CONCRETE COMPRESSIVE STRENGTH TEST REPORT NF EN

12390-3
Number of Test Report 014
Project CONGO – BIOFUEL 1st AGRI HUB - INDUSTRIAL START-UP
Contractor ZEROCK CONSTRUCTION CONGO
Origin of Concrete Zerock Concrete Batching Plant in Loudima

Temperature weather /
25,1 / 27,6 °C Size of specimen 160 x 320 mm
concrete
Pouring date 6/23/2023 Slump test at 0' 14,5 cm
Mix Design Code 25 - XC4 - D25 - S3 - 42.5N - SHR - S0/1
Composition Cement Water Sand Gravel 1 Gravel 2 Admixture
Type 42,5N - 0/1 5/12,5 16/25 Admix150
Quantity(Kg/m3) 450 178.78 574 260 1018 4
Part of Structure

Oil Storage Tank / Footing / C5_Multiseed 2

30A100_RFI_24 EXT
Number notification Date of receipt 6/26/2023
30A100_RFI_55 EXT

Curing by Density Strength (Mpa)


Spec. Tag Crushing date Weight (Kg) Load (kN)
days (T/m3) Unit Average
AH094 16.08 2.50 475.50 23.65
AH095 7 6/30/2023 16.04 2.49 593.86 29.54 27.23
AH096 16.10 2.50 573.09 28.50
AH097 16.16 2.51 617.56 30.72
AH098 28 7/21/2023 16.16 2.51 626.70 31.17 31.15
AH099 16.06 2.50 634.49 31.56
AH100
AH101 56 8/18/2023 N/A
AH102

Inspection execution result


ACCEPTED ⃣ REJECTED ⃣ POSTPONED ⃣ CANCELLED ⃣
Remarks :

Inspectors for : GEOLAB ENI CONGO ZEROCK

Name

Signature

Date