You are on page 1of 3

Sr.

Question Answer A Answer B Answer C Answer D Answer E Answ


No. er

1. WHICH NODE IN MEG1 IS KEPT OFF AFTER Y2K IMS PC GATEWAY IP GATEWAY CONTROLLER C
UPGRADE ? #5
2. WHICH ENVOIRNMENT IS DOWNLOADED IN ES OF MEG- MEG MEG2 MEGES MEG3 D
1?
3. WHAT IS THE MINIMUM NO OF BARRIERS USED IF TWO 1 2 3 4 C
NOS OF RTD’S ARE TO BE CONNECTED?
4. IN MOD300 SYSTEM FOR A T/C INPUT THE COLD INPUT T/C INPUT T/C IN CCF D
JUNCTION COMPENSATION IS DONE AT WHICH PLACE? TERMINALS CARD TERMINATION
ASSEMBLY
5. TWO PID CONTROLLERS CAN BE INCLUDED IN THE NO YES A
SAME LOOP?
6. SPLIT RANGING OF CONTROL VALVE CAN BE DONE BY ANALOG ANALOG INPUT RATIO/ BIAS MULTIPLICATI C
USING WHICH OF THE CCF BLOCKS? OUTPUT ON
7. WHERE IS CCF DEFINED ? ES NODE ITSELF IMS HISTORY A
8. WHICH PROTOCOL IS USED FOR INTERNAL 802.1 802.2 802.3 802.4 C
COMMUNICATION IN ABB MOD300/ADVANT 500
SYSTEM ?
9. A LOOP CAN BE DOWN LOADED IN ON CONDITION ? YES NO B
10. WHAT IS THE TYPE OF HOUSING FOR PRESSURE FLAME PROOF WHEATHER INTRINIC SAFE A
SWITCH IN MEG1 PLANT? PROOF
11. A SOV HAS 110VDC SUPPLY IF THE POLARITY OF THE NO YES B
SUPPLY IS CHANGED WITH THE SOV FUNCTION ?
12. WHAT EFFECT WILL BE OBSERVED IF AMPLIFIER NO CHANGE DISTRUB NO OUTPUT A
CARDS OF TWO TRANSMITTER IS INTERCHANGED ? CALIBRATION
13. A T’X IS CALIBRATED FROM 0 TO 50 mmWC THE SAME ZERO SPAN ZERO & SPAN A
T’X IS TO BE CALIBRATED FROM -50 TO 0 MMWC. BOTH
CALIBRATION WILL REQUIRE FOLLOWING
ADJUSTMENT ?
14. BUTTERFLY TYPE OF CONTROL VALVE CAN HAVE YES NO A
CLASS VI LEAKAGE ?
15. WHAT IS THE AIR FAIL POSITION OF CONTROL VALVE FAIL FIX FAIL OPEN FAIL CLOSE A
PRC222?
16. WHAT HAPPEN IF POSITIONER FEEDBACK LINK IS VALVE CLOSED VALVE OPEN DEPENDS ON C
BROKEN IN OPERATION ? TYPE OF VALVE
& SIGNAL
17. ACTUATOR SIZE DEPENDS ON WHICH OF THE LEAKAGE LINE PLUG DESIGN ALL OF D
FOLLWINGS CLASS PRESSURE ABOVE
18. IN O2 MIXING NOOZLE FOLLOWING IS TRUE ? VENT VALVE BLOCK VALVE B
OPENSFASTER OPENS FASTER
THAN BLOCK THAN VENT
VALVES VALVES
Sr. Question Answer A Answer B Answer C Answer D Answer E Answ
No. er

