PRMS Technical Specifications 2

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

March 28th 2014

Technical specification PRMS


to

Oando / Gaslink
Att.: Shehu
2, Ajose Adeogun Street
Victoria Island
Lagos - Nigeria
from

Elster-Instromet A/S, Denmark


Att.: René Gårdsvig, MD
Anholtvej 1, 9800 Hjørring, Denmark
Tel.: +45 98911055, mobil +45 40307380
Reference: Quote T140090, revision 1;
20140323_GNL_RFQ026.
Revision 0: Technical specification.
Revision 1: Changed sizing of regulators on type 1-3.
Technical specification PRMS

General design data for all PRMS:


Design pressure upstream / downstream: 19 / 10 barG.
Strength test pressure: 1,5 x design pressure. 29 / 15 barG.
All stations with full documentation, including CE/PED/ATEX conformity declaration.
All stations with full SCADA package with solar panels.

1) Specification for PRMS type 3-3, 19 pieces


Flow: Maximum 1000 Sm3/h, rated 800 Sm3/h, minimum 80 Sm3/h.
Inlet pressure: Maximum 19.2 barG, normal 17 barG and minimum 3,5 barG.
Outlet pressure: Maximum 3,5 barG, normal 1,5 barG and minimum 0,5 barG.
Gas temperature: Maximum 45 C, normal 30 C and minimum 25 C.
Inlet flange connection: 3”ANSI 150RF.
As our drawing 10772NR071 rev. 1, as former delivered.
See main components in flow direction:
- 3”ANSI 150 ball valve, BAC, high quality, tight and reliable.
- 3”ANSI 150 welded filter, 5 my filter inserts, type HFA 1,5.
- 3”ANSI 150 rotary meter type Elster Rabo G250, 1:100 range, giving 400 m3/h
corresponding to maximum 1800 Sm3/h at minimum inlet pressure 3,5 barG. And
minimum flow of 80 Sm3/h at maximum pressure 19 barG (worst case conditions).
So calibrated range with above pressures is 80 to 1800 Sm3/h. Compatible with
former Delta meters.
- 3”-1”ANSI 150 reducer spool.
- 1”ANSI 150 SSV type Fiorentini SB82.
- 1”ANSI 150 Regulator with integrated SSV type Fiorentini Reval 182 SB82.
- 1”-3”ANSI 150 spool for sensor lines, relief valve, pressure indicator and blow-off.
- 3”ANSI 150 butterfly valve.

Comments:
Meter: We have taken a flow size bigger (G250 instead of G160) than you have now,
however in same dimension and with a larger metering range (1:100).
2) Specification for PRMS type 1-3, 2 pieces
Flow: Maximum 1200 Sm3/h, rated 1000 Sm3/h, minimum 80 Sm3/h.
Inlet pressure: Maximum 19.2 barG, normal 17 barG and minimum 3,5 barG.
Outlet pressure: Maximum 3,5 barG, normal 1,5 barG and minimum 0,5 barG.
Gas temperature: Maximum 45 C, normal 30 C and minimum 25 C.
Inlet flange connection: 3”ANSI 150RF.
As your drawing 0107040.
See main components in flow direction:
- 3”ANSI 150 ball valve, BAC, high quality, tight and reliable.
- 3”ANSI 150 welded filter, 5 my filter inserts, type HFA 1,5.
- 3”ANSI 150 turbine meter Elster TRZ2 G250, range 1:30 (1:50), or alternative
rotary meter type Elster Rabo G250, 1:100 range, giving 400 m3/h corresponding to
maximum 1800 Sm3/h at minimum inlet pressure 3,5 barG. And minimum flow of 80
Sm3/h for rotary meter at maximum pressure 19 barG (worst case conditions). So
calibrated range with above pressures is 80 to 1800 Sm3/h.
- 3”-2”ANSI 150 reducer spool.
- 2”ANSI 150 SSV type Fiorentini SB82.
- 2”ANSI 150 Regulator with integrated SSV type Fiorentini Reval 182 SB82.
- 2”-4”ANSI 150 spool for sensor lines, relief valve, pressure indicator and blow-off.
- 4”ANSI 150 butterfly valve.

