settings
2201 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
2202 Operating value 150V Characteristic Standard [SI]
2203 Operating time 0.1s Operating value (39) 2.0A(0.40A)
2204 59 Reset method Hold Time multiplier 1.0 times
"ON" control within
51
2205 protection detection Permission Reset method Hold
display
"ON" control within
2206 protection detection Permission
display
2301 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
2302 Operating value (40) 5V(0.025V) Operating value 60V
2303 Operating time 0.1s Operating time 0.1s
2304 64 Reset method Hold 27 Reset method Hold
"ON" control within "ON" control within
2305 protection detection Permission protection detection Permission
display display
2401 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
External "ON" control within External "ON" control within
2401 trip protection detection Permission trip protection detection Permission
display display
2501 Reset time 0.2s Reset time 0.2s
2601 Zero phase monitoring OFF Zero phase monitoring OFF
Note(36) It is a setting item of only a EVT specification. (It is skipped by ZPD specification.)
Note(37) In the equipment for DMR-BN, it is a setting item in a case with a analog output or communication output
option. (It is skipped if there is no option.)
Note(38) It is the setting item of only a Modbus communication output.
Note(39) ( ) is the default value in rated current AC1A.
Note(40) ( ) is the default value in zero-phase rated voltage AC1V (ZPD).
In the default value, each protection factor is OFF (unused). The zero phase monitoring
(voltage, current) of a fail-safe function is also OFF (monitoring stop).
If it uses these factors, please make it setting ON (used).
51
DMR-212-006
Example of a display
Setting No. 1201 , Voltage measurement range setting.
Setting No.
52
DMR-212-006
DMR-FN
Setting No.2301 Setting No.2302 (67) Setting No.2303 (67) Setting No.2304
(67) Current operating Voltage operating (67)
Used/Unused value value Operating angle
Setting No.2402
Setting No.2401
External trip
External trip (DI5)
"ON" control within
Used/Unused protection detection display
Setting No.2501
Reset time
Setting No.2601
Zero phase monitor ON/OFF
53
DMR-212-006
DMR-GN
Setting No.2301 Setting No.2302 (51G) Setting No.2303 Setting No.2304 (51G)
(51G) Current operating (51G) 2nd harmonic
Used/Unused value Operating time suppression
Setting No.2402
Setting No.2401
External trip
External trip (DI5)
"ON" control within
Used/Unused protection detection display
Setting No.2501
Reset time
Setting No.2601
Zero phase monitor ON/OFF
54
DMR-212-006
DMR-BN
Setting No.2402
Setting No.2401
External trip
External trip (DI5)
"ON" control within
Used/Unused protection detection display
Setting No.2501
Reset time
Setting No.2601
Zero phase monitor ON/OFF
55
DMR-212-006
DMR-SN
Setting No.2402
Setting No.2401
External trip
External trip (DI5)
"ON" control within
Used/Unused protection detection display
Setting No.2501
Reset time
Setting No.2601
Zero phase monitor ON/OFF
Example of a display
DMR-FN,GN,SN Setting No. 2101 In case of instantaneous overcurrent relay (50) used / unused setting.
Setting No.
Please refer to the "7.4 Setting" about the details of the contents of setting.
56
DMR-212-006
MODE
Measurement
display
Protection relay 2
(Usual display)
● Protection relay n
Protection factor
Display factor Contents of display
50 51 51G 67 27 59 64
Main monitor Display an instrument number. 「50」 「51」 「51G」 「67」 「27」 「59」 「64」
Sub-monitor Display the value at the time of
A(L1) A(L1) - A0 - - -
(Left) protection detection.
Sub-monitor Display the value at the time of A(L2) A(L2)
- V0 - - -
(Center) protection detection. (41) (41)
Sub-monitor Display the value at the time of V V
A(L3) A(L3) Ao θ VO
(Right) protection detection. (L3L1) (L3L1)
Display "RECORD" on an upside.
Other
In addition to a LCD, "RECORD" LED is lighting.
Note(41) In the case of DMR-FN, DMR-GN, don't display L2 phase. It becomes a blank display.
57
DMR-212-006
MODE
Error code
(Last time)
Measurement
display
(Usual display)
Error code
(Past 20 times)
● Error code
Example of display Display factor Contents of display
Display an error code. Please refer to "8.1.1 Fail-safe
Main monitor
function" about an error code.
Sub-monitor
Display "Err".
(Left)
Sub-monitor
Display "CodE".
(Center)
Sub-monitor Display an error code history number.
(Right) (The latest is “- 1”, then, display “-2” to “-20”.)
● Clear of history
While displaying a error to clear, if a MAX/MIN RESET switch is pushed 3 seconds or more, a protection
detection value is cleared.
An error history is not cleared even if it performs this history clear operation.
Please refer to "7.1.3 Protection detection history display" about the clear of an error history.
58
DMR-212-006
Note(42) It is based on the measurement factor of each model. The factor which is doing setting OFF by display
ON/OFF setting cannot perform the change of a measurement display.
Please refer to "7.1.1 Measurement setting value display (Display ON/OFF)" for the check method
of a setting value.
59
DMR-212-006
60
DMR-212-006
7.4 Setting
This product possesses various setting items to measurement or a protection function. If this operation and the contents
of setting are mistaken, it will become the causality of the display contrary to actual operation, or a malfunction.
Please perform the setting of this product after having understood an operating procedure and contents enough.
And, because it becomes operation by the maker about setting, a user must not set.
ENTER
Sub-monitor Sub-monitor Sub-monitor
Display Main monitor Bar graph
Display item (left) (center) (right)
pattern display display
display display display
▲ SETTING
▼
ENTER
Measurement Current Power Reactive power Power factor
Voltage range Power range
range range polarity range range
▲ SETTING
Zero phase Zero phase
Frequency
voltage output voltage rating
range
range (EVT)
▼
ENTER
Display Maximum Maximum Minimum
Current Voltage Power
ON/OFF current voltage voltage
▲ SETTING
Reactive
var-hour Watt-hour Frequency Power factor
power
▼
ENTER
Phase / line L1 L2 L3 L1L2 L2L3 L3L1
display ON/OFF phase current phase current phase current line voltage line voltage line voltage
SETTING
▲
▼
ENTER
Output 1 Output 2 Output 3 Output 4
Analog output
factor factor factor factor
SETTING
▲
Intrinsic Intrinsic
sensitivity sensitivity
(Reactive power) (Power)
SETTING
▲
▼
61
DMR-212-006
Sub-monitor Sub-monitor
Bar graph
(right) (center)
display
display display
② DMR-BN
Pattern Sub-monitor Sub-monitor Sub-monitor
Main monitor Bar graph
No. (Left) (Center) (Right)
Maximum zero phase Zero phases
1 Voltage (L1L2) Frequency Voltage (L1L2)
voltage voltage
Maximum voltage Minimum voltage
2 Voltage (L1L2) Frequency Voltage (L1L2)
(L1L2) (L1L2)
Maximum voltage Minimum voltage Maximum zero phase
3 Voltage (L1L2) Voltage (L1L2)
(L1L2) (L1L2) voltage
4 Voltage (L1L2) Voltage (L2L3) Voltage (L3L1) Frequency Voltage (L1L2)
Maximum zero phase
5 Voltage (L1L2) Voltage (L2L3) Voltage (L3L1) Voltage (L1L2)
voltage
62
DMR-212-006
63
DMR-212-006
Sub-monitor
Display the setting number (1104).
(Left)
Sub-monitor
Display the sub-monitor (center) display factor.
(Center)
Sub-monitor
Display the present display factor number.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
Sub-monitor
Display the setting number (1105).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor Display the sub-monitor (right) display factor.
(Right) Display the present display factor number.
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
64
DMR-212-006
SETTING
・Voltage measurement range (VT ratio) ・Current measurement range (CT ratio)
65
DMR-212-006
66
DMR-212-006
(7) Frequency measurement range 【No.1207 DMR-FN, DMR-GN, DMR-SN , No.1202 DMR-BN】
Example of display Display factor Contents of display
Display the frequency measurement range and “RANGE” after
Main monitor
change. (45…55Hz:50.0, 55…65Hz:60.0)
Sub-monitor Display the setting number.
(Left) (DMR-FN, DMR-GN, DMR-SN:1207 , DMR-BN:1202)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present frequency measurement range.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
(8) Zero phase voltage rating (EVT) 【No.1208 DMR-FN、No.1203 DMR-BN EVT specification】 (46)
Example of display Display factor Contents of display
Display the zero phase voltage rating and “ZERO PHASE”
Main monitor
after change.
Sub-monitor Display the setting number.
(Left) (DMR-FN:1208, DMR-BN:1203)
Sub-monitor
Display the "rAt".
