DMR-212-006

INSTRUCTION MANUAL
MULTI-FUNCTION DIGITAL RELAY

DMR-Pro

DMR-FN
DMR-GN
DMR-BN
DMR-SN
DMR-212-006

Introduction
Thank you for your purchase of our product.
Read this instruction manual carefully before installation, wiring, and using this product.
This product is a product with the guard relay function for carrier transformation equipment.
Before use, please read this instruction manual and use it correctly.
Please keep it at hand to see always after reading.
If this instruction manual is lost or damaged, please ask our company or a distributing agent.
The detailed specification of a communication output (option), a communication step, and a communications protocol are
not indicated by this instruction manual. Please refer to the communication specification of a separate volume.
In addition, if a communication specification is necessary, please require of our company or a distributing agent.

<Caution>
Have a contact with us when you have any questions or are aware of missing article.

Safety precaution
Important contents are mentioned in this instruction manual to prevent any damage / use this product appropriately.
Keep the following safety precaution in mind after understanding each sign.
Improper use may lead to death or severe injury.

Improper use may possibly lead to death or severe injury.

Improper use may lead to medium injury.

【About a disclaimer】
We are not responsible for the damage caused by following condition (earthquake / fire which is not caused by
us, action by third party, other accident, damage caused by our customer, misuse, product usage under abnormal condition).
We are not responsible for secondary damage caused by product use / product malfunction (loss of profit, halt of
business operation).
We are not responsible for damage produced depending on the usage which is not indicated by the instruction manual.
We are also not responsible for damage caused by false operation in combination with connecting equipment which is beyond
our control.

Do not disassemble, remodel and repair this product.


Have a contact with us or sales agent when product failure happens to prevent fire / electric shock / injury.
Do not get this product wet to prevent heat generation / ignition / product failure.
When this product gets wet, stop using it.
Do not connect metal excepting wiring to terminal in order to prevent heat generation/ignition.
Do not get this product near the inflammable gas / combustible chemicals / combustibles to prevent fire.
In order to prevent an electric shock and the malfunction of a protective device, please do not touch the terminal (metal
part) in a hot line condition.
Please do not perform an open circuit of CT secondary circuit in a hot line condition. The high voltage occurs and
there is fear of an electric shock or CT destruction.

Connect specified power supply.


Connecting power supply beyond specification causes fire / product failure.
If dust has adhered to the terminal, please turn off the power and wipe off a terminal.
Follow the below-mentioned procedure when abnormality (fuming / bad odor) happens.
(1) Stop a power supply and input, and stop using.
(2) Contact our company or a distributing agent.

Do not use this product in a environment of high temperature and high humidity to prevent any damage.
Do not touch the terminal during operation to prevent electric shock.
Please do not pull a connection line by force or do not bend it by force. Damage of codes causes generation of heat
and a burn. And, apparatus breaks down by the loose connection.
Please do not perform connection or inspection of apparatus by the wet hand.
Please wire in applied voltage and the electric wire size suitable for power distribution current.

1
DMR-212-006

Other precaution
If control power supply voltage uses this product in the same input as a voltage measurement circuit by AC.
Please provide a power supply from an uninterruptible power system or dedicated AC power supply backup unit (type:
PBU-93. Option, Refer to 9 section).
If these are not used and control power supply voltage is less than the fluctuation range (AC100/110V±15%) in blackout
etc., it becomes impossible to perform ON / OFF control (any condition of REMOTE/LOCAL), and the relay output by protection
detection.
The abnormal output of equipment (relay break contact output).
The equipment abnormal output of this product is relay b contact output. (At the case of normal, a relay is excited
and the contact is OFF)
For this reason, it takes about 800ms by the contact OFF of an equipment abnormal output from control power supply input
(after the control power supply voltage was settled within ranges).
Please use a timer etc., in order to prevent false detection.
About an initial processing time.
The initial processing time of this product is necessary for about 1 second after control power supply input (after the
control power supply voltage was settled within ranges).
About an protection function stop mode.
This product is equipped with various test modes as a maintenance function.
While performing this mode, all original protection functions are suspended.
The details in each mode, please refer to "8. maintenance and the inspection".
• Sequence test mode.
It is the mode which checks protection detection operation, without applying an input.
Only arbitrary time can make protection detection condition by switch operation.
• Relay test mode.
This mode actually applies an input and confirms protection detection operation.
It outputs the relay contact only for these modes (test).
• Self check mode.
They are an internal memory, display, DI, and the mode that checks whether various option outputs are operating
normally.

About use of the walkie-talkie in the circumference.


About the cellular phone and PHS, it is checking by contact. And, about the transceiver (150MHz, 430MHz, 900MHz)
of 5W, it is checking that there is no malfunction in 30cm distance.
However, please keep away this product from a walkie-talkie.

About dew condensation


If the temperature and humidity of an installation change rapidly when a product is a non-energization, the waterdrop
by dew condensation may adhere to a display inner side. (The display filter and the LCD surface stick and the pattern
of the shape of a circle or an ellipse occur.) This phenomenon improves by doing the power distribution of the auxiliary
power and leaving it for about 2 hours.
Don't mount or store this unit in the following environment.
Places where corrosive gas (SO2 / H2S / etc.)(1) is generated.
Places where dust is generated.
Places with much vibration and shock.
Places with influence of external magnetic field (2).
Note(1) Corrosive gas = Sulfur dioxide SO2 / Hydrogen sulfide H2S / etc.
Note(2) Large current bus / saturable reactor / etc.

Please perform cleaning of this product in the next way.


Wipe off dirt on the surface with dry cloth softly. Keep in mind that strong rubbing of nameplate leads to character
disappearance. Organic solvent is not appropriate for cleaning.
If LCD is wiped, liquid crystal may indicate. This phenomenon is a phenomenon of occurring with static electricity.
By leaving it for a while, it discharges automatically and returns.
Please keep in mind that it will break if a LCD side is pushed strongly.
And, if a filter is pushed, LCD may touch a filter, and the pattern of the shape of a circle or an ellipse may be made.
Therefore, please do not push a filter strongly.

Mercury component and Nickel-cadmium battery are not used in this product.
Please dispose of this product as industrial waste (noncombustible).

2
DMR-212-006

■ The precautions for using it safely


1. Operation and storage environment.
Don’t mount or store this unit in the following environments. If the unit becomes defective due to the use in
an environment other than specified, it may be repaired for pay even during its warranty period (one year after
the date of delivery).
① Don’t mount or store the unit at a place subjected to noticeable external noises.
② If this unit directly measures an inverter output of cycle control, SCR phase angle control or PWM control,
an error may increase due to its operation principle.

2. Cautions on use in an outdoor panel


Be careful with the following items when using this unit in an outdoor panel.
① This product is not dust-proof structure and not waterproof structure. Please install in the place that
requires neither rain nor waterdrop.
② Please do not install it in the place that a dust produces.
③ Don’t install the unit at a place exposed to direct sunlight. Avoid exposing the unit to direct sunlight even
through a glass window. If the meter is directly exposed to sunlight, the surface temperature of the meter rises
and the case may be deformed if the temperature exceeds 80℃.
④ If the average temperature around this product exceeds 40℃, the life of the unit may shorten.

3. Installation and wiring.


Please refer to an instruction manual, if installation and wiring are performed. And, those who follow the following
precautions and have a professional skill need to do.
• Connect the unit after confirming the connection diagram. An improper connection may cause
troubles such as the generation of a high voltage on the secondary side of its current
transformer or burning of the unit or the occurrence of a fire.
• Please forbid a hot line work. It becomes the causality of an electric shock, trouble of
apparatus, a burnout, a fire, and a gas explosion, and is very dangerous.
• The terminal cover is mounted for preventing an electric shock accident. Mount the terminal
cover without fail after the end of work.

4. Setting
This product needs setting and a check of a measurement range or protection detection before use.
In wrong setting, it may cause a malfunction to protection detection. And, measurement display may become abnormal.

5. Operation
Please be careful of the following item at the case of operation.
Use the input within the rated range. Be careful since negligence of this caution may cause troubles of the unit.
Please shut a switch cover, if it is not operated.
• Be careful not to touch any terminal when power is applied to the unit.
• It is not warranted if this product is disassembled and converted without notice.
Also, modifications may cause troubles, a fire, or other accidents.
For specifications change, etc., please contact us.

If a question has arisen or if the unit seems to be defective, please contact us.

3
DMR-212-006

Warranty and service

1. Warranty period
It is for one year after product delivery.

2. Warranty scope
In the state of the normal use of product-specification within the range according to this instruction manual,
the trouble within the warranty period performs exchange or repair gratuitously.
However, the shipping expenses and the packing cost in the case of shipping obtain as payment on a customer.
And, if it corresponds to the next, it does not warrant.
(1) If it breaks down when converted or repaired except our company.
(2) If it breaks down by use outside the specification range.
(3) If the cause of trouble is based on cause other than this product.
(4) Transportation, movement, damage by falling, and trouble.
(5) A natural disaster, disaster, etc., if it is the trouble which is irresponsible for a payment side (our company
or distributing agent).
Only a product simplex is applied with a warranty. We cannot bear the responsibility such as the damage and the loss
that occurred by the use of this product and trouble or the loss of profits.

3. Service
The following service expense is not contained in the price of this product.
(1) Dispatch of an artificer (Test run presence, maintenance inspection).
(2) The trouble investigation of possible cause and repair by cause besides a warranty scope.
(3) The trouble investigation of possible cause and repair in an out of warranty.

4. If fault occurs for this product.


If fault occurs for this product, please inform a delivery side (our company or distributing agent).

Normal service condition

Please use this product within the limits of the following normal service condition about the environment by which
use is done.

1. The fluctuation range of control power supply voltage, +30...-20%(DC) and ±15% (AC) of rated voltage.
2. Fluctuation of frequency is within ±5% of a rated frequency.
3. Ambient temperature is 0...40℃. However, it permits -10℃ to +50℃ for several hours (condition that neither
dew condensation nor freezing occurs).
4. Storage conditions are the same as an operating condition. Storage temperature is -25℃ to +60℃.
5. Relative humidity is a one day average and is 30% to 80%.
6. Altitude is 2000m or less.
7. Condition of not receiving an abnormal vibration (exceeds the 16.7Hz and double amplitude of 0.4mm), a shock
(exceeds the 294m/s2), an inclination (exceeds the 5° from front to back and from side to side), and a magnetic
field (exceeds the 400A/m).
8. Condition which is not exposed to the next conditions.
Harmful smoke or gas. Gas including salt. Waterdrop or steam. Too much dust or powder.
Explosive gas or an explosive powder. Weather.

4
DMR-212-006

Content

1. Product outline ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 7


1.1 Usage of product ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 7
1.2 Features of product ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 7

2. Model list and composition of type ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 7


2.1 Model list ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 7
2.2 Composition of type ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 8

3. Specification ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 9
3.1 Rating ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 9
3.2 The function list according to models ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 9
3.3 Protection factor Specification ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 11
3.3.1 Overcurrent [51] inverse time characteristics ・・・・・・・・・・・・・・・・・・・・・・ 14
3.3.2 Overcurrent [51] calculation formula ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 19
3.3.3 Directional earth-fault [67] phase characteristic ・・・・・・・・・・・・・・・・・・ 19
3.4 Measurement specification ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 20
3.5 Option specification ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 23
3.6 Performance (Strength) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 24

4. The name and function of each part ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 27


4.1 Front view ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 27
4.2 Back view ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 27
4.3 Display section ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 28
4.4 Switch control unit ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 29

5. Preparation ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 30
5.1 Installation ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 30
5.2 Wiring ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 31

6. Control ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 42
6.1 External sequence ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 42
6.1.1 Kind and function of input ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 42
6.1.2 Kind and function of output ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 42
6.2 Control in control output 「ON」 「OFF」 「TRIP」 specification ・・・・・・・・・・・・・・ 43
6.2.1 ON/OFF control ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 43
6.2.2 Control by protection detection ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 44
6.2.3 Block diagram of control ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 45
6.2.4 Timing of control action ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 46

7. Operation・Setting ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 47
《Default setting value》・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 48
7.1 Display change ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 51
7.1.1 Measurement setting value display ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 52
7.1.2 Protection setting value display ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 53
7.1.3 Protection detection history display ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 57
7.1.4 Error code display ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 58
7.2 Measurement factor display change ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 59
7.2.1 Main monitor measurement display factor change ・・・・・・・・・・・・・・・・・・・・・ 59
7.2.2 Phase, line display change ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 59
7.2.3 Integrated value expansion display change ・・・・・・・・・・・・・・・・・・・・・・・・・・ 59
7.3 Measurement value reset ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 60
7.3.1 Maximum value and minimum value reset ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 60
7.3.2 Integrated value reset ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 60
7.4 Setting ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 61
7.4.1 Measurement factor setting ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 61
7.4.2 Protection factor setting ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 76
7.5 LOCAL-REMOTE cahnge ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 94
7.6 ON/OFF control ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 94
7.7 Test mode ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 95
7.7.1 Sequence test mode (STM) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 95
7.7.2 Relay test mode (RTM) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 96
7.7.3 Self check mode ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 97
7.8 Version check ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 98
7.9 Reset operation at the case of protection detection ・・・・・・・・・・・・・・・・・・・・ 99
7.10 Reset operation at the case of fail-safe error occurrence ・・・・・・・・・・・・・・ 100
7.11 Zero phase current input correction ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 101

5
DMR-212-006

8. Maintenance and check ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 102


8.1 Maintenance function ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 102
8.1.1 Fail-safe function ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 102
8.1.2 Protection detection history function ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 107
8.1.3 Error history function ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 108
8.2 Troubleshooting ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 108
8.3 Check ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 109
8.3.1 Daily check ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 109
8.3.2 Periodic check ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 109
8.4 Design expected life ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 109
8.5 Maintenance ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 109
8.6 Exchange of product ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 110
8.7 Sequence test mode (STM) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 111
8.8 Relay test mode (RTM) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 111
8.9 Self check mode ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 111
8.10 Protection characteristic test ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 112
8.10.1 Instantaneous overcurrent (50), Overcurrent (51) test ・・・・・・・・・・・・・ 112
8.10.2 Directional earth-fault (67) test ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 114
8.10.3 Undervoltage (27), Overvoltage (59) test ・・・・・・・・・・・・・・・・・・・・・・・・・・ 118
8.10.4 Earth-fault overvoltage (64) test ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 119
8.10.5 Earth-fault overcurrent (51G) test ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 120

9. Related product
9.1 AC power supply backup unit (TYPE:PBU-93) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 121
9.1.1 Specification ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 121
9.1.2 Block diagram ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 121
9.1.3 The name and function of each part ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 122
9.1.4 Preparation ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 122
9.1.5 Connection ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 124
9.1.6 Compulsive electric discharge ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 124
9.1.7 Cautions on handling ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 124
9.1.8 Check ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 125
9.1.9 Maintenance ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 125
9.1.10 Storage ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 125
9.1.11 Design expected life ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 125
9.1.12 Troubleshooting ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 125
9.1.13 Warranty ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 125

Appendix table 1) Power range, watt-hour multiplying factor list (1/2)


(VT range:15.00kV...210.0kV) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 126
Appendix table 2) Power range, watt-hour multiplying factor list (2/2)
(VT range:150V...9000V) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 127
Appendix table 3) Setting item list (For model) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 128

6
DMR-212-006

1. Product outline
1.1 Usage of product
This product is a guard relay for carrier transformation equipment.
This one product performs a protection function and various measurement displays.
The direct control from a built-in switch is possible. And, circuit breaker ON/OFF control is possible by outside
DI and the remote control from communication.
Analog output, an watt-hour pulse output, and a communication output are possible as an option.

1.2 Features of product


The display adopted the legible large-sized liquid crystal display (LCD).
The lineup of the four types, a feeder (for directional earth-fault), a feeder (for earth-fault overcurrent), a bus,
and a main transformer secondary, was done.
It is a hi reliability product by output circuit duplication of false cutoff prevention, and long life design.
By having built in the test function, the test time of a periodic check (relay test, sequence test) can be shortened.
The error by protection detection or self-diagnostic function builds in the history function.
The cost reduction by the Ministry wiring and one apparatus is possible.

2. Model list and composition of type


2.1 Model list
Rated Rated Zero phase Zero phase
№ Type Model Note
voltage current rated voltage rated current
Feeder (For directional AC110V, 190V EVT, ZCT
1 DMR-FN-A1111□1-□□□□□ AC110V AC5A AC30mA
earth-fault) common use method
Feeder (For directional AC110V, 190V EVT, ZCT
2 DMR-FN-A1211□1-□□□□□ AC110V AC1A AC30mA
earth-fault) common use method
Feeder (For directional ZPD, CT
3 DMR-FN-A1121□1-□□□□□ AC110V AC5A AC 1V AC30mA
earth-fault) method
Feeder (For directional EVT, ZCT
4 DMR-FN-A1221□1-□□□□□ AC110V AC1A AC 1V AC30mA
earth-fault) method
Feeder (For earth-fault CT residual
5 DMR-GN-A1102□1-□□□□□ AC110V AC5A - AC5A
overcurrent) circuit method
Feeder (for earth-fault CT residual
6 DMR-GN-A1202□1-□□□□□ AC110V AC1A - AC1A
overcurrent) circuit method
AC110V, 190V
7 DMR-BN-A1010□1-□□□□□ Bus AC110V - - EVT method
common use

8 DMR-BN-A1020□1-□□□□□ Bus AC110V - AC 1V - ZPD method

Main transformer
9 DMR-SN-A1100□1-□□□□□ AC110V AC5A - -
secondary
Main transformer
10 DMR-SN-A1200□1-□□□□□ AC110V AC1A - -
secondary

7
DMR-212-006

2.2 Composition of type


Type Specification code

DMR-FN-□ □ □ □ □ □ □ -□ □ □ □ □
ON/OFF display color(Switch,LED)
1:「ON」 - Red,「OFF」 - Green
2:「ON」 - Green,「OFF」 - Red

Priority control
1:REMOTE / LOCAL switch priority
2:「OFF」control priority

Installation position
1:For high position installation (LCD visual angle direction:Lower view)
2:For low position installation (LCD visual angle direction:Upper view)

Communication output
0:Nothing
2:Modbus (RS-485)

Analog output, Pulse output [There is no pulse output in DMR-BN]


0:Nothing
1:Analog output, pulse output
2:Pulse output

Control output〔Fixation〕
1:「ON」「OFF」「Trip」

Control power supply voltage


1:DC100/110V
2:AC100/110V

Zero-phase rated current [DMR-BN and DMR-SN are 0 fixation.]


0:Nothing
1:AC30mA (ZCT:AC200mA/1.5mA) DMR-FN only
2:AC5A or AC1A (Same as the rated current) DMR-GN only

Zero-phase rated voltage [DMR-FN and DMR-SN are 0 fixation.]


0:Nothing
1:AC110V and 190V common use (EVT)
2:AC1V (ZPD:AC190V/50mV)

Rated current [DMR-BN is 0 fixation.]


0:Nothing
1:AC5A
2:AC1A

Rated voltage [Fixation]


1:AC110V

Hardware model [Fixation]


A:Hardware model A

Type
F:Feeder (For directional earth-fault【67】)
G:Feeder (For earth-fault overcurrent【51G】)
B:Bus
S:Main transformer secondary

8
DMR-212-006

3. Specification
3.1 Rating
Item Rating
Three-phase three-wire:AC110V,AC5A or 1A [Designation],50/60Hz,
2VT・3CT method (or 2VT・2CT method)
DMR-FN Zero-phase voltage:AC110V,190V common use (EVT) or AC1V (ZPD:AC190V/50mV)
[Designation],50/60Hz
Zero phase current:AC4A/30mA (ZCT:AC200mA/1.5mA), 50/60Hz
Input Three-phase three-wire:AC110V,AC5A or 1A [Designation],50/60Hz, 2VT・3CT method
DMR-GN
( 3) Zero phase current:AC5A or 1A (CT residual circuit) [Designation], 50/60Hz
Three-phase three-wire:AC110V,50Hz/60Hz,2VT method
DMR-BN Zero-phase voltage:AC110V,190V common use(EVT) or AC1V(ZPD:AC190V/50mV)
[Designation],50/60Hz
Three-phase three-wire:AC110V,AC5A or 1A [Designation],50/60Hz,
DMR-SN
2VT・3CT method (or 2VT・2CT method)
Input
Voltage circuit:0.5VA or less, Current circuit:0.1VA or less
consumption VA
Control power
DC100/110V(-20…+30%) or AC100/110V(±15%) [Designation]
supply

Note( ) Please use the following in the case of use of CT, ZPD, and ZCT.
This product can also be used by single phase load.
The connection number of this product per ZPD becomes to eight sets at the maximum.
CT :Overcurrent constant n>10.
ZPD:HIKARI TRADING CO.,LTD. ZPC-9B
ZCT:JEC-1201 compliance product (200mA/1.5mA)

3.2 The function list according to models (1)


Model
Factor Specification Note
DMR-FN DMR-GN DMR-BN DMR-SN

Instantaneous ○ ○ Fundamental wave
[50] - (L1,L2
overcurrent (L1,L3) (L1,L3) computing type
,L3)

○ ○ Fundamental wave
Overcurrent [51] - (L1,L2
(L1,L3) (L1,L3) computing type
,L3)
Fundamental wave
Directional computing type, EVT or ZPD, ZCT
[67] ○ - - -
Protec- earth-fault Computing Fundamental wave phase method
tion type angle detection
Earth-fault Fundamental wave CT residual
[51G] - ○ - -
overcurrent computing type circuit method
Fundamental wave
Undervoltage [27] - - ○ ○ V(L3L1)
computing type
Fundamental wave
Overvoltage [59] - - ○ - V(L3L1)
computing type
Earth-fault Fundamental wave
[64] - - ○ - EVT or ZPD
overvoltage computing type
CB-ON, CB-OFF, CB-TRIP,
DO (Non-voltage contact
Fault 1, Fault 2, Fault 3, Test,
output)
Remote/Local,
Output point:9 points
Control ○ ○ ○ ○ equipment malfunction (b contact)
CB-ON answer, CB-OFF answer,
DI (Voltage input)
REMOTE-ON command,
Input point:5 points
REMOTE-OFF comand, External trip

9
DMR-212-006

The function list according to models (2)


Model
Factor Specification Note
DMR-FN DMR-GN DMR-BN DMR-SN
Current, maximum current Effective value
○ ○ - ○
[A(L1),A(L2),A(L3)] computing type
Voltage, maximum voltage,
Effective value
minimum voltage ○ ○ ○ ○
computing type
[V(L1L2),V(L2L3), V(L3L1)]
Time division
Power ○ ○ - ○
multiplication method
Time division
Reactive power ○ ○ - ○
multiplication method
Calculate from power and
Power factor ○ ○ - ○
Measure- Computing reactive power.
ment type Zero crossing period
Frequency ○ ○ ○ ○
computing type
Integrate from only
Watt-hour ○ ○ - ○ Calculate from power.
positive power.
Integrate from only
Calculate from reactive
var-hour ○ ○ - ○ LAG var of positive
power.
power.
Zero phase current, Fundamental wave
○ ○ - - Response time:100ms
Maximum zero phase current computing type
Zero phase voltage, Fundamental wave
○ - ○ - Response time:100ms
Maximum zero phase voltage computing type
Main monitor character height 11mm 5 digits
Character height 6mm Display update time
Sub monitor
Left:4 digits, :About 1 second
LCD Left, Center, Right
Center, Right:5 digits
Display update time
Bar graph 30 dots
:About 0.25 second
Display ○ ○ ○ ○
LED Backlight (Green)
Backlight Auto off (After 10 minutes by
non-operation)
In order to indicate the condition
LED×14 points of apparatus, and the operating
state of a relay
Lock a trip output at
Error checking of apparatus by the case of error
Fail-safe function
self-diagnostics detection (Output
OFF)
By the fail-safe function,
It is recordable to
save a history for the error
Error history function up to 20 cases (with
continued more than for 15
history number)
seconds at an error code.
About each protection factor,
Protection detection record the detection value at the
history function case of the newest protection
detection in the past as a history.
Other ○ ○ ○ ○ The detection operation (DO, LED)
Sequence CB-trip and fault
test of the protection factor (a
test mode 1…3 are an object
phase is also included) selected
(STM) for DO.
by front switch operation.
The detection operation (DO, LED)
Relay test test of the protection factor which Only test output is
Maintenance
mode (RTM) actually applied and selected the ON in DO.
function
input.
The check function of whether to
operate normally.
Self check
ROM, RAM, LCD, LED, DI,
mode
Analog output, Pulse output,
Communication output

10
DMR-212-006

The function list according to models (3)


Model
Factor Specification Note
DMR-FN DMR-GN DMR-BN DMR-SN
DC4…20mA
4 Load resistance:550Ω or less Insulation with the
Analog output ( ) ○ ○ ○ ○
Between outputs non-insulates. internal circuit
(Negative common)
One-point selection
Pulse output ○ ○ - ○ Photo MOS relay output
from Wh,varh
Option Please refer to a
communication
specification, about
Communication output ○ ○ ○ ○ RS485 (Modbus) specification, a
communication step,
and a communications
protocol.
Note(4) An output possible factor (an output phase is included) can be set about each output.

● The control output for each specification


・Fault 1 to 3
Type
control output
DMR-FN DMR-GN DMR-BN DMR-SN
Instantaneous Instantaneous Instantaneous
Fault 1 Undervoltage [27]
overcurrent[50] overcurrent [50] overcurrent [50]
Fault 2 Overcurrent [51] Overcurrent [51] Overvoltage [59] Overcurrent [51]

Directional Earth-fault Earth-fault


Fault 3 Undervoltage [27]
earth-fault [67] overcurrent [51G] overvoltage [64]

3.3 Protection factor Specification (1)


Factor Item Specification ( ) is 1A rating Tolerance Note
Operating Setting value JEC 2500(1987)
Instantaneous 10…80A (2…16A) 1A(0.2A) unit
current ±5% JEC 2510(1989)
overcurrent
Reset current 90% or more of an operating current setting value JIS C 4602(1986)
For DMR-FN,
Setting value
DMR-GN Instantaneous (40ms or less) 0.1s unit
Operating time ±50ms
(50-L1,L3) or definite time (0.1…1.0s) (Definite time)
(Definite time)
For DMR-SN
100ms or less
(50-L1,L2,L3) Reset time Choice (5)
200…300ms
Operating 2.0…12.0A Setting value JEC 2500(1987)
0.1A(0.02A) unit
current (7) (0.40…2.40A) ±5% JEC 2510(1989)
Reset current 90% or more of an operating current setting value JIS C 4602(1986)
Overcurrent
1…30 times
For DMR-FN, Time multiplier
1…1.9 times 0.1 time unit
DMR-GN ( 7)
2…30 times 1.0 time unit
(51-L1,L3)
100ms or less
For DMR-SN Reset time Choice (5)
200…300ms
(51-L1,L2,L3)
Standard inverse time [SI]
Extremely inverse time [EI]
( 6)
Characteristic Very inverse time [VI] Choice one type
Long inverse time [LI]
Definite time [DT]

11
DMR-212-006

Protection factor Specification (2)


Factor Item Specification ( ) is 1A rating Tolerance Note
Operating 0.1…1.0A JEC 2500(1987)
0.1A unit Setting value ±10%
current (Primary display) JEC 2512(2002)
80% or more of an operating current setting JIS C 4609(1990)
Reset current
value
Operating EVT 5…60V 1V unit
Setting value ±5%
voltage ZPD 0.025…0.400V 0.005V unit
Directional 80% or more of an operating voltage
Reset voltage
earth-fault setting value
(67) Setting value <2s
:±100ms
Operating time 0.1…10.0s 0.1s unit
Setting value ≧2s
:Setting value ±5%
100ms or less
Reset time Choice (5)
200…300ms
Operating angle LEAD 40°±40° 1° unit Setting value ±5°
JEC 2500(1987)
JEC 2510(1989)
CT residual
CT secondary
circuit method
0.25-0.3-0.4-0.5-0.6-0.8-1.0-1.5-2.0-3.0-
Operating There is
4.0-5.0-6.0A Setting value ±5%
current valid/invalid
(0.050-0.060-0.080-0.10-0.12-0.16-0.20-
setting of the
0.30-0.40-0.60-0.80-1.0-1.2)
2nd harmonic
control
Earth-fault
function.
overcurrent
90% or more of an operating current
(51G) Reset current
setting value
Setting value <1s
:±50ms
Instantaneous (50ms or less)
(Definite time)
Operating time or definite time 0.1s unit
Setting value ≧1s
(0.1…60.0s)
:Setting value ±5%
(Definite time)
100ms or less
Reset time Choice (5)
200…300ms
Operating JEC 2500(1987)
60…110V 1V unit Setting value ±5%
voltage JEC 2511(1995)
110% or less of an operating voltage setting Between V(L3L1)
Reset voltage
value
Undervoltage Setting value <2s
(27) :±100ms
Operating time 0.1…10.0s 0.1s unit
Setting value ≧2s
:Setting value ±5%
100ms or less
Reset time Choice (5)
200…300ms
Operating JEC 2500(1987)
110...150V 1V unit Setting value ±5%
voltage JEC 2511(1995)
90% or more of an operating voltage Between V(L3L1)
Reset voltage
setting value
Overvoltage Setting value <2s
(59) :±100ms
Operating time 0.1…10.0s 0.1s unit
Setting value ≧2s
:Setting value ±5%
100ms or less
Reset time Choice (5)
200…300ms

12
DMR-212-006

Protection factor Specification (3)


Factor Item Specification Tolerance Note
Operating EVT 5…60V 1V unit JEC 2500(1987)
Setting value ±5%
voltage ZPD 0.025…0.400V 0.005V unit JEC 2511(1995)
80% or more of an operating voltage JIS C 4601(1993)
Reset voltage
setting value
Earth-fault
Setting value <2s
overvoltage
:±100ms
(64) Operating time 0.1…10.0s 0.1s unit
Setting value ≧2s
:Setting value ±5%
100ms or less
Reset time Choice (5)
200…300ms
Note(5) Setting of reset time is setting by all protection factor packages. (Default:200…300ms)
Note(6) About the operating time in overcurrent (51).
① The minimum value of the operating time is about 50ms.
② The operating time in the input beyond 120A (at 5A rating) may exceed an acceptable error.
Note(7) The range of time multiplier which can be set changes with an operating current setting value.
① Operating current setting value 2.0 to 6.0A (at 5A rating):Time multiplier is an enable in the setting
range to 1 to 30 times.
② Operating current setting value 6.1 to 12.0A (at 5A rating):Time multiplier is an enable in the setting
range to 1 to 10 times. (Although setting to 11 to 30 times is also possible, a product may be damaged by
the input which exceeded overload capacity on the occasion of operation.)

