DIMENSIONS
CONTROLLER PROGRAMMER ube MANUAL RETRIEVAL
KM3 is a panel mounting, Class II instrument. It has been
Unit
(°C/°F)
(in eng. units)
Autotune
Overall dimensions (L x H x D): 48 x 48 x 63 mm
(1.89 x 1.89 x 2.48 in.)
1/16 DIN - 48 x 48 designed with compliance to the European Directives. Alarm in progress Panel Cut-out (L x H): 45+0.6 x 45+0.6 mm
active (flashing) (1.78+0.023 x 1.78+0.023 in.)
KM3 model All information about the controller use can be found in the
Engineering Manual: ISTR-MKM3-ENG0x (“x” is the revision). Set Point
Quick Guide • ISTR-FKM3ENG02 Manual
The Declaration of Conformity and the manual of the controller (auto mode)
mode
can be downloaded (free of charge) from the web-site: Output Value
www.ascontecnologic.com (manual mode)
Output Param. value or
Once connected to the web-site, search: LEDs State/Function
KM3 (Editing mode)
then click on KM3.
In the lower part of the product page (in any language) is present
the download area with links to the documents available for the Operator Mode Editing Mode
controller (in the available languages). MOUNTING 3
Access to: 2
- Operator Commands
(Timer, Setpoint selection ...) Confirm and go to
- Parameters Next parameter
- Configuration
Access to: Increase the displayed
Warning! - Operator additional information 1
value or select the
- Whenever a failure or a malfunction of the device may cause (Output value, running time ...) next element of the
dangerous situations for persons, things or animals, please - Parameter setting parameters list
remember that the plant must be equipped with additional - Configuration
devices which will guarantee safety. Decrease the displayed
Access to:
- We warrant that the products will be free from defects in material and - Set Point
value or select the 2
via Indipendenza 56, 27029 - Vigevano (PV) - ITALY previous element
workmanship for 18 months from the date of delivery. Products
Tel.: +39 0381 698 71, Fax: +39 0381 698 730 Programmable key: Exit from Operator
and components that are subject to wear due to conditions of commands/Parameter
internet site: www.ascontecnologic.com Start the programmed function
use, service life and misuse are not covered by this warranty. (Autotune, Auto/Man, Timer ...) setting/Configuration 1
E-mail: sales@ascontecnologic.com
CONFIGURATION CODE
The KM3 can be easily configured by the “Code Configuration” method for the most common requirements, just entering two 4-digit
codes: Cod1 [LMNO] for the Input Type and Control Mode selection and Cod2 [PQRS] for the Alarms and the Service Functions.
For complete controller configuration see the Engineering Manual.
Note: Before starting the configuration code setting, please define and write down Cod1 and Cod2 as needed:
HOW TO SET THE CONFIGURATION CODE L M N O c%d1 ALARM TYPES (Cod2 digits: P, Q, R)
User c%d1 L MN O Absolute Alarm
PV
PV
Input Type and Range L M Control mode OP1 OP2 OP3 OP4 N O
TC J -50... +1000°C 0 0 H AL1 AL2 AL3 0 0
ON/OFF heating = H
AT
TC K -50... +1370°C 0 1 NU AL1 AL2 H 0 1
TC S -50... 1760°C 0 2 C AL1 AL2 AL3 0 2 Time
ON/OFF cooling = C ON
TC R -50... +1760°C 0 3 NU AL1 AL2 C 0 3 Absolute
High
Press for 3 seconds to TC T -70... +400°C 0 4 H C AL2 AL3 0 4 ON ON
Absolute
access the configuration Infrared J -50... +785°C 0 5 H AL1 AL2 C 0 5 Low
mode Infrared K -50... +785°C 0 6 ON/OFF with neutral zone C H AL2 AL3 0 6
PV
PT 100/PTC KTY81-121 -200... +850°C/-55... +150°C 0 7 (H/C) NU H AL2 C 0 7
PT 1000/NTC 103-AT2 -200... +850°C/-50... +110°C 0 8 C AL1 AL2 H 0 8 Absolute High-Low Alarm
AT
Linear 0... 60 mV 0 9 NU C AL2 H 0 9 PV
Linear 12... 60 mV 1 0 H AL1 AL2 AL3 1 0
PID heating = H
Linear 0... 20 mA (this selection forces Out 4 = TX) 1 1 NU AL1 AL2 H 1 1
Linear 4... 20 mA (this selection forces Out 4 = TX) 1 2 C AL1 AL2 AL3 1 2
