Professional Documents
Culture Documents
Voltage Unbalance in Low Voltage Distribution Networks
Voltage Unbalance in Low Voltage Distribution Networks
SUMMARY
This paper presents a methodology for measuring, a) Unsymmetrical distribution systems, that is
monitoring and controlling voltage unbalance in equipment and phase conductors present different
electrical power distribution networks. The distribution impedance values.
of single-phase and double-phase loads along the b) Unsymmetrical loads, such as arc furnaces, single
network and their random instant demand values can be and double phase loads;
considered as the main causes to voltage unbalance in c) Different voltage drops due to differences in mutual
three-phase distribution systems. impedances between phase conductors and between
phase conductors and ground. This depends on the
Contrary to some other disturbances in electrical power spatial configuration of conductors.
systems, for which the performance is evident for the
ordinary customer, voltage unbalance belongs to those Low voltage distribution networks – the main focus of
disturbances in which their perceptible effects are this paper – introduce a small amount of voltage
produced in the long run. unbalances due to their impedances. The main cause can
be considered as the current unbalance, due to the
Voltage unbalance leads to a sharp decrease on the distribution of single-phase and double-phase loads
efficiency of three-phase induction motors. In Brazil, along the network, such as public lighting and
50% of the electric energy is absorbed by industrial residences.
customers. Since induction motors represent the largest
portion of industrial loads, it is seen that the voltage
unbalance should be carefully studied and controlled. COMPUTING THE VOLTAGE UNBALANCE
INDEX
This work considers voltage unbalance measurements
carried out in a Brazilian distribution company located The voltage unbalance index is generally related to the
in the State of Paraná, namely COPEL – Companhia negative symmetrical component system. This is due to
Paranaense de Energia. the large number of pieces of equipment that have their
efficiency and life affected, mainly the ones like
Since voltage unbalance gradually affects equipment, generators and motors (based on rotating magnetic
this disturbance should be dealt with by statistical fields), where the major part of electrical energy is
analysis. Regarding voltage regulation and voltage transformed.
unbalance, a world-wide tendency is to consider their
monitoring and measuring on 10 minute intervals along Phase-to-phase and phase-to-ground voltage unbalance
a 1 week period. indices (DQV2) are equal and given by the following
equation:
OBJECTIVES
V AN 2 V AB 2
The main objectives of this paper are as follows: DQV 2 = = (1)
V AN 1 V AB1
a) to study the opportunity of using digital simulations where V AN1 , V AN 2 are positive and negative sequence
for the analysis of voltage unbalance disturbances;
phase-to-ground voltages and V AB1 , V AB 2 are positive
b) to compare field measurements and results from
simulations; and negative sequence phase-to-phase voltages.
Equation (1) allows for the computation of voltage INFLUENCE OF NETWORK IMPEDANCES ON
unbalance in a system by using phase-to-phase voltages VOLTAGE UNBALANCE
only. Such computation is carried out by utilising
voltage magnitude only whereas methods based on Networks can contribute on voltage unbalance due to
phase-to-ground voltages require the magnitude and the unsymmetrical spatial configuration of conductors.
phase angles. However such method demands lots of This leads to different phase voltage drops due to
arithmetic operations. The CIGRÉ method was chosen different mutual impedances. In order to evaluate this
to be used, since it is derived from the CO-SENOS effect on the voltage unbalance, a number of
method, that keeps the accuracy. The voltage unbalance simulations were carried out on low voltage networks.
index can be readily determined by the following
equation: Voltage drops due to mutual inductances are
proportional to the flowing electric current and to the
1− 3 − 6 ⋅β
DQV (%) = ×100 (2) conductor length. Thus, a typical distribution network
1+ 3 − 6 ⋅β branch was assumed to have the current fixed by the
4 4 4
maximum allowed voltage drop. In order to ensure the
V AB + V AB + V AB current balance, a three-phase balanced resistive load
where: β =
(V AB
2
+ V AB
2
+ V AB
2 2
) was considered to be installed in the receiving bus. Two
different conductor configurations were considered in
the simulations, as shown in figure 1.