● About the operating time error of overcurrent (51)


Conditions
The lower limit value
Characteristic Operation value Input current Tolerance
of the tolerance
setting (% of setting value)
300% ±12%
Standard inverse time [SI] Minimum 500% ± 7%
Extremely inverse time [EI] 1000% ± 7%
Very inverse time [VI] 300% ±18%
Long inverse time [LI] Exclude the minimum 500% ±10% ±100ms
1000% ±10%
300% ±10%
Definite time [DT] All setting values 500% ±10%
1000% ±10%

● About the tolerance by ZPD combination (Reference)


Tolerance (Reference)
Factor
Operating voltage Operating angle
Directional earth-fault (67) Setting value ±20% Setting value ±20°
Earth-fault overvoltage (64) Setting value ±20% -
By one ZPD, this product is connectable to eight sets (maximum).

● About the tolerance by ZCT combination (Reference)


Tolerance (Reference)
Factor
Operating angle
Directional earth-fault (67) Setting value ±20°
Adjustment of an operating current is possible with this product.
Please refer to "7.11 Adjustment of zero phase current input".

13
DMR-212-006

3.3.1 Overcurrent [51] inverse time characteristics


(1) Standard inverse time [SI]

10000

1000

100

Operating
time
(Second)

Time multiplier:U

10 30
Time multiplier:U
25

30 20
25
20 15
15 10

10 5

1 4
5 3
4
2
3
1.5
2
1.5 1.1
1.1 1
1
0.1

0.01
100% 1000% 10000%
Current (% of the input current to a setting value)

Standard inverse time (SI)

14
DMR-212-006

(2) Extremely inverse time [EI]

10000

1000

100

Operating
time
(Second)

Time multiplier:U
10 30

25

20

15

10

1 4

3
Time multiplier:U
2

1.5
30
1.1
25
20 1
15
0.1
10

1.5 2 3 4 5
1 1.1

0.01
100% 1000% 10000%

Current (% of the input current to a setting value)

Extremely inverse time (EI)

15
DMR-212-006

(3) Very inverse time [VI]

10000

1000

100

Operating
time
(Second)

Time multiplier:U
10
30
25
20
15
10
Time multiplier:U
5

1 4
30
25 3
20 2
15
1.5
10 1.1
1
5
0.1 4
3

2
1 1.1 1.5

0.01
100% 1000% 10000%
Current (% of the input current to a setting value)

Very inverse time (VI)

16
DMR-212-006

(4) Long inverse time [LI]

10000

1000

100

Operating
time
(Second)

Time multiplier:U
10 30

Time multiplier:U 25

20
30
15
25
20 10
15
5
10
1 4

3
5
4 2
3 1.5
2 1.1
1.5 1
1.1
0.1 1

0.01
100% 1000% 10000%

Current (% of the input current to a setting value)


Long inverse time (LI)

17
DMR-212-006

(5) Definite time [DI]

10000

1000

100

Operating
time
(Second)

Time multiplier:U
10
30
Time multiplier:U 25
20
30
15
25
20 10
15
5
1 10 4
3
5 2
4
1.5
3
1.1
2
1
1.5
1.1
0.1 1

0.01
100% 1000% 10000%
Current (% of the input current to a setting value)

Definite time (DT)

18
DMR-212-006

3.3.2 Overcurrent [51] calculation formula


(1) Standard inverse time (SI)
・At I<2 ・At I≧2
10.39 U 10.39 U
T = +1 × T = +1 ×
(I -1)×3.67 10 I +1.67 10

(2) Extremely inverse time (EI)


32.4 U
T = ×
I2-1 10

(3) Very inverse time (VI)


5.4 U
T = ×
I- 1 10

(4) Long inverse time (LI)


21.6 U T:Operating time (Second)
T = ×
I-1 10 I:The input to a setting value
Multiplying factor of current
(5) Definite time (DT) U:Time multiplier (Time)
U
T =
10

The minimum value of the operating time is about 50ms.


The operating time in the input beyond 120A (at 5A rating) may exceed an acceptable error.

3.3.3 Directional earth-fault [67] phase characteristic

Current LEAD Current LAG


(For voltage) (For voltage)

LEAD V0 LAG

Operating angle:40°

An operation range in case operating angle is 40°.

90° 270°
100% 200% 300% 400% 500%
An operation phase angle in case operating
Magnification to current
setting value angle is 0°.

An operation phase angle in case operating


angle is 40°.

An operation phase angle in case operating


angle is 80°.
180°

19
DMR-212-006

3.4 Measurement specification (1)


Intrinsic error (8) Low
Output input
Measurement Measuring range
Item Measurement range Analog, cut Notes
factor ( ) is 1A rating Display
Pulse, value
Communication ( 8)
Maximum, Instant
CT primary value
Current AC0…5A (AC0…1A) AC5.00A…8.00kA ±1.0% ±0.5% 0.5%
display
(60 ranges)
Maximum, Minimum,
Instant VT primary value
Voltage AC0…150V ±1.0% ±0.5% 0.5%
AC150V…210.0kV display
(23 ranges)
0…1kW (0…200W) 480W…1000MW
VT,CT primary
Power -1…0…+1kW ±480…±1000MW ±1.0% ±0.5% 0.5%
value display
(-200…0…+200W) Range choice
LEAD1…0…LAG1kvar LEAD/LAG360var
Reactive VT,CT primary
(LEAD200…0 …1000Mvar ±1.0% ±0.5% 0.5%
power value display
…LAG200var) Range choice
Under input 40V
LEAD0…1…LAG0 (secondary) or
Power LEAD0…1…LAG0 Refer to
LEAD0.5…1…LAG0.5 ±2.0% ±2.0% less than 2% of
factor LEAD0.5…1…LAG0.5 notes
Range choice rated current,
power factor is 1.
45…55Hz Under input 40V
45…55Hz Refer to
Frequency 55…65Hz ±0.5% ±0.5% (secondary),
55…65Hz notes
Digital Range choice frequency is 0Hz.
display Display Expansion display
Integrate only a
:Integer, 5 digit. Power factor 1 :±2.0% is possible to the
Watt-hour positive power -
Multiplying factor Power factor 0.5:±2.5% 3rd place below a
"power receiving".
:10 integer power decimal point.
The lag at the case
of positive power Display Expansion display
"power receiving", :Integer, 5 digit. is possible to the
var-hour ±2.5% -
Integrate only Multiplying factor 3rd place below a
"LAG" reactive :10 integer power decimal point.
power.
±1.5% ZCT primary value
AC0…4A Maximum, Instant
ZCT (Exclude ±1.5% (9) 1.5% display.
( /30mA) AC0...4A
Zero phase ZCT.) For DMR-FN.
current CT Maximum, Instant CT primary value
AC0…5A
residual Current measurement ±1.5% ±1.5% (9) 1.5% display.
[AC0…1A]
circuit range choice For DMR-GN.
AC0…110V EVT primary value
EVT ±1.5% ±1.5% (9) 1.0%
AC0…190V Maximum, Instant display
Zero phase
Voltage measurement ±5.0%
voltage AC0…1V ±5.0% (9) ZPD primary value
ZPD range choice (Exclude 1.5%
(10) (Exclude ZPD.) display
ZPD.)
Note(8) The intrinsic error of a display and a low input cut are % to a measurement range.
An output is % to an output span. (Power, reactive power, and a zero phase voltage are % to rated value.)
In addition, watt-hour and var-hour are % to indicated value, and power factor is % to 90°
of electrical angles.
Note(9) Analog output of zero phase voltage, it is only a maximum zero-phase voltage (DMR-BN only). And, a zero
phase current becomes only a communication output.
Note(10) If it uses ZPD by primary rating 3300V, a measuring range is AC0…0.5V. (if voltage range setting is 3300V
or 3.3kV setting)

20
DMR-212-006

Item Specification
Bar graph Bar graph display (Watt-hour and var-hour exclude) of the main monitor factor.
display A sub monitor factor can also be indicated by setting.
Current / Maximum current (L1,L2,L3),
Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1), Power, Reactive power,
Main monitor Power factor, Frequency, Watt-hour, var-hour,
Zero phase current / Maximum zero phase current,
Zero phase voltage / Maximum zero phase voltage
Current / Maximum current (L1,L2,L3),
Sub monitor Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1),
(Left) Power, Reactive power, Power factor, Zero phase current / Maximum zero phase current,
Display Zero phase voltage / Maximum zero phase voltage
setting Current / Maximum current (L1,L2,L3),
possible Sub monitor Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1), Power, Reactive power,
factor (Center) Frequency, var-hour, Zero phase current / Maximum zero phase current,
(11) Zero phase voltage / Maximum zero phase voltage
Current / Maximum current (L1,L2,L3),
Sub monitor Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1), Power, Power factor,
(Right) Frequency, Watt-hour, Zero phase current / Maximum zero phase current,
Zero phase voltage / Maximum zero phase voltage
Current / Maximum current (L1,L2,L3),
Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1), Power, Reactive power,
Bar graph
Power factor, Frequency, Zero phase current / Maximum zero phase current,
Zero phase voltage / Maximum zero phase voltage
Note(11) It is based on the measurement factor of each model.

● Polarity display of power and reactive power and power factor.


90°
(var=100%,PF=0%)
・Polarity of LEAD and LAG.
- kW + kW
LEAD kvar LEAD kvar It is based on the direction of the current which
LEAD cosφ LEAD cosφ flows into load at power receiving.
・ Measurement (display) is done in the LAG direction
[Ⅱ] [Ⅰ] at lag.
180° 0°
(var=0%,PF=100%) (var=0%,PF=100%)
・ Analog output of reactive power and power factor.
[Ⅲ] [Ⅳ] LEAD direction:DC4…12mA,
LAG direction:DC12…20mA
- kW + kW
LAG kvar LAG kvar
LAG cosφ LAG cosφ

270°
(var=100%,PF=0%)

● Current measurement range ● Voltage measurement range

5.00A 30.0A 200.0A 1000kA 3000A 150.0V (110V) 9000V (6600V/110V)


10.00A 40.0A 200A 1.00kA 3.00kA 150V (110V) 9.00kV (6.6kV/110V)
10.0A 50.0A 250.0A 1200A 4000A 300.0V (220V/110V) 15.00kV (11kV/110V)
12.00A 60.0A 250A 1.20kA 4.00kA 300V (220V/110V) 18.82kV (13.8kV/110V) (13)
12.0A 75.0A 300.0A 1500A 5000A 600V (440V/110V) 30.0kV (22kV/110V)
15.00A 80.0A 300A 1.50kA 5.00kA 627V (460V/110V) (12) 45.0kV (33kV/110V)
15.0A 100.0A 400A 1600A 6000A 655V (480V/110V) (12) 90.0kV (66kV/110V)
20.00A 100A 500A 1.60kA 6.00kA 1500V (1100V/110V) 105.0kV (77kV/110V) (14)
20.0A 120.0A 600A 2000A 7500A 3000V (2200V/110V) 150.0kV (110kV/110V)
25.00A 120A 750A 2.00kA 7.50kA 3.00kV (2.2kV/110V) 180.0kV (132kV/110V)
4500V (3300V/110V) 210.0kV (154kV/110V)
25.0A 150.0A 800A 2500A 8000A
4.50kV (3.3kV/110V)
30.00A 150A 900A 2.50kA 8.00kA

Note(12) Full-scale of bar graph is 600V.


Note(13) Full-scale of bar graph is 18.00kV.
Note(14) Full-scale of bar graph is 120.0kV.

21
DMR-212-006

● Measurement range
Measurement Input Measurement range
Note
factor ( ) is 1A rating Display Analog output
Current AC0…5A (AC0…1A) 120% of input rating DC4…23.2mA Maximum, Instant
Maximum,
Voltage AC0…150V 101% of meter full-scale DC4…20.16mA
Minimum, Instant
0…1kW (0…200W) DC3.84…23.2mA
Power 120% of input rating
-1…0…+1kW (-200…0…+200W) DC3.84…21.6mA
Reactive LEAD 1…0…LAG 1kvar
120% of input rating DC3.84…21.6mA
power (LEAD 200…0…LAG 200var)
LEAD 0…1…LAG 0 LEAD 0.00…1.00…LAG 0.00 DC4…20mA
Power factor
LEAD 0.5…1…LAG 0.5 LEAD 0.49…1.00…LAG 0.49 DC3.84…20.16mA
45…55Hz 44.9…55.1Hz
Frequency DC3.84…20.16mA
55…65Hz 54.9…65.1Hz
ZCT AC0…4A ( /30mA) 120% of input rating -
Zero phase
CT residual Maximum, Instant
current AC0…5A (AC0…1A) 120% of input rating -
circuit
AC0…110V Maximum, Instant
EVT
AC0…190V DC4…23.2mA or Analog output is
Zero phase
120% of input rating DC4…18.08mA only for maximum
voltage
ZPD AC0…1V (15) (16) zero-phase
voltage.
Note(15) If it uses ZPD by primary rating 3300V, a measuring range is AC0…0.5V. (if voltage range setting is
3300V or 3.3kV setting)
Note(16) A measuring range changes by setting of a zero phase voltage output range.
Example) In case of EVT specification, and secondary rating 110V.
・0…150V/DC4…20mA setting:Measurement range 0…132V(1.2 times 110V)/DC4…18.08mA
・0…110V/DC4…20mA setting:Measurement range 0…132V(1.2 times 110V)/DC4…23.20mA
In case of EVT primary rating 6600V, 150V is 9000V equivalency, and 110V is 6600V equivalency.

22
DMR-212-006

3.5 Option specification


Item Specification
Number of output DMR-FN, DMR-GN:4 points, DMR-BN:3 points, DMR-SN:4 points
DMR-FN, DMR-GN:Current (L1,L2,L3), Voltage (L1L2,L2L3,L3L1), Power,
Reactive power, Power factor, Frequency
Output factor DMR-BN:Voltage (L1L2,L2L3,L3L1), Frequency, Maximum zero phase voltage (17)
DMR-SN:Current (L1,L2,L3), Voltage (L1L2,L2L3,L3L1), Power, Reactive power,
Analog Power factor, Frequency
output Output method DC4…20mA (Load resistance:550Ω or less)
1 second or less (Time within ±1% of final constant value.)
Response time * Detect 90% or more of final constant value in the step input for 100ms about a
maximum zero-phase voltage.
Output ripple % for output span. 1%P-P or less.
Between outputs are not insulation. (Negative common)
1 point (Select Watt-hour or var-hour by setting.)
Watt-hour:Integrate only a positive power "power receiving".
Number of output
Var-hour:The lag at the case of positive power "power receiving",
Integrate only "LAG" reactive power.
Output method Optical MOS-FET relay, 1a contact
Contact capacity 125V AC,DC 70mA (Resistance load, inductive load)
On resistance 16Ω or less
Pulse output width 250ms±10% (It may become 130ms±10% in a range) (18)
Pulse output Full load power (kW,kvar)=√3×Rated voltage(V)×Rated current(A)×10-3
Full load power kW(kvar) Output pulse unit. kWh/pulse(kvarh/pulse) Multiplying factor
Below 1 0.1 0.01 0.001 0.0001 0.01
Over 1 Below 10 1 0.1 0.01 0.001 0.1
Over 10 Below 100 10 1 0.1 0.01 1
Over 100 Below 1,000 100 10 1 0.1 10
Over 1,000 Below 10,000 1,000 100 10 1 100
Over 10,000 Below 100,000 10,000 1,000 100 10 1,000
Over 100,000 Below 1,000,000 100,000 10,000 1,000 100 10,000
Transmission system RS-485 Half duplex two-wire system
Transmission rate 4800bps / 9600bps / 19200bps / 38400bps
Connection method Multi-drop
Transmission protocol Modbus RTU
Line code NRZ
Error detection CRC-16 (X16 + X15 + X2 + 1)
Synchronous method Asynchronous communication method
Communication Cable length 1000m (Total)
output Number of connection 31 sets
Address 1…247 (Setting with a front switch.)
Start bit 1 bit
Data length 8 bits
Parity NONE (Nothing) / EVEN (Even number) / ODD (Odd number)
Stop bit 1 bit / 2 bits
Transmission character Binary
Communication cable Shielded Twist Pair cable
Note(17) About a maximum zero-phase voltage, an output is also reset by reset operation of a measurement value.
Refer to the reset of the measurement value of the 7.3 section for reset operation of measurement value.
A maximum zero-phase voltage output can change full-scale one as follows by setting.
AC0…110V(190V,1V)/4…20mA or AC0…150V(259V,1.364V)/4…20mA.
However, an input measuring range is up to 1.2 times of rating (110V, 190V, 1V).
Note(18) By each setting (a voltage measurement range, a current measurement range, pulse unit), if the output pulse
period of a rated power becomes the speed more than 2 pulse / second, output pulse width becomes 130ms±10%.
Output pulse period = Rated power [kW] / Output pulse unit [kWh/pulse] / 3600[second]
Example) Voltage measurement range:9000V(6600V/110V),Current measurement range:80A,
Output pulse unit:0.1kWh/pulse.
Rated power=1kW×(6600V/110V)×(80A/5A)=960[kW]
Output pulse period=960[kW]/0.1[kWh/pulse]/3600[second]=2.667 pulse/second
The output pulse width in this case becomes 130ms±10%.

23
DMR-212-006

3.6 Performance (Strength) (1)


Item Specification
Intrinsic error Refer to specification and measurement specification.
Bar graph intrinsic
±5% (% for span)
error
Protection Fundamental wave effective value computing type
Effective value computing type (Voltage, Current),
Operation method Fundamental wave effective value computing type (Zero phase voltage, Zero phase
Measurement
current)
Time division multiplication method (Power, Reactive power, Watt-hour, var-hour)
Within tolerance by 20℃±20℃.
Influence of Protection
Within the double precision of the tolerance by 20℃±30℃.
temperature
Measurement Within intrinsic error by 23℃±10℃.
JEC 2500:1987 JEC 2510:1989 JEC 2511:1995 JEC 2512:2002
Standard for power B-402
Compliance standard
JIS C 1102:1997 JIS C 1111:1989 JIS C 1216:1995 JIS C 1263:1995
EIA/TIA RS-485:1983
Display update time About 1 second (Bar graph is about 0.25 seconds.)
Main monitor 5 digit, character height 11mm
Sub monitor (Left) 4 digit, character height 6mm
LCD
Sub monitor (Center),(Right) 5 digit, character height 6mm
Display device
Bar graph 30 dots
Display composition
LED backlight (Green), Auto off (After 10 minutes by
Backlight
non-operation)
LED×14 points Red×5 , Green×2 , Yellow×7
① DC100/110V(DC80…143V) 18W Inrush current:4A or less
Control power supply ② AC100/110V(AC85…127V) 28VA Inrush current:5.5A or less [Designation]
Permit the temporary blackout time of a control power supply for 20ms.
Voltage circuit 0.5VA or less
Input consumption VA
Current circuit 0.1VA or less
Voltage circuit 2 times 10 seconds and 1.2 times continuation of rated voltage.
40 times 1 second, 20 times 4 seconds, 10 times 16 seconds and
CT circuit
Current circuit 1.2 times continuation of rated current.
Overload capacity
ZCT circuit 75 times 1 second and 1.2 times continuation of rated current.
Control power 1.5 times 10 seconds and 1.2 times continuation of rated voltage.
supply DC power supply:1.5 times 10 seconds and 1.3 times continuation of rated voltage.
Between electric circuits and earth.
Between input (Ac input and DI) and output (analog output and pulse output
and DO) and control power supply.
Between input and output.
Between AC input and DI.
Between AC inputs (three phase voltage, three phase current, zero
phase voltage, zero phase current). Above 50MΩ at DC500V
Insulation
Between DO and outputs (analog output, pulse output, communication output). megger
resistance
Between outputs (analog output, pulse output) and communication output.
Between analog output and pulse output.
Between DI.
Between DO.
Between DO terminals. (Between electrodes)
An equipment malfunction (b contact) excludes.
Between analog output non-insulates. (Negative side common)

24
DMR-212-006

Performance (Strength) (2)


Item Specification
Between electric circuits and earth.
Between input (Ac input and DI) and output (analog output and pulse
output and DO) and control power supply.
Between input and output. AC2000V (50/60Hz)
Between AC input and DI. 1 minute
Between AC inputs (three phase voltage, three phase current, zero phase
Power frequency voltage, zero phase current).
withstand voltage Between DO and outputs (analog output, pulse output, communication output).
Between outputs (analog output, pulse output) and communication output. AC1500V (50/60Hz)
Between analog output and pulse output. 1 minute
Between DI.
Between DO. AC1000V (50/60Hz)
Between DO terminals. (Between electrodes) 1 minute
An equipment malfunction (b contact) excludes.
Between electric circuits and earth.
Between input (Ac input and DI) and output (analog output and pulse 4.5kV 1.2/50μs
output and DO) and control power supply. Each 3 times to
Between input and output. positive and negative
Between AC inputs (three phase voltage, three phase current, zero phase polarity.
voltage, zero phase current).
Lightning impulse
Between three phase voltage input terminals (P1 and P2).
withstand voltage
Between three phase voltage input terminals (P2 and P3).
3.0kV 1.2/50μs
Between ground voltage input terminals. (Exclude ZPD specification)
Each 3 times to
Between control power supply terminals. (S1 and S2)
positive and negative
Between DI terminals. (Between electrodes) polarity.
Between DO terminals. (Between electrodes)
An equipment malfunction (b contact) excludes.
(1) Oscillatory surge voltage.
If vibration damping waveform (1…1.5MHz, peak voltage:2.5…3kV) is repeated and it adds
for 30 seconds, an error is within ±10%. (Control power supply circuit, Voltage circuit
(ZPD input is only common), Current circuit, DI, DO (common) circuit)
And, there do not need to be DO error output, a communication error, and a communication stop.
(2) Square wave impulse noise
If a noise (1μs, 100ns width) is repeated and added, a measurement error should be within 10%.
And, there is no DO error output. Communicating normally after stopping noise applying
about communication.
・ Voltage, power supply circuits (normal/common) Over 2000V (ZPD input is only common)
・ Current circuit (common) Over 2000V
・ DI,DO (common) Over 2000V
・ Analog output (induction) Over 2000V
・ Pulse output (common) Over 1500V
・ Communication output (induction) Over 1500V
・ Earth noise Over 750V
Noise capacity (3) Radio wave noise
① If the intermittence irradiation of the transceiver (150,430,900MHz band) of rated output
5W and the radio wave of a cellular phone is done from 30cm distance, an error is within
±10%. And, there do not need to be DO error output, a communication error, and a
communication stop.
② If the transceiver (150,430,900MHz band) and cellular phone of rated output 5W are touched
and intermittence irradiation is done, there needs to be no DO error output.
Communicating normally after stopping noise applying about communication.
(4) Electrostatic noise
Do in the state of anticipated use.
Energization ・・・ Aerial discharge 15kV, Contact discharge 8kV, Within ±10% of errors.
And, there do not need to be DO error output, a communication error, and a
communication stop.
Condenser charge method

* Communication error:If transmission and reception are not correctly performed even if it
performed the continuation retry 3 times.

25
DMR-212-006

Performance (Strength) (3)


Item Specification
(1) Endurance vibration
If vibration (sweep vibration frequency range:10Hz…55Hz…10Hz, displacement amplitude:
0.15mm, count of sweep:5 times, sweep speed:1 octave/minute) is added in the perpendicular
direction where equipment is fixed to a use posture, there needs to be no damage electrically
and mechanically.
The error fluctuation after a test is within a standard value.
(2) Malfunction vibration
① 16.7Hz, double amplitude 0.4mm(back and front, right and left, top and bottom).
If vibration of future is added for each 10 minutes, there do not be malfunction and
display error.
Vibration, Shock
② 10Hz, double amplitude 5mm (back and front, right and left), double amplitude 2.5mm
(top and bottom). If vibration of future is added for each 30 seconds, there do not
be malfunction and display error.
Check that there is no resonance point in the vibration frequency range (3…10Hz) before
this test. If there is a resonance point, add the test which applies the appointed acceleration
(for back and front and right and left, 9.8m/s2 and top and bottom are 4.9m/s2) for 30 seconds
with the vibration frequency.
(3) Shock
294m/s2 Direction of X, Y, Z. Each 3 times to a forward reverse.
Trouble must not arise on a performance and appearance.
Dimension :144mm×288mm×64mm (Width×Height×Depth) With a terminal cover.
Case material:ABS(V-0)
Structure
Color :Black (Munsell N1.5)
Mass :Approx. 1.5kg
Performance guarantee :0…40℃,30…90% RH (Non condensing)
An operation value, the operating time, etc. must be within the
Operating
tolerance.
temperature and
An operation guarantee:-10…+50℃,30…90% RH (Non condensing)
humidity limits
An operation value, the operating time, etc. must be within the double
precision of the tolerance.
Storage temperature
-25…+60℃
limits

26
DMR-212-006

4. The name and function of each part


4.1 Front view

Sub monitor (center) Sub monitor (Right)

Sub monitor (Left) ・LED display


Indicate the status of
the operation status of
・LCD apparatus, the display mode
Indicate a measurement of a LED, protection
value, a setting value, and detection, and a circuit
various guidances. breaker.
As the display section,
there are the main monitor, Main monitor
sub monitor (the left, a
center, right), and bar
graph.

Bar graph
Indicate the measurement ・Operation switch
value of the main monitor. Use it for reset and various
(Exclude Watt-hour and settings of the change of the
var-hour) display mode of a LCD, the
And, the measurement value change of the phase (line) of
of sub-monitor can be a measurement factor or a
displayed on bar graph. measurement factor, and a
In this case, a bar is measurement value.
indicated on the bottom of
the set sub monitor digital
display.

・Operation switch
(Inside of switch cover)
Use it for the change of
Switch cover REMOTE/LOCAL control, ON/OFF
control of a circuit breaker,
and the test mode of apparatus.

4.2 Back view

Termination register
ON-OFF switch

27
DMR-212-006

4.3 Display section


Name Display color Application Note
Indicate measurement value, setting value, and various
(LCD) - With a backlight.
guidances.
Indicate operation status.
RUN Green The flicker during a test.
(Lighted at an normal operation.)
Indicate the error status of apparatus. (The error occurrence
ERROR Red
or an error code is unconfirmed and lighted.)
Indicate the status of a LCD.
SETTING Yellow
(Lighted at an setting.)
Indicate the status of a LCD.
RECORD Yellow
(Lighted at an history display.)
Indicate the status of a LCD.
ERROR CODE Yellow
(Lighted at an error code display.)
Automatic reset
TRIP Yellow Indicate the status of a trip output. (Lighted at an output)
(Lights-out)
Indicate the status of an instantaneous overcurrent relay.
50 Red
(Lighted at after protection detection.)
Indicate the status of an overcurrent relay.
51 Red
(Lighted at after protection detection.)
Indicate the status of a directional earth-fault relay. The flicker during a
67 Red
(Lighted at after protection detection.) detection.
Indicate the status of a earth-fault overcurrent relay. The display status at the
51G Red
(Lighted at after protection detection.) case of a trouble reset is
Indicate the status of a under voltage relay. based on setting.
27 Red
(Lighted at after protection detection.) (Hold / Rreset)
Indicate the status of an overvoltage relay.
59 Red
(Lighted at after protection detection.)
Indicate the status of a earth-fault overvoltage relay.
64 Red
(Lighted at after protection detection.)
Indicate the status of equipment.
STM/RTM Yellow
(Lighted at an STM,RTM tests.)
Indicate the status of equipment.
REMOTE Yellow
(Lighted by the switch "REMOTE" side.) An exclusion display of
Indicate the status of equipment. REMOTE/LOCAL.
LOCAL Yellow
(Lighted by the switch "LOCAL" side.)
Indicate the status of DI "CB-ON answer". Circuit
ON Red / Green A color is
(Lighted at an DI input.) breaker-ON
based on
Indicate the status of DI "CB-OFF answer". Circuit
OFF Green / Red designation.
(Lighted at an DI input.) breaker-OFF

28
DMR-212-006

4.4 Switch control unit


Name Application Note
If it pushes 100ms or more simultaneously with "ON/OFF PERMISSION" in the
state of "LOCAL", "CB-ON" output is ON (however, off-switch priority).
Continue Output
ON (19) Invalid at the case of REMOTE.
ON, while the
"ON" control within protection detection display, setting of permission
switch is
and prohibition is possible according to a protection factor.
pushed
If it pushes 100ms or more simultaneously with "ON/OFF PERMISSION" in the
simultaneously
state of "LOCAL", "CB-OFF" output is ON. Invalid at the case of REMOTE.
Inside of OFF (19) .
However, do "CB-OFF" output ON of the case of "OFF" control priority
a switch
regardless of the status of "LOCAL/REMOTE".
cover
ON/OFF
Use it simultaneously with "ON" and "OFF" switch (valid in 100ms or more).
PERMISSION (19)
Right position
LOCAL-REMOTE Change control of LOCAL/REMOTE. is REMOTE.
(19) (For a slide switch, holding in status by the power supply reset is possible.) Left position
is LOCAL.
STM/RTM Change in test mode (It protection-function-stops at the case of test mode.)
Make it return to a measurement display from various status (protection
MEASURING detection, error occurrence, etc. exclude the status that a display shifts
automatically), such as setting and a test.
Change in setting mode. (A protection function continuation-operates also
SETTING
in the case of setting mode.)
ENTER The setting value within setting is decided. (Store in a memory)
The mode change of LCD.
MODE
Measurement display, Setting value check, Error code, History, etc.
Perform reset of a maximum current, a maximum of 0 phase currents, the maximum
MAX./MIN. RESET voltage, the minimum voltage, and a maximum zero phase voltage.
It can reset, only if an applicable factor is indicated on the main monitor.
Protection detection display
:LED of the protection factor which is setting output holding in the
protection detection reset status disappears.
RESET
It returns to a measurement display, and DO reset.
Error occurrence display
:It returns to a measurement display from error reset status.
Measurement factor change of the main monitor, Phase and a line display
change, Integrated value expansion display change, etc.
And, at the case of setting, perform choice of various setting values and
make a change etc.
From the back to
Change the existence of the termination register (100Ω) between the operation.
transmission mediums of a communication output (option) (CN3, between And, a switch is
Termination register
communication output (+) and communication outputs (-)). (20) not attached if
ON-OFF
ON :With a termination register there is no
OFF:With no termination register communication
output option.
Note(19) The next operation is possible also at the case of the malfunction detection by the fail-safe function
except a power supply monitor. (ON, OFF, ON/OFF PERMISSION, LOCAL, REMOTE)
However, operation is impossible at the case of control power supply blackout.
Note(20) Status with a termination register (Switch ON side), please set it as the address used as the terminus
on the connection form of a transmission line.

29
DMR-212-006

5. Preparation
5.1 Installation
Refer to an outline dimension drawing, a panel cutout, and the mounting instruction for a mounting instruction.
And, please install in a panel with an attached installation tool and an attached installation screw.
● Outline dimension drawing

● Caution on handling
The contrast of LCD changes with the angle to see. Please install in the position used as an optimum angle.
(1) For upper case installation. (2) For lower case installation.