(Center)
Sub-monitor
Display the present zero phase voltage and “ZERO PHASE”.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
Note(46) Only EVT specification has setting of zero phase voltage rating.
In the case of ZPD specification, this setting is skipped.
67
DMR-212-006
(9) Zero phase voltage output range 【No.1209 DMR-FN (With communication output),
No.1204 DMR-BN (With analog output or communication output)】(47)
Example of display Display factor Contents of display
Display the zero phase voltage output range and "RANGE"
Main monitor
“ZERO PHASE” after change.
Sub-monitor Display the setting number.
(Left) (DMR-FN:1209, DMR-BN:1204)
Sub-monitor
Display the "FuLL".
(Center)
Sub-monitor Display the present zero phase voltage output range and
(Right) “ZERO PHASE”.
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
Note(47) The analog output and communication output of zero phase voltage measurement display the setting
value of an output range.
This setting is skipped if there is no option of relevance from each model.
68
DMR-212-006
ENTER
Display Maximum Maximum Minimum
Current Voltage
ON/OFF current voltage voltage
SETTING
Reactive
Frequency Power factor Power
power
・Display ON/OFF
69
DMR-212-006
ENTER
Phase / line L1 L2 L3 L1L2
display ON/OFF phase current phase current phase current line voltage
SETTING
L3L1 L2L3
line voltage line voltage
(1) Phase display ON/OFF 【No.1401 to 1403 DMR-FN, DMR-GN, DMR-SN】 (49)
Example of display Display factor Contents of display
Display an applicable phase. And display the setting after
Main monitor
the change.
Sub-monitor
Display the setting number (14□ □ ).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present setting.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
(2) Line display ON/OFF 【No.1404 to 1406:DMR-FN, DMR-GN, DMR-SN,No.1401 to 1403:DMR-BN】 (49)
Example of display Display factor Contents of display
Display an applicable line. And display the setting after
Main monitor
the change.
Sub-monitor
Display the setting number (14□ □ ).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present setting.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
Note(49) This setting is only display ON/OFF. Perform internal measurement and an output (analog output)
regardless of this setting. And, the factor of setting OFF is not displayed as a protection detection
history.
70
DMR-212-006
SETTING
(1) Output n factor 【No.1501 to 1504 (50) All models, With a analog output.】
Example of display Display factor Contents of display
Display the output factor and output factor number after
Main monitor
change.
Sub-monitor
Display the setting number (1501 to 1504). (50)
(Left)
Sub-monitor Display an output point. (50)
(Center) (Output 1:Ao.1 to output 4:Ao.4)
Sub-monitor
Display the present output factor.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
Note(50) DMR-BN becomes to outputs 1 to 3 (setting No.1501 to 1503, output point:Ao.1 to Ao.3).
71
DMR-212-006
(2) Intrinsic sensitivity (power) 【No.1505 DMR-FN, DMR-GN, DMR-SN, With a analog output.】
It is the analog output of power and reactive power, set the output sensitivity (% of the output to an input)
by % to the input range.
Setting range, Power:40.0 to 115.0% (0.1% steps)
Reactive power:30.0 to 115.0% (0.1% steps)
Example) In the case of voltage measurement range:9000V(6600V/110V) and current measurement range:100A/5A.
Rated power = 1000W×(6600V/110V)×(100A/5A)=1200kW
In the case of 100% settings, 0…1200kW/0…1000W/DC4…20mA
In the case of 83.3% settings, 0…1000kW/0…833.3W/DC4…20mA
Sub-monitor
Display the setting number (1505).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present output sensitivity.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
(3) Intrinsic sensitivity (reactive power) 【No.1506 DMR-FN, DMR-GN, DMR-SN, With analog output.】
Example of display Display factor Contents of display
Sub-monitor
Display the setting number (1506).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present output sensitivity.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
72
DMR-212-006
ENTER
Pulse output Output factor Pulse unit
SETTING
(1) Output factor 【No.1601 DMR-FN, DMR-GN, DMR-SN, With analog output.】
Example of display Display factor Contents of display
Display the output factor and output factor number after
Main monitor
change.
Sub-monitor
Display the setting number (1601).
(Left)
Sub-monitor
Display the "Po".
(Center)
Sub-monitor
Display the present output factor.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
Note(52) Display factor number, output factor number (analog output), and output factor number (pulse output),
a factor is respectively different.
(2) Pulse unit 【No.1602 DMR-FN, DMR-GN, DMR-SN, With pulse output.】
Example of display Display factor Contents of display
Sub-monitor
Display the setting number (1602).
(Left)
Sub-monitor
Display the "PuLSE".
(Center)
Sub-monitor
Display the present pulse unit.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
73
DMR-212-006
ENTER
Communication Transmission
Address Parity Stop bit
output rate
SETTING
(1) Address 【No.1701 All models, All with the communication output.】
Example of display Display factor Contents of display
Sub-monitor
Display the setting number (1701).
(Left)
Sub-monitor
Display the "Adr".
(Center)
Sub-monitor
Display the present address.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
・Address range
Modbus 1 to 247
(2) Transmission rate 【No.1702 All models, All with the communication output.】
Example of display Display factor Contents of display
Sub-monitor
Display the setting number (1702).
(Left)
Sub-monitor
Display the "bPS".
(Center)
Sub-monitor
Display the present transmission rate.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
・Transmission rate
Modbus 4800bps,9600bps,19200bps,38400bps
74
DMR-212-006
(3) Parity 【No.1703 All models, All with the communication output.】
Example of display Display factor Contents of display
Sub-monitor
Display the setting number (1703).
(Left)
Sub-monitor
Display the "PAr".
(Center)
Sub-monitor
Display the present parity bit.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
・Parity
E Even parity
o Odd parity
- With no parity
(4) Stop bit 【No.1704 All models, All with the communication output.】
Example of display Display factor Contents of display
Sub-monitor
Display the setting number (1704).
(Left)
Sub-monitor
Display the "StoP .b".
(Center)
Sub-monitor
Display the present stop bit.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
・Stop bit
1 1 bit
2 2 bits
75
DMR-212-006
SETTING STM/RTM
Push 3 seconds
ENTER
Protection Current "ON" control
Operating
relay 1 Used / Unused operating Reset method within protection
time
(50) value detection display
SETTING
▲
▼
SETTING
▲ "ON" control Zero phase
within protection current input Reset method
▼ detection display correction
▲ SETTING
▼ 2nd harmonic
Reset method
suppression
"ON" control
within protection
detection display
76
DMR-212-006
ENTER
Protection Current "ON" control
Operating
relay Used / Unused operating Reset method within protection
time
(50) value detection display
SETTING
77
DMR-212-006
(5) "ON" control within protection detection display 【No.2105 DMR-FN, DMR-GN, DMR-SN】
Example of display Display factor Contents of display
Display the setting value after change.
Main monitor ("ON" control within protection detection display
Permission:Cb-E, Prohibition:Cb-d)
Sub-monitor
Display the setting number (2105).
(Left)
Sub-monitor
Display the "rY.50".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
78
DMR-212-006
Protection ENTER
Current
relay Used / Unused Characteristic Time multiplier
operating value
(51)
SETTING
"ON" control
within protection Reset method
detection display
79
DMR-212-006
(6) "ON" control within protection detection display 【No.2206 DMR-FN, DMR-GN, DMR-SN】
Example of display Display factor Contents of display
Display the setting value after change.
Main monitor ("ON" control within protection detection display
Permission:Cb-E, Prohibition:Cb-d)
Sub-monitor
Display the setting number (2206).
(Left)
Sub-monitor
Display the "rY.51".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
80
DMR-212-006
SETTING
"ON" control Zero phase
within protection current input Reset method
detection display correction
81
DMR-212-006
Main monitor Display the operating time and “OPERATE TIME” after change.
Sub-monitor
Display the setting number (2305).
(Left)
Sub-monitor
Display the "rY.67".
(Center)
Sub-monitor
Display the present operating time.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
82
DMR-212-006
83
DMR-212-006
Protection ENTER
Current 2nd harmonic
relay Used / Unused Operating time
operating value suppression
(51)
SETTING
"ON" control
within protection Reset method
detection display
84
DMR-212-006
Main monitor Display the operating time and “OPERATE TIME” after change.
Sub-monitor
Display the setting number (2303).
(Left)
Sub-monitor
Display the "rY.51G".
(Center)
Sub-monitor
Display the present operating time.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
85
DMR-212-006
ENTER
Protection Voltage "ON" control
Operating
relay Used / Unused operating Reset method within protection
time
(27) value detection display
SETTING
Main monitor Display the operating time and “OPERATE TIME” after change.
Sub-monitor
Display the setting number (DMR-BN:2103, DMR-SN:2303).
