TEST REPORT
$二维码$
Manufacturer .................................... : EnSmart Power Supplies and Energy Storage Systems Ind.
Trade A.S
Halk Cad. No:8/A3, Atasehir, Istanbul 34752, Turkey
Model/Type reference ...................... : COMPACT 10KVA, COMPACT 15KVA, COMPACT 20KVA,
COMPACT 30KVA, COMPACT 40KVA
Battery bank: COMPACT-BT BATTERY BANK SERIES
Ratings .............................................. : See the rating labels.
Caution:
For operation read user manual including safety warnings
first!
This unit may be opened by authorized technicians only!
Lead acid battery in the inside of the enclosure!
The battery may present a risk of electric shock and energy
hazards.
Risk of explosion if battery replaced by an incorrect type. For
battery information, see user’s manual.
For disposal instructions of the battery, see user’s manual.
See installation instructions before connecting to the
supply.
Remark:
- The CE marking and WEEE symbol should be at least 5.0mm and 7.0mm respectively in height.
- The above marking are the minimum requirements required by the safety standard. For the final
production sample, the marking which do not give rise to misunderstanding may be add.
General remarks:
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
When differences exist; they shall be identified in the General product information section.
Name and address of factory (ies) .......................... : None
General product information:
This report is amended from previous report ES160322008S, issued on March 30, 2016, due to below
amendments:
- Changed of Applicant and manufacturer
- Change of trade mark
- Changed of Type name to COMPACT 10KVA, COMPACT 15KVA, COMPACT 20KVA, COMPACT
30KVA and COMPACT 40KVA; Battery bank: COMPACT-BT BATTERY BANK SERIES, which is
identical to original model except for model name.
No any tests need be considered.
1. The equipment with models COMPACT 10KVA, COMPACT 15KVA, COMPACT 20KVA,
COMPACT 30KVA, COMPACT 40KVA are line interactive type uninterruptible power supply with
sinewave o/p in line mode and square waveform in battery mode for general supply of office
equipment.
2. The UPS is designed as "Primary" type: input and output circuits and battery circuits are
considered as primary circuits during line mode. Operator cannot replace the battery.
3. Double/reinforced insulation provided between primary circuits (during line mode) or hazardous
voltage secondary circuits (during battery mode) and external surface USB port and RS232 port by
application of sufficient clearances and creepage distances within the unit.
4. Model difference description:
All models have the same constructions, circuit diagram and PCB layout. Only model name, appearance
and the parameter of some parts are different. Unless otherwise stated, all tests were performed on model
COMPACT 40KVA which means the typical model.
4.7.13 High leakage current (mA) ........................................: Leakage current of the N/A
5.1/RD equipment does not exceed
3.5 mA.
However due to the
connected load has influence
on the overall earth leakage
current a corresponding
statement was provided in the
user’s manual.
4.7.14 Thermostats and other regulating devices Neither thermostats nor other N/A
1.7.10/RD regulating devices provided.
4.7.15 Language(s) ...............................................................: User Manual and markings —
1.7.2.1/RD are both in English.
and Local language versions will
1.7.8.1/RD be made available during
national approval.
4.7.16 Durability of markings The label was subjected to P
1.7.11/RD the permanence of marking
test. The label was rubbed
with cloth soaked with water
for 15 s and then again for 15
s with the cloth soaked with
petroleum spirit. After this test
there was no damage to the
label. The marking on the
label did not fade. There was
neither curling nor lifting of the
label edge.
4.7.17 Removable parts No required markings placed P
1.7.12/RD on removable parts.
4.7.18 Replaceable batteries The battery is not placed in an P
1.7.13/RD operator access area. The
required warning is in the
safety manual.
Language(s) ...............................................................: —
4.7.19 Operator access with a tool ......................................: All areas containing hazard(s) P
1.7.2.5/RD are inaccessible to the
operator.
