Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Find this product online: elandcables.

com | Cables & Accessories


Medium Voltage Cable | NA2XSY Aluminium Conductor XLPE PVC - 18/30 (36)kV Cable

NA2XSY Aluminium Conductor


XLPE PVC - 18/30 (36)kV Cable

Eland Product Group: A9X

APPLICATION CABLE STANDARDS


To be laid directly in ground, outdoors, indoors and in cable DIN VDE 0276-620, HD 620 S1, DIN/BS EN 60228,
ducts. Medium voltage cables for distribution networks, BS EN/IEC 60332-1-2
also for connection to generation units and plant and
process connection.

CONSTRUCTION The electrical and dimensional properties of this product are measured by the
Technical and Quality Assurance department at the Eland Cables laboratory. Cable
Conductor performance in respect of conductor resistance, construction quality (workmanship),
Class 2 stranded aluminium conductor dimensional consistency, and other parameters are verified to published standards
and approved product drawings. Conformance to RoHS (Restriction of the use of
Inner Semi-Conductive Layer Hazardous Substances) is determined and confirmed.
Semi-conductive material

Insulation CHARACTERISTICS
XLPE (Cross-Linked Polyethylene)
Voltage Rating (Uo/U)(Um)
18/30 (36)kV
Outer Semi-Conductive Layer
Semi-conductive material
Test Voltage
63kV
Screen
Copper wires
Temperature Rating
Fixed: -20°C to +70°C
Sheath
Flexed: -5°C to +70°C
PVC (Polyvinyl Chloride)
Short Circuit Temperature
+250°C

Minimum Bending Radius


15 x overall diameter

Sheath Colour
Red
ISSUE NO 01-03 -2014

UK T 020 7241 8787 | F 020 7241 8700 | sales@elandcables.com | www.elandcables.com


technicalspecification | 1 of 2
International T +44 20 7241 8740 | F +44 20 7241 8700 | international@elandcables.com
Find this product online: elandcables.com | Cables & Accessories
Medium Voltage Cable | NA2XSY Aluminium Conductor XLPE PVC - 18/30 (36)kV Cable

DIMENSIONS
ELAND PART NO. NO. OF NOMINAL CROSS MAXIMUM OVERALL NOMINAL WEIGHT
CORES SECTIONAL AREA DIAMETER kg/km
mm
Conductor Copper Wire Screen
mm² mm²

A9XA30KV1050 1 50 RM/16 41 1190


A9XA30KV1070 1 70 RM/16 42 1315
A9XA30KV1095 1 95 RM/16 43 1450
A9XA30KV1120 1 120 RM/16 45 1580
A9XA30KV1150 1 150 RM/25 47 1800
A9XA30KV1185 1 185 RM/25 49 1965
A9XA30KV1240 1 240 RM/25 51 2230
A9XA30KV1300 1 300 RM/25 53 2470
A9XA30KV1400 1 400 RM/35 56 2920

ELECTRICAL CHARACTERISTICS
ELAND PART NO. NO. OF NOMINAL CROSS CURRENT CARRYING CAPACITY
CORES SECTIONAL AREA
In Trefoil

Conductor Copper Wire Screen In Ground In Air


mm² mm² Amps Amps

A9XA30KV1050 1 50 RM/16 175 187


A9XA30KV1070 1 70 RM/16 214 232
A9XA30KV1095 1 95 RM/16 256 281
A9XA30KV1120 1 120 RM/16 290 323
A9XA30KV1150 1 150 RM/25 324 365
A9XA30KV1185 1 185 RM/25 366 418
A9XA30KV1240 1 240 RM/25 426 494
A9XA30KV1300 1 300 RM/25 479 564
A9XA30KV1400 1 400 RM/35 545 654
ISSUE NO 01-03 -2014

The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of
publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.

UK T 020 7241 8787 | F 020 7241 8700 | sales@elandcables.com | www.elandcables.com


2 of 2 | technicalspecification
International T +44 20 7241 8740 | F +44 20 7241 8700 | international@elandcables.com

You might also like