(Left)
Sub-monitor
Display the "rY.27".
(Center)
Sub-monitor
Display the present operating time.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
86
DMR-212-006
(5) "ON" control within protection detection display 【No.2105 DMR-BN / No.2305 DMR-SN】
Example of display Display factor Contents of display
Display the setting value after change.
Main monitor ("ON" control within protection detection display
Permission:Cb-E, Prohibition:Cb-d)
Sub-monitor
Display the setting number (DMR-BN:2105, DMR-SN:2305).
(Left)
Sub-monitor
Display the "rY.27".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
87
DMR-212-006
ENTER
Protection Voltage "ON" control
Operating
relay Used / Unused operating Reset method within protection
time
(59) value detection display
SETTING
Main monitor Display the operating time and “OPERATE TIME” after change.
Sub-monitor
Display the setting number (2203).
(Left)
Sub-monitor
Display the "rY.59".
(Center)
Sub-monitor
Display the present operating time.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
88
DMR-212-006
89
DMR-212-006
ENTER
Protection Voltage "ON" control
Operating
relay Used / Unused operating Reset method within protection
time
(64) value detection display
SETTING
Main monitor Display the operating time and “OPERATE TIME” after change.
Sub-monitor
Display the setting number (2303).
(Left)
Sub-monitor
Display the "rY.64".
(Center)
Sub-monitor
Display the present operating time.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
90
DMR-212-006
91
DMR-212-006
ENTER
"ON" control
External trip
Used / Unused within protection
(DI5)
detection display
SETTING
(2) "ON" control within protection detection display 【No.2402 All models】
Example of display Display factor Contents of display
Display the setting value after change.
Main monitor ("ON" control within protection detection display
Permission:Cb-E, Prohibition:Cb-d)
Sub-monitor
Display the setting number (2402).
(Left)
Sub-monitor
Display the "dI.5".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
92
DMR-212-006
SETTING
Main monitor Display the reset time and "RESET TIME" after change.
Sub-monitor
Display the setting number (2501).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present reset time.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
SETTING
Sub-monitor
Display the setting number (2601).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
93
DMR-212-006
LOCAL REMOTE
・Switch color
LOCAL REMOTE OFF:Green / Red (Designation)
ON / OFF permission:Gray
Circuit breaker Circuit breaker ON :Red / Green (Designation)
"OFF" "ON"
94
DMR-212-006
STM/RTM
Push 3 seconds ENTER
Sequence Protection Protection Protection
test mode relay 1 relay 2 relay 3
SETTING
▲
▼
ENTER
Relay Protection Protection Protection
test mode relay 1 relay 2 relay 3
SETTING
50,51
ENTER (L1 phase)
Sequence test Protection Protection Protection
mode relay 1 relay 2 relay 3
SETTING
95
DMR-212-006
ENTER
Protection Protection Protection
Relay test mode
relay 1 relay 2 relay 3
SETTING
Excess of a Excess of a Excess of a
setting value setting value setting value
96
DMR-212-006
MODE + STM/RTM
Push 3 seconds
Analog output
/ communication Pulse output
ROM check RAM check LED check LCD check DI check
output check check
Automatic ENTER Automatic ENTER STM/RTM ENTER STM/RTM ENTER STM/RTM ENTER STM/RTM ENTER STM/RTM ENTER
reset reset
after a after a Operation.
check Operation Operation Operation Output ON
check Input state
All
Operation. Operation. All display display. 100% output
lights-out
GOOD/ERR GOOD/ERR
display. display.
0% output
Sub-monitor
Display the "SELF".
(Left)
Sub-monitor
Display the "tESt".
(Center)
Sub-monitor
Display the factor number (No.1 to 7) which checks.
(Right)
97
DMR-212-006
MODE MEASURING
Measurement Push 3 seconds
Version display
display
Sub-monitor
Display the “ro.n”.
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor Display the model.
(Right) (Models DMR-FN:Fn, DMR-GN:Gn, DMR-BN:bn, DMR-SN:Sn)
Other -
98
DMR-212-006
② From this display, push the RESET switch for one second and can change it to measurement display.
And, operation of the above (1) can also be switched to a measurement display.
Protection detection status returns by RESET switch operation. And, "FAULT" of a LED disappears.
However, because protection detection status has hold when it was operation of the above (1), "FAULT" of a
LCD does not disappear. In this case, please reset protection detection status with a RESET switch.
③ A protection detection display is hold even if it resets a power supply. In addition, about a measurement display
(protection detection status : "FAULT" of a LCD continues being lighting), it returns to a protection detection
screen by power supply reset.
④ The LED display and DO output after a protection detection reset, operation changes with settings of each
protection factor.
About each operation, please refer to "6.2.2 Control by protection detection".
Protection detection
Other, switch
Protection display
operation
detection
During the Other displays
detection
Other, switch
Measurement Protection
RESET operation
display detection
・Test mode (STM/RTM)
(Usual Push 1 reset MEASURING Measurement display ・Self check mode
display) second Holds of (Protection
detection detection status)
Setting (measurement,
※ It returns to a
※ Even power supply protection)
RESET protection detection
reset, holds a display. Push 1 second display by power supply
reset. Other than those
above
99
DMR-212-006
7.10 Reset operation at the case of fail-safe error occurrence 【All models】
From fail-safe error occurrence to after 15-second efflux, it will change from a measurement display to an error detection
display automatically.
Example of display Display factor Contents of display
Sub-monitor
Display the "Err".
(Left)
Sub-monitor
Display the "CodE".
(Center)
Sub-monitor
Don't display.
(Right)
In addition to a LCD, "RUN" LED disappears and "ERROR" LED
Other
is lighted.
② From this display, push the RESET switch for one second and can change it to measurement display.
Error status returns by RESET switch operation.
About fail-safe error, please refer to "8.1.1 Fail-safe function".
100
DMR-212-006
SETTING + STM/RTM
Push 3 seconds
Protection relay 1
(50)
Protection relay 2
(51)
ENTER ×6 ×2
Protection relay 3 Zero phase current
Used/Unused
(67) input correction
×6 ×2
SETTING
×4
×4
Perform this correction by actually adding a zero phase current. Depending on the setting value of other setting
factors (an operating value, operating time, etc.), protection detection may be done during correction.
Please set protection setting ("Used/Unused") to "Unused" and prevent the false trip within correction.
101
DMR-212-006
102
DMR-212-006
・ The difference between the default setting value of protection setting, and the fixed value at the time of
nonvolatile memory check error occurrence.
At the time of error occurrence, only the setting value of the point judged to be an error is initialized.
DMR-FN
Setting
Default setting value
No. Setting item Default setting value
in error
2101 Used / Unused OFF (Unused) OFF (Unused)
2102 Operating value (58) 10A(2A) 80A(16A)
2103 50 Operating time Instant Instant
2104 Reset method Hold Hold
2105 "ON" control within protection detection display Permission Permission
2201 Used / Unused OFF (Unused) OFF (Unused)
2202 Characteristic Standard [SI] Standard [SI]
2203 Operating value (58) 2.0A(0.40A) 12.0A(2.40A)
51
2204 Time multiplier 1.0 times 30 times
2205 Reset method Hold Hold
2206 "ON" control within protection detection display Permission Permission
2301 Used / Unused OFF (Unused) OFF (Unused)
2302 Operating value (Current) 0.1A 1.0A
2303 Operating value (Voltage) (59) 5V(0.025V) 60V(0.400V)
2304 Operating angle 40° 40°
67
2305 Operating time 0.1s 0.1s
2306 Reset method Hold Hold
2307 Zero phase current input correction 100% 100%
2308 "ON" control within protection detection display Permission Permission
2401 External Used / Unused OFF (Unused) OFF (Unused)
2402 trip "ON" control within protection detection display Permission Permission
58
Note( ) ( ) is a setting value in rated current 1A.
Note(59) ( ) is a setting value in zero phase rated voltage AC1V (ZPD).
103
DMR-212-006
DMR-GN
Setting
Default setting value
No. Setting item Default setting value
in error
2101 Used / Unused OFF (Unused) OFF (Unused)
2102 Operating value (60) 10A(2A) 80A(16A)
2103 50 Operating time Instant Instant
2104 Reset method Hold Hold
2105 "ON" control within protection detection display Permission Permission
2201 Used / Unused OFF (Unused) OFF (Unused)
2202 Characteristic Standard [SI] Standard [SI]
2203 Operating value (60) 2.0A(0.40A) 12.0A(2.40A)
51
2204 Time multiplier 1.0 times 30 times
2205 Reset method Hold Hold
2206 "ON" control within protection detection display Permission Permission
2301 Used / Unused OFF (Unused) OFF (Unused)
2302 Operating value 0.25A(0.050A) 6.0A(1.2A)
Operating time
2303 Operating time 60s
51G (50ms or more)
2304 2nd harmonic suppression OFF OFF
2305 Reset method Hold Hold
2306 "ON" control within protection detection display Permission Permission
2401 External Used / Unused OFF (Unused) OFF (Unused)
2402 trip "ON" control within protection detection display Permission Permission
Note(60) ( ) is a setting value in rated current 1A.