4.7.20 Battery PS with integral batteries P
Clearly legible information .........................................: Warning label attached on the P
outside surface of External
battery pack. Information
clearly legible
Battery type (lead-acid, NiCd, etc.) and number of Lead-Acid P
blocks or cells.............................................................:
Rated current (A), cross-sectional area (mm 2), (see appended table 4.5) —
AWG ...........................................................................:
2.6.3.3/RD Size of protective bonding conductors Refer to 2.6.3.4/RD P
Rated current (A), cross-sectional area (mm 2), Refer to 2.6.3.4/RD —
AWG ...........................................................................:
Protective current rating (A), cross-sectional area Refer to 2.6.3.4/RD —
(mm2), AWG ...............................................................:
2.6.3.4/RD Resistance of earthing conductors and their (See appended table 5.3.1) P
terminations; resistance (), voltage drop (V), test
current (A), duration (min) .........................................:
2.6.3.5/RD Colour of insulation ....................................................: Green/yellow P
2.6.4/RD Terminals See above P
2.6.4.1/RD General P
2.6.4.2/RD Protective earthing and bonding terminals Adequate protective earth P
connection, see also Sub-
clause 2.6.3.4/RD and 3.3/RD
Rated current (A), type, nominal thread diameter Separate PE and protective —
(mm) ...........................................................................: bonding conductor used.
2.6.4.3/RD Separation of the protective earthing conductor Separate wire for each P
from protective bonding conductors bonding connection.
2.6.5/RD Integrity of protective earthing See below P
2.6.5.1/RD Interconnection of equipment This UPS has its own earthing P
connection. Any other units
connected via a signal cable
to the PC by RS485 port shall
provide SELV only.
Additionally the parallel
connection port only
connected to the same type
port of other UPS units which
was classified as primary
circuits in the product and
reinforced insulated signal
wire will be used. Connection
for outputs and battery supply
have their own earth
connections which are
mounted on the internal metal
enclosure.
2.6.5.2/RD Components in protective earthing conductors and There are no switches or P
protective bonding conductors overcurrent protective devices
in the protective earthing /
bonding conductors.
2.6.5.3/RD Disconnection of protective earth P
2.6.5.4/RD Parts that can be removed by an operator P
2.10.1.7/R Insulation in circuits generating starting pulses No such circuit generating N/A
D starting pulses.
2.10.2/RD Determination of working voltage (See appended table 5.7) P
2.10.2.1/R General P
See below.
D
2.10.2.2/R RMS working voltage P
(See appended table 5.7)
D
2.10.2.3/R Peak working voltage P
(See appended table 5.7)
D
2.10.3/RD Clearances See below. Annex G/RD was P
not considered.
2.10.3.1/R General Annex F/RD and minimum P
D clearances considered.
2.10.3.2/R Mains transient voltages P
See below.
D
a) AC mains supply ...................................................: Equipment is Overvoltage P
Category II.
b) Earthed d.c. mains supplies .................................: Not intended for d.c. mains N/A
supplies
c) Unearthed d.c. mains supplies .............................: Not intended for d.c. mains N/A
supplies
d) Battery operation ...................................................: Dedicated battery used. P
2.10.3.3/R Clearances in primary circuits P
(see appended table 5.7)
D
2.10.3.4/R Clearances in secondary circuits P
Sub-clause 5.3.4 considered.
D
2.10.3.5/R Clearances in circuits having starting pulses No such circuit generating N/A
D starting pulses.
2.10.3.6/R Transients from a.c. mains supply ............................: Normal transient voltage N/A
D considered (overvoltage
category II for primary circuit).
2.10.3.7/R Transients from d.c. mains supply ............................: N/A
D
2.10.3.8/R Transients from telecommunication networks and N/A
D cable distribution systems .........................................:
2.10.3.9/R Measurement of transient voltage levels N/A
D
a) Transients from a mains supply N/A
For an a.c. mains supply ...........................................: N/A
For a d.c. mains supply .............................................: N/A
b) Transients from a telecommunication network ...: N/A
7 Physical requirements P
7.1 Enclosure The UPS does not overturn P
when:
-tilted to an angle of 10°
-use a constant downward
force of 800N
-a force of 20% of the weight
is applied from any direction.
7.2 Stability P
4.1/RD
4.5.1/RD General P
4.5.2/RD Temperature tests P
Normal load condition per Annex L ..........................: Equipment loaded with rated P
output power.
