AES-AES-0110-OFD-GEN-INC-003-012
Revision: 03
Issue date: 25-12-2022
Review due date: 24-12-2023
Controlled √ OR Un controlled
STANDARD MAINTENANCE PROCEDURE FOR CALIBRATION / MAINTENANCE OF PRESSURE TRANSMITTERS
AES-AES-0110-OFD-GEN-INC-003-012
Issued by
Informed
AES-AES-0110-OFD-GEN-INC-003-012
Revision responsibility
AES-AES-0110-OFD-GEN-INC-003-012
Contents
1. GENERAL.....................................................................................................................5
2. PURPOSE.....................................................................................................................5
3. SCOPE.........................................................................................................................5
4. ORGANIZATION AND RESPONSIBILITY……………………………………………………………….
……….5
5. HEALTH & SAFETY REQUIREMENTS..............................................................................6
5.1 Safety Aspects..................................................................................................6
5.2 Environmental Aspects.....................................................................................6
6. TASK/ ACTIVITY/ PROCEDURE.....................................................................................7
6.1 Pressure Transmitter.........................................................................................7
7. ACCEPTANCE CRITERIA................................................................................................8
8. RECORDS.....................................................................................................................8
9. REPLACEMENT (e.g., Spares/Software)........................................................................8
10. REPLACEMENT.............................................................................................................8
AES-AES-0110-OFD-GEN-INC-003-012
1. GENERAL
Amguri Field processing facility is provided with various instruments for monitoring and
controlling the process so that the production is maintained in an optimum manner and hazards
due to process upsets are kept in a controlled state.
These instruments are provided with static equipment as well as moving machinery. These
instruments also act as protective devices for the moving machinery and shut down the
machinery during abnormal operating condition. Many devices provide indications of machinery
distress also before the failure condition can occur.
2. PURPOSE
The purpose of this SMP is for Calibration / Maintenance of Pressure Transmitters.
3. SCOPE
This SMP is applicable to Pressure Transmitters at Amguri-EPS, AM#05, AM#14, AM#08
Onshore terminal well pads or as applicable.
4. ORGANIZATION AND RESPONSIBILITY
Designation Responsibility
Health and Safety Officer 1. To ensure that proper permit & other
safety related documents are issued.
2. Ensure that unsafe or hazardous acts
are not at all entertained during the
whole work.
AES-AES-0110-OFD-GEN-INC-003-012
b) Use appropriate personal protective equipment while performing the work and
adhere to permit to work system 3 Use appropriate tools & tackles.
c) Ensure all tools / tackles & equipment properly secured while performing the job.
e) Ensure that the activity is carried out buddy system pattern. Isolate the gas/ liquid
system in case of emergency
c) Used non-functional spares and consumables (scrapped cable, wires, PVC material,
tubing & fittings, junction box, etc) are stored temporarily at designated waste bins
and finally disposed as per Waste Management Plan.
d) Store waste paper, cardboards and packing materials generated in the nearby
designated dust bins.
e) Glasses of damaged/ faulty gauges are stored temporarily at designated waste bins
and finally disposed as per Waste Management Plan.
f) Empty aerosol cans are stored temporary at designated waste bins & puncher it
before sending for final disposal as per the Waste Management plan.
g) Ensure that drip tray/ container is in place to collect any spillage/ leakage of
condensate, oil, etc during draining/ depressurisation which are disposed into the
AES-AES-0110-OFD-GEN-INC-003-012
a) Take the clearance from process. Override the trip logic if transmitter is connected
to any trip system.
c) Slowly open the vent plug and bleed off the trap pressure at control rate by slow
opening vent valve.
d) Note down the zero reading in HART (PV, mA). Take Field & Flow computer reading
in case of metering skid’s pressure transmitter.
f) Apply pressure to transmitter and check for any leakage. If pressure is not holding,
then check leakage at fittings and calibrator.
g) After pressure is holding properly then apply pressure at 25%, 50%, 75% and 100%
of transmitter range & note down the readings. After that note down the all above
readings in decreasing trend.
i) If noted readings are coming within acceptable limit then instrument calibration is
okay. If calibration is okay, then go-to step (o). Otherwise continue step (j).
j) If readings are not within acceptable limit, then zero and span calibration required.
Go-to calibration then sensor calibration menu in HART.
k) For zero calibration release the pressure and wait for stabilization of the reading.
Then go-to the sensor trim in HART and then go-to zero trim. After steady reading
press zero trim.
l) For Span calibration apply 100% of range and wait for stabilization of the reading.
Then go-to the sensor trim in HART and then go-to span trim. After steady reading
AES-AES-0110-OFD-GEN-INC-003-012
m) After doing zero and span adjustment, again check reading at 0%, 25%, 50%, 75%
and 100% of transmitter range. Also check and note down the all above readings in
decreasing trend.
o) After completion of the same, release the pressure from the calibrator.
q) Take it in line. Also check for any leakage. Normalise the trip override if applicable.
r) Inform to control room to check the transmitter value according with the process
parameters after calibration.
7. ACCEPTANCE CRITERIA
a) No leakage from the system. Normalise the trip override if applicable.
b) The transmitter should deliver the accuracy as per following.
a. Pressure / DP Transmitter: - +/- 1.0 % Span.
8. RECORDS
a) Maintenance activity shall be entered into Maintenance Management system as
applicable.
c) Calibration Report shall be prepared for all the transmitters which are calibrated.
The report shall provide details of valid Certificates of standard calibrators.
AES-AES-0110-OFD-GEN-INC-003-012
Feedback Form
This form should be used to notify comment or suggestions for improvement, relating to any aspect
of the document identified below. Please return the completed form by Email to the author of the
document.