(Side view) (Top view) (Side view) (Top view)

● Installation
(1) Insert a product in the cut hole of a panel from the front.
(2) Install an attached installation tool in the mounting hole
of a product side from a back of panel. (Two points of right
and left. Total of four points.)
(3) Put the nail of an installation tool into the hole of a
product, draw it into the back side and insert it.
(4) Perform the screw bundle of an installation tool in a cross
slot screwdriver, and fix a product. (Two points of right
and left. Total of four points.) Please give a tightening
torque as 0.59 to 1.08N・m (6 to 11 kg・cm).
Recommendation tightening torque:0.88N・m(9kg・cm).
When you tighten a screw, please tighten by turns.
And, if it installs in the place where vibration is added,
please use a screw lock etc.

● Control power supply


Please provide a control power supply as follows.
(1) The fluctuation range is +30 to -20% of rated voltage (DC), and within ±15% (AC).
The fluctuation range of frequency is within ±5% of a rated frequency.
(2) Supply from AC power supply backup unit PBU-93.

30
DMR-212-006

5.2 Wiring
If it wires this product, please perform connection with reference to the following.
● Wiring step
(1) Wiring of a terminal block.
A terminal block is screw stop structure. Please be sure to use a solderless contact. In that case, please protect
a tightening torque and press a screw correctly.
The short bar is beforehand installed in the current input terminal. If this short bar is removed and it wires,
there is a possibility of damaging a product. Please be sure to wire, with a short bar installed.
・Terminal block (Manufacturer:FUJICON CO.,LTD.)
Compatibility Compatibility Terminal Tightening
No. Application
electric wire solderless contact screw torque
AWG22(0.25mm2 ) to
Terminal block for control 1.25-3.5
16(1.65mm2 ) 0.8…1.0N・m
TB power supply, AC input M3.5×8×8L
AWG16(1.04mm2 ) to (8…10kg・cm)
(connecting terminal) 2-3.5
14(2.63mm2 )

(2) Wiring of a connector.


Use contact and housing for connection of a connector. Please use compatibility contact and the compatibility
housing of the following list. And, please wire it after performing crimp with an adapted crimp tool.
The electric wire used for the connector for DO, please use AWG14 or AWG16.
The electric wire for communication must use a shielded twisted pair cable.

・Connector compatibility housing list.


(Manufacturer:Tyco Electronics Japan G.K.)
No. Application Compatibility housing
CN1 Connector for DO 178289-8
CN2 Connector for DI 178289-5
CN3 Connector for options 178289-7

・Connector compatibility contact and electric wire, a crimp tool.


(Manufacturer:Tyco Electronics Japan G.K.)
Electric cable Compatibility contact Compatibility crimp tool
AWG20 (0.50mm2 )
AWG18 (0.85mm2 ) 175218-3 91558-1
AWG16 (1.25mm2 )
AWG16 (1.25mm2 )
353717-3 91561-1
AWG14 (2.20mm2 )

False insertion can be prevented because there is polarity in a connector.


In case you insert housing in a connector, please insert till the place in which there is sound.
And, please check that after installation is locked surely.
In addition, refer to the manufacturer catalog for the part details of an upper list.

31
DMR-212-006

● Terminal composition, arrangement

TB:Control power supply, AC input (For DMR-FN) (21)

E 1S 1L 2S 2L 3S 3L

CN3 1 3 5 7 9 11 13 15 17 19 21 23 25

2 4 6 8 10 12 14 16 18 20 22 24 26

CN1 P N P1 P2 P3 V0 Z1 Z2
AUX.SUPPLY (24) I0
CN2

TB

CN1:DO
No. Terminal name No. Terminal name
A1 CB-ON B1 CB-ON
A2 CB-OFF B2 CB-OFF
A3 CB-Trip B3 CB-Trip
A4 NC B4 NC
A5 Fault 1 B5 Fault 1
A6 Fault 2 B6 Fault 2
A7 Fault 3 B7 Fault 3
A8 REMOTE/LOCAL B8 REMOTE/LOCAL
A9 TEST B9 TEST
A10 Equipment malfunction B10 Equipment malfunction

CN2:DI
No. Terminal name No. Terminal name
A1 CB-ON answer (+) B1 CB-ON answer (-)
A2 CB-OFF answer (+) B2 CB-OFF answer (-)
A3 REMOTE-ON (+) B3 REMOTE-ON (-)
A4 REMOTE-OFF (+) B4 REMOTE-OFF (-)
A5 External trip (+) B5 External trip (-)

CN3:Option (Analog output, pulse output, communication output) (22)


No. Terminal name No. Terminal name
A1 Analog output 1(+) B1 Analog output 1(-)
A2 Analog output 2(+) B2 Analog output 2(-)
A3 Analog output 3(+) B3 Analog output 3(-)
A4 Analog output 4(+) (23) B4 Analog output 4(-) (23)
A5 Pulse output (23) B5 Pulse output (23)
A6 Communication output (+) B6 Communication output (-)
A7 Communication output (SG) B7 NC
A8 NC B8 NC

Note(21) In the case of DMR-BN, there are no three phase current (1S, 1L, 2S, 2L, 3S, 3L) and zero phase current
(Z1, Z2) input. In the case of DMR-SN, there are no zero phase voltage (V0) and zero phase current (Z1,
Z2) input. In the case of DMR-GN, there is no zero phase voltage (Vo) input. And, wiring of Io changes.
Note(22) If there is no option, there is no CN3.
Note(23) In the case of DMR-BN, analog output becomes to three factors. And, a pulse output cannot be performed.
Therefore, these terminals are non-connected (NC) terminals.
Note(24) As for the zero phase voltage Vo input, polarity of the wiring changes in ZPD and EVT.

32
DMR-212-006

● Block diagram
(1) DMR-FN

P1 Input DO1
circuit (CB-ON)
P2
Input DO2
circuit (CB-OFF)
P3
1S Input DO3
circuit (CB-TRIP)
1L
2S Input DO4
circuit (50)
2L S/H
+ I/O
3S Input DO5
ADC (51)
3L circuit

Input
DO6
Vo (67)
circuit
DO7
Input (LOCAL/REMOTE)
Io circuit
DO8
(TEST)

Vref
DO9
[b contact]
(Equipment
malfunction)
S1 Power
supply
circuit WDT
S2

E RESET

DI1 CLK
(CB-ON answer)

DI2 LCD
(CB-OFF answer)

DI3 I/O
(REMOTE-ON)

CPU (+)
DI4 T/D AO1
(REMOTE-OFF) (-)

(+)
DI5 T/D AO2
(External trip) (-)

(+)
T/D AO3
(-)
NVSRAM (+)
T/D AO4
(-)

LED I/O
Photo MOS
relay WHP

Switch I/O


SCI
TX/RX -
SG
Ter.

33
DMR-212-006

(2) DMR-GN

P1 Input DO1
circuit (CB-ON)
P2
Input DO2
circuit (CB-OFF)
P3
1S Input DO3
circuit (CB-TRIP)
1L
2S Input DO4
circuit (50)
2L S/H
+ I/O
3S Input DO5
ADC (51)
3L circuit

DO6
(51G)

DO7
Input (LOCAL/REMOTE)
Io circuit
DO8
(TEST)

Vref
DO9
[b contact]
(Equipment
malfunction)
S1 Power
supply
circuit WDT
S2

E RESET

DI1 CLK
(CB-ON answer)

DI2 LCD
(CB-OFF answer)

DI3 I/O
(REMOTE-ON)

CPU (+)
DI4 T/D AO1
(REMOTE-OFF) (-)

(+)
DI5 T/D AO2
(External trip) (-)

(+)
T/D AO3
(-)
NVSRAM (+)
T/D AO4
(-)

LED I/O
Photo MOS
relay WHP

Switch I/O


SCI
TX/RX -
SG
Ter.

34
DMR-212-006

(3) DMR-BN

P1 Input DO1
circuit (CB-ON)
P2
Input DO2
circuit (CB-OFF)
P3
DO3
(CB-TRIP)

DO4
(27)
S/H
+ I/O
ADC
DO5
(59)

Input
DO6
Vo (64)
circuit
DO7
(LOCAL/REMOTE)

DO8
(TEST)

Vref
DO9
[b contact]
(Equipment
malfunction)
S1 Power
supply
circuit WDT
S2

E RESET

DI1 CLK
(CB-ON answer)

DI2 LCD
(CB-OFF answer)

DI3 I/O
(REMOTE-ON)

CPU (+)
DI4 T/D AO1
(REMOTE-OFF) (-)

(+)
DI5 T/D AO2
(External trip) (-)

(+)
T/D AO3
(-)
NVSRAM

LED I/O

Switch I/O


SCI
TX/RX -
SG
Ter.

35
DMR-212-006

(4) DMR-SN

P1 Input DO1
circuit (CB-ON)
P2
Input DO2
circuit (CB-OFF)
P3
1S Input DO3
circuit (CB-TRIP)
1L
2S Input DO4
circuit (50)
2L S/H
+ I/O
3S Input DO5
ADC (51)
3L circuit

DO6
(27)

DO7
(LOCAL/REMOTE)

DO8
(TEST)

Vref
DO9
[b contact]
(Equipment
malfunction)
S1 Power
supply
circuit WDT
S2

E RESET

DI1 CLK
(CB-ON answer)

DI2 LCD
(CB-OFF answer)

DI3 I/O
(REMOTE-ON)

CPU (+)
DI4 T/D AO1
(REMOTE-OFF) (-)

(+)
DI5 T/D AO2
(External trip) (-)

(+)
T/D AO3
(-)
NVSRAM (+)
T/D AO4
(-)

LED I/O
Photo MOS
relay WHP

Switch I/O


SCI
TX/RX -
SG
Ter.

36
DMR-212-006

● Connecting diagram
(1) DMR-FN

● 2CT,EVT ● ZPD

ON B1

OFF B2

TRIP B3

Fault 1 (50)
Fault 2 (51) ● 3CT
Fault 3 (67)
REMOTE/LOCAL
Test
Equipment malfunction

REMOTE-ON
REMOTE-OFF
External trip

Communication
output

If there is no option, there is no CN3.


Note(25) As for the zero phase voltage Vo input, polarity of the wiring changes in ZPD and EVT.
Note(26) Please perform shield treatment of a shielded line by the panel side.

● If single phase load is taken ● If single phase load is taken ● If single phase load is taken
from between L1 and L2. from between L2 and L3. from between L3 and L1.

37
DMR-212-006

(2) DMR-GN

ON B1

OFF B2

TRIP B3

Fault 1 (50)
Fault 2 (51)
Fault 3 (51G)
REMOTE/LOCAL
Test
Equipment malfunction

REMOTE-ON
REMOTE-OFF
External trip

Communication
output

If there is no option, there is no CN3.


Note(27) Please perform shield treatment of a shielded line by the panel side.

38
DMR-212-006

(3) DMR-BN
● EVT ● ZPD

B1

B2

B3

Fault 1 (27)
Fault 2 (59)
Fault 3 (64)
REMOTE/LOCAL
Test
Equipment malfunction

REMOTE-ON
REMOTE-OFF
External trip

Communication
output

If there is no option, there is no CN3.


Note(28) As for the zero phase voltage Vo input, polarity of the wiring changes in ZPD and EVT.
Note(29) Please perform shield treatment of a shielded line by the panel side.

39
DMR-212-006

(4) DMR-SN
● 3CT, EVT ● 2CT

ON B1

OFF B2

TRIP B3

Fault 1 (50)
Fault 2 (51)
Fault 3 (27)
REMOTE/LOCAL
Test
Equipment malfunction

REMOTE-ON
REMOTE-OFF
External trip

Communication
output

If there is no option, there is no CN3.


Note(30) Please perform shield treatment of a shielded line by the panel side.

● If single phase load is taken ● If single phase load is taken ● If single phase load is taken
from between L1 and L2. from between L2 and L3. from between L3 and L1.

40
DMR-212-006

● Caution on handling
(1) Please install a terminal cover, if connection is finished.

(2) Please be sure to separate the wiring by the input and the output. Please do consideration (malfunction
prevention) to an exogenous noise.
(3) Please ground a earth terminal (E) in order to increase the shield effect.
And, please give the earthing resistance between a earth terminal and the ground as 100Ω or less.
(4) Please shorten wiring for this product from secondary of ZPD and ZCT, as much as possible.
In order to avoid the influence of noise sources, such as a main circuit, recommend a shielded twisted pair cable
line.
(5) In case analog output is sent at a distance, even if there is a possibility of receiving the influence of indirect
stroke serge etc. in a transmission line, protection is unnecessary for this product.
In addition, in order to protect the equipment by the receiver, please install an about 500V arrester etc. to
a receiver side between the line serge protector, and a transmission line and the ground.
(6) Wiring of analog output recommends a twisted pair cable line. (Normal mode noise abatement)
If the influence of an exogenous noise is large, recommend a shielded twisted pair cable line.
(Normal mode and common mode noise abatement) And, please ground a shield one point.
(7) Please use a shielded twisted pair cable line for a communication output. Please use the same cables including
the inside of a board.
And, please ground in the existing most operative place in a place with many inductive noises.
(8) If an inductive load is connected to a pulse output and an alarm output, recommend installation of a serge
killer to the outside. The life of a contact may become short if there is no serge killer.

(9) This product has the control output of three points. (Circuit breaker trip control by the protection function,
And contact output for circuit breaker "ON/OFF" control.)
In order to prevent the mistake trip of a circuit breaker, please connect these outputs correctly.
(Refer to the following figure.)
Please refer to "6. Control" about operation of an output.

(10) The indication for "ON" and "OFF" LED of this product, carry out by receiving the answer signal from a
circuit breaker by DI. Please connect wiring of DI to an answer from each circuit breaker. (Please refer
to the following figure.)
(DI1:CB-ON answer , DI2:CB-OFF answer)

Control 1 (CB-ON) B1

Control 2 (CB-OFF) B2

Control 3 (CB-TRIP) B3

CB-ON Answer

CB-OFF Answer

41
DMR-212-006

6. Control
6.1 External sequence
6.1.1 Kind and function of input
No. Factor Specification・Use Note
The answer of circuit breaker-ON status.
DI1 CB-ON answer
During an input, LED "ON" is lighted. Use it for LED
The answer of circuit breaker-OFF status. lighting.
DI2 CB-OFF answer
During an input, LED "OFF" is lighted.
By the input at the case of "REMOTE", "CB-ON" output is ON (OFF priority).
REMOTE-ON Invalid at the case of "LOCAL".
DI3
Command Trouble displaying "ON" control, setting of enable/disable is possible
according to a protection factor.
Valid in the input
"CB-OFF" output ON in the input at the case of "REMOTE."
for 100ms or more.
REMOTE-OFF Invalid at the case of "LOCAL".
DI4
Command However, the case of "OFF" control priority, it is not based on the status of
"REMOTE/LOCAL" but is "CB-OFF" output ON.
DI5 External trip “CB-trip” output ON. "CB-Trip" output ON while the input is continuing.
Number of inputs :5 points, Photo coupler insulation method
Input rating Input :DC100V/110V 0.6W,AC100V/110V 0.6VA
Minimum pulse width:100ms or more

6.1.2 Kind and function of output


No. Factor Specification・Use Note
Minimum output
DO1 CB-ON An output ON by "ON" control. *
time 1 second
Minimum output
DO2 CB-OFF An output ON by "OFF" control. *
time 1 second
An output ON by protection detection.
DO3 CB-Trip (OR detection of the protection factor set to protection "used") Automatic reset
Or an output ON by external trip input (DI5).
DMR-FN DMR-GN DMR-BN DMR-SN
The output state
Instantaneous Instantaneous Instantaneous
DO4 Fault 1 Undervoltage at the case of a
overcurrent overcurrent overcurrent It outputs by
[27] protection
[50] [50] [50] detection of
detection reset,
Overcurrent Overcurrent Overvoltage Overcurrent a mentioned
DO5 Fault 2 it is based on
[51] [51] [59] [51] protection
setting.
Directional Earth-fault Earth-fault factor.
Undervoltage (Hold / Automatic
DO6 Fault 3 earth-fault overcurrent overvoltage reset)
[27]
[67] [51G] [64]
The status of a switch "REMOTE/LOCAL" is outputted.
DO7 REMOTE/LOCAL
LOCAL side:Output ON , REMOTE side:Output OFF
DO8 Test An output ON by the protection detection by relay test mode (RTM).
Equipment
DO9 An output ON by equipment malfunction (fail-safe error) detection. b contact
malfunction
Output factor:CB-ON, CB-OFF, CB-Trip G2R-1A-E
Output rating:DC110V 0.4A (L/R=7ms),AC110V 16A (cosφ=0.4) (OMRON
Closed circuit current:15A,0.5 or less seconds Corporation)
G6B-1174P-US
Output factor:Fault 1 to 3, REMOTE/LOCAL, Test
(OMRON
Relay rating Output rating:DC110V 0.1A (L/R=7ms),AC110V 5A (cosφ=0.4)
Corporation)
G6B-2114P-US
Output factor:Equipment malfunction b contact
Output rating:DC110V 0.1A (L/R=7ms),AC110V 3A (cosφ=0.4) (OMRON
Corporation)
* "ON" control and "OFF" control are control by the switch and DI and communication.

42
DMR-212-006

6.2 Control in control output 「ON」 「OFF」 「TRIP」 specification


6.2.1 ON/OFF control
(1) Common items
・ Even if equipment malfunction by the fail-safe error occurs, the next control is possible.
Operation of a switch "ON", "OFF", "ON/OFF PERMISSION", and "LOCAL-REMOTE", and DI “REMOTE-ON”, ”REMOTE-OFF”.
DO "CB-ON", "CB-OFF" by communication.
・ "OFF" control (based on a switch, DI, and communication) is possible for the case of "OFF" control priority
irrespective of the status of "LOCAL-REMOTE".
・ About ON control while displaying protection detection (within FAULT display), setting of enable/disable
is possible according to a protection factor.
・"CB-ON" "CB-OFF" each output by ON / OFF control, warrant the minimum output time 1 second to the input for less
than 1 second. In a continuation input, an output is also continued.
・ If "OFF" input is during "CB-ON" output, "CB-ON" output is OFF in moment, and "CB-OFF" output is ON.
And, "ON" input between ON of "CB-OFF" output becomes invalid.
However, if "ON" input is continued with "CB-OFF" output OFF after that, "CB-ON" output is ON at the time.
・Display (LCD, LED)
LCD :Normal measurement display
ON :Lighted in DI "CB-ON answer" (answer signal of circuit breaker) input.
OFF :Lighted in DI "CB-OFF answer" (answer signal of circuit breaker) input.
TRIP:Don't display in ON / OFF control.

(2) Control by the switch


・ If the "LOCAL-REMOTE" switch is "LOCAL", control by the switch is possible.
・ If "ON" and the "ON/OFF PERMISSION" switch are pushed 100ms or more simultaneously, "CB-ON" output is ON.
・ If "OFF" and the "ON/OFF PERMISSION" switch are pushed 100ms or more simultaneously, "CB-OFF" output is ON.
However, in "OFF" control priority, "CB-OFF" output is ON regardless of the status of "LOCAL-REMOTE".
・ Only with the "ON/OFF PERMISSION" switch, "CB-ON" and "CB-OFF" do not output.

(3) Control by DI
・ If the "LOCAL-REMOTE" switch is "REMOTE", control by DI is possible.
・ "CB-ON" output is ON in 100ms or more of "REMOTE-ON" inputs.
・ "CB-OFF" output is ON in 100ms or more of "REMOTE” OFF" inputs.
However, in "OFF" control priority, "CB-OFF" output is ON regardless of the status of "LOCAL-REMOTE".

(4) Control by communication


・ If the "LOCAL-REMOTE" switch is "REMOTE", control by communication is possible.
・ "CB-ON" output is ON in communication simultaneous command of "ON" and "ON/OFF PERMISSION".
・ "CB-OFF" output is ON in communication simultaneous command of "OFF" and "ON/OFF PERMISSION".
However, in "OFF" control priority, "CB-OFF" output is ON regardless of the status of "LOCAL-REMOTE".
・ Only with the "ON/OFF PERMISSION" communication command, "CB-ON" and "CB-OFF" do not output.

43
DMR-212-006

6.2.2 Control by protection detection


(1) Common items
・ Control according to protection regardless of the "LOCAL-REMOTE" switch is possible.
・ If protection detection or an external trip (DI5) is during "CB-ON" output, "CB-ON" output is OFF in moment,
and "CB-trip" output is ON. And, "ON" input between ON of "CB-trip" output is invalid.
About ON control while displaying protection detection, setting of enable/disable is possible according to a
protection factor.
・ Even if equipment malfunction by the fail-safe error occurs, "CB-trip" output is locked (OFF) and control by
protection cannot be performed.
・ The relay setting to "used" by "used/unused" of protection relay setting, it is controllable by protection
detection.
・ They are "CB-trip" output of protection detection, and the fault output "fault 1 to 3" of an applicable
protection factor, one arbitrary point is ON.
However, if "Trip action prohibition" is set by used/unused setting, at the case of detection for fault output
outputs, "CB-trip" without outputting. "CB-trip" does not output it at the time of the detection, and outputs
the fault output.
"Trip action prohibition" setting can be setting by the protection relay (67), (51G),(27), (59), and (64).
(The setting item of a protection relay (50) and (51) is "used" or "unused".)
・ In the case of a protection detection reset, "CB-trip" output returns within a reset time setting value.
And, each fault output "fault 1 to 3", it becomes operation of an automatic reset or holding by operation
setting at the time of a reset.
Automatic reset:It returns in time for "100 or less ms" or "200 to 300ms" (based on setting of "reset time")
after a protection detection reset.
Holding:After a protection detection reset is output hold. It returns with the "RESET" switch.
・Status display (LCD, LED)
LCD :It shifts to a protection detection display. And hold after a protection detection reset.
The reset to a measurement display pushes the "RESET" switch for 1 second.
If reset operation within protection detection and after protection detection is not performed, even if
it passes for 10 minutes by no operating it, it does not return to a measurement display.
And, it is even if it does power supply reset after a protection detection reset, unless the "RESET"
switch is pushed, a protection detection display is holding.
OFF :Lighted in DI "CB-OFF answer" (answer signal of circuit breaker) input.
TRIP:Lighted in synchronizing with the output (ON) of "CB-trip" output.
Fault 1 to 3:Synchronizing with the output ON by protection factor detection of "Fault 1 to 3", LED of the
corresponding protection factor is lighted.

44
DMR-212-006

6.2.3 Block diagram of control


● REMOTE/LOCAL switch priority specification

ON
100ms
Delay
OFF circuit

ON/OFF
Switch PERMISSION 1s
Monostable
circuit CB-ON
LOCAL-REMOTE
[LOCAL] 1s
Monostable
CB-OFF DO
circuit
[REMOTE]

ON
REMOTE-ON
Control signal from CPU
(The command by protection OFF CB-Trip
detection and communication.)
DI REMOTE-OFF Trip

External
trip
Output lock by
Lock
fail-safe error

● "OFF" control priority specification

ON
100ms
Delay
OFF circuit

ON/OFF
Switch PERMISSION 1s
Monostable
circuit CB-ON
LOCAL-REMOTE
[LOCAL] 1s
Monostable
CB-OFF DO
circuit
[REMOTE]

ON
REMOTE-ON
Control signal from CPU
(The command by protection OFF CB-Trip
detection and communication.)
DI REMOTE-OFF Trip

External
trip
Output lock by
Lock
fail-safe error

45
DMR-212-006

6.2.4 Timing of control action

Fault 1 input
Reset time Reset time
(Automatic reset
setting)
Fault 2 input
Reset time Reset time
(Hold setting)

OFF priority
ON 100ms
SW/DI/Communication or more 100ms or more 100ms or more

OFF 100ms
SW/DI/Communication or more

100ms
ON/OFF permission
or more
SW/DI/Communication
ON operation reset
(For an ON continuation input)
ON is off (with no input)
CB-ON DO 1 sec
min.

CB-OFF DO

Operating time Operating time Operating time Operating time


CB-Trip DO

Trip priority Trip priority


Fault 1 DO
(Automatic reset
setting)

Fault 2 DO
(Hold setting)

Fault 1 LED
(Automatic reset
setting)
Flicker Flicker
Fault 2 LED
(Hold setting)
Flicker Flicker

TRIP LED

Protection
detection display
LCD display Protection
detection display
Protection
detection display Protection detection
1 second 1 second display (Update)
or more or more 1 second or more
RESET SW

46
DMR-212-006

7. Operation・Setting
This product displays various measurement values on a LCD. And, a display and change of a protection setting value can
be performed. Perform a change and setting of a display by the front push switch.

MODE

MODE MODE MODE MODE

Measurement Protection Protection


Measurement display Error code
setting value setting value detection
(Usual display) display
display display history display

SETTING Push 3 seconds


▼ ▲
Measurement factor
Measurement display factor setting display
change of the main monitor

SETTING + STM/RTM Protection


Push 3 seconds detection
All phase (line) display Protection factor Protection
(voltage, current) changes setting display detection
of the main monitor and a display
sub-monitor
STM/RTM Push 3 seconds After a protection detection reset
RESET Push 1 second
Test mode display Returns to a
An expansion display of
measurement display.
Watt-hour and var-hour

MODE + STM/RTM Equipment malfunction


Push 3 occurrence
MAX./MIN. RESET Push 3 seconds Error
seconds Self check mode
detection
Reset of maximum value and display
display
minimum value
(Only a displaying factor)
MODE + MEASURING After an equipment malfunction reset
RESET Push 1 second

Push 3 seconds
MAX./MIN. RESET ▼ Returns to a
Version display
Push 3 seconds measurement display.

Reset of integrated value


MEASURING
(Watt-hour, var-hour)
Returns to a measurement
display from each display.

47
DMR-212-006

《Default settings》(1)
This product is shipped with the following setting value. Please set according to an use conditions.
Feeder(For directional earth-fault)DMR-FN Feeder(For earth-fault overcurrent)DMR-GN
Setting
Default Default
No. Setting item Setting item
settings settings
1101 Display pattern Pattern 1 Display pattern Pattern 1
1102 Main monitor display factor Current (L2) Main monitor display factor Current (L2)
1103 Sub-monitor (left) display factor Voltage (L1L2) Sub-monitor (left) display factor Voltage(L1L2)
1104 Sub-monitor (center) display factor Power Sub-monitor (center) display factor Power
1105 Sub-monitor (right) display factor Watt-hour (Wh) Sub-monitor (right) display factor Watt-hour (Wh)
1106 Bar graph display factor Main monitor Bar graph display factor Main monitor
1201 Voltage measurement range 6600V Voltage measurement range 6600V
1202 Current measurement range 100.0A Current measurement range 100.0A
One-way One-way
1203 Power polarity Power polarity
deflection deflection
1204 Power measurement range 1200kW Power measurement range 1200kW
1205 Reactive power measurement range 600kvar Reactive power measurement range 600kvar
1206 Power factor measurement range 0.5-1-0.5 Power factor measurement range 0.5-1-0.5
1207 Frequency measurement range 45-55Hz Frequency measurement range 45-55Hz
1208 Zero phase voltage rating (EVT) (31) 110V
1209 Zero phase voltage output range (32) 9000V
1301 A display ON/OFF ON A display ON/OFF ON
1302 Amax. display ON/OFF ON Amax. display ON/OFF ON
1303 V display ON/OFF ON V display ON/OFF ON
1304 Vmax. display ON/OFF ON Vmax. display ON/OFF ON
1305 Vmin. display ON/OFF ON Vmin. display ON/OFF ON
1306 W display ON/OFF ON W display ON/OFF ON
1307 var display ON/OFF ON var display ON/OFF ON
1308 cosφ display ON/OFF ON cosφ display ON/OFF ON
1309 Hz display ON/OFF ON Hz display ON/OFF ON
1310 Wh display ON/OFF ON Wh display ON/OFF ON
1311 varh display ON/OFF ON varh display ON/OFF ON
1312 A0 display ON/OFF ON A0 display ON/OFF ON
1313 A0max. display ON/OFF ON A0max. display ON/OFF ON
1314 V0 display ON/OFF ON
1315 V0max. display ON/OFF ON
1401 L1 phase display ON/OFF ON L1 phase display ON/OFF ON
1402 L2 phase display ON/OFF ON L2 phase display ON/OFF ON
1403 L3 phase display ON/OFF ON L3 phase display ON/OFF ON
1404 L1L2 line display ON/OFF ON L1L2 line display ON/OFF ON
1405 L2L3 line display ON/OFF ON L2L3 line display ON/OFF ON
1406 L3L1 line display ON/OFF ON L3L1 line display ON/OFF ON
1501 Analog output 1 factor Current (L2) Analog output 1 factor Current (L2)
1502 Analog output 2 factor Voltage (L1L2) Analog output 2 factor Voltage (L1L2)
1503 Analog output 3 factor Power Analog output 3 factor Power
1504 Analog output 4 factor Power factor Analog output 4 factor Power factor
1505 Output intrinsic sensitivity (W) 100.0% Output intrinsic sensitivity (W) 100.0%
1506 Output intrinsic sensitivity (var) 50.0% Output intrinsic sensitivity (var) 50.0%
1601 Pulse output factor Watt-hour (Wh) Pulse output factor Watt-hour (Wh)
1602 Pulse unit 10kWh/pulse Pulse unit 10kWh/pulse
1701 Address 1 Address 1
1702 Transmission rate (33) 9600bps Transmission rate (33) 9600bps
33
1703 Parity ( ) Even Parity (33) Even
1704 Stop bit (33) 1 Stop bit (33) 1

48
DMR-212-006

《Default settings》(2)
Feeder(For directional earth-fault)DMR-FN Feeder(For earth-fault overcurrent)DMR-GN
Setting
Default Default
No. Setting item Setting item
settings settings
2101 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
2102 Operating value (34) 10A(2A) Operating value (34) 10A(2A)
2103 Operating time Instantaneous Operating time Instantaneous
2104 50 Reset method Hold 50 Reset method Hold
"ON" control within "ON" control within
2105 protection detection Permission protection detection Permission
display display
2201 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
2202 Characteristic Standard [SI] Characteristic Standard [SI]
2203 Operating value (34) 2.0A(0.40A) Operating value (34) 2.0A(0.40A)
2204 Time multiplier 1.0 times Time multiplier 1.0 times
51 51
2205 Reset method Hold Reset method Hold
"ON" control within "ON" control within
2206 protection detection Permission protection detection Permission
display display
2301 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
2302 Operating value (Current) 0.1A Operating value 0.25A(0.050A)
Operating value (Voltage) Instantaneous
2303 5V(0.025V) Operating time
(35) (50ms or less)
2304 Operating angle 40° 51G 2nd harmonic suppression OFF
2305 Operating time 0.1s Reset method Hold
"ON" control within
67
2306 Reset method Hold protection detection Permission
display
Zero phase current input
2307 100%
correction
"ON" control within
2308 protection detection Permission
display
2401 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
External "ON" control within External "ON" control within
2401 trip protection detection Permission trip protection detection Permission
display display
2501 Reset time 0.2s Reset time 0.2s
2601 Zero phase monitoring OFF Zero phase monitoring OFF
Note(31) It is a setting item of only a EVT specification. (It is skipped by ZPD specification.)
Note(32) In the equipment for DMR-FN, it is a setting item in a case with a communication output option.
(It is skipped if there is no option.)
Note(33) It is the setting item of only a Modbus communication output.
Note(34) ( ) is the default value in rated current AC1A
Note(35) ( ) is the default value in zero-phase rated voltage AC1V (ZPD)

In the default value, each protection factor is OFF (unused). The zero phase monitoring
(voltage, current) of a fail-safe function is also OFF (monitoring stop).
If it uses these factors, please make it setting ON (used).

