Cable Specification 400kV AL-800SQ
Cable Specification 400kV AL-800SQ
: LSGS-15-PC0405
User/Customer : CFE Page No. : 1 of 4
Project Title : 400kV – CFE 314 LT RED DE TRANSMISIÓN ASOCIADA AL CC EMPALME II (1911)
Bidder : LS Cable & System Ltd.
Document Title
Specification
For
400kV XLPE POWER CABLE
This specification covers the construction, dimensions and tests of 400kV single core, XLPE insulated, smooth welded
aluminum sheathed and black HDPE outer sheathed power cable.
2. Reference standards
Construction of the cable shall meet the requirements specified in the attached table and as follows.
3.1 Conductor
The conductor shall consist of compacted circular construction from the aluminum wires in accordance with IEC
60228(class 2). The conductor shall be water sealed by addition of a swellable tape between each layer of conductor
wires.
The conductor screen shall consist of an extruded layer of semi-conducting thermosetting compound.
Semi-conducting tape(s) shall be applied between the conductor and the conductor screen.
3.3 Insulation
The insulation shall consist of an extruded layer of cross-linked polyethylene (XLPE) over the conductor screen.
The minimum average thickness shall be not less than the nominal thickness specified and the minimum thickness at
any point shall be not less than 95% of nominal thickness specified in the attached table.
The insulation screen shall consist of an extruded layer of semi-conducting thermosetting compound and shall be firmly
bonded to the insulation. The conductor screen, insulation and insulation screen shall be extruded simultaneously by dry
curing process.
The semi-conducting swellable tape(s) shall be applied over the insulation screen to prevent longitudinal water
penetration.
The metallic sheath shall consist of a smooth welded aluminum sheath. The minimum thickness at any point shall not fall
below 90%-0.1mm of the nominal thickness given in the attached table.
The outer sheath shall be extruded black HDPE compound with semi-conducting layer. The minimum average
thickness shall be not less than nominal thickness specified and the minimum thickness at any point shall be not less
Ref. No. : LSGS-15-PC0405
Rev. No. : 0
Page No. : 3 of 4
than 4.0mm.
The conductive layer shall be extruded on the outer sheath to serve as electrode for the voltage test on the outer sheath
4. Cable Marking
The following description shall be embossed on the outer sheath throughout the entire length of the cable at regular
intervals, so that the unmarked surface is equal of less than 60cm.
Ex) LS Cable & System CFE IEC 62067-2011 800mm2 Al XLPE 26mm Al Bw 230/400(420)kV 2015
Continuously increasing meter marking shall be provided on the outer sheath at an interval of 1 meter.
Immediately after the works tests, one end of the cable length shall be sealed by means of metal cap and the other of the
cable length shall be sealed by pulling eye. The complete cable shall be wound on non-returnable metallic drum. All
cable drums shall be arranged to take a round spindle and lagged with closely fitting metal sheets.
6. Tests
The following tests shall be carried out at manufacturer’s works according to the procedure of IEC 62067.
Attached Table
1 5
2 6
3 7
4 8