Comments:
1) Meter: With a rotary meter the range will be better than with the turbine meter. If
rotary meter then the meter is the same as on type 3-3”.
2) Regulator and SSV is 2”instead of 1½”, which ensure flow capacity. Actually up to
1800 Sm3/h even at low pressures.
3) Specification for type Small Volume Meters (Industrial Standard PRMS). 16
pieces
Flow: Maximum 200 Sm3/h, rated 120 Sm3/h, minimum 5 Sm3/h.
Inlet pressure: Maximum 19.2 barG, normal 17 barG and minimum 3,5 barG.
Outlet pressure: Maximum 3,5 barG, normal 1,5 barG and minimum 0,5 barG.
Gas temperature: Maximum 45 C, normal 30 C and minimum 25 C.
Corresponding our drawing 10772NR081 rev. 2.
See main components in flow direction:
- 1”ANSI 150 ball valve, BAC, high quality, tight and reliable.
- 1”ANSI 150 welded filter, 5 my filter inserts.
- 1”ANSI 150 SSV type Fiorentini.
- 1”ANSI 150 spool, bend.
- 1”ANSI 150 regulator with SSV type Fiorentini Dival 500.
- 1”-2”spool for sensor lines, relief valve, manometer and blow-off valve.
- 2”ANSI 150 rotary meter type Elster Rabo, G100 with 160 m3/h maximum,
corresponding to maximum 240 Sm3/h at minimum pressure 0,5 barG (worst case).
1:100 giving minimum flow 5 Sm3/h at maxium pressure. Total worst case
calibrated metering range 240 to 5 Sm3/h.
- 2”ANSI 150 ball valve with manual lever.
4) Specification for PRMS type 1-4, 9 pieces
Flow: Maximum 7000 Sm3/h, rated 5000 Sm3/h, minimum 150 Sm3/h.
Inlet pressure: Maximum 19.2 barG, normal 17 barG and minimum 3,5 barG.
Outlet pressure: Maximum 3,5 barG, normal 1,5 barG and minimum 0,5 barG.
Gas temperature: Maximum 45 C, normal 30 C and minimum 25 C.
As your drawing 0107040.
See main components in flow direction:
- 6”ANSI 150 ball valve, BAC, high quality, tight and reliable.
- 6”ANSI 150 welded filter, 5 my filter inserts, type HFA 3.
- 6”ANSI 150 turbine meter Elster TRZ2 G1000, range 1:30 (1:50), giving 1600 m3/h
corresponding to maximum 7200 Sm3/h at minimum inlet pressure 3,5 barG. And
minimum flow of 640 Sm3/h at maximum pressure 19 barG (worst case conditions).
So calibrated range with above pressures is 640 to 7200 Sm3/h. With official proof
that range is minimum 440 Sm3/h and that the meter measures down to 150
Sm3/h, but with a less accuracy.
- 6”-3”ANSI 150 reducer spool.
- 3 ANSI 150 SSV type Fiorentini SB82.
- 3”ANSI 150 Regulator with integrated SSV type Fiorentini Reval 182 SB82.
- 3”-8”ANSI 150 spool for sensor lines, relief valve, pressure indicator and blow-off.
- 8”ANSI 150 butterfly valve.
5) Specification for DPRMS 5000, 2 pieces
Double stream station.
Flow: Maximum 7000 Sm3/h, rated 5000 Sm3/h, minimum 150 Sm3/h.
Inlet pressure: Maximum 19.2 barG, normal 17 barG and minimum 3,5 barG.
Outlet pressure: Maximum 3,5 barG, normal 1,5 barG and minimum 0,5 barG.
Gas temperature: Maximum 45 C, normal 30 C and minimum 25 C.
Similar layout as your drawing 0107012.
See main components in flow direction:
- 6”ANSI 150 spool for distribution to 2 identical streams:
- 6”ANSI 150 ball valve, BAC, high quality, tight and reliable.
- 6”ANSI 150 welded filter, 5 my filter inserts, type HFA 3.
- 6”ANSI 150 turbine meter Elster TRZ2 G1000, range 1:30 (1:50), giving 1600 m3/h
corresponding to maximum 7200 Sm3/h at minimum inlet pressure 3,5 barG. And