49
DMR-212-006

《Default settings》(3)
This product is shipped with the following setting value. Please set according to an use conditions.
Bus DMR-BN Main transformer secondary DMR-SN
Setting
Default Default
No. Setting item Setting item
settings settings
1101 Display pattern Pattern 1 Display pattern Pattern 1
1102 Main monitor display factor Voltage (L1L2) Main monitor display factor Current (L2)
Maximum zero-
1103 Sub-monitor (left) display factor Sub-monitor (left) display factor Voltage (L1L2)
phase voltage
Zero-phase
1104 Sub-monitor (center) display factor Sub-monitor (center) display factor Power
voltage
1105 Sub-monitor (right) display factor Frequency Sub-monitor (right) display factor Watt-hour (Wh)
1106 Bar graph display factor Main monitor Bar graph display factor Main monitor
1201 Voltage measurement range 6600V Voltage measurement range 6600V
1202 Frequency measurement range 45-55Hz Current measurement range 100.0A
36 One-way
1203 Zero phase voltage rating (EVT) ( ) 110V Power polarity
deflection
1204 Zero phase voltage output range (37) 9000V Power measurement range 1200kW
1205 Reactive power measurement range 600kvar
1206 Power factor measurement range 0.5-1-0.5
1207 Frequency measurement range 45-55Hz
1301 V display ON/OFF ON A display ON/OFF ON
1302 Vmax. display ON/OFF ON Amax. display ON/OFF ON
1303 Vmin. display ON/OFF ON V display ON/OFF ON
1304 Hz display ON/OFF ON Vmax. display ON/OFF ON
1305 V0 display ON/OFF ON Vmin. display ON/OFF ON
1306 V0max. display ON/OFF ON W display ON/OFF ON
1307 var display ON/OFF ON
1308 cosφ display ON/OFF ON
1309 Hz display ON/OFF ON
1310 Wh display ON/OFF ON
1311 varh display ON/OFF ON
1401 L1L2 line display ON/OFF ON L1 phase display ON/OFF ON
1402 L2L3 line display ON/OFF ON L2 phase display ON/OFF ON
1403 L3L1 line display ON/OFF ON L3 phase display ON/OFF ON
1404 L1L2 line display ON/OFF ON
1405 L2L3 line display ON/OFF ON
1406 L3L1 line display ON/OFF ON
1501 Analog output 1 factor Voltage (L1L2) Analog output 1 factor Current (L2)
1502 Analog output 2 factor Frequency Analog output 2 factor Voltage (L1L2)
Maximum zero-
1503 Analog output 3 factor Analog output 3 factor Power
phase voltage
1504 Analog output 4 factor Power factor
1505 Output intrinsic sensitivity (W) 100.0%
1506 Output intrinsic sensitivity (var) 50.0%
1601 Pulse output factor Watt-hour (Wh)
1602 Pulse unit 10kWh/pulse
1701 Address 1 Address 1
1702 Transmission rate (38) 9600bps Transmission rate (38) 9600bps
1703 Parity (38) Even Parity (38) Even
1704 Stop bit (38) 1 Stop bit (38) 1
2101 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
2102 Operating value 60V Operating value (39) 10A(2A)
2103 Operating time 0.1s Operating time Instantaneous
2104 27 Reset method Hold 50 Reset method Hold
"ON" control within "ON" control within
2105 protection detection Permission protection detection Permission
display display

50
DMR-212-006

《Default settings》(4)
Bus DMR-BN Main transformer secondary DMR-SN
Setting
Default Default
No. Setting item Setting item
settings settings
2201 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
2202 Operating value 150V Characteristic Standard [SI]
2203 Operating time 0.1s Operating value (39) 2.0A(0.40A)
2204 59 Reset method Hold Time multiplier 1.0 times
"ON" control within
51
2205 protection detection Permission Reset method Hold
display
"ON" control within
2206 protection detection Permission
display
2301 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
2302 Operating value (40) 5V(0.025V) Operating value 60V
2303 Operating time 0.1s Operating time 0.1s
2304 64 Reset method Hold 27 Reset method Hold
"ON" control within "ON" control within
2305 protection detection Permission protection detection Permission
display display
2401 Used / Unused OFF (Unused) Used / Unused OFF (Unused)
External "ON" control within External "ON" control within
2401 trip protection detection Permission trip protection detection Permission
display display
2501 Reset time 0.2s Reset time 0.2s
2601 Zero phase monitoring OFF Zero phase monitoring OFF
Note(36) It is a setting item of only a EVT specification. (It is skipped by ZPD specification.)
Note(37) In the equipment for DMR-BN, it is a setting item in a case with a analog output or communication output
option. (It is skipped if there is no option.)
Note(38) It is the setting item of only a Modbus communication output.
Note(39) ( ) is the default value in rated current AC1A.
Note(40) ( ) is the default value in zero-phase rated voltage AC1V (ZPD).

In the default value, each protection factor is OFF (unused). The zero phase monitoring
(voltage, current) of a fail-safe function is also OFF (monitoring stop).
If it uses these factors, please make it setting ON (used).

7.1 Display change


With a MODE switch, the contents of a display of LCD can be changed as follows.
[Measurement display] → [Measurement setting value display] → [Protection setting value display] →
[Protection detection history display] → [Error code display]
And, it returns from any display to a measurement display by MEASURING switch operation (or switch non-operation
for 10 minutes).
MODE

MODE MODE MODE MODE


Measurement Measurement Protection Protection
display Error code
setting value setting value detection
(Usual display) display
display display history display

51
DMR-212-006

7.1.1 Measurement setting value display


Check the measurement factor and measurement range which are displayed on LCD, the output factor of analog
output and pulse output, and the setting value of communication output.
In addition, a setting value cannot be changed by this display screen.
About the details of the setting method of a measurement factor, or the contents of setting, please refer to
"7.4.1 Measurement factor setting".
<Cautions> It is skipped by a model, specification, and the option if there is no applicable item.

Setting No.1103 Setting No.1104 Setting No.1105


Setting No.1101 Setting No.1102 Setting No.1106
Sub-monitor Sub-monitor Sub-monitor
Display pattern Main monitor Bar graph display
(left) display (center) display (right) display
display

Setting No.1201 DMR-FN,GN,SN DMR-FN,GN,SN DMR-FN,GN,SN DMR-FN,GN,SN


No.1202 No.1203 No.1204 No.1205
Voltage
Current Power measurement Reactive power
measurement range Power polarity
measurement range range measurement range

DMR-FN No.1209 DMR-FN No.1208 DMR-FN,GN,SN No.1207 DMR-FN,GN,SN


DMR-BN No.1204 DMR-BN No.1203 DMR-BN No.1202 No.1206
Zero phase voltage Zero phase voltage Frequency Power factor
output range rating (EVT) measurement range measurement range

DMR-FN,GN,SN DMR-FN,GN,SN DMR-FN,GN,SN DMR-FN,GN,SN DMR-FN,GN,SN DMR-FN,GN,SN


No.1301 No.1302 No.1303 No.1304 No.1305 No.1306
Display ON/OFF DMR-BN No.1301 DMR-BN No.1302 DMR-BN No.1303
Maximum current Power
current Voltage Maximum voltage Minimum voltage

DMR-FN,GN,SN DMR-FN,GN,SN DMR-FN,GN,SN DMR-FN,GN,SN DMR-FN,GN,SN


No.1311 No.1310 No.1309 No.1308 No.1307
Reactive energy Electric energy DMR-B No.1304
Power factor Reactive power
Frequency

DMR-FN,GN No.1312 DMR-FN,GN No.1313 DMR-FN No.1314 DMR-FN No.1315


DMR-BN No.1305 DMR-BN No.1306
Zero phase Maximum zero
Zero phase Maximum zero
current phase current voltage phase voltage

DMR-FN,GN,SN DMR-FN,GN,SN DMR-FN,GN,SN DMR-FN,GN,SN DMR-FN,GN,SN DMR-FN,GN,SN


No.1401
No.1402 No.1403 No.1404 No.1405 No.1406
Phase / line
DMR-BN No.1401 DMR-BN No.1402 DMR-BN No.1403
display ON/OFF L2 phase current L3 phase current
L1 phase current L1L2 line voltage L2L3 line voltage L3L1 line voltage

Setting No.1501 Setting No.1502 Setting No.1503 DMR-FN,GN,SN


No.1504
Output 1 factor Output 2 factor Output 3 factor
Output 4 factor

DMR-FN,GN,SN No.1506 DMR-FN,GN,SN No.1505


Intrinsic sensitivity Intrinsic sensitivity
(reactive power) (power)
Each display is skipped if there is
no corresponding option.
DMR-FN,GN,SN No.1601 DMR-FN,GN,SN No.1602
Pulse unit
Output factor
multiplying factor

Setting No.1701 Setting No.1702 Setting No.1703 Setting No.1704


Address Transmission rate Parity Stop bit

Example of a display
Setting No. 1201 , Voltage measurement range setting.

Setting No.

Guidance (Based on a setting item.)

Present setting value

Please refer to the "7.4 Setting" about the details of the


contents of setting.

52
DMR-212-006

7.1.2 Protection setting value display


Check the setting value (Used/Unused, Operating value, Operating time, Reset time) of each protection factor.
In addition, a setting value cannot be changed by this display screen.
About the details of the setting method of a measurement factor, or the contents of setting, please refer to
"7.4.2 Protection factor setting".
Please refer to "" about the details of the setting method of a protection factor, or the contents of setting.

DMR-FN

Setting No.2101 Setting No.2102 (50) Setting No.2103 Setting No.2104


(50) Current operating (50) (50)
Used/Unused value Operating time Reset method

Setting No.2105 (50)


"ON" control within
protection detection display

Setting No.2201 Setting No.2202 Setting No.2203 (51) Setting No.2204


(51) (51) Current operating (51)
Used/Unused Characteristic value Time multiplier

Setting No.2206 (51) Setting No.2205


"ON" control within (51)
protection detection display Reset method

Setting No.2301 Setting No.2302 (67) Setting No.2303 (67) Setting No.2304
(67) Current operating Voltage operating (67)
Used/Unused value value Operating angle

Setting No.2307 (67) Setting No.2306 Setting No.2305


Zero phase current (67) (67)
input correction Reset method Operating time

Setting No.2308 (67)


"ON" control within
protection detection display

Setting No.2402
Setting No.2401
External trip
External trip (DI5)
"ON" control within
Used/Unused protection detection display

Setting No.2501
Reset time

Setting No.2601
Zero phase monitor ON/OFF

53
DMR-212-006

DMR-GN

Setting No.2101 Setting No.2102 (50) Setting No.2103 Setting No.2104


(50) Current operating (50) (50)
Used/Unused value Operating time Reset method

Setting No.2105 (50)


"ON" control within
protection detection display

Setting No.2201 Setting No.2202 Setting No.2203 (51) Setting No.2204


(51) (51) Current operating (51)
Used/Unused Characteristic value Time multiplier

Setting No.2206 (51) Setting No.2205


"ON" control within (51)
protection detection display Reset method

Setting No.2301 Setting No.2302 (51G) Setting No.2303 Setting No.2304 (51G)
(51G) Current operating (51G) 2nd harmonic
Used/Unused value Operating time suppression

Setting No.2306 (51G) Setting No.2305


"ON" control within (51G)
protection detection display Reset method

Setting No.2402
Setting No.2401
External trip
External trip (DI5)
"ON" control within
Used/Unused protection detection display

Setting No.2501
Reset time

Setting No.2601
Zero phase monitor ON/OFF

54
DMR-212-006

DMR-BN

Setting No.2101 Setting No.2102 (27) Setting No.2103 Setting No.2104


(27) Voltage operating (27) (27)
Used/Unused value Operating time Reset method

Setting No.2105 (27)


"ON" control within
protection detection display

Setting No.2201 Setting No.2202 (59) Setting No.2203 Setting No.2204


(59) Voltage operating (59) (59)
Used/Unused value Operating time Reset method

Setting No.2205 (59)


"ON" control within
protection detection display

Setting No.2301 Setting No.2302 (64) Setting No.2303 Setting No.2304


(64) Voltage operating (64) (64)
Used/Unused value Operating time Reset method

Setting No.2305 (64)


"ON" control within
protection detection display

Setting No.2402
Setting No.2401
External trip
External trip (DI5)
"ON" control within
Used/Unused protection detection display

Setting No.2501
Reset time

Setting No.2601
Zero phase monitor ON/OFF

55
DMR-212-006

DMR-SN

Setting No.2101 Setting No.2102 (50) Setting No.2103 Setting No.2104


(50) Current operating (50) (50)
Used/Unused value Operating time Reset method

Setting No.2105 (50)


"ON" control within
protection detection display

Setting No.2201 Setting No.2202 Setting No.2203 (51) Setting No.2204


(51) (51) Current operating (51)
Used/Unused Characteristic value Time multiplier

Setting No.2206 (51) Setting No.2205


"ON" control within (51)
protection detection display Reset method

Setting No.2301 Setting No.2302 (27) Setting No.2303 Setting No.2304


(27) Voltage operating (27) (27)
Used/Unused value Operating time Reset method

Setting No.2305 (27)


"ON" control within
protection detection display

Setting No.2402
Setting No.2401
External trip
External trip (DI5)
"ON" control within
Used/Unused protection detection display

Setting No.2501
Reset time

Setting No.2601
Zero phase monitor ON/OFF

Example of a display
DMR-FN,GN,SN Setting No. 2101 In case of instantaneous overcurrent relay (50) used / unused setting.

Setting No.

Protection relay factor

Present setting value

Please refer to the "7.4 Setting" about the details of the contents of setting.

56
DMR-212-006

7.1.3 Protection detection history display 【All models】


Display the protection detection value at the time of the newest protection detection of each protection factor.

MODE

MODE MODE MODE MODE

Measurement Protection Protection detection


Error code
setting value setting value history display
display
display display
Protection relay 1

Measurement
display
Protection relay 2
(Usual display)

MEASURING or Protection relay 3


switch non-operation for 10 minutes

● Protection relay n
Protection factor
Display factor Contents of display
50 51 51G 67 27 59 64
Main monitor Display an instrument number. 「50」 「51」 「51G」 「67」 「27」 「59」 「64」
Sub-monitor Display the value at the time of
A(L1) A(L1) - A0 - - -
(Left) protection detection.
Sub-monitor Display the value at the time of A(L2) A(L2)
- V0 - - -
(Center) protection detection. (41) (41)
Sub-monitor Display the value at the time of V V
A(L3) A(L3) Ao θ VO
(Right) protection detection. (L3L1) (L3L1)
Display "RECORD" on an upside.
Other
In addition to a LCD, "RECORD" LED is lighting.
Note(41) In the case of DMR-FN, DMR-GN, don't display L2 phase. It becomes a blank display.

Example of display ● Clear of history


While displaying a protection factor to clear, if a MAX/MIN RESET
switch is pushed 3 seconds or more, a protection detection value is
cleared.
An error history is not cleared even if it performs this history
clear operation.
Please refer to "7.1.4 Error code display" about the clear of an
error history.

57
DMR-212-006

7.1.4 Error code display 【All models】


Check the fail-safe error occurred with this product.

MODE

MODE MODE MODE MODE


Protection Error code display
Measurement Protection
detection
setting value setting value Error code
history
display display (Latest)
display

Error code
(Last time)
Measurement
display
(Usual display)

MEASURING or switch non-operation for 10 minutes

Error code
(Past 20 times)

● Error code
Example of display Display factor Contents of display
Display an error code. Please refer to "8.1.1 Fail-safe
Main monitor
function" about an error code.
Sub-monitor
Display "Err".
(Left)
Sub-monitor
Display "CodE".
(Center)
Sub-monitor Display an error code history number.
(Right) (The latest is “- 1”, then, display “-2” to “-20”.)

Other In addition to a LCD, "ERROR CODE" LED is lighting.

● Clear of history
While displaying a error to clear, if a MAX/MIN RESET switch is pushed 3 seconds or more, a protection
detection value is cleared.
An error history is not cleared even if it performs this history clear operation.
Please refer to "7.1.3 Protection detection history display" about the clear of an error history.

58
DMR-212-006

7.2 Measurement factor display change


The display change of measurement factor, and change of phase (line), and change an expansion display of electric
energy. (By measurement display.)
And, it returns from any display to a measurement display by MEASURING switch operation (or switch non-operation
for 10 minutes).

7.2.1 Main monitor measurement display factor change 【All models】


The measurement factor of the main monitor can be changed with a ▲ ▼ switch. (42)

Maximum current Maximum voltage


Current (L1) Power var-hour
(L3) (L2L3)

Maximum voltage Zero phase


Current (L2) Voltage (L1L2) Reactive power
(L3L1) current

Minimum voltage Maximum zero


Current (L3) Voltage (L2L3) Power factor
(L1L2) phase current

Maximum current Minimum voltage Zero phase


Voltage (L3L1) Frequency
(L1) (L2L3) voltage

Maximum current Maximum voltage Minimum voltage Maximum zero


Watt-hour
(L2) (L1L2) (L3L1) phase voltage

Note(42) It is based on the measurement factor of each model. The factor which is doing setting OFF by display
ON/OFF setting cannot perform the change of a measurement display.
Please refer to "7.1.1 Measurement setting value display (Display ON/OFF)" for the check method
of a setting value.

7.2.2 Phase, line display change 【All models】


The phase and the display between lines of the main monitor and a sub-monitor (current, voltage) can be changed with
a switch during a measurement display.

L1 phase L2 phase L3 phase


(L1L2 line) (L2L3 line) (L3L1 line)

7.2.3 Integrated value expansion display change 【DMR-FN / DMR-GN / DMR-SN】


Change the usual display (integer 5 digits), and an expansion display (integer 2 digits + less than decimal point,
3 digits) for watt-hour and var-hour by turns with switch during a measurement display.
In addition, it is because the multiplying factor which can be indicated on LCD is to x0.1, in the case of
multiplying factor x0.01, an integrated value display will be the next.
・Usual display :Integer 4 digits + Less than decimal point, 1 digit.
・Expansion display:Integer 1 digit + Less than decimal point, 4 digits.

Usual display Expansion display

59
DMR-212-006

7.3 Measurement value reset 【All models】


7.3.1 Maximum value and minimum value reset
Reset the maximum voltage / minimum voltage, a maximum current, a maximum of zero phase current, and a maximum
zero phase voltage.
An applicable factor can reset by pushing a MAX./MIN. RESET switch for 3 seconds during the main monitor
display. And, communication data is also reset.
If a maximum zero phase voltage is reset by this operation, the analog output of a maximum zero phase voltage is
also reset.
MAX./MIN. RESET
Measurement Push 3 seconds
Reset
value

7.3.2 Integrated value reset


Reset the integrated value of Watt-hour and var-hour.
Push a MAX./MIN. RESET + ▲ + ▼ switch for 3 seconds, and reset it. (This operation is valid even if the
applicable factor does not indicate) And, communication data is also reset.
MAX./MIN. RESET + +
Integrated Push 3 seconds
Reset
value

60
DMR-212-006

7.4 Setting
This product possesses various setting items to measurement or a protection function. If this operation and the contents
of setting are mistaken, it will become the causality of the display contrary to actual operation, or a malfunction.
Please perform the setting of this product after having understood an operating procedure and contents enough.
And, because it becomes operation by the maker about setting, a user must not set.

7.4.1 Measurement factor setting


Perform the measurement factor and measurement range which are displayed on a LED, the output factor of analog
output and a pulse output, and setting of a communication output.
Come into setting by pushing a SETTING switch for 3 seconds.
Change of a setting value, an articles changes a setting value with ▼ ▲ switch, and update it with an
ENTER switch. And, it returns from any setting to a measurement display with a MEASURING switch.
The kind of each setting item changes by the model.
The setting item according to model, please refer to an "Appendix table 3) Setting item list (For model)”.

Measurement display (Usual display)

SETTING Push 3 seconds

ENTER
Sub-monitor Sub-monitor Sub-monitor
Display Main monitor Bar graph
Display item (left) (center) (right)
pattern display display
display display display
▲ SETTING


ENTER
Measurement Current Power Reactive power Power factor
Voltage range Power range
range range polarity range range

▲ SETTING
Zero phase Zero phase
Frequency
voltage output voltage rating
range
range (EVT)


ENTER
Display Maximum Maximum Minimum
Current Voltage Power
ON/OFF current voltage voltage

▲ SETTING

Reactive
var-hour Watt-hour Frequency Power factor
power

Zero phase Maximum zero Zero phase Maximum zero


current phase current voltage phase voltage


ENTER
Phase / line L1 L2 L3 L1L2 L2L3 L3L1
display ON/OFF phase current phase current phase current line voltage line voltage line voltage

SETTING


ENTER
Output 1 Output 2 Output 3 Output 4
Analog output
factor factor factor factor
SETTING

Intrinsic Intrinsic
sensitivity sensitivity
(Reactive power) (Power)

▼ Each display is skipped if there is


ENTER no corresponding option.
Pulse unit
Pulse output Output factor multiplying
factor
SETTING


ENTER
Communication Transmission
Address Parity Stop bit
output rate

SETTING

61
DMR-212-006

● Display item (Setting No. 1101 to 1106)


Set the factor which indicates by measurement in the main monitor, a sub-monitor (left, center, right), and bar
graph. Come into each setting display with an ENTER switch from a display item. It returns to a display
item with a SETTING switch.
・Item display
ENTER
Sub-monitor
Display Display Main monitor
(left)
item pattern display
display
SETTING

Sub-monitor Sub-monitor
Bar graph
(right) (center)
display
display display

(1) Display pattern 【No.1101 All models】


Select a display of the main monitor, a sub-monitor (left, center, right), and bar graph from the display combination
patterns which were able to be decided beforehand.
It is possible to select a display factor individually besides a display combination pattern.
In this case, pattern No. is 0.
Example of display Display factor Contents of display
Display the main monitor display factor. And, display the
Main monitor
display combination pattern number after change.
Sub-monitor Display the sub-monitor (left) display factor.
(Left) And display the setting number (1101).
Sub-monitor
Display the sub-monitor (center) display factor.
(Center)
Sub-monitor Display the sub-monitor (right) display factor. And,
(Right) display the present display combination pattern number.
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

・Display combination pattern


① DMR-FN, DMR-GN, DMR-SN.
Pattern Sub-monitor Sub-monitor Sub-monitor
Main monitor Bar graph
No. (Left) (Center) (Right)
1 Current (L2) Voltage (L1L2) Power Watt-hour Current (L2)
2 Current (L2) Voltage (L1L2) Power Power factor Current (L2)
3 Current (L2) Voltage (L1L2) Power Frequency Current (L2)
4 Power Voltage (L1L2) Current (L2) Watt-hour Power
5 Power Voltage (L1L2) Current (L2) Power factor Power
6 Power Voltage (L1L2) Current (L2) Frequency Power
7 Current (L2) Power factor Power Watt-hour Current (L2)
8 Current (L2) Reactive power Power Watt-hour Current (L2)
9 Power Power factor Reactive power Watt-hour Power
10 Current (L2) Current (L1) Current (L3) Watt-hour Current (L2)
Maximum zero phase
11 Current (L2) Voltage (L1L2) Power Current (L2)
voltage
Pattern No. 11:DMR-FN only

② DMR-BN
Pattern Sub-monitor Sub-monitor Sub-monitor
Main monitor Bar graph
No. (Left) (Center) (Right)
Maximum zero phase Zero phases
1 Voltage (L1L2) Frequency Voltage (L1L2)
voltage voltage
Maximum voltage Minimum voltage
2 Voltage (L1L2) Frequency Voltage (L1L2)
(L1L2) (L1L2)
Maximum voltage Minimum voltage Maximum zero phase
3 Voltage (L1L2) Voltage (L1L2)
(L1L2) (L1L2) voltage
4 Voltage (L1L2) Voltage (L2L3) Voltage (L3L1) Frequency Voltage (L1L2)
Maximum zero phase
5 Voltage (L1L2) Voltage (L2L3) Voltage (L3L1) Voltage (L1L2)
voltage

62
DMR-212-006

(2) Main monitor display 【No.1102 All models】


Example of display Display factor Contents of display
Display the main monitor display factor. And, display the
Main monitor
display factor number after change.
Sub-monitor
Display the setting number (1102).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present display factor number.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

・The display factor number according to model


Factor Display factor
No. DMR-FN DMR-GN DMR-BN DMR-SN
0 Nothing Nothing Nothing Nothing
1 Current (L1) Current (L1) Voltage (L1L2) Current (L1)
2 Current (L2) Current (L2) Voltage (L2L3) Current (L2)
3 Current (L3) Current (L3) Voltage (L3L1) Current (L3)
4 Maximum current (L1) Maximum current (L1) Maximum voltage (L1L2) Maximum current (L1)
5 Maximum current (L2) Maximum current (L2) Maximum voltage (L2L3) Maximum current (L2)
6 Maximum current (L3) Maximum current (L3) Maximum voltage (L3L1) Maximum current (L3)
7 Voltage (L1L2) Voltage (L1L2) Minimum voltage (L1L2) Voltage (L1L2)
8 Voltage (L2L3) Voltage (L2L3) Minimum voltage (L2L3) Voltage (L2L3)
9 Voltage (L3L1) Voltage (L3L1) Minimum voltage (L3L1) Voltage (L3L1)
10 Maximum voltage (L1L2) Maximum voltage (L1L2) Frequency Maximum voltage (L1L2)
11 Maximum voltage (L2L3) Maximum voltage (L2L3) Zero phase voltage Maximum voltage (L2L3)
Maximum zero phase
12 Maximum voltage (L3L1) Maximum voltage (L3L1) Maximum voltage (L3L1)
voltage
13 Minimum voltage (L1L2) Minimum voltage (L1L2) - Minimum voltage (L1L2)
14 Minimum voltage (L2L3) Minimum voltage (L2L3) - Minimum voltage (L2L3)
15 Minimum voltage (L3L1) Minimum voltage (L3L1) - Minimum voltage (L3L1)
16 Power Power - Power
17 Reactive power Reactive power - Reactive power
18 Power factor Power factor - Power factor
19 Frequency Frequency - Frequency
20 Watt-hour Watt-hour - Watt-hour
21 var-hour var-hour - var-hour
22 Zero phase current Zero phase current - -
Maximum zero phase Maximum zero phase
23 - -
current current
24 Zero phase voltage - - -
Maximum zero phase
25 - - -
voltage

(3) Sub-monitor (left) display 【No.1103 All models】


Example of display Display factor Contents of display

Main monitor Display the display factor number after change.

Sub-monitor Display the sub-monitor (left) display factor.


(Left) Display the setting number (1103).
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present display factor number.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

63
DMR-212-006

(4) Sub-monitor (center) display 【No.1104 All models】


Example of display Display factor Contents of display

Main monitor Display the display factor number after change.

Sub-monitor
Display the setting number (1104).
(Left)
Sub-monitor
Display the sub-monitor (center) display factor.
(Center)
Sub-monitor
Display the present display factor number.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(5) Sub-monitor (right) display 【No.1105 All models】


Example of display Display factor Contents of display

Main monitor Display the display factor number after change.

Sub-monitor
Display the setting number (1105).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor Display the sub-monitor (right) display factor.
(Right) Display the present display factor number.
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(6) Bar graph display 【No.1106 All models】


Example of display Display factor Contents of display

Main monitor Display the display factor number after change.

Sub-monitor Display the sub-monitor (left) display factor.


(Left) Display the setting number (1106).
Sub-monitor
Display the sub-monitor (center) display factor.
(Center)
Sub-monitor
Display the sub-monitor (right) display factor.
(Right)
Display "SETTING" on an upside.
If the factor which does bar graph display is a sub-monitor,
Other
display a bar on the corresponding monitor point.
In addition to a LCD, "SETTING" LED is lighting.

・The possible factor of display setting


Current / Maximum current (L1,L2,L3), Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1),
Main monitor Power, Reactive power, Power factor, Frequency, Watt-hour, var-hour,
Zero phase current / Maximum zero phase current, Zero phase voltage / Maximum zero phase voltage
Current / Maximum current (L1,L2,L3), Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1),
Sub-monitor
Power, Reactive power, Power factor, Zero phase current / Maximum zero phase current,
(Left)
Zero phase voltage / Maximum zero phase voltage
Current / Maximum current (L1,L2,L3), Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1),
Sub-monitor
Power, Reactive power, Frequency, var-hour,
(Center)
Zero phase current / Maximum zero phase current, Zero phase voltage / Maximum zero phase voltage
Current / Maximum current (L1,L2,L3), Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1),
Sub-monitor
Power, Power factor, Frequency, Watt-hour,
(Right)
Zero phase current / Maximum zero phase current, Zero phase voltage / Maximum zero phase voltage
Current / Maximum current (L1,L2,L3), Voltage / Maximum voltage / Minimum voltage (L1L2,L2L3,L3L1),
Bar graph Power, Reactive power, Power factor, Frequency,
Zero phase current / Maximum zero phase current, Zero phase voltage / Maximum zero phase voltage

64
DMR-212-006

● Measurement range (Setting No.1201 to 1207)


Perform the measurement range of each measurement factor, and setting of zero phase voltage rating.
Come into each setting display with an ENTER switch from a measurement range display. It returns to a display
range with a SETTING switch.
・Measurement range display
ENTER
Measurement Current Power
Voltage range Power range
range range polarity

SETTING

Reactive Power factor Frequency


power range range range

Zero phase voltage Zero phase voltage


output range rating (EVT)

(1) Voltage measurement range 【No.1201 All models】


Example of display Display factor Contents of display
Display the primary rated value (bar graph is scale value)
Main monitor
and “RANGE” after change.
Sub-monitor
Display the setting number (1201).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor Display the present primary rated value (bar graph is scale
(Right) value).
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(2) Current measurement range 【No.1202 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the primary rated value (bar graph is scale value)
Main monitor
and “RANGE” after change.
Sub-monitor
Display the setting number (1202).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor Display the present primary rated value (bar graph is
(Right) scale value).
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

・Voltage measurement range (VT ratio) ・Current measurement range (CT ratio)

150.0V(110V) 9000V (6600V/110V) 5.00A 30.0A 200.0A 1000 A 3000 A


150V (110V) 9.00kV (6.6kV/110V) 10.00A 40.0A 200 A 1.00kA 3.00kA
300.0V(220V/110V) 15.00kV (11kV/110V) 10.0 A 50.0A 250.0A 1200 A 4000 A
300V (220V/110V) 18.82kV (13.8kV/110V)(44) 12.00A 60.0A 250 A 1.20kA 4.00kA
600V (440V/110V) 30.0kV (22kV/110V) 12.0 A 75.0A 300.0A 1500 A 5000 A
627V (460V/110V) (43) 45.0kV (33kV/110V) 15.00A 80.0A 300 A 1.50kA 5.00kA
655V (480V/110V) (43) 90.0kV (66kV/110V) 15.0 A 100.0A 400 A 1600 A 6000 A
1500V (1100V/110V) 105.0kV (77kV/110V) (45) 20.00A 100 A 500 A 1.60kA 6.00kA
3000V (2200V/110V) 150.0kV (110kV/110V) 20.0 A 120.0A 600 A 2000 A 7500 A
3.00kV (2.2kV/110V) 180.0kV (132kV/110V) 25.00A 120 A 750 A 2.00kA 7.50kA
4500V (3300V/110V) 210.0kV (154kV/110V) 25.0 A 150.0A 800 A 2500 A 8000 A
4.50kV (3.3kV/110V) 30.00A 150 A 900 A 2.50kA 8.00kA

Note(43) Full-scale of bar graph is 600V.