DMR-BN
Setting
Default setting value
No. Setting item Default setting value
in error
2101 Used / Unused OFF (Unused) OFF (Unused)
2102 Operating value 60V 60V
2103 27 Operating time 0.1s 1.0s
2104 Reset method Hold Hold
2105 "ON" control within protection detection display Permission Permission
2201 Used / Unused OFF (Unused) OFF (Unused)
2202 Operating value 150V 150V
2203 59 Operating time 0.1s 1.0s
2204 Reset method Hold Hold
2205 "ON" control within protection detection display Permission Permission
2301 Used / Unused OFF (Unused) OFF (Unused)
2302 Operating value (61) 5V(0.025V) 60V(0.400V)
2303 64 Operating time 0.1s 1.0s
2304 Reset method Hold Hold
2305 "ON" control within protection detection display Permission Permission
2401 External Used / Unused OFF (Unused) OFF (Unused)
2402 trip "ON" control within protection detection display Permission Permission
61
Note( ) ( ) is a setting value in zero phase rated voltage AC1V (ZPD).
104
DMR-212-006
DMR-SN
Setting
Default setting value
No. Setting item Default setting value
in error
2101 Used / Unused OFF (Unused) OFF (Unused)
2102 Operating value (62) 10A(2A) 80A(16A)
2103 50 Operating time Instant Instant
2104 Reset method Hold Hold
2105 "ON" control within protection detection display Permission Permission
2201 Used / Unused OFF (Unused) OFF (Unused)
2202 Characteristic Standard [SI] Standard [SI]
2203 Operating value (62) 2.0A(0.40A) 12.0A(2.40A)
51
2204 Time multiplier 1.0 times 30 times
2205 Reset method Hold Hold
2206 "ON" control within protection detection display Permission Permission
2301 Used / Unused OFF (Unused) OFF (Unused)
2302 Operating value 60V 60V
2303 27 Operating time 0.1s 1.0s
2304 Reset method Hold Hold
2305 "ON" control within protection detection display Permission Permission
2401 External Used / Unused OFF (Unused) OFF (Unused)
2402 trip "ON" control within protection detection display Permission Permission
Note(62) ( ) is a setting value in rated current 1A.
15 秒経過後
・Operation of the equipment at the time of the error detection by the fail-safe function.
Status of equipment
After error
At error reset After error reset
Error item Factor At error detection
(Automatic ("RESET" switch
detection (After 15
reset) operation)
seconds)
Measurement Error detection Error detection Measurement
LCD
Display display display display display
「ERROR」LED Lights-out Lighting Lighting Lights-out
About 0% of About 0% of
Analog output Normal inputs is inputs is Normal
Zero phase monitor outputted. outputted.
(voltage) Output Pulse output Normal Stop Stop Normal
Zero phase voltage About 0% of About 0% of
Communication
input monitor Normal inputs is inputs is Normal
output
outputted. outputted.
Output lock Output lock
DO output Normal Normal
(63)(64) (63)(64)
DO output (Equipment
OFF ON ON OFF
malfunction)
Measurement Error detection Error detection Measurement
LCD
Display display display display display
「ERROR」LED Lights-out Lighting Lighting Lights-out
About 0% of About 0% of
Analog output Normal inputs is inputs is Normal
outputted. outputted.
Zero phase monitor
Output Pulse output Normal Stop Stop Normal
(Current)
About 0% of About 0% of
Communication
Normal inputs is inputs is Normal
output
outputted. outputted.
DO output Normal Output lock (64) Normal Normal
DO output (Equipment
OFF ON ON OFF
malfunction)
105
DMR-212-006
Status of equipment
After error
At error reset After error reset
Error item Factor At error detection
(Automatic ("RESET" switch
detection (After 15
reset) operation)
seconds)
Measurement Error detection Error detection Measurement
LCD
A/D accuracy check. Display display display display display
A/D conversion 「ERROR」LED Lights-out Lighting Lighting Lights-out
period check. About 0% of About 0% of
Read Write check. Analog output Normal inputs is inputs is Normal
Clock monitor. outputted. outputted.
Setting value Output Pulse output Normal Stop Stop Normal
collation. About 0% of About 0% of
Communication
Interrupt monitor. Normal inputs is inputs is Normal
output
DO monitor. outputted. outputted.
Power supply DO output Output lock (64) Output lock (64) Normal Normal
monitor (24V,±8V). DO output (Equipment
OFF ON ON OFF
malfunction)
Measurement Measurement Measurement
LCD -
display display display
Display
Lighting
「ERROR」LED - Lights-out Lights-out
(Instant)
About 0% of
Watchdog timer Analog output inputs is - Normal Normal
power supply outputted.
monitor (5V) Output Pulse output Stop - Normal Normal
(65) About 0% of
Communication
inputs is - Normal Normal
output
outputted.
DO output Output lock (64) - Normal Normal
DO output (Equipment
ON - OFF OFF
malfunction)
Error detection Error detection Error detection Error detection
LCD
Display display display display display
「ERROR」LED Lighting Lighting Lighting Lighting
About 0% of About 0% of About 0% of About 0% of
Analog output inputs is inputs is inputs is inputs is
Sum check. outputted. outputted. outputted. outputted.
Nonvolatile memory Output Pulse output Stop Stop Stop Stop
check. About 0% of About 0% of About 0% of About 0% of
Communication
inputs is inputs is inputs is inputs is
output
outputted. outputted. outputted. outputted.
DO output Output lock (64) Output lock (64) Output lock (64) Output lock (64)
DO output (Equipment
ON ON ON ON
malfunction)
Note(63) If an error is detected under a zero phase monitor (voltage), in DMR-BN, only 27 and 59 do an output
lock. And, in DMR-SN, only 27 does an output lock.
If an error is detected under a zero phase voltage input monitor, only 64 of DMR-BN does an output lock.
(Even if it detects an error, the output lock of DMR-FN and DMR-GN is not done.)
Note(64) If an error is detected by the fail-safe function, trip operation by protection detection is locked (output
OFF). In addition, the output by switch operation or ON/OFF control of DI and the output by REMOTE/LOCAL
operation are not locked.
DO output locked:Each DO output of "CB-Trip" and "fault 1 to 3".
Note(65) In a watchdog timer and a power supply monitor (5V), CPU is immediately reset after error detection.
Therefore, there is no operation of continuation for 15 seconds, and it will become normal operation if
the error has returned after CPU reset.
106
DMR-212-006
(2) A protection detection history can be checked by protection detection history display.
"RECODE" LED is lighted during a history display.
(3) A protection detection history display displays a detection value (maximum value within detection), and a detection
phase (only an instantaneous overcurrent and overcurrent).
In addition, in a directional earth-fault, display a phase angle, a zero phase current, and a zero phase voltage.
The phase angle in this case, if current is a leading phase to voltage, is displayed.
And if current is a lagging phase to voltage, is displayed.
(4) A protection detection history is not cleared even if it does power supply reset.
(5) If a MAX./MIN. RESET switch is pushed for 3 seconds while displaying a protection detection history, a
displaying protection factor history will be cleared.
(6) The protection factor which has not done protection detection to the past once displays "-----".
(7) The detection value is not displayed if the factor of OFF does protection detection by the phase / line display
ON/OFF setting.
Contents of display
Protection factor Sub-monitor Sub-monitor Sub-monitor Note
Main monitor
(left) (center) (right)
Instantaneous [L1 phase [L3 phase
50 (66) Secondary rating displays
overcurrent [50] current] current]
[L1 phase [L3 phase
Overcurrent [51] 51 (66) Secondary rating displays
current] current]
Secondary rating displays
Directional [Zero phase [Zero phase
67 [Phase angle] (zero phase current is
earth-fault [67] current] voltage]
primary rating display)
Earth-fault
51G (Blank) (Blank) [Detection value] Secondary rating displays
overcurrent [51G]
Undervoltage [27] 27 (Blank) (Blank) [Detection value] Secondary rating displays
Overvoltage [59] 59 (Blank) (Blank) [Detection value] Secondary rating displays
Earth-fault
64 (Blank) (Blank) [Detection value] Secondary rating displays
overvoltage [64]
Note(66) DMR-FN and DMR-GN become a blank display. DMR-SN becomes L2 phase current display.