Press and to enter PID cooling = C
Linear 0... 5 V 1 3 NU AL1 AL2 C 1 3
the configuration
Linear 1... 5 V 1 4 H C AL2 AL3 1 4
Password 4 Time
Linear 0... 10 V 1 5 H AL1 AL2 C 1 5
(default 300) PV Absolute ON ON
Linear 2... 10 V 1 6 C H AL2 AL3 1 6 External
PID double action (H/C)
TC J -58... +1832°F 1 7 NU H AL2 C 1 7 ON ON
Absolute
AT
TC K -58... +2498°F 1 8 C AL1 AL2 H 1 8 Internal
TC S -58... 3200°F 1 9 NU C AL2 H 1 9
TC R -58... +3200°F 2 0
Press and to enter TC T -94... +752°F 2 1 Deviation Alarm
c%d1 (Input Type and Infrared J -58... +1445°F 2 2 PV
Control Mode) Infrared K -58... +1445°F 2 3
PT 100/PTC KTY81-121 -328... +1562°F/-67... +302°F 2 4
PV
AT
P Q R S c%d2 Time
User c%d2 P Q R S Deviation ON
High
ON ON
Press and to enter Alarm 3 R Service functions activation S
Deviation
c%d2 (Alarms and Low
Alarm 2 Q None 0
Service Functions) Wattmeter (instantaneous power expressed in kW) (note 1) 1
Alarm 1 P
PV
Not used 0 0 0 Wattmeter (Power consuption expressed in kWh/h) (note 2) 2
Band Alarm
Sensor break 1 1 1 Absolute worked time (expressed in days) (note 3) 3
PV
AT
High 2 2 2 Absolute worked time (expressed in hours) (note 3) 4
Absolute
Low 3 3 3 Notes: 1. Wattmeter Instantaneous power is continuously computed
External High/Low 4 4 4 as multiplication of the Load Voltage, Load Current parameter
Absolute High/Low
Internal High/Low 5 5 5 values and the controller output instantaneous value.
Press to store the Deviation high 6 6 6 2. Wattmeter power consumption is the estimated hourly
energy consumption (using Load Voltage and Load Current Time
Configuration code Deviation
Deviation low 7 7 7 ON ON
parameter values), computed on the previous 15 minutes Band
External band 8 8 8 period. The readout is updated every 15 minutes. Internal
Note: To leave the Configuration session without Band
Internal band 9 9 9 3. Worked Time counter is continuously increased when Band ON ON ON
saving the settings made, press the button the controller is turned ON. External
Note: To access all the instrument features, please see the “Complete configuration procedure” in the “Engineering Manual”.
Complete Configuration and Parameter setting can be easily uploaded from the controller and downloaded to other controllers using the:
Configuration Key and Communication Adapter model: A-01.
FUNCTION SELECTION
Timer Types (selected by tr.f) (option) dif$ Digital Inputs DI1 and DI2 Functions usrb Key Function
i.d.a Delayed ON at Start command i.p.l Asymmetrical oscillator with start in OFF Code displayed Description Code displayed Description
Tr.t1 Tr.t2 Tr.t2 Tr.t2 Tr.t2 0 Disabled (OFF) (default) nonE Not used
Start Start Tr.t1 Tr.t1 Tr.t1 1 Alarm Reset tune Starts auto tuning functions (default)
off ON off off ON off ON off ON 2 Alarm Acknowledge (ACK) oplo Manual mode
OUT OUT
3 Hold of the measured value aac Alarm Reset
PWR ON Reset 4 Stand by mode asi Alarm Acknowledge
5 Manual Mode chsp Circular Set Point Selection (shows SP, SP2, SP3)
i.up.d Delayed ON at Power ON i.L.p Asymmetrical oscillator with start in ON
6 Heat with “SP” and CooL with “SP2” st.by Stand-by mode
Tr.t1 Tr.t2 Tr.t2 Tr.t2 Tr.t2 7 Timer Run/Hold/Reset [on transition] str.t Starts/Stop/Reset timer
Start Tr.t1 Tr.t1 Tr.t1
8 Timer Run [on transition]
ON off ON off ON off Available only if
off ON off OUT
9 Timer Reset [on transition]
timer option and
OUT 10 Timer Run/Hold
PWR ON Reset tr.F is NOT set to
11 Timer Run/Reset nonE
i.d.d At Start command 12
Timer Run/Reset with lock at the end
of the time count
Tr.t1 18 Sequential Set Point selection [on transition]
Start
19 SP/SP2 selection
ON off Binary coding for Set Point selection on DI1 and DI2
OUT 20
(00 = SP, 01 = SP2, 10 = SP3, 11 = SP4)
Reset Digital inputs in parallel to the UP and Down keys
21
PWR ON (DI1 = UP key, DI2 = DOWN key)