Note(44) Full-scale of bar graph is 18.00kV.
Note(45) Full-scale of bar graph is 120.0kV.

65
DMR-212-006

(3) Power polarity 【No.1203 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the power polarity and “RANGE” after change.
Main monitor
(One-way deflection:P□□□□, Both deflections:-□□□□)
Sub-monitor
Display the setting number (1203).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present power polarity.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(4) Power measurement range 【No.1204 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the power measurement range and “RANGE” after
Main monitor
change.
Sub-monitor
Display the setting number (1204).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present power measurement range.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(5) Reactive power measurement range 【No.1205 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the reactive power measurement range and “RANGE”
Main monitor
after change.
Sub-monitor
Display the setting number (1205).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present reactive power measurement range.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

・The setting ranges of power and reactive power measurement.


Power and a reactive power measurement range are automatically decided in a voltage measurement range (VT ratio)
and a current measurement range (CT ratio).
However, if a rated power (VT ratio xCT ratio) is made into 100%, a measurement range can be selected from the
following values. (Power is 40 to 115% and reactive power is 30 to 115% of range.)
Power and reactive power range (×10n)
1.□ 1.0/1.2/1.4/1.5/1.6/1.8 Example) In case of VT ratio×CT ratio=1200kW
2.□ 2.0/2.4/2.5/2.8 ・40% of 1200kW is 480kW.
3.□ 3.0/3.2/3.6 ・115% of 1200kW is 1380kW.
4.□ 4.0/4.2/4.5/4.8 Than the above, a measurement range can be selected within
5.□ 5.0/5.6 the limits of 480 to 1380kW.
Therefore, from a left table, a measurement range can be
6.□ 6.0/6.4
selected from the following.
7.□ 7.2/7.5
480 / 500 / 560 / 600 / 640 / 720 / 750 / 800 / 840 / 900 /
8.□ 8.0/8.4
960 / 1000 / 1200kW
9.□ 9.0/9.6

66
DMR-212-006

(6) Power factor measurement range 【No.1206 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the power factor measurement range and “RANGE” after
Main monitor
change. (LEAD0-1-LAG0:0.000、LEAD0.5-1-LAG0.5:0.500)
Sub-monitor
Display the setting number (1206).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present power factor measurement range.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(7) Frequency measurement range 【No.1207 DMR-FN, DMR-GN, DMR-SN , No.1202 DMR-BN】
Example of display Display factor Contents of display
Display the frequency measurement range and “RANGE” after
Main monitor
change. (45…55Hz:50.0, 55…65Hz:60.0)
Sub-monitor Display the setting number.
(Left) (DMR-FN, DMR-GN, DMR-SN:1207 , DMR-BN:1202)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present frequency measurement range.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

・Power factor measurement range ・Frequency measurement range


LEAD 0…1…LAG 0 50Hz(45…55Hz)

LEAD 0.5…1…LAG 0.5 60Hz(55…65Hz)

(8) Zero phase voltage rating (EVT) 【No.1208 DMR-FN、No.1203 DMR-BN EVT specification】 (46)
Example of display Display factor Contents of display
Display the zero phase voltage rating and “ZERO PHASE”
Main monitor
after change.
Sub-monitor Display the setting number.
(Left) (DMR-FN:1208, DMR-BN:1203)
Sub-monitor
Display the "rAt".
(Center)
Sub-monitor
Display the present zero phase voltage and “ZERO PHASE”.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
Note(46) Only EVT specification has setting of zero phase voltage rating.
In the case of ZPD specification, this setting is skipped.

67
DMR-212-006

(9) Zero phase voltage output range 【No.1209 DMR-FN (With communication output),
No.1204 DMR-BN (With analog output or communication output)】(47)
Example of display Display factor Contents of display
Display the zero phase voltage output range and "RANGE"
Main monitor
“ZERO PHASE” after change.
Sub-monitor Display the setting number.
(Left) (DMR-FN:1209, DMR-BN:1204)
Sub-monitor
Display the "FuLL".
(Center)
Sub-monitor Display the present zero phase voltage output range and
(Right) “ZERO PHASE”.
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
Note(47) The analog output and communication output of zero phase voltage measurement display the setting
value of an output range.
This setting is skipped if there is no option of relevance from each model.

・Zero phase voltage output range


Zero phase voltage output range Zero phase voltage rating Analog output measurement range
110V AC0…132V/DC4…23.2mA
EVT
6600V 190V AC0…228V/DC4…23.2mA
ZPD 1V AC0…1.2V/DC4…23.2mA
110V AC0…132V/DC4…18.08mA
EVT
9000V 190V AC0…228V/DC4…18.08mA
ZPD 1V AC0…1.2V/DC4…18.08mA

68
DMR-212-006

● Display ON/OFF (Setting No. 1301 to 1315)


Set a measurement display (display measurement or do not display measurement) to each measurement factor. (48)
If it is made setting which does not indicate by measurement (OFF), an applicable factor is skipped at the time
of measurement display change operation. Therefore, it can avoid displaying an unnecessary measurement factor.
Come into each setting display with an ENTER switch from a display ON/OFF. It returns to a display ON/OFF with
a SETTING switch.

ENTER
Display Maximum Maximum Minimum
Current Voltage
ON/OFF current voltage voltage

SETTING

Reactive
Frequency Power factor Power
power

Zero phase Maximum zero


Watt-hour var-hour
current phase current

Maximum zero Zero phase


phase voltage voltage

・Display ON/OFF

(1) "Measurement factor" display ON/OFF 【No.1301 to 1315 All models】


Example of display Display factor Contents of display
Display an applicable factor. And display the setting after
Main monitor
the change. (Display ON:on, Display OFF:oFF)
Sub-monitor
Display the setting number (13□ □ ).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present setting.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
Note(48) It is based on the measurement factor of each model.
This setting is only display ON/OFF. Perform internal measurement and an output (analog output,
pulse output, communication output) regardless of this setting.

69
DMR-212-006

● Phase / line display ON/OFF (Setting No. 1401 to 1406)


Set the phase (or line) measurement display ON/OFF (display or do not display) of a current (voltage) measurement
factor.
If it sets to the measurement display OFF and a phase / line display change operation is performed, the corresponding
phase (or line) is skipped. Therefore, it can avoid displaying an unnecessary measurement phase (or line).
Come into each setting display with an ENTER switch from a phase / line display ON/OFF. It returns to a phase
/ line display ON/OFF with a SETTING switch.
If it uses this product by single phase load, recommend this setting item.

ENTER
Phase / line L1 L2 L3 L1L2
display ON/OFF phase current phase current phase current line voltage

SETTING

L3L1 L2L3
line voltage line voltage

・Phase / line display ON/OFF

(1) Phase display ON/OFF 【No.1401 to 1403 DMR-FN, DMR-GN, DMR-SN】 (49)
Example of display Display factor Contents of display
Display an applicable phase. And display the setting after
Main monitor
the change.
Sub-monitor
Display the setting number (14□ □ ).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present setting.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(2) Line display ON/OFF 【No.1404 to 1406:DMR-FN, DMR-GN, DMR-SN,No.1401 to 1403:DMR-BN】 (49)
Example of display Display factor Contents of display
Display an applicable line. And display the setting after
Main monitor
the change.
Sub-monitor
Display the setting number (14□ □ ).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present setting.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
Note(49) This setting is only display ON/OFF. Perform internal measurement and an output (analog output)
regardless of this setting. And, the factor of setting OFF is not displayed as a protection detection
history.

70
DMR-212-006

● Analog output (Setting No. 1501 to 1506)


Set the output factor and output sensitivity (sensitivity of the output to an input) of each analog output.
Come into each setting display with an ENTER switch from a analog output display. It returns to a analog output
display with a SETTING switch.
ENTER
Output 1 Output 2 Output 3 Output 4
Analog output
factor factor factor factor

SETTING

Intrinsic sensitivity Intrinsic sensitivity


(Reactive power) (Power)

・Analog output display.

(1) Output n factor 【No.1501 to 1504 (50) All models, With a analog output.】
Example of display Display factor Contents of display
Display the output factor and output factor number after
Main monitor
change.
Sub-monitor
Display the setting number (1501 to 1504). (50)
(Left)
Sub-monitor Display an output point. (50)
(Center) (Output 1:Ao.1 to output 4:Ao.4)
Sub-monitor
Display the present output factor.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.
Note(50) DMR-BN becomes to outputs 1 to 3 (setting No.1501 to 1503, output point:Ao.1 to Ao.3).

・The output factor number according to model (Analog output) (51)


Output factor
Factor No.
DMR-FN, DMR-GN DMR-BN DMR-SN
- OFF OFF OFF
1 Current (L1) Voltage (L1L2) Current (L1)
2 Current (L2) Voltage (L2L3) Current (L2)
3 Current (L3) Voltage (L3L1) Current (L3)
4 Voltage (L1L2) Frequency Voltage (L1L2)
5 Voltage (L2L3) Maximum zero phase voltage Voltage (L2L3)
6 Voltage (L3L1) - Voltage (L3L1)
7 Power - Power
8 Reactive power - Reactive power
9 Power factor - Power factor
10 Frequency - Frequency
An output is 4mA when it sets at OFF.
Note(51) Display factor number, output factor number (analog output), and output factor number (pulse output),
a factor is respectively different.

71
DMR-212-006

(2) Intrinsic sensitivity (power) 【No.1505 DMR-FN, DMR-GN, DMR-SN, With a analog output.】
It is the analog output of power and reactive power, set the output sensitivity (% of the output to an input)
by % to the input range.
Setting range, Power:40.0 to 115.0% (0.1% steps)
Reactive power:30.0 to 115.0% (0.1% steps)
Example) In the case of voltage measurement range:9000V(6600V/110V) and current measurement range:100A/5A.
Rated power = 1000W×(6600V/110V)×(100A/5A)=1200kW
In the case of 100% settings, 0…1200kW/0…1000W/DC4…20mA
In the case of 83.3% settings, 0…1000kW/0…833.3W/DC4…20mA

Example of display Display factor Contents of display

Main monitor Display the output sensitivity after change.

Sub-monitor
Display the setting number (1505).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present output sensitivity.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(3) Intrinsic sensitivity (reactive power) 【No.1506 DMR-FN, DMR-GN, DMR-SN, With analog output.】
Example of display Display factor Contents of display

Main monitor Display the output sensitivity after change.

Sub-monitor
Display the setting number (1506).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present output sensitivity.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

72
DMR-212-006

● Pulse output (Setting No. 1601 to 1602)


Set the pulse output factor and a pulse unit.
Come into each setting display with an ENTER switch from a pulse output display. It returns to a pulse output
display with a SETTING switch.

ENTER
Pulse output Output factor Pulse unit

SETTING

・Pulse output display

(1) Output factor 【No.1601 DMR-FN, DMR-GN, DMR-SN, With analog output.】
Example of display Display factor Contents of display
Display the output factor and output factor number after
Main monitor
change.
Sub-monitor
Display the setting number (1601).
(Left)
Sub-monitor
Display the "Po".
(Center)
Sub-monitor
Display the present output factor.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

・Output factor number (Pulse output) (52)


Factor No. Factor
- OFF
1 Watt-hour
2 var-hour

Note(52) Display factor number, output factor number (analog output), and output factor number (pulse output),
a factor is respectively different.

(2) Pulse unit 【No.1602 DMR-FN, DMR-GN, DMR-SN, With pulse output.】
Example of display Display factor Contents of display

Main monitor Display the pulse unit after change.

Sub-monitor
Display the setting number (1602).
(Left)
Sub-monitor
Display the "PuLSE".
(Center)
Sub-monitor
Display the present pulse unit.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

About the setting range, please refer to "3.5 Option specification".

73
DMR-212-006

● Communication output (Setting No. 1701 to 1704)


Sets the address, transmission rate, parity, and stop bit, of communication output.
Come into each setting display with an ENTER switch from a communication output display.
It returns to a Communication output display with a SETTING switch.
The displayed setting item varies according to communication specifications.

ENTER
Communication Transmission
Address Parity Stop bit
output rate

SETTING

・Communication output display

(1) Address 【No.1701 All models, All with the communication output.】
Example of display Display factor Contents of display

Main monitor Display the address after change.

Sub-monitor
Display the setting number (1701).
(Left)
Sub-monitor
Display the "Adr".
(Center)
Sub-monitor
Display the present address.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

・Address range
Modbus 1 to 247

(2) Transmission rate 【No.1702 All models, All with the communication output.】
Example of display Display factor Contents of display

Main monitor Display the transmission rate after change.

Sub-monitor
Display the setting number (1702).
(Left)
Sub-monitor
Display the "bPS".
(Center)
Sub-monitor
Display the present transmission rate.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

・Transmission rate
Modbus 4800bps,9600bps,19200bps,38400bps

74
DMR-212-006

(3) Parity 【No.1703 All models, All with the communication output.】
Example of display Display factor Contents of display

Main monitor Display the parity bit after change.

Sub-monitor
Display the setting number (1703).
(Left)
Sub-monitor
Display the "PAr".
(Center)
Sub-monitor
Display the present parity bit.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

・Parity
E Even parity
o Odd parity
- With no parity

(4) Stop bit 【No.1704 All models, All with the communication output.】
Example of display Display factor Contents of display

Main monitor Display the stop bit after change.

Sub-monitor
Display the setting number (1704).
(Left)
Sub-monitor
Display the "StoP .b".
(Center)
Sub-monitor
Display the present stop bit.
(Right)
Display "SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

・Stop bit
1 1 bit
2 2 bits

75
DMR-212-006

7.4.2 Protection factor setting


Set the each protection factor (used/unused, operating value, operating time, reset time).
Come into setting by pushing a SETTING and STM/RTM switch for 3 seconds.
Change of a setting value, an articles changes a setting value with ▼ ▲ switch, and update it with an
ENTER switch. And, it returns from any setting to a measurement display with a MEASURING switch.
The protection factor changes by the model.
The setting item according to model, please refer to an "Appendix table 3) Setting item list (For model)”.

Measurement display (Usual display)

SETTING STM/RTM
Push 3 seconds
ENTER
Protection Current "ON" control
Operating
relay 1 Used / Unused operating Reset method within protection
time
(50) value detection display
SETTING

Protection ENTER Current


Used / Unused Characteristic Time
relay 2 operating Reset method
multiplier
(51) value
SETTING
▲ "ON" control
within protection
▼ detection display

Protection ENTER Current Voltage


Operating Operating
relay 3 Used / Unused operating operating angle time
(67) value value

SETTING
▲ "ON" control Zero phase
within protection current input Reset method
▼ detection display correction

ENTER "ON" control


External trip Used / Unused within protection
detection display
▲ SETTING

ENTER In case of protection factor (27, 59, 64)
Reset time Reset time ▲

SETTING
▲ Protection ENTER Voltage
▼ Operating
relay n Used / Unused operating
ENTER time
Zero phase (27,59,64) value
Zero phase
monitoring
monitoring SETTING
ON/OFF ▲
▼ "ON" control
▲ SETTING within protection Reset method
▼ detection display

In case of protection factor (51G)



Protection ENTER Current


Operating
relay 3 Used / Unused operating
time
(51G) value

▲ SETTING
▼ 2nd harmonic
Reset method
suppression

"ON" control
within protection
detection display

76
DMR-212-006

● Protection relay (50) (Setting No. 2101 to 2105)


Set the protection factor (used/unused, operating value, operating time, reset method, "ON" control within
protection detection display) of an instantaneous overcurrent relay (50).
Come into each setting display with an ENTER switch from a protection relay (50) display.
It returns to a protection relay (50) display with a SETTING switch.

ENTER
Protection Current "ON" control
Operating
relay Used / Unused operating Reset method within protection
time
(50) value detection display
SETTING

・Protection relay (50) display

(1) Used / Unused 【No.2101 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the setting value after change.
Main monitor
(Used:on ,Unused:oFF)
Sub-monitor
Display the setting number (2101).
(Left)
Sub-monitor
Display the "rY.50".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(2) Current operating value 【No.2102 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the current operating value and “OPERATE VALUE”
Main monitor
after change.
Sub-monitor
Display the setting number (2102).
(Left)
Sub-monitor
Display the "rY.50".
(Center)
Sub-monitor
Display the present current operating value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

77
DMR-212-006

(3) Operating time 【No.2103 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the operating time and “OPERATE TIME” after change.
Main monitor (Instant (40ms or less):0.04s,Definite time (0.1…1.0s):
0.1…1.0s)
Sub-monitor
Display the setting number (2103).
(Left)
Sub-monitor
Display the "rY.50".
(Center)
Sub-monitor
Display the present operating time.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(4) Reset method 【No.2104 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the setting value and “RESET” after change.
Main monitor
(Automatic reset:Auto ,Hold:HoLd)
Sub-monitor
Display the setting number (2104).
(Left)
Sub-monitor
Display the "rY.50".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(5) "ON" control within protection detection display 【No.2105 DMR-FN, DMR-GN, DMR-SN】
Example of display Display factor Contents of display
Display the setting value after change.
Main monitor ("ON" control within protection detection display
Permission:Cb-E, Prohibition:Cb-d)
Sub-monitor
Display the setting number (2105).
(Left)
Sub-monitor
Display the "rY.50".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

78
DMR-212-006

● Protection relay (51) (Setting No. 2201 to 2206)


Set the protection factor (used/unused, characteristic, operating value, Time multiplier, reset method,
"ON" control within protection detection display) of an overcurrent relay (51).
Come into each setting display with an ENTER switch from a protection relay (51) display.
It returns to a protection relay (51) display with a SETTING switch.

Protection ENTER
Current
relay Used / Unused Characteristic Time multiplier
operating value
(51)
SETTING
"ON" control
within protection Reset method
detection display

・Protection relay (51) display

(1) Used / Unused 【No.2201 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the setting number after change.
Main monitor
(Used:on ,Unused:oFF)
Sub-monitor
Display the setting number (2201).
(Left)
Sub-monitor
Display the "rY.51".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(2) Characteristic 【No.2202 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the characteristic and “CHARACTERISTIC” after
change.
Main monitor
(Standard inverse time:SI,Very inverse time:VI,Long inverse
time:LI,Extremely inverse time:EI,Definite time:dt)
Sub-monitor
Display the setting number (2202).
(Left)
Sub-monitor
Display the "rY.51".
(Center)
Sub-monitor
Display the present characteristic.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

79
DMR-212-006

(3) Current operating value 【No.2203 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the current operating value and “OPERATE VALUE”
Main monitor
after change.
Sub-monitor
Display the setting number (2203).
(Left)
Sub-monitor
Display the "rY.51".
(Center)
Sub-monitor
Display the present current operating value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(4) Time multiplier 【No.2204 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the time multiplier and “TIME MULTIPLIER” after
Main monitor
change.
Sub-monitor
Display the setting number (2204).
(Left)
Sub-monitor
Display the "rY.51".
(Center)
Sub-monitor
Display the present time multiplier.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(5) Reset method 【No.2205 DMR-FN, DMR-GN, DMR-SN】


Example of display Display factor Contents of display
Display the setting value and “RESET” after change.
Main monitor
(Automatic reset:Auto ,Hold:HoLd)
Sub-monitor
Display the setting number (2205).
(Left)
Sub-monitor
Display the "rY.51".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(6) "ON" control within protection detection display 【No.2206 DMR-FN, DMR-GN, DMR-SN】
Example of display Display factor Contents of display
Display the setting value after change.
Main monitor ("ON" control within protection detection display
Permission:Cb-E, Prohibition:Cb-d)
Sub-monitor
Display the setting number (2206).
(Left)
Sub-monitor
Display the "rY.51".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

80
DMR-212-006

● Protection relay (67) (Setting No. 2301 to 2308)


Set the protection factor (used/unused, operating value, operating time, reset method, correction of zero phase
current input, "ON" control within protection detection display) of an directional earth-fault relay (67).
Come into each setting display with an ENTER switch from a protection relay (67) display.
It returns to a protection relay (67) display with a SETTING switch.

Protection ENTER Current Voltage


Operating angle Operating
relay Used / Unused operating operating
time
(67) value value

SETTING
"ON" control Zero phase
within protection current input Reset method
detection display correction

・Protection relay (67) display

(1) Used / Unused 【No.2301 DMR-FN】


Example of display Display factor Contents of display
Display the setting number after change.
Main monitor
(Used:on ,Unused:oFF , Tripping prohibition:tr.oFF)
Sub-monitor
Display the setting number (2301).
(Left)
Sub-monitor
Display the "rY.67".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(2) Current operating value 【No.2302 DMR-FN】


Example of display Display factor Contents of display
Display the current operating value and “OPERATE VALUE”
Main monitor
after change.
Sub-monitor
Display the setting number (2302).
(Left)
Sub-monitor
Display the "rY.67".
(Center)
Sub-monitor
Display the present current operating value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

81
DMR-212-006

(3) Voltage operating value 【No.2303 DMR-FN】


Example of display Display factor Contents of display
Display the voltage operating value and “OPERATE VALUE”
Main monitor
after change.
Sub-monitor
Display the setting number (2303).
(Left)
Sub-monitor
Display the "rY.67".
(Center)
Sub-monitor
Display the present voltage operating value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(4) Operating angle 【No.2304 DMR-FN】


Example of display Display factor Contents of display
Display the operating angle and “OPERATE ANGLE” after
Main monitor change. And, in the case of a leading phase (except
for 0°) setting value, display .
Sub-monitor
Display the setting number (2304).
(Left)
Sub-monitor
Display the "rY.67".
(Center)
Sub-monitor
Display the present operating angle.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(5) Operating time 【No.2305 DMR-FN】


Example of display Display factor Contents of display

Main monitor Display the operating time and “OPERATE TIME” after change.

Sub-monitor
Display the setting number (2305).
(Left)
Sub-monitor
Display the "rY.67".
(Center)
Sub-monitor
Display the present operating time.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(6) Reset method 【No.2306 DMR-FN】


Example of display Display factor Contents of display
Display the setting value and “RESET” after change.
Main monitor
(Automatic reset:Auto ,Hold:HoLd)
Sub-monitor
Display the setting number (2306).
(Left)
Sub-monitor
Display the "rY.67".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

82
DMR-212-006

(7) Zero phase current input correction 【No.2307 DMR-FN】


In combination with ZCT, input correction of a zero phase current input can be performed.
Please refer to "7.11 Zero phase current input correction" about the step of correction.
Example of display Display factor Contents of display
Display the zero phase current input correction value (%)
Main monitor
and “ZERO PHASE” after change.
Sub-monitor
Display the setting number (2307).
(Left)
Display the zero phase current input value and "ZERO PHASE"
Sub-monitor
which were corrected by the correction value (%) after
(Center)
change.
Sub-monitor Display the present zero phase current input correction value
(Right) (%) and “ZERO PHASE”.
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(8) "ON" control within protection detection display 【No.2308 DMR-FN】


Example of display Display factor Contents of display
Display the setting value after change.
Main monitor ("ON" control within protection detection display
Permission:Cb-E, Prohibition:Cb-d)
Sub-monitor
Display the setting number (2308).
(Left)
Sub-monitor
Display the "rY.67".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

83
DMR-212-006

● Protection relay (51G) (Setting No. 2301 to 2305)


Set the protection factor (used/unused, operating value, operating time, 2nd harmonic suppression, reset method,
"ON" control within protection detection display) of an earth-fault overcurrent relay (51G).
Come into each setting display with an ENTER switch from a protection relay (51G) display.
It returns to a protection relay (51G) display with a SETTING switch.

Protection ENTER
Current 2nd harmonic
relay Used / Unused Operating time
operating value suppression
(51)
SETTING
"ON" control
within protection Reset method
detection display

・Protection relay (51G) display

(1) Used / Unused 【No.2301 DMR-GN】


Example of display Display factor Contents of display
Display the setting number after change.
Main monitor
(Used:on ,Unused:oFF , Tripping prohibition:tr.oFF)
Sub-monitor
Display the setting number (2301).
(Left)
Sub-monitor
Display the "rY.51G".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(2) Current operating value 【No.2302 DMR-GN】


Example of display Display factor Contents of display
Display the current operating value and “OPERATE VALUE”
Main monitor
after change.
Sub-monitor
Display the setting number (2302).
(Left)
Sub-monitor
Display the "rY.51G".
(Center)
Sub-monitor
Display the present current operating value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

84
DMR-212-006

(3) Operating time 【No.2303 DMR-GN】


Example of display Display factor Contents of display

Main monitor Display the operating time and “OPERATE TIME” after change.

Sub-monitor
Display the setting number (2303).
(Left)
Sub-monitor
Display the "rY.51G".
(Center)
Sub-monitor
Display the present operating time.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(4) 2nd harmonic suppression 【No.2304 DMR-GN】


Example of display Display factor Contents of display
Display the setting value and “2nd” after change.
With no 2nd harmonic suppression:OFF
If the 2nd relative harmonic content is less than 10%,
Main monitor
operation:10%
If the 2nd relative harmonic content is less than 15%,
operation:15%
Sub-monitor
Display the setting number (2304).
(Left)
Sub-monitor
Display the "rY.51G".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(5) Reset method 【No.2305 DMR-GN】


Example of display Display factor Contents of display
Display the setting value and “RESET” after change.
Main monitor
(Automatic reset:Auto ,Hold:HoLd)
Sub-monitor
Display the setting number (2305).
(Left)
Sub-monitor
Display the "rY.51G".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(6) "ON" control within protection detection display 【No.2306 DMR-GN】


Example of display Display factor Contents of display
Display the setting value after change.
Main monitor ("ON" control within protection detection display
Permission:Cb-E, Prohibition:Cb-d)
Sub-monitor
Display the setting number (2306).
(Left)
Sub-monitor
Display the "rY.51G".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

85
DMR-212-006

● Protection relay (27) (Setting No. DMR-BN:2101 to 2105 / DMR-SN:2301 to 2305)


Set the protection factor (used/unused, operating value, operating time, reset method, "ON" control within
protection detection display) of an undervoltage relay (27).
Come into each setting display with an ENTER switch from a protection relay (27) display.
It returns to a protection relay (27) display with a SETTING switch.

ENTER
Protection Voltage "ON" control
Operating
relay Used / Unused operating Reset method within protection
time
(27) value detection display
SETTING

・Protection relay (27) display

(1) Used / Unused 【No.2101 DMR-BN / No.2301 DMR-SN】


Example of display Display factor Contents of display
Display the setting value after change.
Main monitor
(Used:on ,Unused:oFF , Tripping prohibition:tr.oFF)
Sub-monitor
Display the setting number (DMR-BN:2101, DMR-SN:2301).
(Left)
Sub-monitor
Display the "rY.27".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(2) Voltage operating value 【No.2102 DMR-BN / No.2302 DMR-SN】


Example of display Display factor Contents of display
Display the voltage operating value and “OPERATE VALUE”
Main monitor
after change.
Sub-monitor
Display the setting number (DMR-BN:2102, DMR-SN:2302).
(Left)
Sub-monitor
Display the "rY.27".
(Center)
Sub-monitor
Display the present voltage operating value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(3) Operating time 【No.2103 DMR-BN / No.2303 DMR-SN】


Example of display Display factor Contents of display

Main monitor Display the operating time and “OPERATE TIME” after change.

Sub-monitor
Display the setting number (DMR-BN:2103, DMR-SN:2303).
(Left)
Sub-monitor
Display the "rY.27".
(Center)
Sub-monitor
Display the present operating time.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

86
DMR-212-006

(4) Reset method 【No.2104 DMR-BN / No.2304 DMR-SN】


Example of display Display factor Contents of display
Display the setting value and “RESET” after change.
Main monitor
(Automatic reset:Auto ,Hold:HoLd)
Sub-monitor
Display the setting number (DMR-BN:2104, DMR-SN:2304).
(Left)
Sub-monitor
Display the "rY.27".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(5) "ON" control within protection detection display 【No.2105 DMR-BN / No.2305 DMR-SN】
Example of display Display factor Contents of display
Display the setting value after change.
Main monitor ("ON" control within protection detection display
Permission:Cb-E, Prohibition:Cb-d)
Sub-monitor
Display the setting number (DMR-BN:2105, DMR-SN:2305).
(Left)
Sub-monitor
Display the "rY.27".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

87
DMR-212-006

● Protection relay (59) (Setting No. 2201 to 2205)


Set the protection factor (used/unused, operating value, operating time, reset method, "ON" control within
protection detection display) of an overvoltage relay (59).
Come into each setting display with an ENTER switch from a protection relay (59) display.
It returns to a protection relay (59) display with a SETTING switch.

ENTER
Protection Voltage "ON" control
Operating
relay Used / Unused operating Reset method within protection
time
(59) value detection display
SETTING

・Protection relay (59) display

(1) Used / Unused 【No.2201 DMR-BN】


Example of display Display factor Contents of display
Display the setting value after change.
Main monitor
(Used:on ,Unused:oFF , Tripping prohibition:tr.oFF)
Sub-monitor
Display the setting number (2201).
(Left)
Sub-monitor
Display the "rY.59".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(2) Voltage operating value 【No.2202 DMR-BN】


Example of display Display factor Contents of display
Display the voltage operating value and “OPERATE VALUE”
Main monitor
after change.
Sub-monitor
Display the setting number (2202).
(Left)
Sub-monitor
Display the "rY.59".
(Center)
Sub-monitor
Display the present voltage operating value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(3) Operating time 【No.2203 DMR-BN】


Example of display Display factor Contents of display

Main monitor Display the operating time and “OPERATE TIME” after change.

Sub-monitor
Display the setting number (2203).
(Left)
Sub-monitor
Display the "rY.59".
(Center)
Sub-monitor
Display the present operating time.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

88
DMR-212-006

(4) Reset method 【No.2204 DMR-BN】


Example of display Display factor Contents of display
Display the setting value and “RESET” after change.
Main monitor
(Automatic reset:Auto ,Hold:HoLd)
Sub-monitor
Display the setting number (2204).
(Left)
Sub-monitor
Display the "rY.59".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(5) "ON" control within protection detection display 【No.2205 DMR-BN】


Example of display Display factor Contents of display
Display the setting value after change.
Main monitor ("ON" control within protection detection display
Permission:Cb-E, Prohibition:Cb-d)
Sub-monitor
Display the setting number (2205).
(Left)
Sub-monitor
Display the "rY.59".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

89
DMR-212-006

● Protection relay (64) (Setting No. 2301 to 2305)


Set the protection factor (used/unused, operating value, operating time, reset method, "ON" control within
protection detection display) of an earth-fault overvoltage relay (64).
Come into each setting display with an ENTER switch from a protection relay (64) display.
It returns to a protection relay (64) display with a SETTING switch.