minimum flow of 640 Sm3/h at maximum pressure 19 barG (worst case conditions).
So calibrated range with above pressures is 640 to 7200 Sm3/h. With official proof
that range is minimum 440 Sm3/h and that the meter measures down to 150
Sm3/h, but with less accuracy.
- 6”-3”ANSI 150 reducer spool.
- 3 ANSI 150 SSV type Fiorentini SB82.
- 3”ANSI 150 Regulator with integrated SSV type Fiorentini Reval 182 SB82.
- 3”-8”ANSI 150 spool for sensor lines, relief valve, pressure indicator and blow-off.
- 8”ANSI 150 butterfly valve.
- 8”ANSI 150 spool for collecting the 2 streams and outlet.
6) Specification for DPRMS 10000, 2 pieces
Double stream station.
Flow: Maximum 12000 Sm3/h, rated 10000 Sm3/h, minimum 600 Sm3/h.
Inlet pressure: Maximum 19.2 barG, normal 17 barG and minimum 3,5 barG.
Outlet pressure: Maximum 6,0 barG, normal 4,0 barG and minimum 2,5 barG.
Gas temperature: Maximum 45 C, normal 30 C and minimum 25 C.
As your drawing 0107012.
See main components in flow direction:
- 8”ANSI 150 spool for distribution to 2 identical streams:
- 8”ANSI 150 ball valve, BAC, high quality, tight and reliable.
- 8”ANSI 150 welded filter, 5 my filter inserts, type HFA 4.
- 8”ANSI 150 turbine meter Elster SM-RI-X G1600, range 1:30 (1:50), giving 2500
m3/h corresponding to maximum 11,250 Sm3/h at minimum inlet pressure 3,5 barG
or 12,500 Sm3/h at 4 barG. And minimum flow of 1000 Sm3/h at maximum
pressure 19 barG (worst case conditions). So calibrated range with above
pressures is 1000 to 11,250 Sm3/h. With official proof that range is minimum 690
Sm3/h and that the meter measures down to 600 Sm3/h, but with less accuracy.
- 6”-3”ANSI 150 reducer spool.
- 3 ANSI 150 SSV type Fiorentini SB82.
- 3”ANSI 150 Regulator with integrated SSV type Fiorentini Reval 182 SB82.
- 3”-8”ANSI 150 spool for sensor lines, relief valve, pressure indicator and blow-off.
- 8”ANSI 150 butterfly valve.
- 8”ANSI 150 spool for collecting the 2 streams and outlet.

Instrumentation:
Stainless steel sensor lines, hydraulic fittings type Waltersheid corresponding to former
stations.
Uniflo 1200 PTZ with GPRS-modem in a SCADA package with solar panels, battery and
ex-box.
SCADA connects to solenoids for closing SSV, position switches on SSV, filter differential
pressure switch. All serial via Uniflo 1200 PTZ.

Cabinets and bottom frames:


Cabinets in stainless steel and corresponding bottom frames in hot galvanized steel.
Double stream stations with double doors on both sides.

Documentation:
Full digital documentation with as-built drawings, parts lists, datasheets and manuals for all
components.
Certificate file with full weld, x-ray and strength pressure test for spools with full
traceability.
CE with PED certification with 3rd party notified body inspection where applicable.
Generally designed, manufactured and inspected according to ASME 31.8 and EN12186.

Price
Prices for above packages:
See separate quote.

If there are any questions then please do not hesitate to call or mail.
If there are any comments to the last delivery of stations then please let us know, so we
can change or improve accordingly.

Best regards

René Gårdsvig, Managing Director


Elster-Instromet A/S, Denmark
www.elster-instromet.dk and www.elster-instromet.com

You might also like