4.5.3/RD Temperature limits for materials (see appended table 7.7) P
4.5.4/RD Touch temperature limits (see appended table 7.7) P
4.5.5/RD Resistance to abnormal heat ....................................: (see appended table 7.4) P
7.4.2 Openings See appended table 7.4.2 P
7.4.3 Gas Concentration The ventilation by openings P
exceeds the required airflow.
Refer to Annex M.
7.4.4 Equipment movement N/A
B/RD Annex B, Motor tests under abnormal conditions (see 4.7.2.2/RD and P
5.3.2/RD)
B.1/RD General requirements Motor in secondary DC Fan P
Position .......................................................................: —
Manufacturer ..............................................................: —
Type ............................................................................: —
Rated values ..............................................................: —
B.2/RD Test conditions P
B.3/RD Maximum temperatures N/A
B.4/RD Running overload test N/A
B.5/RD Locked-rotor overload test N/A
Test duration (days) ...................................................: —
Electric strength test: test voltage (V) ......................: —
B.6/RD Running overload test for d.c. motors in N/A
secondary circuits
B.6.1/RD General N/A
B.6.2/RD Test procedure N/A
B.6.3/RD Alternative test procedure N/A
B.6.4/RD Electric strength test; test voltage (V) ......................: N/A
B.7/RD Locked-rotor overload test for d.c. motors in P
secondary circuits
B.7.1/RD General P
B.7.2/RD Test procedure N/A
B.7.3/RD Alternative test procedure P
B.7.4/RD Electric strength test; test voltage (V) ......................: N/A
B.8/RD Test for motors with capacitors N/A
B.9/RD Test for three-phase motors N/A
B.10/RD Test for series motors N/A
Operating voltage (V) ................................................: —
D/RD Annex D, Measuring instruments for touch current tests (see 5.1.4/RD) P
D.1/RD Measuring instrument Measuring instrument P
according to figure D.1 was
used.
D.2/RD Alternative measuring instrument N/A
U/RD Annex U, Insulated winding wires for use without interleaved insulation N/A
(see 2.10.5.4/RD)
Supplementary information:
No isolation components used, main voltage considered
-- -- -- --
Supplementary information: Phenolic material bobbin used in Transformer and Line Choke without test.
Output o-l 415 3 hour F1, -- Unit shut down, when load to
20mins F2,F3 40KVA. No hazardous.
Maximum temperature:
On PSDR Board:
K1 coil= 57.3℃
K1 coil= 55.5℃
CT1 winding= 52.9℃
CT2 winding = 52.4℃
On CNTL Board:
U73 body= 42.2℃
T2 coil = 53.4℃
Ambient= 25.2℃
Output o-l Battery 10 min F1, -- When add to 40KVA load, UPS
mode F2,F3 transfer to fault mode and shut
down immediately. No damage.
No hazard.
Output s-c 415 10 min F1, 0 UPS transfer to fault mode and
F2,F3 no output, no damage, no
hazards
Output s-c Battery 10 min F1, -- UPS transfer to fault mode and
mode F2,F3 no output, no damage, no
hazards.
Ventilation Block-ed 415 2 hours F1, -- Unit work continuously. No
openings 09mins F2,F3 abnormal. No hazardous.
Maximum temperature:
On PSDR Board:
K1 coil= 55.5℃
K1 coil= 54.7℃
CT1 winding= 54.6℃
CT2 winding = 53.9℃
On CNTL Board:
U73 body= 42.8℃
T2 coil = 53.9℃
Ambient= 25.5℃
to
secondary
winding/pin
T2 Primary
winding/pin reinforced insulation 1500Vac 2.8 3.3 *
to core
T2
Secondary
reinforced insulation 1500Vac 2.8 3.3 *
winding/pin
to core
Supplementary information:
* 2 or 3 layers .
C :
A ≥ (0.054 * n * 0.2 A/100 Ah * C)/360
A≥
Verdict
The size of ventilation openings in battery cabinet exceeds the required airflow by
far (as well as the UPS).
