Function Block Library ILS_CEM
Function Description Edition 07/16

SIMOCODE Adapter C_SIM_AD


Safety Guidelines
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage
to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices
referring to property damage only have no safety alert symbol. The notices shown below are graded according to the
degree of danger.

Danger
! indicates that death or severe personal injury will result if proper precautions are not taken.

Warning
! indicates that death or severe personal injury may result if proper precautions are not taken.

Caution
! with a safety alert symbol indicates that minor personal injury can result if proper precautions are not
taken.

Caution
without a safety alert symbol indicates that property damage can result if proper precautions are not
taken.

Attention
indicates that an unintended result or situation can occur if the corresponding notice is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used.
A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.

Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation
of a device/system may only be performed by qualified personnel. Within the context of the safety notices in this
documentation qualified persons are defined as persons who are authorized to commission, ground and label devices,
systems and circuits in accordance with established safety practices and standards.

Prescribed Usage
Note the following:

Warning
! This device and its components may only be used for the applications described in the catalog or the
technical description, and only in connection with devices or components from other manufacturers
which have been approved or recommended by Siemens.
Correct, reliable operation of the product requires proper transport, storage, positioning and assembly
as well as careful operation and maintenance.

Trademarks
All names identified by ® are registered trademarks of the Siemens AG.
The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes
could violate the rights of the owner.

Copyright Siemens AG 2005 All rights reserved Disclaimer of Liability


The distribution and duplication of this document or the We have reviewed the contents of this publication to ensure consistency
utilization and transmission of its contents are not permitted with the hardware and software described. Since variance cannot be
without express written permission. Offenders will be liable for precluded entirely, we cannot guarantee full consistency. However, the
damages. All rights, including rights created by patent grant information in this publication is reviewed regularly and any necessary
or registration of a utility model or design, are reserved corrections are included in subsequent editions.

Siemens AG
Automation and Drives Siemens AG 2005
Postfach 4848, 90327 Nuremberg, Germany Technical data subject to change.
Siemens Aktiengesellschaft
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

SIMOCODE ADAPTER C_SIM_AD 1

Description of C_SIM_AD 4
Type/Number 4
Calling OBs 4
Function 4
Interface between block C_SIM_AD and SIMOCODE Device 5
Basic Type 2, cyclic Signaling data 5
Basic Type 2, cyclic Control data 6
Basic Type 1 and 2, Acyclic Signaling data 7
Hardware inputs (Hardware Configuration) 8
Input interfaces 9
Output interfaces 12
Time characteristics 13
Message characteristics 13

Engineering 14
Settings and Configuration for SIMOCODE 14
Software configuration 16
Naming conventions in CFC 16
Example: C_DRV_1D with C_SIM_AD 17
Using the SIMOCODE blocks from SIMOCODE PCS7 library 18
Example: C_DRV_1D with SMC_REV 18
Visualisation 19
SIMOCODE faceplate 19
Diagnosis dialog 20
Trend curve dialog 21

I/O-bar of C_SIM_AD 22

OS-Variable table 27

Variable details 30

Copyright Ó Siemens AG. All Rights Reserved. 3

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

Description of C_SIM_AD

Type/Number
Module name: C_SIM_AD
Module no.: FB1035

Calling OBs
C_SIM_AD must be called in OB1 (MAIN_TASK).

Function
The SIMOCODE Adapter block C_SIM_AD can be used to establish a connection between the
CEMAT blocks and the SIMOCODE. Due to the modular concept the SIMOCODE Adapter
block can be used for unidirectional drives, bi-directional drives, valves and dampers.
The 12 possible input signals of the SIMOCODE will be transferred to a block output and can be
used individually (e. g. for Local Switch or ESB).
Additionally to the functions of C_SIMO_A, with C_SIM_AD the Motor Power can be displayed.
The current value in Amps and the Power (if enabled) in kW are shown in a curve window.

Basic type 1 and 2 are supported.


- Basic type 1: (10 bytes read and 4 byte write) (with Current- and Power Value)
- Basic type 2: (4 bytes read and 2 byte write) (with Current Value only)

The SIMOCODE adapter block is open (no KNOW_HOW_PROTECT) and you can modify the
block according to your requirements.

Important: In general, no warranty can be given for changes of the block, because this is
! entirely the responsibility of the user. It is always recommended to make a backup of the block
before proceeding.