107
DMR-212-006
(4) A maximum of 20 error histories are recorded. If a maximum is exceeded, it is deleted from old record.
(5) A error history is not cleared even if it does power supply reset.
(6) If a MAX./MIN. RESET switch is pushed for 3 seconds while displaying a error history, a displaying error
history will be cleared.
8.2 Troubleshooting
Phenomenon Probable cause Necessary measures
The control power supply is not provided. Check of control power supply.
(It is not wired. An voltage is low.) Restore control power supply.
LCD does not display. By measurement display ON/OFF setting, it is setting
Check of setting value
OFF.
Trouble of equipment Exchange of equipment
Backlight puts out the Put out the light automatically after 10 minutes by no
It is not trouble.
light. operating it. (It is re-lighting by switch operation.)
The error of a measurement Setting of a range is wrong. Check of setting value
value is large. Out of the rated frequency range This product cannot be used.
Analog output is not
Analog output setting is OFF. Check of setting value
outputted.
Pulse output setting is OFF. Check of setting value
Pulse output is not
Make an output pulse unit into
outputted. By range change, an output pulse unit is out of range.
setting within the range.
The control power supply is not provided. Check of control power supply.
(It does not wire. Voltage is low.) Restore control power supply.
ON/OFF control cannot be
The slide switch is [REMOTE]. Set a switch to [LOCAL].
performed from a front
Only "ON" or the "OFF" switch is pushed. Push simultaneously with the
switch.
It is not pushing simultaneously with the "ON/OFF "ON/OFF PERMISSION" switch and
PERMISSION" switch. operate it again.
The control power supply is not provided. Check of control power supply.
ON/OFF control from DI
(It does not wire. Voltage is low.) Restore control power supply.
cannot be performed.
The slide switch is [LOCAL]. Set a switch to [REMOTE].
The control power supply is not provided. Check of control power supply.
(It does not wire. Voltage is low.) Restore control power supply.
ON/OFF control by
The slide switch is [LOCAL]. Set a switch to [REMOTE].
communication cannot be
Only the command of "ON" or "OFF", it is not ordered The simultaneous command of the
performed.
simultaneously with the "ON/OFF PERMISSION" command "ON/OFF PERMISSION" command.
"ERROR" LED is lighting. Exchange of equipment
The setting (use / unused) of the applicable protection
Check of setting value
element becomes the unused.
Don't do protection
They are test mode or self check mode.
detection. The change in the mode
("STM/RTM" LED lighting, or "RUN" LED flicker)
"ERROR" LED is lighting. Exchange of equipment
"ON" LED or "OFF" LED is The wiring (52a, 52b) from a circuit breaker is wrong.
Check of wiring
not lighted. Or it does not wire.
108
DMR-212-006
8.3 Check
8.3.1 Daily check
This product contains the self-diagnostic function by the fail-safe function.
The appearance check, please check the next item. In addition, those who have technical knowledge, such as an
electrical work, need to perform check.
(1) Discoloration of a LCD, and damage of a case.
8.5 Maintenance
(1) Please do not change wiring of an input and an control power supply by the hot line condition.
(2) In case you check an output unavoidably by the hot line condition, please warn to be unable to touch output wiring
and a human body to an input and an auxiliary power terminal.
(3) If it checks an input, an output, and an control power supply, please carry out after checking schematics.
(4) If a name-plate is wiped with solvents (an alcoholic nature), a display item may disappear.
Please wipe with the dry cloth.
The liquid crystal display (LCD) may light during cleaning on the LCD face. However, this phenomenon is caused
by the static electricity that may be produced in the filter, and it does not show any trouble.
Leave the unit as it is for a while, and the display goes out due to natural discharge.
(5) Please keep in mind that it will break if a LCD is pushed strongly. And, if a filter is pushed, a LCD face will
touch a filter. Therefore, the pattern of the shape of a circle or an ellipse may occur.
This phenomenon improves by doing the power distribution of the auxiliary power and leaving it for about 2 hours.
(6) If the temperature and humidity of an installation change rapidly when a product is a non-energization, the waterdrop
by dew condensation may adhere to a display inner side. (The display filter and the LCD surface stick and the pattern
of the shape of a circle or an ellipse occur.)
This phenomenon improves by doing the power distribution of the auxiliary power and leaving it for about 2 hours.
(7) In the case of a periodic check, it is possible by doing test mode (STM/RTM) and self check mode to aim at shortening
of check time. In the case of operation in each mode, please carry out after checking an operation step and an
operating procedure enough.
109
DMR-212-006
・Removal of a connector
Push a connector lock part.
The lock mechanism is built in the connector.
Draw out perpendicularly to a connector, draw out
perpendicularly to a connector, pressing down the lock of a
connector top and bottom.
Pull out If it pulls out by force, without pushing a lock or pulls out
aslant, there is a possibility of damaging a connector.
110
DMR-212-006
111
DMR-212-006
Overcurrent (51)
Test conditions
Test item Test method Operating Time Criterion
Input to DMR Characteristic
value multiplier
Increase the input of a current input
90% of
terminal (L1 phase / L2 phase / L3 phase)
operating Maximum, Standard
Operating from 90% of an operating value. Setting value
value Middle, inverse time ×1
value The current value to which “51” LED ±5%
→Operating Minimum (SI)
started the flicker is an operating value.
value
(Please cut current after a test.)
0→300% of
operating 3.22±0.39
Change the input of a current input value second
terminal (L1 phase / L2 phase / L3 phase) setting
to 300% of operating value setting 0→500% of Standard
Operating suddenly from 0. operating 2.56±0.18
Minimum inverse time ×10
time Measure the time to the control output ON value second
(SI)
after applying. setting
Do 0…500% and 0…1000% similarly. 0→1000% of
(Please cut current after a test.) operating 1.89±0.13
value second
setting
112
DMR-212-006
10 4
P Control power
12
6
14 N supply
3
A
Constant K ~ K 5
current L1 phase 7
generator L L 9
11
K 13
L2 phase 15
L 17 DMR-Pro
19
K 21
Simultaneous ON L3 phase 23
L 25
TB
CN1
ON
OFF
A3
Counter
B3 TRIP
(Hour meter)
Notes
① This product is supervising the balance of each phase current by the zero phase monitor function.
A control output may not operate by this function. Therefore, where a function (setting number:2601) is
setting at OFF, please examine.
② Applying to a current input terminal must not exceed overload capacity (40 time 1-second, 20 times 4 seconds,
10 times 16 seconds and 1.2 times continuation of rated current).
And, if it continues and applies the short-time overcurrent exceeding 1.2 times of rating, please make the
interval for 1 minute or more.
③ In DMR-FN and DMR-GN, please examine about L1 phase and L3 phase. And in DMR-GN, please setting as OFF (unused)
by use/unused setting (setting number:2301) at earth-fault overcurrent (51G).
④ In DMR-SN, please examine about L1 phase, L2 phase, and L3 phase. And please setting as OFF (unused) by
use/unused setting (setting number:2301) at undervoltage (27).
⑤ If it examines instantaneous overcurrent (50), please setting as OFF (unused) by use/unused setting (setting
number:2201) at overcurrent (51).
If it examines overcurrent (51), please setting as OFF (unused) by use/unused setting (setting number:2101)
at overcurrent (51).
113
DMR-212-006
114
DMR-212-006
Test conditions
Input to DMR Setting
Test item Test method Zero Zero Current Voltage Criterion
Phase Phase Operating
phase phase operating operating
angle angle time
current voltage value value
The input of a zero phase
current input terminal and
a zero phase voltage input
terminal is in constant
status.
The phase of the current to
voltage is gradually
changed in the LEAD side or
the LAG side from the phase
angle (operating phase
angle of about ±90°) out
Out of the
of the detection range.
detection
operating If "67" LED is lighted, 500% of
30% of range Maximum, Setting
phase angle value of current phase current Minimum
rated ↓ Minimum Minimum Middle, value
(Phase angle when "FAULT" operating (0.1s)
voltage Operating Minimum ±5°
characteristic) displays on LCD is an value
phase
operating value.
angle
Optimum
sensitivity
①+②
phase angle =
2
① Operating phase angle
(LEAD side)
② Operating phase angle
(LAG side)
115
DMR-212-006
a 16 5
u 7
Constant
voltage V 18 9
~ ~
generator v 11
f
13
15
V ± DMR-Pro 17
Oscillator Phase meter 19
A ± 21
ZCT
23
K k Z1 22
A 25
Constant K ~
current 24
~
generator L L l Z2 TB
CN1
ON
Simultaneous ON
OFF
Counter A3
B3 TRIP
(Hour meter)
V A
V
~ ± ±
v u
Step-up transformer
110 6600
(Example) :
v u √3 √3
T
ZPD y1 16
y2 18
E TB
Notes
① As for a zero phase voltage input, the polarity of connection is different. (Polarity is contrary to usual)
(Polarity is connection contrary to usual.)