ENTER
Protection Voltage "ON" control
Operating
relay Used / Unused operating Reset method within protection
time
(64) value detection display
SETTING

・Protection relay (64) display

(1) Used / Unused 【No.2301 DMR-BN】


Example of display Display factor Contents of display
Display the setting value after change.
Main monitor
(Used:on ,Unused:oFF , Tripping prohibition:tr.oFF)
Sub-monitor
Display the setting number (2301).
(Left)
Sub-monitor
Display the "rY.64".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(2) Voltage operating value 【No.2302 DMR-BN】


Example of display Display factor Contents of display
Display the voltage operating value and “OPERATE VALUE”
Main monitor
after change.
Sub-monitor
Display the setting number (2302).
(Left)
Sub-monitor
Display the "rY.64".
(Center)
Sub-monitor
Display the present voltage operating value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(3) Operating time 【No.2303 DMR-BN】


Example of display Display factor Contents of display

Main monitor Display the operating time and “OPERATE TIME” after change.

Sub-monitor
Display the setting number (2303).
(Left)
Sub-monitor
Display the "rY.64".
(Center)
Sub-monitor
Display the present operating time.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

90
DMR-212-006

(4) Reset method 【No.2304 DMR-BN】


Example of display Display factor Contents of display
Display the setting value and “RESET” after change.
Main monitor
(Automatic reset:Auto ,Hold:HoLd)
Sub-monitor
Display the setting number (2304).
(Left)
Sub-monitor
Display the "rY.64".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(5) "ON" control within protection detection display 【No.2305 DMR-BN】


Example of display Display factor Contents of display
Display the setting value after change.
Main monitor ("ON" control within protection detection display
Permission:Cb-E, Prohibition:Cb-d)
Sub-monitor
Display the setting number (2305).
(Left)
Sub-monitor
Display the "rY.64".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

91
DMR-212-006

● External trip (DI5) (Setting No. 2401 to 2402)


Set the external trip (DI5). (used/unused, "ON" control within protection detection display)
Come into each setting display with an ENTER switch from a external trip (DI5) display.
It returns to a external trip (DI5) display with a SETTING switch.

ENTER
"ON" control
External trip
Used / Unused within protection
(DI5)
detection display
SETTING

・External trip (DI5) display

(1) Used / Unused 【No.2401 All models】


Example of display Display factor Contents of display
Display the setting value and "EXT.TRIP" after change.
Main monitor
(Used:on ,Unused:oFF)
Sub-monitor
Display the setting number (2401).
(Left)
Sub-monitor
Display the "dI.5".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

(2) "ON" control within protection detection display 【No.2402 All models】
Example of display Display factor Contents of display
Display the setting value after change.
Main monitor ("ON" control within protection detection display
Permission:Cb-E, Prohibition:Cb-d)
Sub-monitor
Display the setting number (2402).
(Left)
Sub-monitor
Display the "dI.5".
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

92
DMR-212-006

● Reset time (Setting No.2501)


It is common to each protection factor, and set the reset time.
Come into each setting display with an ENTER switch from a reset time display.
It returns to a reset time display with a SETTING switch.

・Reset time display


ENTER
Reset time
Reset time
setting

SETTING

(1) Reset time setting 【No.2501 All models】


Example of display Display factor Contents of display

Main monitor Display the reset time and "RESET TIME" after change.

Sub-monitor
Display the setting number (2501).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present reset time.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

● Zero phase monitor (Setting No.2601)


Set an operation or non-operation of the zero phase monitor (voltage, current) in a fail-safe function.
Come into each setting display with an ENTER switch from a zero phase monitor display.
It returns to a zero phase monitor display with a SETTING switch.

・Zero phase monitor display


ENTER
Zero phase Zero phase
monitoring monitoring ON/OFF

SETTING

(1) Zero phase monitor ON/OFF 【No.2601 All models】


Example of display Display factor Contents of display

Main monitor Display the setting value after change.

Sub-monitor
Display the setting number (2601).
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor
Display the present setting value.
(Right)
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

93
DMR-212-006

7.5 LOCAL-REMOTE change 【All models】


Switching of LOCAL / REMOTE in ON / OFF control of a circuit breaker can be performed. (From a front switch)
Refer to "6. Control" for the details of control.
Please open a switch cover and operate a switch.

Switch position Status of equipment


ON / OFF control can be done in an
「REMOTE」
external input (DI, communication).
ON / OFF control can be performed with
「LOCAL」
a front switch.

In the case of "OFF" control priority specification,


regardless of the status of LOCAL-REMOTE, "OFF" control
is possible.

LOCAL REMOTE

7.6 ON/OFF control 【All models】


At the time of "LOCAL", ON / OFF control of a circuit breaker can be performed from a front switch.
However, in the case of "OFF" control priority specification, "OFF" control can be done regardless of the status of
LOCAL-REMOTE.
Refer to "6. Control" for the details of control.
Please open a switch cover and operate a switch.

Control Switch operation DO


It will become valid if a switch
Circuit
"ON" and "ON/OFF PERMISSION" 「CB-ON」
breaker
are pushed 100ms or more output ON
"ON"
simultaneously.
It will become valid if a switch
Circuit
"OFF" and "ON/OFF PERMISSION" 「CB-OFF」
breaker
are pushed 100ms or more output ON
「OFF」
simultaneously.

・Switch color
LOCAL REMOTE OFF:Green / Red (Designation)
ON / OFF permission:Gray
Circuit breaker Circuit breaker ON :Red / Green (Designation)
"OFF" "ON"

94
DMR-212-006

7.7 Test mode


Push a STM/RTM switch for 3 seconds and come into sequence test mode and relay test mode.

Measurement display (Usual display)

STM/RTM
Push 3 seconds ENTER
Sequence Protection Protection Protection
test mode relay 1 relay 2 relay 3
SETTING


ENTER
Relay Protection Protection Protection
test mode relay 1 relay 2 relay 3
SETTING

7.7.1 Sequence test mode (STM) 【All models】


Perform sequence test mode (STM).
Come into test display of each protection relay with an ENTER switch from a sequence test mode display.
It returns to a sequence test mode display with a SETTING switch.
While pushing the STM/RTM switch by the test display of each protection relay, each relay of "CB-trip" output
and "Fault n" turns on.
The change of the phase to detect with a ▲ ▼ switch is possible for instantaneous overcurrent [50] and
overcurrent [51].
About the details of the sequence test mode, please refer to "8.7 Sequence test mode".

50,51
ENTER (L1 phase)
Sequence test Protection Protection Protection
mode relay 1 relay 2 relay 3
SETTING

STM/RTM STM/RTM STM/RTM 50,51


(L2 phase)

Protection detection Protection detection Protection detection


The control output The control output The control output
and "fault 1" ON and "fault 2" ON and "fault 3" ON
50,51
in connection with in connection with in connection with
(L3 phase)
protection detection protection detection protection detection

・Sequence test mode display

Example of display Display factor Contents of display


Display the status of an output.
Main monitor
(Output on:on , Output off:oFF)
Sub-monitor
Display the "SEq".
(Left)
Sub-monitor
Display the "tESt".
(Center)
Sub-monitor
Display the corresponding protection factor.
(Right)
In addition to a LCD, "STM/RTM" LED is lighting, and "RUN"
Other
LED is flicker.

95
DMR-212-006

7.7.2 Relay test mode (RTM) 【All models】


Perform relay test mode (RTM).
Come into test display of each protection relay with an ENTER switch from a relay test mode display.
It returns to a relay test mode display with a SETTING switch.
When it changes to the test screen of each protection relay, it is possible of protection detection.
In this status, if an external input detects protection, the relay of a "test" turns on. (Don't turn on the
relay of "CB-trip" output and "Fault n".)
About the details of the sequence test mode, please refer to "8.8 Relay test mode".

ENTER
Protection Protection Protection
Relay test mode
relay 1 relay 2 relay 3
SETTING
Excess of a Excess of a Excess of a
setting value setting value setting value

Protection detection Protection detection Protection detection


DO "TEST" ON DO "TEST" ON DO "TEST" ON

・Relay test mode display

Example of display Display factor Contents of display


Display the status of a protection factor.
Main monitor
(Detection:on , Not detectable:oFF)
Sub-monitor
Display the "rY".
(Left)
Sub-monitor
Display the "tESt".
(Center)
Sub-monitor
Display the corresponding protection factor.
(Right)
In addition to a LCD, "STM/RTM" LED is lighting, and "RUN"
Other
LED is flicker.

96
DMR-212-006

7.7.3 Self check mode 【All models】


Come into self check mode by pushing a MODE switch and a STM/RTM switch for 3 seconds simultaneously.
Push an ENTER switch by each check display, and start a self check.
About the details of the self check mode, please refer to "8.9 Self check mode".

Measurement display (Usual display)

MODE + STM/RTM
Push 3 seconds
Analog output
/ communication Pulse output
ROM check RAM check LED check LCD check DI check
output check check

Automatic ENTER Automatic ENTER STM/RTM ENTER STM/RTM ENTER STM/RTM ENTER STM/RTM ENTER STM/RTM ENTER
reset reset
after a after a Operation.
check Operation Operation Operation Output ON
check Input state
All
Operation. Operation. All display display. 100% output
lights-out
GOOD/ERR GOOD/ERR
display. display.

All lighting Do not all


50% output
display

0% output

Example of display Display factor Contents of display

Main monitor Display the factor which checks.

Sub-monitor
Display the "SELF".
(Left)
Sub-monitor
Display the "tESt".
(Center)
Sub-monitor
Display the factor number (No.1 to 7) which checks.
(Right)

Other In addition to a LCD, "RUN" LED is flicker.

・Check factor number


Factor Main monitor Contents of
Factor Note
number display operation
Normal “Good”, Abnormal “Err”.
1 ROM 「ro」 ROM sum check
Display on the main monitor after check finishing.
Normal “Good”, Abnormal “Err”.
2 RAM 「rA」 RAM R/W check
Display on the main monitor after check finishing.
Lighting / Exclude RUN, ON, OFF, REMOTE, LOCAL.
3 LED 「LEd」
lights-out The LED backlight for LCD is included.
Lighting /
4 LCD 「LCd」 It has been lighted of the LED backlight for LCD.
lights-out
Display the status of an input on the main monitor in
With an input / number of five digits.
5 DI 「dI」
With no input 1 (With an input) / 0 (With no input)
(5th digit:DI5 to First digit:DI1)
Analog output / Selected value
An output value can be changed to 0%, 50%, and 100%
6 Communication 「Ao.SIo」 is outputted
(% for output span).
output without an input.
7 Pulse output 「PuLSE」 Contact ON It becomes as output ON during execution.

97
DMR-212-006

7.8 Version check 【All models】


Check the program version of this product.
Come into version display by pushing a MODE switch and a MEASURING switch for 3 seconds simultaneously.
Push an MEASURING switch by measurement display.
It returns to a measurement display with a MEASURING switch.

MODE MEASURING
Measurement Push 3 seconds
Version display
display

Example of display Display factor Contents of display

Main monitor Display the program number (4 digits).

Sub-monitor
Display the “ro.n”.
(Left)
Sub-monitor
Don't display.
(Center)
Sub-monitor Display the model.
(Right) (Models DMR-FN:Fn, DMR-GN:Gn, DMR-BN:bn, DMR-SN:Sn)

Other -

98
DMR-212-006

7.9 Reset operation at the case of protection detection 【All models】


If protection detection is done, it changes from a measurement display to a protection detection display automatically.
Example of display Display factor Contents of display
Display the instrument number of the detected protection
Main monitor
factor.
Sub-monitor Display the value at the time of protection detection.
(Left) (53)
Sub-monitor Display the value at the time of protection detection.
(Center) (By protection factor) (53)
Sub-monitor Display the value at the time of protection detection.
(Right) (By protection factor) (53)

Other Display "FAULT" on an upside.

Note(53) Display the maximum value within the operating time.


In addition, a detection value is not displayed if the factor of OFF does protection detection by the
phase / line display ON/OFF setting.
Example) If a display of L1 phase current is set at OFF (DMR-FN)
Even if an instantaneous overcurrent is detected with L1 phase, the value of L1 phase at the
time of detection is not displayed, but become as blank display. (The sub-monitor (left) of
the above figure becomes a blank display.)

(1) Operation within protection detection.


① From this display, only switching to the measurement display by the MEASURING switch is possible.
And, if this operation is performed, it cannot return to a protection detection display.
Please perform the check of a detection value by protection detection history display.
Operation to a protection detection history display, please refer to "7.1.3 Protection detection history display".
② After changing to a measurement display by operation of above (1), it is possible of other operations.
(Exclude test mode (STM/RTM) and self check mode)
③ As for protection detection status, any display is hold. And, display "FAULT" on a LCD.

(2) Operation after a protection detection reset.


① This display is holding even if protection detection returns.

② From this display, push the RESET switch for one second and can change it to measurement display.
And, operation of the above (1) can also be switched to a measurement display.
Protection detection status returns by RESET switch operation. And, "FAULT" of a LED disappears.
However, because protection detection status has hold when it was operation of the above (1), "FAULT" of a
LCD does not disappear. In this case, please reset protection detection status with a RESET switch.

③ A protection detection display is hold even if it resets a power supply. In addition, about a measurement display
(protection detection status : "FAULT" of a LCD continues being lighting), it returns to a protection detection
screen by power supply reset.
④ The LED display and DO output after a protection detection reset, operation changes with settings of each
protection factor.
About each operation, please refer to "6.2.2 Control by protection detection".

Protection detection
Other, switch
Protection display
operation
detection
During the Other displays
detection
Other, switch
Measurement Protection
RESET operation
display detection
・Test mode (STM/RTM)
(Usual Push 1 reset MEASURING Measurement display ・Self check mode
display) second Holds of (Protection
detection detection status)
Setting (measurement,
※ It returns to a
※ Even power supply protection)
RESET protection detection
reset, holds a display. Push 1 second display by power supply
reset. Other than those
above

99
DMR-212-006

7.10 Reset operation at the case of fail-safe error occurrence 【All models】
From fail-safe error occurrence to after 15-second efflux, it will change from a measurement display to an error detection
display automatically.
Example of display Display factor Contents of display

Main monitor Display the error code.

Sub-monitor
Display the "Err".
(Left)
Sub-monitor
Display the "CodE".
(Center)
Sub-monitor
Don't display.
(Right)
In addition to a LCD, "RUN" LED disappears and "ERROR" LED
Other
is lighted.

(1) Operation within fail-safe error occurrence.


① From this display, push the RESET switch for one second and can change it to measurement display.
However, a LOCAL-REMOTE change, and the ON / OFF control by the switch (only if direct) are possible.

(2) Operation after a fail-safe error reset.


① This display is holding even if fail-safe error returns.

② From this display, push the RESET switch for one second and can change it to measurement display.
Error status returns by RESET switch operation.
About fail-safe error, please refer to "8.1.1 Fail-safe function".

Error detection display Other, switch


Fail-safe error operation
occurrence
During the Other displays
Measurement detection
display
(Usual Error
RESET reset
display)
Push 1 second
Holds of
detection

100
DMR-212-006

7.11 Zero phase current input correction 【DMR-FN】


(1) Perform input correction in combination with ZCT about a zero phase current input.
① Perform correction by "zero phase current input correction" of the setting item of directional earth-fault [67].
② Add a rating primary current (200mA) to the primary side of ZCT which corrects combining this product.
Correct a secondary current so that it may become the rating secondary current (1.5mA) of ZCT.
③ Correction is 75 to 150% of range to the rating secondary current (1.5mA) of ZCT. And, it can carry out at a
0.5% steps.
④ If a ZCT secondary current is the range which is 1 to 2mA in this correction, it can correct to the value of a
ZCT rating secondary current (1.5mA) inside this product.
・Correct an input 75% :When it becomes 1.5mA by 75% correction, an actual input is 1.5mA÷0.75=2mA.
・Correct an input 150%:When it becomes 1.5mA by 150% correction, an actual input is 1.5mA÷1.5=1mA.

(2) Correction operating procedure


① Connect ZCT with this product.
② Operate the switch of this product and make it a display of "zero phase current input correction" setting.
(Please refer to the following operating procedure.)
③ Add the rated current (200mA) to a ZCT primary side.
④ The measurement value (ZCT primary value display) which corrected with the present correction is displayed on "a
sub-monitor (center)" of the LCD of this product.
Please change correction with a ▲ , ▼ switch, and set so that a measurement value becomes a ZCT rating
primary current (0.200A).
⑤ Correction value is updated by pushing an ENTER switch. And, please check that the main monitor (correction value
after change) and a sub-monitor (right) (the present correction value) are the same values.
⑥ Cut the input of ZCT and it is the completion of correction.

● The operating procedure to zero phase current input correction

Measurement display (Usual display)

SETTING + STM/RTM
Push 3 seconds
Protection relay 1
(50)

Protection relay 2
(51)

ENTER ×6 ×2
Protection relay 3 Zero phase current
Used/Unused
(67) input correction
×6 ×2
SETTING
×4
×4

● Zero phase current input correction display


Example of display Display factor Contents of display
Display the zero phase current input correction value (%)
Main monitor
and “ZERO PHASE” after change.
Sub-monitor
Display the setting number (2307).
(Left)
Display the zero phase current input value corrected by the
Sub-monitor
correction value (%) after change. And display the “ZERO
(Center)
PHASE”.
Sub-monitor Display the present zero phase current input correction
(Right) value (%) and "ZERO PHASE".
Display "PROTECTION SETTING" on an upside.
Other
In addition to a LCD, "SETTING" LED is lighting.

Perform this correction by actually adding a zero phase current. Depending on the setting value of other setting
factors (an operating value, operating time, etc.), protection detection may be done during correction.
Please set protection setting ("Used/Unused") to "Unused" and prevent the false trip within correction.

101
DMR-212-006

8. Maintenance and check


8.1 Maintenance function
8.1.1 Fail-safe function
This product is doing self-diagnostics by the fail-safe function, and performs error checking about the following
item.

(1) Record of error occurrence is recorded on an error history as an error code. ( 54 )


(2) When an error is detected, a control output (CB-trip) and DO output of fault 1 to 3 (50, 51, 51G, 67, 27,
59, 64) are locked. (Exclude a zero phase monitor (current).)
(When an error continues 15 seconds or more, the output lock of the zero phase monitor (current) is done.)
Furthermore, if an error continues 15 seconds or more, it will be in equipment malfunction status. ( 54 )
Equipment malfunction status:Pulse output is stop. Analog output and communication output is locked by the
output value of an input 0. "equipment malfunction" output ON.
"ERROR" LED lighting. LCD is automatic change for "error detection display".
However, when a "watchdog timer", a "sum check", a "nonvolatile memory check", and "a power supply monitor (5V)"
detect an error, they will be in equipment malfunction status. (Instantaneous detection)
(3) At the time of the malfunction detection by the fail-safe function, switch operation, and the ON/OFF control by
DI are possible. (Exclude a power supply monitor.)
(4) When error detection or equipment malfunction status returns, DO output lock is canceled. (Others hold
status) (55)
After a reset of equipment malfunction status, push for RESET switch 1 second, and cancel error status.
And each output (a pulse output, a communication output, analog output) returns to a normal state.
And, in an "equipment malfunction" output OFF, and "ERROR" LED puts out the light, and LCD returns to measurement
display.
However, by the fail-safe of the above instantaneous detection, when error detection returns, each output
returns to a normal state, and an "equipment malfunction" becomes output OFF. (Automatic reset)
(5) If power supply reset is performed in the status that the error has occurred, error occurrence status is
cleared and performs error detection operation again.

Item Methods of operation Error code Note


V(L1L2),V(L3L1)>40V and V(L2L3)<10V, or DMR-BN output-locks only
Zero phase monitor
V(L2L3),V(L3L1)>40V and V(L1L2)<10V, or 27 and 59.
(voltage) Err01
V(L1L2)+V(L2L3)+V(L3L1)>20% of rated voltage DMR-SN output-locks only
(56)
(22V) 27.
Output-lock in the state of
Zero phase monitor
an equipment malfunction
(current) A(L1)+A(L2)+A(L3)>10% of rated current Err02
(15-seconds
(56)
continuation).
Detect the measurement error (±10%) of a fixed
A/D accuracy check Err03
value input.
Detect the abnormalities in an A/D conversion period.
A/D conversion (An applicable factor is before occurrence of A/D
Err04
period check conversion finishing interrupt, the A/D conversion
start interrupt of the next factor occurs.)
Zero phase voltage Detect the abnormalities of a zero phase voltage DMR-BN output-locks only
Err05
input monitor input circuit. 64.
Reset an external timer circuit for each program
At the time of error
constant time, and detect a runaway program. (CPU is
Watchdog timer Err11 occurrence, it is a program
an automatic reset.)
restart to an instant.
Detection 20ms (For output lock priority)
As opposed to all memory regions, write in and readout
Read Write check Err12
to predetermined data.
The summation of the data of all program regions, and
Sum check Err13
comparison with known data.
Clock monitor Detect the periodic error of Fixation CLK. Err14
Setting value Detect the setting value incompatibility of the
Err15
collation duplication setting memory.

102
DMR-212-006

Item Methods of operation Error code Note


At the time of error
Nonvolatile memory occurrence, update to an
Detect setting values other than the setting range. Err16
check default setting to
corresponding data. (57)
Detect the error of each interrupt period of a
Interrupt monitor Err17
program, and a main period.
Feed back DO output command (control 1 to 3), and
DO monitor Err21
detect incompatibility.
Power supply
Supervise the depression of supply voltage (24V,
monitor Err31
±8V).
(24V,±8V)
CPU reset is done at the time
of an instantaneous
Power supply
Supervise the depression of supply voltage (5V). - detection. And, it is not
monitor (5V)
recorded on an error
history.
Note(54) If abnormalities return within 15 seconds, "ERROR" LED puts out the light. And, an "equipment
malfunction" output remains OFF. In this case, it is not recorded on an error history.
Note(55) In order that a sum check and a nonvolatile memory check may do only at the time of starting, it does
not return other than power supply reset.
Note(56) In relay test mode or zero phase monitor setting "OFF", don't perform a zero phase monitor (voltage,
current). And, a protection function takes priority even if it detect zero phase monitor during the
earth-fault protection detection. (Don't perform an output lock.)
Note(57) About the default setting, please refer to "7 Operation・Setting 《Default setting value》".
In addition, a protection setting value is set by different fixed value in part from an default setting value.

・ The difference between the default setting value of protection setting, and the fixed value at the time of
nonvolatile memory check error occurrence.
At the time of error occurrence, only the setting value of the point judged to be an error is initialized.

DMR-FN
Setting
Default setting value
No. Setting item Default setting value
in error
2101 Used / Unused OFF (Unused) OFF (Unused)
2102 Operating value (58) 10A(2A) 80A(16A)
2103 50 Operating time Instant Instant
2104 Reset method Hold Hold
2105 "ON" control within protection detection display Permission Permission
2201 Used / Unused OFF (Unused) OFF (Unused)
2202 Characteristic Standard [SI] Standard [SI]
2203 Operating value (58) 2.0A(0.40A) 12.0A(2.40A)
51
2204 Time multiplier 1.0 times 30 times
2205 Reset method Hold Hold
2206 "ON" control within protection detection display Permission Permission
2301 Used / Unused OFF (Unused) OFF (Unused)
2302 Operating value (Current) 0.1A 1.0A
2303 Operating value (Voltage) (59) 5V(0.025V) 60V(0.400V)
2304 Operating angle 40° 40°
67
2305 Operating time 0.1s 0.1s
2306 Reset method Hold Hold
2307 Zero phase current input correction 100% 100%
2308 "ON" control within protection detection display Permission Permission
2401 External Used / Unused OFF (Unused) OFF (Unused)
2402 trip "ON" control within protection detection display Permission Permission
58
Note( ) ( ) is a setting value in rated current 1A.
Note(59) ( ) is a setting value in zero phase rated voltage AC1V (ZPD).

103
DMR-212-006

DMR-GN
Setting
Default setting value
No. Setting item Default setting value
in error
2101 Used / Unused OFF (Unused) OFF (Unused)
2102 Operating value (60) 10A(2A) 80A(16A)
2103 50 Operating time Instant Instant
2104 Reset method Hold Hold
2105 "ON" control within protection detection display Permission Permission
2201 Used / Unused OFF (Unused) OFF (Unused)
2202 Characteristic Standard [SI] Standard [SI]
2203 Operating value (60) 2.0A(0.40A) 12.0A(2.40A)
51
2204 Time multiplier 1.0 times 30 times
2205 Reset method Hold Hold
2206 "ON" control within protection detection display Permission Permission
2301 Used / Unused OFF (Unused) OFF (Unused)
2302 Operating value 0.25A(0.050A) 6.0A(1.2A)
Operating time
2303 Operating time 60s
51G (50ms or more)
2304 2nd harmonic suppression OFF OFF
2305 Reset method Hold Hold
2306 "ON" control within protection detection display Permission Permission
2401 External Used / Unused OFF (Unused) OFF (Unused)
2402 trip "ON" control within protection detection display Permission Permission
Note(60) ( ) is a setting value in rated current 1A.

DMR-BN
Setting
Default setting value
No. Setting item Default setting value
in error
2101 Used / Unused OFF (Unused) OFF (Unused)
2102 Operating value 60V 60V
2103 27 Operating time 0.1s 1.0s
2104 Reset method Hold Hold
2105 "ON" control within protection detection display Permission Permission
2201 Used / Unused OFF (Unused) OFF (Unused)
2202 Operating value 150V 150V
2203 59 Operating time 0.1s 1.0s
2204 Reset method Hold Hold
2205 "ON" control within protection detection display Permission Permission
2301 Used / Unused OFF (Unused) OFF (Unused)
2302 Operating value (61) 5V(0.025V) 60V(0.400V)
2303 64 Operating time 0.1s 1.0s
2304 Reset method Hold Hold
2305 "ON" control within protection detection display Permission Permission
2401 External Used / Unused OFF (Unused) OFF (Unused)
2402 trip "ON" control within protection detection display Permission Permission
61
Note( ) ( ) is a setting value in zero phase rated voltage AC1V (ZPD).

104
DMR-212-006

DMR-SN
Setting
Default setting value
No. Setting item Default setting value
in error
2101 Used / Unused OFF (Unused) OFF (Unused)
2102 Operating value (62) 10A(2A) 80A(16A)
2103 50 Operating time Instant Instant
2104 Reset method Hold Hold
2105 "ON" control within protection detection display Permission Permission
2201 Used / Unused OFF (Unused) OFF (Unused)
2202 Characteristic Standard [SI] Standard [SI]
2203 Operating value (62) 2.0A(0.40A) 12.0A(2.40A)
51
2204 Time multiplier 1.0 times 30 times
2205 Reset method Hold Hold
2206 "ON" control within protection detection display Permission Permission
2301 Used / Unused OFF (Unused) OFF (Unused)
2302 Operating value 60V 60V
2303 27 Operating time 0.1s 1.0s
2304 Reset method Hold Hold
2305 "ON" control within protection detection display Permission Permission
2401 External Used / Unused OFF (Unused) OFF (Unused)
2402 trip "ON" control within protection detection display Permission Permission
Note(62) ( ) is a setting value in rated current 1A.
15 秒経過後
・Operation of the equipment at the time of the error detection by the fail-safe function.
Status of equipment
After error
At error reset After error reset
Error item Factor At error detection
(Automatic ("RESET" switch
detection (After 15
reset) operation)
seconds)
Measurement Error detection Error detection Measurement
LCD
Display display display display display
「ERROR」LED Lights-out Lighting Lighting Lights-out
About 0% of About 0% of
Analog output Normal inputs is inputs is Normal
Zero phase monitor outputted. outputted.
(voltage) Output Pulse output Normal Stop Stop Normal
Zero phase voltage About 0% of About 0% of
Communication
input monitor Normal inputs is inputs is Normal
output
outputted. outputted.
Output lock Output lock
DO output Normal Normal
(63)(64) (63)(64)
DO output (Equipment
OFF ON ON OFF
malfunction)
Measurement Error detection Error detection Measurement
LCD
Display display display display display
「ERROR」LED Lights-out Lighting Lighting Lights-out
About 0% of About 0% of
Analog output Normal inputs is inputs is Normal
outputted. outputted.
Zero phase monitor
Output Pulse output Normal Stop Stop Normal
(Current)
About 0% of About 0% of
Communication
Normal inputs is inputs is Normal
output
outputted. outputted.
DO output Normal Output lock (64) Normal Normal
DO output (Equipment
OFF ON ON OFF
malfunction)

105
DMR-212-006

Status of equipment
After error
At error reset After error reset
Error item Factor At error detection
(Automatic ("RESET" switch
detection (After 15
reset) operation)
seconds)
Measurement Error detection Error detection Measurement
LCD
A/D accuracy check. Display display display display display
A/D conversion 「ERROR」LED Lights-out Lighting Lighting Lights-out
period check. About 0% of About 0% of
Read Write check. Analog output Normal inputs is inputs is Normal
Clock monitor. outputted. outputted.
Setting value Output Pulse output Normal Stop Stop Normal
collation. About 0% of About 0% of
Communication
Interrupt monitor. Normal inputs is inputs is Normal
output
DO monitor. outputted. outputted.
Power supply DO output Output lock (64) Output lock (64) Normal Normal
monitor (24V,±8V). DO output (Equipment
OFF ON ON OFF
malfunction)
Measurement Measurement Measurement
LCD -
display display display
Display
Lighting
「ERROR」LED - Lights-out Lights-out
(Instant)
About 0% of
Watchdog timer Analog output inputs is - Normal Normal
power supply outputted.
monitor (5V) Output Pulse output Stop - Normal Normal
(65) About 0% of
Communication
inputs is - Normal Normal
output
outputted.
DO output Output lock (64) - Normal Normal
DO output (Equipment
ON - OFF OFF
malfunction)
Error detection Error detection Error detection Error detection
LCD
Display display display display display
「ERROR」LED Lighting Lighting Lighting Lighting
About 0% of About 0% of About 0% of About 0% of
Analog output inputs is inputs is inputs is inputs is
Sum check. outputted. outputted. outputted. outputted.
Nonvolatile memory Output Pulse output Stop Stop Stop Stop
check. About 0% of About 0% of About 0% of About 0% of
Communication
inputs is inputs is inputs is inputs is
output
outputted. outputted. outputted. outputted.
DO output Output lock (64) Output lock (64) Output lock (64) Output lock (64)
DO output (Equipment
ON ON ON ON
malfunction)
Note(63) If an error is detected under a zero phase monitor (voltage), in DMR-BN, only 27 and 59 do an output
lock. And, in DMR-SN, only 27 does an output lock.
If an error is detected under a zero phase voltage input monitor, only 64 of DMR-BN does an output lock.
(Even if it detects an error, the output lock of DMR-FN and DMR-GN is not done.)
Note(64) If an error is detected by the fail-safe function, trip operation by protection detection is locked (output
OFF). In addition, the output by switch operation or ON/OFF control of DI and the output by REMOTE/LOCAL
operation are not locked.
DO output locked:Each DO output of "CB-Trip" and "fault 1 to 3".
Note(65) In a watchdog timer and a power supply monitor (5V), CPU is immediately reset after error detection.
Therefore, there is no operation of continuation for 15 seconds, and it will become normal operation if
the error has returned after CPU reset.