- Primary 130℃
Various Various UL1446 UL
Winding Wire
TeamWork
-Triple insulated
International TIWW-B 130℃ IEC 60950 VDE
wire
Corporation
- Insulation JINGJIANG WF 130℃
Tape(Margin YAHUA
Tape) PRESSURE UL510 UL
SENSITIVE
GLUE CO LTD
- Teflon Tube CHANGYUAN TFL 200℃
ELECTRONICS UL 224 UL
GROUP CO LTD
- Varnish HANG CHEUNG 8562 150℃
PETROCHEMICA UL1446 UL
L LTD
Transformer CLICK BCK4201-967 360uH, 130℃
Test in
(T3) TECHNOLOGY IEC 62040-1
appliance
CO LTD
Film capacitors various various 0.22uF, 1000Vdc Test in
IEC 62040-1
(C1,C7,C13) appliance
Temperature co XC KSD301 10A/250Vac, 90℃ UL 873, UL
ntrolled switch ELECTRONICS UL 60730-1
(J5-HS3) (SHENZHEN)
CORP LTD
INV Inductor board
Fuse COOPER ET F100A/690Vac EN 60127-1, VDE
(F1,F2,F3) BUSSMANN LLC EN 60127-2
Alternate MERSEN URS 100A/690Vac EN 60127-1, VDE
FRANCE SB S A EN 60127-2
S
Mutual inductor various various 1.0H, 130℃ Test in
IEC 62040-1
(CT1,CT2,CT3) appliance
Inductance various various 300uH, 180℃ Test in
IEC 62040-1
(L1,L5,L9) appliance
Relay SONG CHUAN 897P-1AH-C 12Vdc 70A/14Vdc DIN VDE 0435 VDE
(RLY1,RLY2,K3 PRECISION CO EN 60255
) LTD
The following referenced documents are indispensable for the application of this
document. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any
amendments) applies.
Note: When an international publication has been modified by common
modifications, indicated by (mod), the relevant EN/HD Applies.
ZB ANNEX (normative)
The FI, NO and SE - SNCs originate from IEC 60950-1 2nd Edition, which is the reference document (RD)
for IEC 62040-1. The national requirements are included in IEC 62040-1 through the following statement
in the scope of the standard:
“National requirements additional to those in IEC 60950-1 apply and are found as notes under relevant
clauses of the RD.”
The national requirements have not been specifically listed in the EN 62040-1:2008.
If demanded, CLC/TC 22X will be requested to take proper measures to complete EN 62040-1 with
Annexes ZB containing the SNCs as presented below.
EN 62040-1:2008 supersedes EN 62040-1-1:2003. As a reference, see also SNCs for Finland, Norway
and Sweden as included in the earlier EN 62040-1-1:2003
Clause Requirement + Test Result - Remark Verdict
4.7.3 In Finland, Norway and Sweden, when safety Permanent connection N/A
relies upon connection to the safety earth (see equipment
5.3), a pluggable equipment type A UPS shall
have a marking on the equipment, stating that the
UPS must be connected to an earthed mains
socket-outlet.
1. 本报告无授权批准人签字及“检验报告专用章”无效;
This report will be void without authorized signature or special seal for testing report.
2. 未经许可本报告不得部分复制;
3. 本报告的检测结果仅对送测样品有效,委托方对样品的代表性和资料的真实性负责;
The test results or observations are applicable only to tested sample. Client shall be responsible for
4. 本检测报告中检测项目标注有特殊符号则该项目不在资质认定范围内,仅作为客户委托、科研、教学或内部质量
控制等目的使用;
The observations or tests with special mark fall outside the scope of accreditation, and are only used for
5. 本检测报告以实测值进行符合性判定,未考虑不确定度所带来的风险,本实验室不承担相关责任,特别约定、标
准或规范中有明确规定的除外;
The test results or observations are provided in accordance with measured value, without taking risks caused
by uncertainty into account. Without explicit stipulation in special agreements, standards or regulations,
6. 对本检验报告若有异议,请于收到报告之日起 20 日内提出;
Objections shall be raised within 20 days from the date receiving the report.