② If the error of an operating value (current) test is large, please perform combination input correction with ZCT
by the zero phase current input correction function (setting number: 2307).
③ If applying of the test voltage of ZPD cannot be performed in order that there may be no step-up transformer,
Please do in 150% of input of a setting value.
(However, a difference may arise in a ZPD phase characteristic with the size of an input.)
④ The performance within a criterion is a performance of a DMR simplex. If it combines ZPD and ZCT, please
make a criterion into the value which added each tolerance.
⑤ Voltage operating value setting of directional earth-fault (67) is a secondary voltage display.
To examine by ZPD specification, it is necessary to convert the input value from a constant voltage generator
into an equivalent for ZPD secondary voltage. (By EVT specification, in order to input directly from a constant
voltage generator, it is conversion needlessness.)
Please examine with a relative input value with reference to a following conversion table and a following
conversion formula.
116
DMR-212-006
Constant voltage generator input [V] ZPD primary input value [V] ZPD secondary voltage reduced value [V]
1.588 95.28 (165/√3) 0.0250
3.175 190.5 (330/√3) 0.0500
12.70 762.1 (1320/√3) 0.2000
25.40 1524 (2640/√3) 0.4000
31.75 1905 (3300/√3) 0.5000
63.51 3811 (6600/√3) 1.0000
(Example)
If voltage operating value setting of DMR is 0.200V and the input of a constant voltage generator does protection
detection by 12.75V, calculate a ZPD secondary voltage as follows. 0.2008V is convert with a voltage operating
value.
ZPD primary input value = 12.75 × 60 = 765V
ZPD secondary voltage reduced value = 765 × √3 / 6600 = 0.2008V
117
DMR-212-006
Overvoltage (59)
Test Test conditions
Test method Criterion
item Input to DMR Operating value Operating time
Decrease the input of a voltage input
terminal (L1l2 line / L2L3 line) Maximum,
Operating 0→Operating Setting
gradually. If "59" LED is lighted, Middle, Minimum (0.1s)
value value value ±5%
voltage value when "FAULT" displays on LCD Minimum
is an operating value.
Change input of voltage input terminal
0→
(L1L2 line) from the rating voltage into
Operating 120% of Setting
120% of operating value setting suddenly. Minimum (110V) Maximum (10s)
time operating value value ±5%
Measure the time to the control output ON
setting
after applying.
P1 10 4
P Control power
Constant u
V P2 12 6
voltage ~ N supply
generator v P3 14
3
5
7
9
11
13
15 DMR-Pro
17
Simultaneous ON 19
21
23
25
TB
CN1
ON
OFF
A3
Counter
B3 TRIP
(Hour meter)
Notes
① This product is supervising the balance of each line voltage by the zero phase monitor function.
A control output may not operate by this function. Therefore, where a function (setting number:2601) is
setting at OFF, please examine.
② Please do the test of an operating value in L1L2 line and L2L3 line, respectively. (Because an input signal is
compounded inside and it detects as L3L1 line voltage, a test is possible even if there is no input of one side.)
③ If the undervoltage (27) test of DMR-BN is performed, please setting as OFF (unused) by use/unused setting (setting
number:2201) at overvoltage (59). If the overvoltage (59) test of DMR-BN is performed, please setting as OFF (unused)
by use/unused setting (setting number:2101) at undervoltage (27).
118
DMR-212-006
4
Constant
10
12 P Control power voltage
14 6 generator
N supply
f 16
v u
Constant u
18
voltage V V
~ a ~
generator v 3
5
v u Step-up transformer
7
9 110 6600
(Example) :
11 √3 √3
13 v u
15 DMR-Pro
17
19
Simultaneous ON 21
23 T
25 ZPD y1 16
TB
CN1 y2 18
ON
E TB
OFF
Counter A3
B3 TRIP
(Hour meter)
Notes
① If the earth-fault overvoltage (64) test of DMR-BN is performed, please setting as OFF (unused) by use/unused
setting (setting number:2101) at undervoltage (27).
② Voltage operating value setting of earth-fault overvoltage (64) is a secondary voltage display.
To examine by ZPD specification, it is necessary to convert the input value from a constant voltage generator
into an equivalent for ZPD secondary voltage. (By EVT specification, in order to input directly from a constant
voltage generator, it is conversion needlessness.)
Please examine with a relative input value with reference to a 96-pages conversion table and a conversion formula.
119
DMR-212-006
10 4
12 P Control power
6
14
N supply
K 16
A
Constant K ~ 18
current 22
L 24
generator L
3
5
7
9
11
13
15 DMR-Pro
17
19
Simultaneous ON 21
23
25
TB
CN1
ON
OFF
A3
Counter
B3 TRIP
(Hour meter)
Notes
① If the earth-fault overcurrent (51G) test of DMR-GN is performed, please setting as OFF (unused) by use/unused
setting (setting number:2101,2201) at instantaneous overcurrent (50) and overcurrent (51).
120
DMR-212-006
9. Related product
9.1 AC power supply backup unit (TYPE:PBU-93)
The control power supply of a Multi-function digital relay (DMR-Pro) is a AC power supply (AC100/110V), and, in the
same
input as a voltage measurement circuit, is used of this product.
In the system which provides a control power supply from a self-system, if AC power supply is lowered or dissipates
by the short-circuiting accident or power failure, by combining this product and DMR-Pro, normal operation of the
function of a protective relay can be done for at least 1 second.
Multi-function digital relay (DMR-Pro) connectable with this one product is one set.
9.1.1 Specification
Item Specification
Product name AC power supply backup unit
Type PBU-93
Rated voltage AC100/110V 50/60Hz
Input
Voltage variation range AC85…127V
Output (67) DC141/155V (At no-load)
Rush current 5.5A or less
Input consumption VA (68) AC100/110V:15VA or less (DMR-FN, DMR-GN, DMR-BN, DMR-SN)
Blackout guarantee time (69) 1 second
Insulation resistance Between electrical circuit and case. Avobe 50MΩ at DC500V megger
Withstand voltage Between electrical circuit and case. AC2000V 50/60Hz 1 minute
Lightning impulse withstand Between power supply (INPUT) terminals 3.0kV 1.2/50μs Positive and
voltage (S1 and S2). negative polarity, for each 3 times
Overload capacity 1.5 times 10 seconds and 1.2 times continuation of rated voltage.
Sweep vibration frequency range:10…55Hz, Displacement amplitude:0.15mm,
Vibration
Strength Number of sweep:5, Sweep velocity:1 octave /minute
Peak acceleration:294m/s2
Shock
Each 3 times of forward reverse to the direction of X Y Z.
Dimension 120mm(Width)×120mm(Height)×130mm(Depth)
Material Case:Fire retardancy ABS(V-0) Terminal cover:Polycarbonate resin
Structure Outward color Black (Munsell N1.5)
Terminal screw Input,Output,Discharge terminal, M4 screw
Mass Approx. 700g
Operating temperature and
-10…+50℃ ,30…90%RH (Non condensing)
humidity limits
Storage temperature limits -25…+60℃
Design expected life 10 years
Note(67) Please connect an output only to PN terminal (Multi-function digital relay, No. 4 terminal, No. 6 terminal)
of
DMR-Pro. Please be used combining Multi-function digital relay (DMR-Pro, 1 set).
Note(68) It is the input consumption VA at the time of one Multi-function digital relay (DMR-Pro) connection.
Note(69) It is the blackout guarantee time in being used by rated voltage AC100V (-5% variation allowance).
The blackout guarantee time in being used at a voltage fluctuation range lower limit (AC85V) becomes
0.5 seconds. And, when it is used of the undervoltage function of DMR-BN/SN and operating time
setting is used exceeding blackout guarantee time, the relay output by protection detection of a
undervoltage cannot be performed at the time of blackout.
In this case, please provide a power supply from an uninterruptible power system.
121
DMR-212-006
感電注意
Unused terminal
An unused terminal
becomes a black screw.
・本製品は必ずディジタルマルチリレー DMR-Pro 1台と組合せてご使用ください。 CHARGE LED (Red)
・強制放電は必ず入力電源を切った状態で、D1とD2端子を短絡して行ってください。
また、入力電源を印加した状態での強制放電は絶対に行わないでください。 An output puts out the light
注意 ・結線は必ずCHARGEランプが消灯している事を確認した後に行ってください。
・出力端子の短絡は故障の原因となりますので絶対に行わないでください。 in DC20V or less.