19. WHAT IS THE SETPRESSURE OF TRIP VALVE OF O.S.S 4 PSI 4 KG/CM2 100 PSI NONE OF THE B
VALVES? ABOVE
20. IN VIJAY FIRE SYSTEM IONISATION SMOKE DETECTOR YES NO A
COULD BE USED IN PLACE OF PHOTOSENSITIVE SMOKE
DETECTORS?
21. WHICH ACCESAY WILL BE REQUIRED FOR A PRESSURE SIPHON SNUBBER B
GUAGE MOUNTING IN PUMP DISCHARGE?
22. WHY FREQUECY OUTPUT FORM MICROMOTION IS SHORT TOTALISER 4-20 ma DC FREQUECY D
PREFERRED WHEN LOADING TO ETHYLENE OXIDE DISTANCE ACCEPTS ONLY OUTPUT NOT OUTPUT
TANKERS ? FREQUECNY POSSIBLE FORM INCREASES
MICROMOTION THE
RESOLUTION
23. FOR A GAS CHROMATOGRAPH WHAT IS EQUAL TO START TIME END TIME RETENTION C
CREST TIME? TIME
24. IN TOTAL SULPHUR ANALYSER, LEAD ACETATE TAPE LEAD LEAD LEAD SULFIDE C
IS CONVERTED IN TO WHICH CHEMICAL FOR PHOSPAHTE SULPHUR
DETECTION OF SULPJUR?
25. IN GAS CHROMATOGRAPH USING FID DETECTOS, WHAT INDICATION SHIFTING OF BOTH OG THE C
WILL INDICATE FLAME EXTINGUISH ? LAMP BASE LINE ABOVE
26. WHICH OF THE FOLLOWING REASON IS TRUE FOR KEEPING KEEPING REDUCE DECREASE C
USING FAST LOOP IN SAMPLE HANDLING SYSTEM FOR SAMPLE HOT SAMPLE COLD REDSIDENCE THE
ANALYSER? TIME RESPONSE
TIME
27. SERVO-MLI WORKS ON THE PRINCIPLE OF ARISTOTLE ARCHIMEDES EINSTEIN COPERNICUS B
28. ULTRASONIC LT WORKS ON THE PRICIPLE OF TRANSIT TIME STRAIN GAUGE DIFFERENTIAL NONE OF THE A
DIFFERENCE PRESSURE ABOVE
29. LEL DETECTORS IN TF-1 SPHERE AREA ARE OF IR TYPE SEMICONDUCT PELLISTOR CONDUCTIVIT C
OR TYPE TYPE Y TYPE
30. 1% METHANE IN AIR CORRESPONDS TO 50% LEL 100%LEL 20%LEL 75% LEL A
31. WEIGH BRIDGE CALIBRATION IS DONE DAILY WEEKLY MONTHLY YEARLY B
32. LOAD CELL USED IN TF-1 WEIGH BRIDGE IS OF JISL MAKE SENSORTRONI INDCHEM MAKE AVERY MAKE B
CS MAKE
33. RS-485 IS PREFERRED OVER RS232 FOR SERIAL IT IS A NONE OF THE ALL THE ABOVE B
COMMUNICATION OVER LARGE DISTANCES BECAUSE BALANCED ABOVE
A)IT CAN WITHSTAND GREATER CURRENT AND TYPE OF
VOLTAGE LEVELS COMMUNICATI
ON STANDARD
34. VAPOUR RECOVERY UNIT PLC IS OF ASEA BROWN MODICON TRICONEX ALLEN D
BOVERI BRADELY
35. THERE ARE _____ NOS OF ICN LOOPS IN TF-1 1 2 3 4 D
Sr. Question Answer A Answer B Answer C Answer D Answer E Answ
No. er

36. PM OF PCVs IN QUALITY TAGS IS DONE ONCE A YEAR TWICE A YEAR ONCE A MONTH ONCE EVERY A
TWO YEARS
37. PD METERS IN LPG LOADING ARE OF BROOKS FISHER- DARLING- LIQUID D
ROSEMOUNT MUESCO CONTROLS
38. WHAT IS THE NAME OF MEG INSTRUMENT QUALITY ABHINAVA SAMIKSHA SAFALIA ABHILASHA B
CIRCLE?
39. THE MAX. NO. OF EXPANSION CHASSIS THAT CAN BE 8 12 14 15 C
CONNECTED TO A TRICON SYSTEM ARE ______________
40. IN TRICON SYSTEM, MODEL #3005 MAIN PROCESSOR 1 MB 2 MB 3 MB 4 MB B
HAS A MEMORY OF ________ SRAM.
41. TO COMMUNICATE TRICON SYSTEMS WITH SOE NCM EICM SIM A
PC,WHICH MODULE IS USED
42. IN TRICON SYSTEM, HOW MANY I/O MODULES CAN BE 3 5 7 9 B
DEFINED IN EXPANSION CHASIS.
43. IN TRICON SYSTEM, COLD JUNCTION SENSOR IS TRUE FALSE A
SEPARATE FOR EACH LEG OF A T/C INPUT.
44. IN ABB ADVANT DCS, HOW MANY MONITORS ARE 2 3 1 4 A
THERE IN 520 TYPE OPERATOR STATION ?
45. HOW MANY NODES ARE THERE IN MEG2&3 DCS? 11 12 10 13 A
46. IN MEG2/MEG3, HISTORY IS DEFINED IN WHICH IMS2 OSAB IMS1 ES C
STATION?
47. IN ABB ADVANT DCS, ADVANT STATION 515 SUPPORTS 1 2 3 4 A
----------- MONITOR.
48. IN ABB ADVANT DCS, WHICH SOFTWARE IS USED IN ADVACOMMAN ADVAINFORM ADVABUILD A
OPERATOR STATION ? D
49. IN ABB ADVANT DCS, DCN NETWORK USES IEEE 802.3 IEEE 803.2 TCP/IP TOKEN D
-----------------------PROTOCOL. PASSING
50. IN ABB ADVANT DCS, MAXIMUM LOOP SCAN RATE FOR 20 250 100 300 C
SC CONTROLLER IS ___________ MILLISEC.