106
DMR-212-006

8.1.2 Protection detection history function


(1) Each protection factor records the detection value at the time of the newest protection detection.

(2) A protection detection history can be checked by protection detection history display.
"RECODE" LED is lighted during a history display.
(3) A protection detection history display displays a detection value (maximum value within detection), and a detection
phase (only an instantaneous overcurrent and overcurrent).
In addition, in a directional earth-fault, display a phase angle, a zero phase current, and a zero phase voltage.
The phase angle in this case, if current is a leading phase to voltage, is displayed.
And if current is a lagging phase to voltage, is displayed.

● The example of a display


(If the detection lag of a phase angle is 39° and directional earth-fault 67 detection.)

(4) A protection detection history is not cleared even if it does power supply reset.

(5) If a MAX./MIN. RESET switch is pushed for 3 seconds while displaying a protection detection history, a
displaying protection factor history will be cleared.

(6) The protection factor which has not done protection detection to the past once displays "-----".

(7) The detection value is not displayed if the factor of OFF does protection detection by the phase / line display
ON/OFF setting.

Contents of display
Protection factor Sub-monitor Sub-monitor Sub-monitor Note
Main monitor
(left) (center) (right)
Instantaneous [L1 phase [L3 phase
50 (66) Secondary rating displays
overcurrent [50] current] current]
[L1 phase [L3 phase
Overcurrent [51] 51 (66) Secondary rating displays
current] current]
Secondary rating displays
Directional [Zero phase [Zero phase
67 [Phase angle] (zero phase current is
earth-fault [67] current] voltage]
primary rating display)
Earth-fault
51G (Blank) (Blank) [Detection value] Secondary rating displays
overcurrent [51G]
Undervoltage [27] 27 (Blank) (Blank) [Detection value] Secondary rating displays
Overvoltage [59] 59 (Blank) (Blank) [Detection value] Secondary rating displays
Earth-fault
64 (Blank) (Blank) [Detection value] Secondary rating displays
overvoltage [64]
Note(66) DMR-FN and DMR-GN become a blank display. DMR-SN becomes L2 phase current display.

107
DMR-212-006

8.1.3 Error history function


(1) By a fail-safe function, record the error of equipment malfunction status on a history by the error code.
(2) A error history can be checked by error code check display. "ERROR CODE" LED is lighted during a history display.
(3) Display an error code and a history number as an error history display.
A history number is displayed by "-1" to "-20". "-1" is the newest error.

(4) A maximum of 20 error histories are recorded. If a maximum is exceeded, it is deleted from old record.
(5) A error history is not cleared even if it does power supply reset.

(6) If a MAX./MIN. RESET switch is pushed for 3 seconds while displaying a error history, a displaying error
history will be cleared.

8.2 Troubleshooting
Phenomenon Probable cause Necessary measures
The control power supply is not provided. Check of control power supply.
(It is not wired. An voltage is low.) Restore control power supply.
LCD does not display. By measurement display ON/OFF setting, it is setting
Check of setting value
OFF.
Trouble of equipment Exchange of equipment
Backlight puts out the Put out the light automatically after 10 minutes by no
It is not trouble.
light. operating it. (It is re-lighting by switch operation.)
The error of a measurement Setting of a range is wrong. Check of setting value
value is large. Out of the rated frequency range This product cannot be used.
Analog output is not
Analog output setting is OFF. Check of setting value
outputted.
Pulse output setting is OFF. Check of setting value
Pulse output is not
Make an output pulse unit into
outputted. By range change, an output pulse unit is out of range.
setting within the range.
The control power supply is not provided. Check of control power supply.
(It does not wire. Voltage is low.) Restore control power supply.
ON/OFF control cannot be
The slide switch is [REMOTE]. Set a switch to [LOCAL].
performed from a front
Only "ON" or the "OFF" switch is pushed. Push simultaneously with the
switch.
It is not pushing simultaneously with the "ON/OFF "ON/OFF PERMISSION" switch and
PERMISSION" switch. operate it again.
The control power supply is not provided. Check of control power supply.
ON/OFF control from DI
(It does not wire. Voltage is low.) Restore control power supply.
cannot be performed.
The slide switch is [LOCAL]. Set a switch to [REMOTE].
The control power supply is not provided. Check of control power supply.
(It does not wire. Voltage is low.) Restore control power supply.
ON/OFF control by
The slide switch is [LOCAL]. Set a switch to [REMOTE].
communication cannot be
Only the command of "ON" or "OFF", it is not ordered The simultaneous command of the
performed.
simultaneously with the "ON/OFF PERMISSION" command "ON/OFF PERMISSION" command.
"ERROR" LED is lighting. Exchange of equipment
The setting (use / unused) of the applicable protection
Check of setting value
element becomes the unused.
Don't do protection
They are test mode or self check mode.
detection. The change in the mode
("STM/RTM" LED lighting, or "RUN" LED flicker)
"ERROR" LED is lighting. Exchange of equipment
"ON" LED or "OFF" LED is The wiring (52a, 52b) from a circuit breaker is wrong.
Check of wiring
not lighted. Or it does not wire.

108
DMR-212-006

8.3 Check
8.3.1 Daily check
This product contains the self-diagnostic function by the fail-safe function.
The appearance check, please check the next item. In addition, those who have technical knowledge, such as an
electrical work, need to perform check.
(1) Discoloration of a LCD, and damage of a case.

(2) Looseness of wiring, and looseness of installation screw.


(3) Is the connector inserted correctly?
(4) Adhesion of dust to a product.
(5) Lighting of "RUN" LED, lights-out of "ERROR" LED.

8.3.2 Periodic check


There are no replacement parts in a periodic check.
A periodic check recommends the periods of two - four years by the case where the environment (ambient temperature,
dust, etc.) is good. In addition, first time check recommends the check in one year after installation.
And, the product for ten years or more recommends one time check in every year.

8.4 Design expected life


This product design expected life is 15 years.
This is the case where the annual par ambient temperature within a switch gear is 25℃.
If this goes up by 5℃, a design expected life will become about ten years. However, this is not a guarantee life.
If the trouble after exceeding a product-life cycle, please exchange for a new product.

8.5 Maintenance
(1) Please do not change wiring of an input and an control power supply by the hot line condition.

(2) In case you check an output unavoidably by the hot line condition, please warn to be unable to touch output wiring
and a human body to an input and an auxiliary power terminal.

(3) If it checks an input, an output, and an control power supply, please carry out after checking schematics.

(4) If a name-plate is wiped with solvents (an alcoholic nature), a display item may disappear.
Please wipe with the dry cloth.
The liquid crystal display (LCD) may light during cleaning on the LCD face. However, this phenomenon is caused
by the static electricity that may be produced in the filter, and it does not show any trouble.
Leave the unit as it is for a while, and the display goes out due to natural discharge.

(5) Please keep in mind that it will break if a LCD is pushed strongly. And, if a filter is pushed, a LCD face will
touch a filter. Therefore, the pattern of the shape of a circle or an ellipse may occur.
This phenomenon improves by doing the power distribution of the auxiliary power and leaving it for about 2 hours.
(6) If the temperature and humidity of an installation change rapidly when a product is a non-energization, the waterdrop
by dew condensation may adhere to a display inner side. (The display filter and the LCD surface stick and the pattern
of the shape of a circle or an ellipse occur.)
This phenomenon improves by doing the power distribution of the auxiliary power and leaving it for about 2 hours.
(7) In the case of a periodic check, it is possible by doing test mode (STM/RTM) and self check mode to aim at shortening
of check time. In the case of operation in each mode, please carry out after checking an operation step and an
operating procedure enough.

109
DMR-212-006

8.6 Exchange of product


(1) How to remove
① Remove the terminal block and connector which are wiring the product.
② The detachable terminal block and the connector are used for this
product. Removal of a product is possible even if it does not remove
wiring.

・Removal of a terminal block


Please loosen the fixation screw of terminal block both sides, and
remove a terminal block. In addition, please loosen the fixation
screw of both sides little by little by turns. If only the screw
of one side is loosened, there is a possibility of damaging a
terminal block.

• Please do not perform removal of the terminal block in a hot line


condition. The high voltage occurs by open circuit of CT secondary Fixation screw of terminal block
circuit, there is fear of an electric shock or CT destruction.

・Removal of a connector
Push a connector lock part.
The lock mechanism is built in the connector.
Draw out perpendicularly to a connector, draw out
perpendicularly to a connector, pressing down the lock of a
connector top and bottom.
Pull out If it pulls out by force, without pushing a lock or pulls out
aslant, there is a possibility of damaging a connector.

③ Please remove a product from a panel in step contrary to the


installation method.
Refer to "5.1 Installation" for the installation method.

・An installation of terminal block


Please press the fixation screw of the both sides of a terminal
block certainly.
Tightening torque:0.8 to 1.0N・m (8 to 10kg・cm)
In addition, please tighten the fixation screw of both sides
little by little by turns. Please do not tighten only the
fixation screw of one side.

Fixation screw of terminal block

110
DMR-212-006

8.7 Sequence test mode (STM)


It is the mode which checks protection detection operation, without applying an input. By front switch operation,
only arbitrary time can make protection detection status.
At the time of protection detection, it becomes the usual detection operation.
While pushing the "STM/RTM" switch, the corresponding protection factor will be in detection status.
And, LCD becomes "on" display.
A LCD expresses the status of the "STM/RTM" switch.
・Perform detection operation (DO, LED, communication output) of the protection factor (a phase is also included)
selected by front switch operation.
DO :CB-Trip,Fault 1 to 3
LED:LED of the protection factor detected out of the following is lighted.
"TRIP" and "50", "51", "67", "51G", "27", "59", "64".
・Detection operation does the same operation as an actual setting value (Protection relay, Used/Unused, Reset
method). In addition, reset operation is operation (hold of DO and LED, or automatic reset) seied with "Reset
method" setting.
・Status in the mode
Protection:The protection detection by the input stops.
Control :The control by the front switch and DI, and the external trip are possible.
However, the control by communication stops.
Display :"RUN" LED flicker, "STM/RTM" LED lighting.
A LCD does not return to a measurement display by the case of not operating it, for 10 minutes.

8.8 Relay test mode (RTM)


After applying an input, it is the mode which checks protection detection operation.
A "test" output is turned on at the time of protection detection.
The control output at the time of the usual protection detection and a "fault 1 to 3" output do not turn on.
A LCD displays detection operation of a relay.
・Perform detection operation (DO, LED, Communication output) of the protection factor which applied and selected
the actual input.
DO :Only a "test" is outputted. (It is not outputted to a control output CB-Trip and "fault 1 to 3".)
LED:LED of the protection factor detected out of the following is lighted.
"50", "51", "67", "51G", "27", "59", "64".
・Detection operation does the same operation as an next setting value. ("Operating value", "Operating time", "reset
time", "protection relay Used/Unused")
However, in relay test mode, there is nothing with regards to "Reset method" setting, reset operation is an automatic
reset (a protection detection reset is DO "test" output OFF, LED puts out the light, LCD "on→oFF" display).
・Status in the mode
Protection:Other than the selected protection relay factor, the protection detection by the input stops.
Control :The control by the front switch and DI, and the external trip are possible.
However, the control by communication stops.
Display :"RUN" LED flicker, "STM/RTM" LED lighting.
A LCD does not return to a measurement display by the case of not operating it, for 10 minutes.

8.9 Self check mode


The inside memory (ROM, RAM) and the display (LED, LCD), and DI and option outputs (analog output, pulse output,
communication output) of this product are the mode which checks whether it is operating normally.
・Check whether it is operating normally.
ROM, RAM, LCD, LED (the LED backlight for LCD is included. However, exclude "RUN", "ON", "OFF", "REMOTE", and
"LOCAL".), DI, analog output, pulse output, communication output.
・With analog output and a communication output, value is outputted of 0%, 50%, and 100% (for output span).
(with all factors)
・Status in the mode
Protection:All protection detection and external trips stop.
Control :The ON/OFF control by DI is possible from the front switch.
However, the ON/OFF control by communication stops.
Display :"RUN" LED flicker
A LCD does not return to a measurement display by the case of not operating it, for 10 minutes.

111
DMR-212-006

8.10 Protection characteristic test


8.10.1 Instantaneous overcurrent (50), Overcurrent (51) test
Instantaneous overcurrent (50)
Test conditions
Test item Test method Criterion
Input to DMR Operating value Operating time
Increase the input of a current input
terminal (L1 phase / L2 phase / L3 phase)
90% of
from 90% of an operating value. Maximum,
Operating operating value Instant Setting
If "50" LED is lighted, current value Middle,
value → Operating (40ms or less) value ±5%
when "FAULT" displays on LCD is an Minimum
value
operating value.
(Please cut current after a test.)
Change the input of a current input
terminal (L1 phase / L2 phase / L3 phase)
0 →
to 200% of operating value setting
Operating 200% of Instant
suddenly from 0. Minimum 40ms or less
time operating value (40ms or less)
Measure the time to the control output ON
setting
after applying.
(Please cut current after a test.)

Overcurrent (51)
Test conditions
Test item Test method Operating Time Criterion
Input to DMR Characteristic
value multiplier
Increase the input of a current input
90% of
terminal (L1 phase / L2 phase / L3 phase)
operating Maximum, Standard
Operating from 90% of an operating value. Setting value
value Middle, inverse time ×1
value The current value to which “51” LED ±5%
→Operating Minimum (SI)
started the flicker is an operating value.
value
(Please cut current after a test.)
0→300% of
operating 3.22±0.39
Change the input of a current input value second
terminal (L1 phase / L2 phase / L3 phase) setting
to 300% of operating value setting 0→500% of Standard
Operating suddenly from 0. operating 2.56±0.18
Minimum inverse time ×10
time Measure the time to the control output ON value second
(SI)
after applying. setting
Do 0…500% and 0…1000% similarly. 0→1000% of
(Please cut current after a test.) operating 1.89±0.13
value second
setting

112
DMR-212-006

The example of test composition

10 4
P Control power
12
6
14 N supply
3
A
Constant K ~ K 5
current L1 phase 7
generator L L 9
11
K 13
L2 phase 15
L 17 DMR-Pro
19
K 21
Simultaneous ON L3 phase 23
L 25

TB
CN1
ON

OFF
A3
Counter
B3 TRIP
(Hour meter)

Notes
① This product is supervising the balance of each phase current by the zero phase monitor function.
A control output may not operate by this function. Therefore, where a function (setting number:2601) is
setting at OFF, please examine.

② Applying to a current input terminal must not exceed overload capacity (40 time 1-second, 20 times 4 seconds,
10 times 16 seconds and 1.2 times continuation of rated current).
And, if it continues and applies the short-time overcurrent exceeding 1.2 times of rating, please make the
interval for 1 minute or more.
③ In DMR-FN and DMR-GN, please examine about L1 phase and L3 phase. And in DMR-GN, please setting as OFF (unused)
by use/unused setting (setting number:2301) at earth-fault overcurrent (51G).
④ In DMR-SN, please examine about L1 phase, L2 phase, and L3 phase. And please setting as OFF (unused) by
use/unused setting (setting number:2301) at undervoltage (27).
⑤ If it examines instantaneous overcurrent (50), please setting as OFF (unused) by use/unused setting (setting
number:2201) at overcurrent (51).
If it examines overcurrent (51), please setting as OFF (unused) by use/unused setting (setting number:2101)
at overcurrent (51).

113
DMR-212-006

8.10.2 Directional earth-fault (67) test

Directional earth-fault (67)


Test conditions
Input to DMR Setting
Test item Test method Zero Zero Current Voltage Criterion
Phase Phase Operating
phase phase operating operating
angle angle time
current voltage value value
The input of a zero phase
voltage input terminal is
constant, and it is the
status that the phase
relation between voltage Current
and current is constant. 0 → phase Maximum, Setting
Operating value Rated Minimum Minimum
Increase the input of a Operating LEAD 0° Middle, Minimum value
(Current) voltage (LEAD 0°) (0.1s)
zero phase current input value (Voltage Minimum ±10%
terminal gradually. standard)
If "67" LED is lighted,
current value when "FAULT"
displays on LCD is an
operating value.
The input of a zero phase
voltage input terminal is
constant, and it is the
status that the phase
relation between voltage Current
Operating value and current is constant. 0 → 30% of phase Setting
Minimum Minimum
(Voltage-current Increase the input of a Operating rated LEAD 0° Minimum Minimum value
(LEAD 0°) (0.1s)
characteristics) zero phase current input value voltage (Voltage ±10%
terminal gradually. standard)
If "67" LED is lighted,
current value when "FAULT"
displays on LCD is an
operating value.
The input of a zero phase
current input terminal is
constant, and it is the
status that the phase
relation between voltage Current
500% of
and current is constant. 0 → phase Maximum, Setting
Operating value current Minimum Minimum
Increase the input of a Operating LEAD 0° Minimum Middle, value
(Voltage) operating (LEAD 0°) (0.1s)
zero phase voltage input value (Voltage Minimum ±5%
value
terminal gradually. standard)
If "67" LED is lighted,
voltage value when "FAULT"
displays on LCD is an
operating value.

114
DMR-212-006

Test conditions
Input to DMR Setting
Test item Test method Zero Zero Current Voltage Criterion
Phase Phase Operating
phase phase operating operating
angle angle time
current voltage value value
The input of a zero phase
current input terminal and
a zero phase voltage input
terminal is in constant
status.
The phase of the current to
voltage is gradually
changed in the LEAD side or
the LAG side from the phase
angle (operating phase
angle of about ±90°) out
Out of the
of the detection range.
detection
operating If "67" LED is lighted, 500% of
30% of range Maximum, Setting
phase angle value of current phase current Minimum
rated ↓ Minimum Minimum Middle, value
(Phase angle when "FAULT" operating (0.1s)
voltage Operating Minimum ±5°
characteristic) displays on LCD is an value
phase
operating value.
angle
Optimum
sensitivity
①+②
phase angle =
2
① Operating phase angle
(LEAD side)
② Operating phase angle
(LAG side)

"- " Lead, "+" Lag.


The phase relation between
voltage and current is in
constant status, change
the input of a zero phase
current input terminal to Maximum Maximum
0 → Current
500% of operating value (10s) (±0.5s)
500% of 0 → phase
setting suddenly from 0. Middle Middle
Operating time current Rated LEAD 40° Minimum Minimum Middle
And, change the input of a (5s) (±0.25s)
operating voltage (Voltage
zero phase voltage input Minimum Minimum
value standard)
terminal to rated voltage (0.1s) (±0.1s)
suddenly from 0.
Measure the time to the
control output ON after
applying.

115
DMR-212-006

The example of test composition


● EVT input specification
10 4
P Control power
12
6
14 N supply
3

a 16 5

u 7
Constant
voltage V 18 9
~ ~
generator v 11
f
13
15
V ± DMR-Pro 17
Oscillator Phase meter 19

A ± 21
ZCT
23
K k Z1 22
A 25
Constant K ~
current 24

generator L L l Z2 TB

CN1
ON
Simultaneous ON
OFF
Counter A3
B3 TRIP
(Hour meter)

● ZPD input specification


Constant
voltage
generator
v u
Phase meter

V A
V
~ ± ±

v u
Step-up transformer
110 6600
(Example) :
v u √3 √3

T
ZPD y1 16

y2 18

E TB

Notes
① As for a zero phase voltage input, the polarity of connection is different. (Polarity is contrary to usual)
(Polarity is connection contrary to usual.)
② If the error of an operating value (current) test is large, please perform combination input correction with ZCT
by the zero phase current input correction function (setting number: 2307).
③ If applying of the test voltage of ZPD cannot be performed in order that there may be no step-up transformer,
Please do in 150% of input of a setting value.
(However, a difference may arise in a ZPD phase characteristic with the size of an input.)
④ The performance within a criterion is a performance of a DMR simplex. If it combines ZPD and ZCT, please
make a criterion into the value which added each tolerance.
⑤ Voltage operating value setting of directional earth-fault (67) is a secondary voltage display.
To examine by ZPD specification, it is necessary to convert the input value from a constant voltage generator
into an equivalent for ZPD secondary voltage. (By EVT specification, in order to input directly from a constant
voltage generator, it is conversion needlessness.)
Please examine with a relative input value with reference to a following conversion table and a following
conversion formula.

116
DMR-212-006

● ZPD secondary voltage conversion of a constant voltage generator input value.


The input value of a constant voltage generator is convertible into a ZPD secondary voltage at the time of ZPD
specification. If primary rated voltage is used of ZPD which is 3300V, please carry out similarly.
(If used of a step-up transformer.)
ZPD primary input value [V] = Constant voltage generator input [V] × Step-up transformer VT ratio
(If not used of a step-up transformer.)
ZPD primary input value [V] = Constant voltage generator input [V]
(ZPD secondary voltage conversion formula.)
ZPD secondary voltage reduced value [V] = ZPD primary input value [V] × √3 / 6600
The reduced value list at the time of step-up transformer (VT ratio:60) use.

Constant voltage generator input [V] ZPD primary input value [V] ZPD secondary voltage reduced value [V]
1.588 95.28 (165/√3) 0.0250
3.175 190.5 (330/√3) 0.0500
12.70 762.1 (1320/√3) 0.2000
25.40 1524 (2640/√3) 0.4000
31.75 1905 (3300/√3) 0.5000
63.51 3811 (6600/√3) 1.0000

(Example)
If voltage operating value setting of DMR is 0.200V and the input of a constant voltage generator does protection
detection by 12.75V, calculate a ZPD secondary voltage as follows. 0.2008V is convert with a voltage operating
value.
ZPD primary input value = 12.75 × 60 = 765V
ZPD secondary voltage reduced value = 765 × √3 / 6600 = 0.2008V

117
DMR-212-006

8.10.3 Undervoltage (27), Overvoltage (59) test


Undervoltage (27)
Test Test conditions
Test method Criterion
item Input to DMR Operating value Operating time
Decrease the input of a voltage input
terminal (L1l2 line / L2L3 line) Maximum,
Operating 150V → Setting
gradually. If "27" LED is lighted, Middle, Minimum (0.1s)
value Operating value value ±5%
voltage value when "FAULT" displays on LCD Minimum
is an operating value.
Change the input of a voltage input
Rated voltage
terminal (L1L2 line) to 70% of operating
Operating → 70% of Setting
value setting suddenly from rated voltage. 100V Maximum (10s)
time operating value value ±5%
Measure the time to the control output ON
setting
after applying.

Overvoltage (59)
Test Test conditions
Test method Criterion
item Input to DMR Operating value Operating time
Decrease the input of a voltage input
terminal (L1l2 line / L2L3 line) Maximum,
Operating 0→Operating Setting
gradually. If "59" LED is lighted, Middle, Minimum (0.1s)
value value value ±5%
voltage value when "FAULT" displays on LCD Minimum
is an operating value.
Change input of voltage input terminal
0→
(L1L2 line) from the rating voltage into
Operating 120% of Setting
120% of operating value setting suddenly. Minimum (110V) Maximum (10s)
time operating value value ±5%
Measure the time to the control output ON
setting
after applying.

The example of test composition

P1 10 4
P Control power
Constant u
V P2 12 6
voltage ~ N supply
generator v P3 14

3
5
7
9
11
13
15 DMR-Pro
17
Simultaneous ON 19
21
23
25
TB

CN1

ON

OFF
A3
Counter
B3 TRIP
(Hour meter)

Notes
① This product is supervising the balance of each line voltage by the zero phase monitor function.
A control output may not operate by this function. Therefore, where a function (setting number:2601) is
setting at OFF, please examine.
② Please do the test of an operating value in L1L2 line and L2L3 line, respectively. (Because an input signal is
compounded inside and it detects as L3L1 line voltage, a test is possible even if there is no input of one side.)

③ If the undervoltage (27) test of DMR-BN is performed, please setting as OFF (unused) by use/unused setting (setting
number:2201) at overvoltage (59). If the overvoltage (59) test of DMR-BN is performed, please setting as OFF (unused)
by use/unused setting (setting number:2101) at undervoltage (27).

118
DMR-212-006

8.10.4 Earth-fault overvoltage (64) test

Earth-fault overvoltage (64)


Test Test conditions
Test method Criterion
item Input to DMR Operating value Operating time
Increase the input of a zero phase voltage
Maximum,
Operating input terminal gradually. If "64" LED is 0→ Setting
Middle, Minimum (0.1s)
value lighted, voltage value when "FAULT" Operating value value ±5%
Minimum
displays on LCD is an operating value.
Change the input of a zero phase voltage
input terminal to 150% of operating value 0→
Operating Setting
setting suddenly from 0. 150% of a Minimum Maximum (10s)
time value ±5%
Measure the time to the control output ON setting value
after applying.

The example of test composition


● EVT input specification ● ZPD input specification

4
Constant
10
12 P Control power voltage
14 6 generator
N supply
f 16
v u
Constant u
18
voltage V V
~ a ~
generator v 3
5
v u Step-up transformer
7
9 110 6600
(Example) :
11 √3 √3
13 v u
15 DMR-Pro
17
19
Simultaneous ON 21
23 T
25 ZPD y1 16
TB
CN1 y2 18
ON
E TB
OFF
Counter A3
B3 TRIP
(Hour meter)

Notes
① If the earth-fault overvoltage (64) test of DMR-BN is performed, please setting as OFF (unused) by use/unused
setting (setting number:2101) at undervoltage (27).
② Voltage operating value setting of earth-fault overvoltage (64) is a secondary voltage display.
To examine by ZPD specification, it is necessary to convert the input value from a constant voltage generator
into an equivalent for ZPD secondary voltage. (By EVT specification, in order to input directly from a constant
voltage generator, it is conversion needlessness.)
Please examine with a relative input value with reference to a 96-pages conversion table and a conversion formula.

119
DMR-212-006

8.10.5 Earth-fault overcurrent (51G) test

Earth-fault overcurrent (51G)


Test conditions
Test item Test method Criterion
Input to DMR Operating value Operating time
Increase the input of a zero phase current
90% of an
input terminal gradually. Maximum,
Operating operating value Instant Setting
If "51G" LED is lighted, current value Middle,
value → (50ms or less) value ±5%
when "FAULT" displays on LCD is an Minimum
Operating value
operating value.
0→ 300% of
Change the input of a zero phase current operating value
input terminal to 300% (for operating setting
value setting) suddenly from 0. 0→ 500% of
Operating Setting
Measure the time to the control output ON operating value Minimum Maximum (60s)
time value ±5%
after applying. setting
Do 0…500% and 0…1000% similarly. 0→ 1000% of
(Please cut current after a test.) operating value
setting

The example of test composition

10 4
12 P Control power
6
14
N supply
K 16
A
Constant K ~ 18

current 22
L 24
generator L
3
5
7
9
11
13
15 DMR-Pro
17
19
Simultaneous ON 21
23
25
TB
CN1
ON

OFF
A3
Counter
B3 TRIP
(Hour meter)

Notes
① If the earth-fault overcurrent (51G) test of DMR-GN is performed, please setting as OFF (unused) by use/unused
setting (setting number:2101,2201) at instantaneous overcurrent (50) and overcurrent (51).

120
DMR-212-006

9. Related product
9.1 AC power supply backup unit (TYPE:PBU-93)
The control power supply of a Multi-function digital relay (DMR-Pro) is a AC power supply (AC100/110V), and, in the
same
input as a voltage measurement circuit, is used of this product.
In the system which provides a control power supply from a self-system, if AC power supply is lowered or dissipates
by the short-circuiting accident or power failure, by combining this product and DMR-Pro, normal operation of the
function of a protective relay can be done for at least 1 second.
Multi-function digital relay (DMR-Pro) connectable with this one product is one set.

9.1.1 Specification
Item Specification
Product name AC power supply backup unit
Type PBU-93
Rated voltage AC100/110V 50/60Hz
Input
Voltage variation range AC85…127V
Output (67) DC141/155V (At no-load)
Rush current 5.5A or less
Input consumption VA (68) AC100/110V:15VA or less (DMR-FN, DMR-GN, DMR-BN, DMR-SN)
Blackout guarantee time (69) 1 second
Insulation resistance Between electrical circuit and case. Avobe 50MΩ at DC500V megger
Withstand voltage Between electrical circuit and case. AC2000V 50/60Hz 1 minute
Lightning impulse withstand Between power supply (INPUT) terminals 3.0kV 1.2/50μs Positive and
voltage (S1 and S2). negative polarity, for each 3 times
Overload capacity 1.5 times 10 seconds and 1.2 times continuation of rated voltage.
Sweep vibration frequency range:10…55Hz, Displacement amplitude:0.15mm,
Vibration
Strength Number of sweep:5, Sweep velocity:1 octave /minute
Peak acceleration:294m/s2
Shock
Each 3 times of forward reverse to the direction of X Y Z.
Dimension 120mm(Width)×120mm(Height)×130mm(Depth)
Material Case:Fire retardancy ABS(V-0) Terminal cover:Polycarbonate resin
Structure Outward color Black (Munsell N1.5)
Terminal screw Input,Output,Discharge terminal, M4 screw
Mass Approx. 700g
Operating temperature and
-10…+50℃ ,30…90%RH (Non condensing)
humidity limits
Storage temperature limits -25…+60℃
Design expected life 10 years
Note(67) Please connect an output only to PN terminal (Multi-function digital relay, No. 4 terminal, No. 6 terminal)
of
DMR-Pro. Please be used combining Multi-function digital relay (DMR-Pro, 1 set).
Note(68) It is the input consumption VA at the time of one Multi-function digital relay (DMR-Pro) connection.
Note(69) It is the blackout guarantee time in being used by rated voltage AC100V (-5% variation allowance).
The blackout guarantee time in being used at a voltage fluctuation range lower limit (AC85V) becomes
0.5 seconds. And, when it is used of the undervoltage function of DMR-BN/SN and operating time
setting is used exceeding blackout guarantee time, the relay output by protection detection of a
undervoltage cannot be performed at the time of blackout.
In this case, please provide a power supply from an uninterruptible power system.

9.1.2 Block diagram


P(+)
Short circuit
protection D1
S1(~) CHARGE Output
LED Discharge
D2 DC141/155V
Input AC/DC Condenser (Red) circuit
(At no load)
AC100/110V converter charge N(-)

S2(~) Discharge terminal


(Discharge of short-circuits)
Don't insulate the input and output of this product.
CHARGE LED (red) puts out the light in DC20V or less output.