9.1.4 Preparation
(1) Outline dimension
122
DMR-212-006
110
PBU-93 PBU-93 PBU-93 PBU-93
10 10 10 10 10 10
90
65 65 65
110
PBU-93 PBU-93
《Recommendation product》 Fuji electric Co., Ltd. TH35-15AL
10 10 10
Slider
Slider
Slotted screwdriver
123
DMR-212-006
9.1.5 Connection
Please perform connection after checking that CHARGE LED (red) is in lights-out status.
(There is danger of an electric shock at the time of CHARGE LED lighting.)
Please be used combining PBU-93 and a Multi-function digital relay (DMR-Pro, 1 set).
Please connect an output only to P, N terminal (Multi-function digital relay, No. 4 terminal, No. 6 terminal)
of DMR-Pro.
Please install a terminal cover after connection work.
And, please perform input of a power supply after checking that a discharge terminal (D1, D2) is open.
If used of the discharge terminal short-circuit, a remarkable life depression and blackout guarantee time are
shortened. Therefore, there is a possibility that protection detection may become impossible.
② Between the discharge terminal D1 and D2 is short-circuited. (Please carry out after checking a discharge terminal
position.) Short-circuiting must use an insulator to be unable to touch a hand at a conductive part.
Please do not let me contact absolutely other than discharge terminal D1 and D2.
③ Please continue short-circuiting until CHARGE LED (red) puts out the light. Discharge is completed in about
10 seconds.
④ Please cancel short-circuiting between the discharge terminal D1 and D2.
③ Please do not remove a terminal cover at the time of operation. There is a danger of receiving an electric
shock. And, please install a terminal cover after connection work.
④ If connection is done, please be sure to shut off an input and a power supply. And, please carry out after checking
that CHARGE LED (red) has gone out.
(If it performs compulsive discharge, check that the input and the power supply are not applied, please carry
out in the step of the 9.1.6 section.)
⑤ Because internal condenser capacity is large, please stop the continuous power supply switching.
Rush current time becomes long and there is a possibility that equipment may deteriorate.
⑥ If an input power supply is applied by unloaded condition, the electric charge is charged by the inside condenser
even if it shuts down an input and a power supply. Therefore, discharge takes time. (Being natural discharge
about 8 minutes.)
If it does forcible discharge, please do correctly according to the steps. And, please apply an input and a
power supply in the status that it combined with DMR-Pro.
124
DMR-212-006
9.1.8 Check
■ Periodic check
There are no replacement parts in a periodic check.
The periodic check of this product, Recommend carrying out by combining with a Multi-function digital relay
(DMR-Pro).
In addition, those who have technical knowledge, such as an electrical work, need to perform.
9.1.9 Maintenance
Please do neither wiring change nor discharge work by any means during operation.
And, be careful for people to be unable to touch a terminal.
The terminal cover is mounted for preventing an electric shock accident. Mount the terminal cover
without fail after the end of work.
9.1.10 Storage
Please avoid storage in the place of the high temperature and the high humidity.
Please avoid storage in the place exposed to direct sunlight.
If a long term storage is done in the state of a non-energization, there is a possibility that an aluminum
electrolytic capacitor may do a capacity depression.
In this case, please apply (for 30 to 60 minutes) rated voltage (AC100/110V). (About 1 time in three years.)
9.1.12 Troubleshooting
Phenomenon Probable cause Necessary measures
The input is not applied. Check of connection.
CHARGE LED is not
(It is not wiring. An voltage is low.) Again, apply an input.
lighted.
Trouble of equipment (PBU-93). Exchange of equipment
The input is not applied. Check of connection.
(It is not wiring. An voltage is low.) Again, apply an input.
Connected DMR-Pro
The control power supply is not provided to DMR-Pro. Check of connection.
does not operate.
(It is not wiring. An voltage is low.) Again, apply an input.
Trouble of equipment (PBU-93 or DMR-Pro). Exchange of equipment
The points of a discharge terminal are different. Check a terminal position.
Discharge treatment
The input is applying. Cutoff of an input power supply
cannot be performed.
Trouble of equipment (PBU-93). Exchange of equipment
An input voltage is low. Again, apply an input.
Blackout guarantee
Trouble of equipment (PBU-93). Exchange of equipment
time is short.
Equipment (PBU-93) is over the life period. Exchange of equipment
9.1.13 Warranty
The warranty period of this product is for one year after product delivery.
Product failure which we are not responsible for (When responsibility in manufacturing process is not recognized,
when product is disassembled/remodeled, in case of false operation by customer, etc.) is beyond our warranty.
In addition, please refer to this product in addition because the applicable item of 1-4 pages of this instruction
manual is applied.
125
DMR-212-006
Appendix table 1) Power range, Watt-hour multiplying factor list (1/2) (VT range:15.00kV…210.0kV)
V range 210.0kV 180.0kV 150.0kV 105.0kV 90.0kV 45.0kV 30.0kV 18.00kV 15.00kV
(VT 154000 (VT 132000 (VT 110000 (VT 77000 (VT 66000 (VT 33000 (VT 22000 (VT 13800 (VT 11000
Multiplying /110V) /110V) /110V) /110V) /110V) /110V) /110V) /110V) /110V) Multiplying
factor A range [W] [W] [W] [W] [W] [W] [W] [W] [W] factor
1400 k 1200 k 1000 k 720 k 600 k 300.0 k 200.0 k 140.0 k 100.0 k
5A
(700) (125.5)
2800 k 2400 k 2000 k 1400 k 1200 k 600 k 400 k 280.0 k 200.0 k
10A
(250.9)
3600 k 3000 k 2400 k 1800 k 1500 k 720 k 480 k 320.0 k 240.0 k
12A
(3360) (2880) (1680) (1440) (301.1)
4.20 M 3600 k 3000 k 2400 k 1800 k 900 k 600 k 400 k 300.0 k
15A
(2100) (376)
5.60 M 4.80 M 4.00 M 2800 k 2400 k 1200 k 800 k 560 k 400 k
20A
(502)
7.20 M 6.00 M 5.00 M 3600 k 3000 k 1500 k 1000 k 640 k 500 k
25A
(7.00) (3500) (627)
8.40 M 7.20 M 6.00 M 4.20 M 3600 k 1800 k 1200 k 800 k 600 k
30A
×100 (753)
12.00 M 9.60 M 8.00 M 5.60 M 4.80 M 2400 k 1600 k 1000 k 800 k
40A
(11.20) (1004)
14.00 M 12.00 M 10.00 M 7.00 M 6.00 M 3000 k 2000 k 1400 k 1000 k
50A
(1255) ×10
18.00 M 15.00 M 12.00 M 8.40 M 7.20 M 3600 k 2400 k 1600 k 1200 k
60A
(16.80) (14.40) (1505)
24.00 M 18.00 M 15.00 M 12.00 M 9.00 M 4.50 M 3000 k 2000 k 1500 k
75A
(21.00) (10.50) (1882)
24.00 M 20.00 M 16.00 M 12.00 M 9.60 M 4.80 M 3200 k 2000 k 1600 k
80A
(22.40) (19.20) (11.20) (2007)
30.00 M 24.00 M 20.00 M 14.00 M 12.00 M 6.00 M 4.00 M 2800 k 2000 k
100A
(28.00) (2509)
36.00 M 30.00 M 24.00 M 18.00 M 15.00 M 7.20 M 4.80 M 3200 k 2400 k
120A
(33.60) (28.80) (16.80) (14.40) (3011)
42.0 M 36.00 M 30.00 M 24.00 M 18.00 M 9.00 M 6.00 M 4.00 M 3000 k
150A
(21.00) (3.76)
56.0 M 48.0 M 40.0 M 28.00 M 24.00 M 12.00 M 8.00 M 5.60 M 4.00 M
200A
(5.02)
72.0 M 60.0 M 50.0 M 36.00 M 30.00 M 15.00 M 10.00 M 6.40 M 5.00 M
250A
(70.0) (35.00) (6.27)
84.0 M 72.0 M 60.0 M 42.0 M 36.00 M 18.00 M 12.00 M 8.00 M 6.00 M
300A
×1000 (7.527)
120.0 M 96.0 M 80.0 M 56.0 M 48.0 M 24.00 M 16.00 M 10.00 M 8.00 M
400A
(112.0) (10.04)
140.0 M 120.0 M 100.0 M 72.0 M 60.0 M 30.00 M 20.00 M 14.00 M 10.00 M
500A
(70.0) (12.55) ×100
180.0 M 150.0 M 120.0 M 84.0 M 72.0 M 36.00 M 24.00 M 16.00 M 12.00 M
600A
(168.0) (144.0) (15.05)
240.0 M 180.0 M 150.0 M 120.0 M 90.0 M 45.0 M 30.00 M 20.00 M 15.00 M
750A
(210.0) (105.0) (18.82)
240.0 M 200.0 M 160.0 M 120.0 M 96.0 M 48.0 M 32.00 M 20.00 M 16.00 M
800A
(224.0) (192.0) (112.0) (20.07)
280.0 M 240.0 M 180.0 M 140.0 M 120.0 M 54.0 M 36.00 M 24.00 M 18.00 M
900A
(252.0) (216.0) (126.0) (108.0) (22.58)
280.0 M 240.0 M 200.0 M 140.0 M 120.0 M 60.0 M 40.0 M 28.00 M 20.00 M
1000A
(25.09)
360.0 M 300.0 M 240.0 M 180.0 M 150.0 M 72.0 M 48.0 M 32.00 M 24.00 M
1200A
(336.0) (288.0) (168.0) (144.0) (30.11)
420 M 360.0 M 300.0 M 240.0 M 180.0 M 90.0 M 60.0 M 40.0 M 30.00 M
1500A
(210.0) (37.6)
450 M 400 M 320.0 M 240.0 M 200.0 M 96.0 M 64.0 M 45.0 M 32.00 M
1600A
(448.0) (384.0) (224.0) (192.0) (40.1)
560 M 480 M 400 M 280.0 M 240.0 M 120.0 M 80.0 M 56.0 M 40.0 M
2000A
(50.2)
720 M 600 M 500 M 360.0 M 300.0 M 150.0 M 100.0 M 64.0 M 50.0 M
2500A
(700) (350.0) (62.7)
840 M 720 M 600 M 420 M 360.0 M 180.0 M 120.0 M 80.0 M 60.0 M
3000A
×10000 (75.3)
960 M 800 M 560 M 480 M 240.0 M 160.0 M 100.0 M 80.0 M
4000A
(100.4)
1000 M 720 M 600 M 300.0 M 200.0 M 140.0 M 100.0 M
5000A
(700) (125.5) ×1000
840 M 720 M 360.0 M 240.0 M 160.0 M 120.0 M
6000A
(150.5)
900 M 450 M 300.0 M 200.0 M 150.0 M
7500A
(188.2)
960 M 480 M 320.0 M 200.0 M 160.0 M
8000A
(200.7) ×10000
( ) is a primary power value at /1kW.