A variant of the above method is here named CIGRÉ-2
and is based on the relative deviations in phase-to-phase
voltage magnitudes δAB, δBC and δCA, with respect the
average value VM, given by:
DVQ ′ = 2
3
(δ AB
2
+ δ BC 2 + δ CA 2 ) (3)
where:
V AB − V M V BC − V M
δ AB = , δ BC = ,
VM VM vertical configuration triangle configuration
(A, B and C are phase conductors and N is the ground conductor)
VCA − V M V AB + V BC + VCA
δ CA = and V M = Fig. 1 – Conductor configurations
VM 3
Table 2 presents the computed voltage values and the
Equation 3 is a simpler calculation method as compared corresponding voltage unbalance indices (D%) along
to equation 2, though there is a slight loss in accuracy. the branch, for different distances (L) from the source.
ALLOWED VOLTAGE UNBALANCE INDICES Table 2 – Voltage unbalance due to different conductor
configurations
Brazilian standards do not establish limits for voltage Vertical Configuration Triangle configuration
unbalance indices as yet. There are some references to (a) (b)
those indices in norms that regulate equipment tests and L Vab Vbc Vca D% Vab Vbc Vca D%
standards [7] [8]. Table 1 shows a comparative figure of (m) (V) (V) (V) (V) (V) (V)
adopted limits in world-wide standards. 100 219.10 219.10 219.10 0.00 219.09 219.09 219.09 0.00
150 211.14 212.53 211.80 0.38 211.75 211.75 211.75 0.00
180 206.45 208.68 207.54 0.62 207.47 207.47 207.47 0.00
Table 1 – Voltage unbalance limits 200 203.36 206.15 204.76 0.79 204.67 204.67 204.67 0.00
Voltage Unbalance Compatibility Level Results shown in Table 2 confirm the small influence
Immunity Levels (95% probability from conductor configuration on the voltage unbalance
of not exceeding the indices.
amount)
Standards Normal Majority of
condition single and Sampling Period PROBABILISTIC COMPUTATIONAL MODEL
double phase TO EVALUATE VOLTAGE UNBALANCE
loads
EN50160 2% 3% 10 min 1 week A computational model was developed to evaluate
NRS-048 2% 3% 10 min 1 week(*) voltage unbalance indices in electrical power
(*) this standard considers the maximum daily voltage unbalance index distribution networks. The model considers a three-
phase representation of the network, taking into account Table 3 shows a compilation of the main network
medium and low voltage network branches as well as characteristics taken from COPEL´s data base. The table
distribution transformers (three-phase transformers or also presents the number and monthly energy of
bank of single-phase transformers), capacitor banks, etc. residential (R), commercial (C) and industrial (I)
customers as well as total (T) figures. Table 4 shows the
The load flow method is carried out as many times as most relevant voltage unbalance results obtained from
necessary following a Monte Carlo method that the measurements.
randomly generates scenarios in a given instant along
the load daily curve.
Table 3 – Characteristics of the selected low voltage
Load modelling to support such simulations is the result networks
of an extended load demand measurement campaign CUSTOMERS
carried out in the 90´s to stratify all customers Case Netw. Transf. L Number of Monthly energy (kWh)
connected to distribution networks in Brazil. This customers
method classifies residential customers according to # Code (kVA) (m) R C I T R C I T
different ranges for monthly consumed energy and 1 C0148 75,0 781 126 04 03 133 25314 2636 687 28637
2 C0950 45,0 401 55 0 0 55 12525 0 0 12525
commercial and industrial customers according to their
3 C0994 45,0 399 71 02 03 76 12659 719 674 14052
activities. Other load categories were also considered, 4 C1317 75,0 518 106 03 00 109 16145 810 0 16955
such as public lighting. Each customer is modelled by 5 C3807 45,0 487 97 04 0 101 16229 2179 0 18408
its corresponding typical daily load curve. For every 15 6 C4211 45,0 382 69 02 0 71 10532 2241 0 12773
minute intervals the probability distribution curve is 7 C4835 75,0 694 99 01 03 103 20919 180 563 21662
given to be used by the Monte Carlo simulation method. 8 C4974 75,0 642 118 02 0 120 20722 554 0 21276
9 C5174 45,0 394 26 0 03 29 9583 0 1369 10952
10 C6212 45,0 485 72 0 0 72 12466 0 0 12466
Figure 2 illustrates a typical probability distribution for 7038 3152 3238 13428
11 C9079 112,5 312 35 07 03 45
the demand in residential customers during the peak 12 C4617 112,5 582 68 16 04 88 14502 18584 4298 37384
load period (from 8 to 9 pm).
1.125
2.142
10.71
0
0.75
1.5
Simulations
Instantaneous
Average