121
DMR-212-006

9.1.3 The name and function of each part

Input terminal Discharge terminal Output terminal


S1 S2 D1 D2 P N
(~) (~) (+) (-)

感電注意

Unused terminal
An unused terminal
becomes a black screw.
・本製品は必ずディジタルマルチリレー DMR-Pro 1台と組合せてご使用ください。 CHARGE LED (Red)
・強制放電は必ず入力電源を切った状態で、D1とD2端子を短絡して行ってください。
また、入力電源を印加した状態での強制放電は絶対に行わないでください。 An output puts out the light
注意 ・結線は必ずCHARGEランプが消灯している事を確認した後に行ってください。
・出力端子の短絡は故障の原因となりますので絶対に行わないでください。 in DC20V or less.

9.1.4 Preparation
(1) Outline dimension

Note(70) In case of DIN rail (height 15mm) installation.

(2) Mounting instruction


The environmental conditions of installation space. Please select indoors without low mechanical vibration, dust,
and corrosive gas. And, please select indoors without the influence of the strong electric magnetic field by
the large current bus, saturable reactor. There is no limit of a mounting position.
A mounting instruction can select 35mm width DIN rail mounting and screw mounting.
In screw mounting, please install with M4 screw or M5 screw. (However, the screw is not attached. The tightening
torque of a screw, M4:1.0 to 1.3N・m,M5:2.0 to 2.5N・m)
Please consider radiation and separate more than 10mm of the interval of mounting side-by-side.
Please consider radiation and wiring space and separate more than 90mm of the space above and below.
Please secure the space distance of a terminal and a metal panel 10mm or more.

122
DMR-212-006

(3) Combination installation dimensions (For example) (Unit mm)


■ Screw installation ■ Rail installation
65 65 65 65

110
PBU-93 PBU-93 PBU-93 PBU-93

10 10 10 10 10 10

90
65 65 65

Please use rail of IEC, DIN technical standard


35mm width rail (strong type).

110
PBU-93 PBU-93
《Recommendation product》 Fuji electric Co., Ltd. TH35-15AL

10 10 10

(4) Installation and removal to a rail


Please use the rail based on the DIN standard of 35mm width.

● How to install to a DIN rail.


The upside nail of the slot for rail installation in a BOX bottom is inserted in a rail.
Next, if it pushes against the lower side (arrow), it is fixed with a lower part slider.
Ⅰ Ⅱ

35mm width DIN rail

Slider

● How to remove from a rail


A minus screwdriver is inserted in the square socket of a slider.
Please pull up BOX to the front, lowering a slotted screwdriver in the direction of an arrow.
Caution) BOX may be damaged, if BOX is pulled up without lowering a slider completely.
Ⅲ Ⅳ

Slider
Slotted screwdriver

123
DMR-212-006

9.1.5 Connection
Please perform connection after checking that CHARGE LED (red) is in lights-out status.
(There is danger of an electric shock at the time of CHARGE LED lighting.)
Please be used combining PBU-93 and a Multi-function digital relay (DMR-Pro, 1 set).
Please connect an output only to P, N terminal (Multi-function digital relay, No. 4 terminal, No. 6 terminal)
of DMR-Pro.
Please install a terminal cover after connection work.
And, please perform input of a power supply after checking that a discharge terminal (D1, D2) is open.
If used of the discharge terminal short-circuit, a remarkable life depression and blackout guarantee time are
shortened. Therefore, there is a possibility that protection detection may become impossible.

Control power supply


AC100/110V Discharge
(~) (~) Input terminal Output
4 Control
P
power
N supply
6
71
( )
S1 S2 D1 D2 P N
(~)(~) (+)(-)

Note(71) Terminal number of DMR-Pro body.


PBU-93 DMR-Pro

9.1.6 Compulsive electric discharge


D1 and D2 of a discharge terminal can be short-circuited, and the chargeable electric charge can be discharged
compulsorily. If it does forcible discharge, please do correctly according to the following steps.
Short-circuiting between the output terminals P and N damages this product.
① Please check that the input and the power supply are not applied to this product.
(Please do not do forcible discharge by any means in the state of power supply applying.)

② Between the discharge terminal D1 and D2 is short-circuited. (Please carry out after checking a discharge terminal
position.) Short-circuiting must use an insulator to be unable to touch a hand at a conductive part.
Please do not let me contact absolutely other than discharge terminal D1 and D2.
③ Please continue short-circuiting until CHARGE LED (red) puts out the light. Discharge is completed in about
10 seconds.
④ Please cancel short-circuiting between the discharge terminal D1 and D2.

9.1.7 Cautions on handling

① Please be not used of this product other than DMR-Pro.


② Please do not short-circuit of an output terminal, P(+) and N(-). There is a possibility of becoming the
causality of a fire and trouble.

③ Please do not remove a terminal cover at the time of operation. There is a danger of receiving an electric
shock. And, please install a terminal cover after connection work.
④ If connection is done, please be sure to shut off an input and a power supply. And, please carry out after checking
that CHARGE LED (red) has gone out.
(If it performs compulsive discharge, check that the input and the power supply are not applied, please carry
out in the step of the 9.1.6 section.)
⑤ Because internal condenser capacity is large, please stop the continuous power supply switching.
Rush current time becomes long and there is a possibility that equipment may deteriorate.
⑥ If an input power supply is applied by unloaded condition, the electric charge is charged by the inside condenser
even if it shuts down an input and a power supply. Therefore, discharge takes time. (Being natural discharge
about 8 minutes.)
If it does forcible discharge, please do correctly according to the steps. And, please apply an input and a
power supply in the status that it combined with DMR-Pro.

124
DMR-212-006

9.1.8 Check
■ Periodic check
There are no replacement parts in a periodic check.
The periodic check of this product, Recommend carrying out by combining with a Multi-function digital relay
(DMR-Pro).
In addition, those who have technical knowledge, such as an electrical work, need to perform.

9.1.9 Maintenance
Please do neither wiring change nor discharge work by any means during operation.
And, be careful for people to be unable to touch a terminal.
The terminal cover is mounted for preventing an electric shock accident. Mount the terminal cover
without fail after the end of work.

9.1.10 Storage
Please avoid storage in the place of the high temperature and the high humidity.
Please avoid storage in the place exposed to direct sunlight.
If a long term storage is done in the state of a non-energization, there is a possibility that an aluminum
electrolytic capacitor may do a capacity depression.
In this case, please apply (for 30 to 60 minutes) rated voltage (AC100/110V). (About 1 time in three years.)

9.1.11 Design expected life


This product design expected life is 10 years. However, this is not a guarantee life.
If the trouble after exceeding a product-life cycle, please exchange for a new product.

9.1.12 Troubleshooting
Phenomenon Probable cause Necessary measures
The input is not applied. Check of connection.
CHARGE LED is not
(It is not wiring. An voltage is low.) Again, apply an input.
lighted.
Trouble of equipment (PBU-93). Exchange of equipment
The input is not applied. Check of connection.
(It is not wiring. An voltage is low.) Again, apply an input.
Connected DMR-Pro
The control power supply is not provided to DMR-Pro. Check of connection.
does not operate.
(It is not wiring. An voltage is low.) Again, apply an input.
Trouble of equipment (PBU-93 or DMR-Pro). Exchange of equipment
The points of a discharge terminal are different. Check a terminal position.
Discharge treatment
The input is applying. Cutoff of an input power supply
cannot be performed.
Trouble of equipment (PBU-93). Exchange of equipment
An input voltage is low. Again, apply an input.
Blackout guarantee
Trouble of equipment (PBU-93). Exchange of equipment
time is short.
Equipment (PBU-93) is over the life period. Exchange of equipment

9.1.13 Warranty
The warranty period of this product is for one year after product delivery.
Product failure which we are not responsible for (When responsibility in manufacturing process is not recognized,
when product is disassembled/remodeled, in case of false operation by customer, etc.) is beyond our warranty.
In addition, please refer to this product in addition because the applicable item of 1-4 pages of this instruction
manual is applied.

125
DMR-212-006

Appendix table 1) Power range, Watt-hour multiplying factor list (1/2) (VT range:15.00kV…210.0kV)
V range 210.0kV 180.0kV 150.0kV 105.0kV 90.0kV 45.0kV 30.0kV 18.00kV 15.00kV
(VT 154000 (VT 132000 (VT 110000 (VT 77000 (VT 66000 (VT 33000 (VT 22000 (VT 13800 (VT 11000
Multiplying /110V) /110V) /110V) /110V) /110V) /110V) /110V) /110V) /110V) Multiplying
factor A range [W] [W] [W] [W] [W] [W] [W] [W] [W] factor
1400 k 1200 k 1000 k 720 k 600 k 300.0 k 200.0 k 140.0 k 100.0 k
5A
(700) (125.5)
2800 k 2400 k 2000 k 1400 k 1200 k 600 k 400 k 280.0 k 200.0 k
10A
(250.9)
3600 k 3000 k 2400 k 1800 k 1500 k 720 k 480 k 320.0 k 240.0 k
12A
(3360) (2880) (1680) (1440) (301.1)
4.20 M 3600 k 3000 k 2400 k 1800 k 900 k 600 k 400 k 300.0 k
15A
(2100) (376)
5.60 M 4.80 M 4.00 M 2800 k 2400 k 1200 k 800 k 560 k 400 k
20A
(502)
7.20 M 6.00 M 5.00 M 3600 k 3000 k 1500 k 1000 k 640 k 500 k
25A
(7.00) (3500) (627)
8.40 M 7.20 M 6.00 M 4.20 M 3600 k 1800 k 1200 k 800 k 600 k
30A
×100 (753)
12.00 M 9.60 M 8.00 M 5.60 M 4.80 M 2400 k 1600 k 1000 k 800 k
40A
(11.20) (1004)
14.00 M 12.00 M 10.00 M 7.00 M 6.00 M 3000 k 2000 k 1400 k 1000 k
50A
(1255) ×10
18.00 M 15.00 M 12.00 M 8.40 M 7.20 M 3600 k 2400 k 1600 k 1200 k
60A
(16.80) (14.40) (1505)
24.00 M 18.00 M 15.00 M 12.00 M 9.00 M 4.50 M 3000 k 2000 k 1500 k
75A
(21.00) (10.50) (1882)
24.00 M 20.00 M 16.00 M 12.00 M 9.60 M 4.80 M 3200 k 2000 k 1600 k
80A
(22.40) (19.20) (11.20) (2007)
30.00 M 24.00 M 20.00 M 14.00 M 12.00 M 6.00 M 4.00 M 2800 k 2000 k
100A
(28.00) (2509)
36.00 M 30.00 M 24.00 M 18.00 M 15.00 M 7.20 M 4.80 M 3200 k 2400 k
120A
(33.60) (28.80) (16.80) (14.40) (3011)
42.0 M 36.00 M 30.00 M 24.00 M 18.00 M 9.00 M 6.00 M 4.00 M 3000 k
150A
(21.00) (3.76)
56.0 M 48.0 M 40.0 M 28.00 M 24.00 M 12.00 M 8.00 M 5.60 M 4.00 M
200A
(5.02)
72.0 M 60.0 M 50.0 M 36.00 M 30.00 M 15.00 M 10.00 M 6.40 M 5.00 M
250A
(70.0) (35.00) (6.27)
84.0 M 72.0 M 60.0 M 42.0 M 36.00 M 18.00 M 12.00 M 8.00 M 6.00 M
300A
×1000 (7.527)
120.0 M 96.0 M 80.0 M 56.0 M 48.0 M 24.00 M 16.00 M 10.00 M 8.00 M
400A
(112.0) (10.04)
140.0 M 120.0 M 100.0 M 72.0 M 60.0 M 30.00 M 20.00 M 14.00 M 10.00 M
500A
(70.0) (12.55) ×100
180.0 M 150.0 M 120.0 M 84.0 M 72.0 M 36.00 M 24.00 M 16.00 M 12.00 M
600A
(168.0) (144.0) (15.05)
240.0 M 180.0 M 150.0 M 120.0 M 90.0 M 45.0 M 30.00 M 20.00 M 15.00 M
750A
(210.0) (105.0) (18.82)
240.0 M 200.0 M 160.0 M 120.0 M 96.0 M 48.0 M 32.00 M 20.00 M 16.00 M
800A
(224.0) (192.0) (112.0) (20.07)
280.0 M 240.0 M 180.0 M 140.0 M 120.0 M 54.0 M 36.00 M 24.00 M 18.00 M
900A
(252.0) (216.0) (126.0) (108.0) (22.58)
280.0 M 240.0 M 200.0 M 140.0 M 120.0 M 60.0 M 40.0 M 28.00 M 20.00 M
1000A
(25.09)
360.0 M 300.0 M 240.0 M 180.0 M 150.0 M 72.0 M 48.0 M 32.00 M 24.00 M
1200A
(336.0) (288.0) (168.0) (144.0) (30.11)
420 M 360.0 M 300.0 M 240.0 M 180.0 M 90.0 M 60.0 M 40.0 M 30.00 M
1500A
(210.0) (37.6)
450 M 400 M 320.0 M 240.0 M 200.0 M 96.0 M 64.0 M 45.0 M 32.00 M
1600A
(448.0) (384.0) (224.0) (192.0) (40.1)
560 M 480 M 400 M 280.0 M 240.0 M 120.0 M 80.0 M 56.0 M 40.0 M
2000A
(50.2)
720 M 600 M 500 M 360.0 M 300.0 M 150.0 M 100.0 M 64.0 M 50.0 M
2500A
(700) (350.0) (62.7)
840 M 720 M 600 M 420 M 360.0 M 180.0 M 120.0 M 80.0 M 60.0 M
3000A
×10000 (75.3)
960 M 800 M 560 M 480 M 240.0 M 160.0 M 100.0 M 80.0 M
4000A
(100.4)
1000 M 720 M 600 M 300.0 M 200.0 M 140.0 M 100.0 M
5000A
(700) (125.5) ×1000
840 M 720 M 360.0 M 240.0 M 160.0 M 120.0 M
6000A
(150.5)
900 M 450 M 300.0 M 200.0 M 150.0 M
7500A
(188.2)
960 M 480 M 320.0 M 200.0 M 160.0 M
8000A
(200.7) ×10000
( ) is a primary power value at /1kW.

126
DMR-212-006

Appendix table 2) Power range, Watt-hour multiplying factor list (2/2) (VT range:150V…9000V)
V range 9000V 4500V 3000V 1500V 655V(600V) 627V(600V) 600V 300V 150V
(VT 6600 (VT 3300 (VT 2200 (VT 1100 (VT 480 (VT 460 (VT 440 (VT 220 (110V)
Multiplying /110V) /110V) /110V) /110V) /110V) /110V) /110V) /110V) Multiplying
factor A range [W] [W] [W] [W] [W] [W] [W] [W] [W] factor
60.0 k 30.00 k 20.00 k 10.00 k 4.50 k 4.20 k 4.00 k 2000 1000
5A
×1 (4.36) (4.18) ×0.01
120.0 k 60.0 k 40.0 k 20.00 k 9.00 k 8.40 k 8.00 k 4.00 k 2000
10A
(8.73) (8.36)
150.0 k 72.0 k 48.0 k 24.00 k 12.00 k 10.00 k 9.60 k 4.80 k 2400
12A
(144.0) (10.47) (10.04)
180.0 k 90.0 k 60.0 k 30.00 k 14.00 k 14.00 k 12.00 k 6.00 k 3000
15A
(13.09) (12.55)
240.0 k 120.0 k 80.0 k 40.0 k 18.00 k 18.00 k 16.00 k 8.00 k 4.00 k
20A
(17.45) (16.73)
300.0 k 150.0 k 100.0 k 50.0 k 24.00 k 24.00 k 20.00 k 10.00 k 5.00 k
25A
(21.82) (20.91)
360.0 k 180.0 k 120.0 k 60.0 k 28.00 k 25.00 k 24.00 k 12.00 k 6.00 k
30A
(26.18) (25.09)
480 k 240.0 k 160.0 k 80.0 k 36.00 k 36.00 k 32.00 k 16.00 k 8.00 k
40A
(34.91) (33.45)
600 k 300.0 k 200.0 k 100.0 k 45.0 k 42.0 k 40.0 k 20.00 k 10.00 k
50A
(43.6) (41.8) ×0.1
720 k 360.0 k 240.0 k 120.0 k 56.0 k 56.0 k 48.0 k 24.00 k 12.00 k
60A
(52.4) (50.2)
900 k 450 k 300.0 k 150.0 k 72.0 k 64.0 k 60.0 k 30.00 k 15.00 k
75A
(65.5) (62.7)
960 k 480 k 320.0 k 160.0 k 72.0 k 72.0 k 64.0 k 32.00 k 16.00 k
80A
×10 (69.8) (66.9)
1200 k 600 k 400 k 200.0 k 90.0 k 84.0 k 80.0 k 40.0 k 20.00 k
100A
(87.3) (83.6)
1500 k 720 k 480 k 240.0 k 120.0 k 100.0 k 96.0 k 48.0 k 24.00 k
120A
(1440) (104.7) (100.4)
1800 k 900 k 600 k 300.0 k 140.0 k 140.0 k 120.0 k 60.0 k 30.00 k
150A
(130.9) (125.5)
2400 k 1200 k 800 k 400 k 180.0 k 180.0 k 160.0 k 80.0 k 40.0 k
200A
(174.5) (167.3)
3000 k 1500 k 1000 k 500 k 240.0 k 240.0 k 200.0 k 100.0 k 50.0 k
250A
(218.2) (209.1)
3600 k 1800 k 1200 k 600 k 280.0 k 250.0 k 240.0 k 120.0 k 60.0 k
300A
(261.8) (250.9)
4.80 M 2400 k 1600 k 800 k 360.0 k 360.0 k 320.0 k 160.0 k 80.0 k
400A
(349.1) (334.5)
6.00 M 3000 k 2000 k 1000 k 450 k 420 k 400 k 200.0 k 100.0 k
500A
(436) (418) ×1
7.20 M 3600 k 2400 k 1200 k 560 k 500 k 480 k 240.0 k 120.0 k
600A
(524) (502)
9.00 M 4.50 M 3000 k 1500 k 720 k 640 k 600 k 300.0 k 150.0 k
750A
(655) (627)
9.60 M 4.80 M 3200 k 1600 k 720 k 720 k 640 k 320.0 k 160.0 k
800A
×100 (698) (669)
12.00 M 5.60 M 3600 k 1800 k 800 k 800 k 720 k 360.0 k 180.0 k
900A
(10.80) (5.40M) (785) (753)
12.00 M 6.00 M 4.00 M 2000 k 900 k 900 k 800 k 400 k 200.0 k
1000A
(873) (836)
15.00 M 7.20 M 4.80 M 2400 k 1200 k 1000 k 960 k 480 k 240.0 k
1200A
(14.40) (1047) (1004)
18.00 M 9.00 M 6.00 M 3000 k 1400 k 1400 k 1200 k 600 k 300.0 k
1500A
(1309) (1255)
20.00 M 9.60 M 6.40 M 3200 k 1400 k 1400 k 1400 k 640 k 320.0 k
1600A
(19.20) (1396) (1338) (1280)
24.00 M 12.00 M 8.00 M 4.00 M 1800 k 1800 k 1600 k 800 k 400 k
2000A
(1745) (1673)
30.00 M 15.00 M 10.00 M 5.00 M 2400 k 2400 k 2000 k 1000 k 500 k
2500A
(2182) (2091)
36.00 M 18.00 M 12.00 M 6.00 M 2800 k 2500 k 2400 k 1200 k 600 k
3000A
(2618) (2509)
48.0 M 24.00 M 16.00 M 8.00 M 3600 k 3600 k 3200 k 1600 k 800 k
4000A
(3491) (3345)
60.0 M 30.00 M 20.00 M 10.00 M 4.50 M 4.20 M 4.00 M 2000 k 1000 k
5000A
(4.36) (4.18) ×10
72.0 M 36.00 M 24.00 M 12.00 M 6.00 M 5.60 M 4.80 M 2400 k 1200 k
6000A
(5.24) (5.02)
90.0 M 45.0 M 30.00 M 15.00 M 7.20 M 6.40 M 6.00 M 3000 k 1500 k
7500A
(6.55) (6.27)
96.0 M 48.0 M 32.00 M 16.00 M 7.20 M 7.20 M 6.40 M 3200 k 1600 k
8000A
×1000 (6.98) (6.69) ×100
( ) is a primary power value at /1kW.

127
DMR-212-006

Appendix table 3) Setting item list (For model) (1)


Setting Reference pages Setting item
Application
No. Check Setting DMR-FN DMR-GN
1101 Set the factor which indicates by P52,53 P62…64 Display pattern
1102 measurement to each monitor (main The main monitor display factor
1103 monitor, sub-monitor, bar graph) Sub-monitor (left) display factor
1104 of a LCD. Sub-monitor (center) display factor
1105 Sub-monitor (right) display factor
1106 Bar graph display factor
1201 Set the zero phase voltage rating P52 P65…68 Voltage measurement range Voltage measurement range
1202 and the output range of a zero Current measurement range Current measurement range
1203 phase voltage output (analog Power polarity Power polarity
1204 output, communication output) in Power measurement range Power measurement range
the display range of various Reactive power measurement Reactive power measurement
1205
measurement factors. range range
1206 Power factor measurement range Power factor measurement range
1207 Frequency measurement range Frequency measurement range
73 Zero phase voltage rating
1208 ( ) -
(EVT)
Zero phase voltage output
1209 (72) -
range
1301 Set the measurement display of P52 P69 A display ON/OFF A display ON/OFF
1302 each measurement factor. Amax. display ON/OFF Amax. display ON/OFF
1303 If it sets here at OFF, it becomes V display ON/OFF V display ON/OFF
1304 impossible to select measurement Vmax. display ON/OFF Vmax. display ON/OFF
1305 factor in the case of the main Vmin. display ON/OFF Vmin. display ON/OFF
1306 monitor display change. W display ON/OFF W display ON/OFF
1307 var display ON/OFF var display ON/OFF
1308 cosφ display ON/OFF cosφ display ON/OFF
1309 Hz display ON/OFF Hz display ON/OFF
1310 Wh display ON/OFF Wh display ON/OFF
1311 varh display ON/OFF varh display ON/OFF
1312 A0 display ON/OFF A0 display ON/OFF
1313 A0max. display ON/OFF A0max. display ON/OFF
1314 V0 display ON/OFF -
1315 V0max. display ON/OFF -
1401 Set the measurement display of each P52 P70 L1 phase display ON/OFF L1 phase display ON/OFF
phase (line) with current and a
1402 L2 phase display ON/OFF L2 phase display ON/OFF
voltage measurement factor.
1403 If it sets here at OFF, it becomes L3 phase display ON/OFF L3 phase display ON/OFF
1404 impossible to select the L1L2 line display ON/OFF L1L2 line display ON/OFF
measurement factor of the phase (or
1405 L2L3 line display ON/OFF L2L3 line display ON/OFF
line) of relevance in the case of
1406 the main monitor display change. L3L1 line display ON/OFF L3L1 line display ON/OFF
72
1501 ( ) Set the output factor of each P52 P71 Analog output 1 factor Analog output 1 factor
1502 (72) output. Analog output 2 factor Analog output 2 factor
1503 (72) Analog output 3 factor Analog output 3 factor
1504 (72) Analog output 4 factor Analog output 4 factor
Adjust the output sensitivity (% P52 P71,72 Output intrinsic sensitivity Output intrinsic sensitivity
1505 (72)
of an output to an input) of W and (W) (W)
72 a var output. Output intrinsic sensitivity Output intrinsic sensitivity
1506 ( )
(var) (var)
1601 (72) Set the output factor of a pulse P52 P73 Pulse output factor Pulse output factor
1602 (72) output. Pulse unit Pulse unit
1701 (72) Set the communication output P52 P74,75 Address
1702 (72) (Modbus). Transmission rate
1703 (72) Parity
1704 (72) Stop bit
Note(72) Only with an option.
Note(73) Only EVT specification.

128
DMR-212-006

Appendix table 3) Setting item list (For model) (2)


Setting Reference pages Setting item
Application
No. Check Setting DMR-FN DMR-GN
2101 Perform various setting of a 50: 50: 50 Used/Unused 50 Used/Unused
2102 protection relay 1. P53…56 P77,78 50 Current operating value 50 Current operating value
2103 If it sets unused, don't perform 50 Operating time 50 Operating time
2104 detection by external equipment. 50 Reset method 50 Reset method
A protection factor changes by the 50 "ON" control within 50 "ON" control within
2105 model. protection detection protection detection
display display
2201 Perform various setting of a 51: 51: 51 Used/Unused 51 Used/Unused
2202 protection relay 2. P53…56 P79,80 51 Characteristic 51 Characteristic
2203 If it sets unused, don't perform 51 Current operating value 51 Current operating value
2204 detection by external equipment. 51 Time multiplier 51 Time multiplier
2205 A protection factor changes by the 51 Reset method 51 Reset method
model. 51 "ON" control within 51 "ON" control within
2206 protection detection protection detection
display display
2301 Perform various setting of a 67: 67: 67 Used/Unused 51G Used/Unused
2302 protection relay 3. P53…56 P81…83 67 Current operating value 51G Current operating value
2303 If it sets unused, don't perform 67 Voltage operating value 51G Operating time
2304 detection by external equipment. 51G: 51G: 67 Operating angle 51G 2nd harmonic suppression
A protection factor changes by the P53…56 P84,85 51G "ON" control within
2305 model. 67 Operating time protection detection
display
2306 67 Reset method -
67 Zero phase current input
2307 -
correction
67 "ON" control within
2308 protection detection -
display
Perform various setting of an
2401 Used/Unused
external trip (DI5).
P53…56 P92
If it sets unused, don't perform
2402 "ON" control within protection detection display
detection by external equipment.
Set the reset time common to a
2501 P53…56 P93 Reset time
protection factor.
Set the zero phase monitor of a
2601 P53…56 P93 Zero phase monitor
fail-safe function.

129
DMR-212-006

Appendix table 3) Setting item list (For model) (3)


Setting Reference pages Setting item
Application
No. Check Setting DMR-BN DMR-SN
1101 Set the factor which indicates by P52 P62…64 Display pattern
1102 measurement to each monitor (main The main monitor display factor
1103 monitor, sub-monitor, bar graph) Sub-monitor (left) display factor
1104 of a LCD. Sub-monitor (center) display factor
1105 Sub-monitor (right) display factor
1106 Bar graph display factor
1201 Set the zero phase voltage rating P52 P65…68 Voltage measurement range Voltage measurement range
1202 and the output range of a zero Frequency measurement range Current measurement range
phase voltage output (analog Zero phase voltage rating
1203 Power polarity
output, communication output) in (EVT)
the display range of various Zero phase voltage output
1204 Power measurement range
measurement factors. range
Reactive power measurement
1205 -
range
1206 - Power factor measurement range
1207 - Frequency measurement range
1208 (75) - -
1209 (74) - -
1301 Set the measurement display of P52 P69 V display ON/OFF A display ON/OFF
1302 each measurement factor. Vmax. display ON/OFF Amax. display ON/OFF
1303 If it sets here at OFF, it becomes Vmin. display ON/OFF V display ON/OFF
1304 impossible to select measurement Hz display ON/OFF Vmax. display ON/OFF
1305 factor in the case of the main V0 display ON/OFF Vmin. display ON/OFF
1306 monitor display change. V0max. display ON/OFF W display ON/OFF
1307 - var display ON/OFF
1308 - cosφ display ON/OFF
1309 - Hz display ON/OFF
1310 - Wh display ON/OFF
1311 - varh display ON/OFF
1312 - -
1313 - -
1314 - -
1315 - -
1401 Set the measurement display of P52 P70 L1L2 line display ON/OFF L1 phase display ON/OFF
each phase (line) with current and
1402 a voltage measurement factor. L2L3 line display ON/OFF L2 phase display ON/OFF
1403 If it sets here at OFF, it becomes L3L1 line display ON/OFF L3 phase display ON/OFF
impossible to select the
1404 measurement factor of the phase - L1L2 line display ON/OFF
1405 (or line) of relevance in the case - L2L3 line display ON/OFF
of the main monitor display
1406 change. - L3L1 line display ON/OFF
1501 (74) Set the output factor of each P52 P71 Analog output 1 factor Analog output 1 factor
1502 (74) output. Analog output 2 factor Analog output 2 factor
1503 (74) Analog output 3 factor Analog output 3 factor
1504 (74) - Analog output 4 factor
Adjust the output sensitivity (% P52 P71,72 Output intrinsic sensitivity
1505 (74) -
of an output to an input) of W and (W)
a var output. Output intrinsic sensitivity
1506 (74) -
(var)
1601 (74) Set the output factor of a pulse P52 P73 - Pulse output factor
1602 (74) output. - Pulse unit
1701 (74) Set the communication output P52 P74,75 Address
1702 (74) (Modbus). Transmission rate
1703 (74) Parity
1704 (74) Stop bit
Note(74) Only with an option.
Note(75) Only EVT specification.

130
DMR-212-006

Appendix table 3) Setting item list (For model) (4)


Setting Reference pages Setting item
Application
No. Check Setting DMR-BN DMR-SN
2101 Perform various setting of a 50: 50: 27 Used/Unused 50 Used/Unused
2102 protection relay 1. P53…56 P77,78 27 Voltage operating value 50 Current operating value
2103 If it sets unused, don't perform 27 Operating time 50 Operating time
2104 detection by external equipment. 27: 27: 27 Reset method 50 Reset method
A protection factor changes by the P53…56 P86,87 27 "ON" control within 50 "ON" control within
2105 model. protection detection protection detection
display display
2201 Perform various setting of a 51: 51: 59 Used/Unused 51 Used/Unused
2202 protection relay 2. P53…56 P79,80 59 Voltage operating value 51 Characteristic
2203 If it sets unused, don't perform 59 Operating time 51 Current operating value
2204 detection by external equipment. 59: 59: 59 Reset method 51 Time multiplier
A protection factor changes by the P53…56 P88,89 59 "ON" control within
2205 model. protection detection 51 Reset method
display
51 "ON" control within
2206 - protection detection
display
2301 Perform various setting of a 64: 64: 64 Used/Unused 27 Used/Unused
2302 protection relay 3. P53…56 P90,91 64 Voltage operating value 27 Voltage operating value
2303 If it sets unused, don't perform 64 Operating time 27 Operating time
2304 detection by external equipment. 27: 27: 64 Reset method 27 Reset method
A protection factor changes by the P53…56 P86,87 64 "ON" control within 27 "ON" control within
2305 model. protection detection protection detection
display display
Perform various setting of an
2401 Used/Unused
external trip (DI5).
P53…56 P92
If it sets unused, don't perform
2402 "ON" control within protection detection display
detection by external equipment.
Set the reset time common to a
2501 P53…56 P93 Reset time
protection factor.
Set the zero phase monitor of a
2601 P53…56 P93 Zero phase monitor
fail-safe function.

Tokyo Office : 11-13, Hitotsuya 1-chome, Adachi-ku, Tokyo, 121-8639, JAPAN.


TEL:+81-3-3885-2411 , Fax:+81-3-3858-3966
Kyoto Office : 1-19, Ichinobe-Nishikawahara, Jyoyou-shi, Kyoto, 610-0114, JAPAN.
TEL:+81-774-55-1391 , Fax:+81-774-54-1353

DATE:March 12, 2012

131