126
DMR-212-006
Appendix table 2) Power range, Watt-hour multiplying factor list (2/2) (VT range:150V…9000V)
V range 9000V 4500V 3000V 1500V 655V(600V) 627V(600V) 600V 300V 150V
(VT 6600 (VT 3300 (VT 2200 (VT 1100 (VT 480 (VT 460 (VT 440 (VT 220 (110V)
Multiplying /110V) /110V) /110V) /110V) /110V) /110V) /110V) /110V) Multiplying
factor A range [W] [W] [W] [W] [W] [W] [W] [W] [W] factor
60.0 k 30.00 k 20.00 k 10.00 k 4.50 k 4.20 k 4.00 k 2000 1000
5A
×1 (4.36) (4.18) ×0.01
120.0 k 60.0 k 40.0 k 20.00 k 9.00 k 8.40 k 8.00 k 4.00 k 2000
10A
(8.73) (8.36)
150.0 k 72.0 k 48.0 k 24.00 k 12.00 k 10.00 k 9.60 k 4.80 k 2400
12A
(144.0) (10.47) (10.04)
180.0 k 90.0 k 60.0 k 30.00 k 14.00 k 14.00 k 12.00 k 6.00 k 3000
15A
(13.09) (12.55)
240.0 k 120.0 k 80.0 k 40.0 k 18.00 k 18.00 k 16.00 k 8.00 k 4.00 k
20A
(17.45) (16.73)
300.0 k 150.0 k 100.0 k 50.0 k 24.00 k 24.00 k 20.00 k 10.00 k 5.00 k
25A
(21.82) (20.91)
360.0 k 180.0 k 120.0 k 60.0 k 28.00 k 25.00 k 24.00 k 12.00 k 6.00 k
30A
(26.18) (25.09)
480 k 240.0 k 160.0 k 80.0 k 36.00 k 36.00 k 32.00 k 16.00 k 8.00 k
40A
(34.91) (33.45)
600 k 300.0 k 200.0 k 100.0 k 45.0 k 42.0 k 40.0 k 20.00 k 10.00 k
50A
(43.6) (41.8) ×0.1
720 k 360.0 k 240.0 k 120.0 k 56.0 k 56.0 k 48.0 k 24.00 k 12.00 k
60A
(52.4) (50.2)
900 k 450 k 300.0 k 150.0 k 72.0 k 64.0 k 60.0 k 30.00 k 15.00 k
75A
(65.5) (62.7)
960 k 480 k 320.0 k 160.0 k 72.0 k 72.0 k 64.0 k 32.00 k 16.00 k
80A
×10 (69.8) (66.9)
1200 k 600 k 400 k 200.0 k 90.0 k 84.0 k 80.0 k 40.0 k 20.00 k
100A
(87.3) (83.6)
1500 k 720 k 480 k 240.0 k 120.0 k 100.0 k 96.0 k 48.0 k 24.00 k
120A
(1440) (104.7) (100.4)
1800 k 900 k 600 k 300.0 k 140.0 k 140.0 k 120.0 k 60.0 k 30.00 k
150A
(130.9) (125.5)
2400 k 1200 k 800 k 400 k 180.0 k 180.0 k 160.0 k 80.0 k 40.0 k
200A
(174.5) (167.3)
3000 k 1500 k 1000 k 500 k 240.0 k 240.0 k 200.0 k 100.0 k 50.0 k
250A
(218.2) (209.1)
3600 k 1800 k 1200 k 600 k 280.0 k 250.0 k 240.0 k 120.0 k 60.0 k
300A
(261.8) (250.9)
4.80 M 2400 k 1600 k 800 k 360.0 k 360.0 k 320.0 k 160.0 k 80.0 k
400A
(349.1) (334.5)
6.00 M 3000 k 2000 k 1000 k 450 k 420 k 400 k 200.0 k 100.0 k
500A
(436) (418) ×1
7.20 M 3600 k 2400 k 1200 k 560 k 500 k 480 k 240.0 k 120.0 k
600A
(524) (502)
9.00 M 4.50 M 3000 k 1500 k 720 k 640 k 600 k 300.0 k 150.0 k
750A
(655) (627)
9.60 M 4.80 M 3200 k 1600 k 720 k 720 k 640 k 320.0 k 160.0 k
800A
×100 (698) (669)
12.00 M 5.60 M 3600 k 1800 k 800 k 800 k 720 k 360.0 k 180.0 k
900A
(10.80) (5.40M) (785) (753)
12.00 M 6.00 M 4.00 M 2000 k 900 k 900 k 800 k 400 k 200.0 k
1000A
(873) (836)
15.00 M 7.20 M 4.80 M 2400 k 1200 k 1000 k 960 k 480 k 240.0 k
1200A
(14.40) (1047) (1004)
18.00 M 9.00 M 6.00 M 3000 k 1400 k 1400 k 1200 k 600 k 300.0 k
1500A
(1309) (1255)
20.00 M 9.60 M 6.40 M 3200 k 1400 k 1400 k 1400 k 640 k 320.0 k
1600A
(19.20) (1396) (1338) (1280)
24.00 M 12.00 M 8.00 M 4.00 M 1800 k 1800 k 1600 k 800 k 400 k
2000A
(1745) (1673)
30.00 M 15.00 M 10.00 M 5.00 M 2400 k 2400 k 2000 k 1000 k 500 k
2500A
(2182) (2091)
36.00 M 18.00 M 12.00 M 6.00 M 2800 k 2500 k 2400 k 1200 k 600 k
3000A
(2618) (2509)
48.0 M 24.00 M 16.00 M 8.00 M 3600 k 3600 k 3200 k 1600 k 800 k
4000A
(3491) (3345)
60.0 M 30.00 M 20.00 M 10.00 M 4.50 M 4.20 M 4.00 M 2000 k 1000 k
5000A
(4.36) (4.18) ×10
72.0 M 36.00 M 24.00 M 12.00 M 6.00 M 5.60 M 4.80 M 2400 k 1200 k
6000A
(5.24) (5.02)
90.0 M 45.0 M 30.00 M 15.00 M 7.20 M 6.40 M 6.00 M 3000 k 1500 k
7500A
(6.55) (6.27)
96.0 M 48.0 M 32.00 M 16.00 M 7.20 M 7.20 M 6.40 M 3200 k 1600 k
8000A
×1000 (6.98) (6.69) ×100
( ) is a primary power value at /1kW.
127
DMR-212-006
128
DMR-212-006
129
DMR-212-006
130
DMR-212-006
131