4 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

Interface between block C_SIM_AD and SIMOCODE Device


Basic Type 2, cyclic Signaling data
Read Byte 0

Bit Signal
0.0 Cyclic Receive Bit 0.0 (free assignable)
0.1 Cyclic Receive Bit 0.1 (free assignable)
0.2 Cyclic Receive Bit 0.2 (free assignable)
0.3 Cyclic Receive Bit 0.3 (free assignable)
0.4 Cyclic Receive Bit 0.4 (free assignable)
0.5 Cyclic Receive Bit 0.5 (free assignable)
0.6 Cyclic Receive Bit 0.6 (free assignable)
0.7 Cyclic Receive Bit 0.7 (free assignable)

Read Byte 1

Bit Signal
1.0 Cyclic Receive Bit 1.0 (free assignable)
1.1 Cyclic Receive Bit 1.1 (free assignable)
1.2 Cyclic Receive Bit 1.2 (free assignable)
1.3 Cyclic Receive Bit 1.3 (free assignable)
1.4 Cyclic Receive Bit 1.4 (free assignable)
1.5 SIMOCODE available (Device OK)
1.6 SIMOCODE General Fault
1.7 SIMOCODE General Warning

Read Byte 2/ 3 current value [A]

The assignment of the Cyclic Read Bits 1.5, 1.6 and 1.7 is fixed due to the fact that the
function block uses this bits to evaluate the status information.

Additional for Basic Type 1


Read Byte 4/5 Active Power (High-Word)
Read Byte 6/7 Active Power (Low-Word) } when power measurement is released
Read Byte 8/9 free assignable analog value
When the power measurement is not released the Read Bytes 4/5 and 6/7 may be used for
other analog values.

Copyright Ó Siemens AG. All Rights Reserved. 5

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

Basic Type 2, cyclic Control data

Write Control Byte 0

Bit Signal
0.0 Cyclic Send Bit 0.0 (free assignable)
0.1 Cyclic Send Bit 0.1 (free assignable)
0.2 Cyclic Send Bit 0.2 (free assignable)
0.3 Cyclic Send Bit 0.3 (free assignable)
0.4 Cyclic Send Bit 0.4 (free assignable)
0.5 Cyclic Send Bit 0.5 (free assignable)
0.6 Cyclic Send Bit 0.6 (free assignable)
0.7 Cyclic Send Bit 0.7 (free assignable)

Write Control Byte 1

Bit Signal
1.0 Cyclic Send Bit 0.0 (free assignable)
1.1 Cyclic Send Bit 0.1 (free assignable)
1.2 Cyclic Send Bit 0.2 (free assignable)
1.3 Cyclic Send Bit 0.3 (free assignable)
1.4 Cyclic Send Bit 0.4 (free assignable)
1.5 Cyclic Send Bit 0.5 (free assignable)
1.6 Cyclic Send Bit 0.6 (free assignable)
1.7 Cyclic Send Bit 0.7 (free assignable)

Additional for Basic Type 1


Write Byte 2/3 free assignable analog value to SIMOCODE

6 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

Basic Type 1 and 2, Acyclic Signaling data

With the C_SIM_AD Adapter it possible to read, in addition to the cyclic data, two bytes
acyclic data. This function needs to be enabled due to an interface flag (refer to the
description below). The meaning of the acyclic signaling bits is free assignable.

Acyclic Read Byte 0

Bit Signal
0.0 Acyclic Receive Bit 0.0 (free assignable)
0.1 Acyclic Receive Bit 0.1 (free assignable)
0.2 Acyclic Receive Bit 0.2 (free assignable)
0.3 Acyclic Receive Bit 0.3 (free assignable)
0.4 Acyclic Receive Bit 0.4 (free assignable)
0.5 Acyclic Receive Bit 0.5 (free assignable)
0.6 Acyclic Receive Bit 0.6 (free assignable)
0.7 Acyclic Receive Bit 0.7 (free assignable)

Acyclic Read Byte 1

Bit Signal
1.0 Acyclic Receive Bit 1.0 (free assignable)
1.1 Acyclic Receive Bit 1.1 (free assignable)
1.2 Acyclic Receive Bit 1.2 (free assignable)
1.3 Acyclic Receive Bit 1.3 (free assignable)
1.4 Acyclic Receive Bit 1.4 (free assignable)
1.5 Acyclic Receive Bit 1.5 (free assignable)
1.6 Acyclic Receive Bit 1.6 (free assignable)
1.7 Acyclic Receive Bit 1.7 (free assignable)

The acyclic read function is per default disabled. Only in case the cyclic read data bits are
not sufficient, this function should be enabled, because acyclic read functions causes
additional load on the profibus.

Copyright Ó Siemens AG. All Rights Reserved. 7

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

Operating principle
Hardware inputs (Hardware Configuration)
BASICTYP Basic type Default: 2
Format INTEGER
SIMOCODE Communication Type
Type 2: 2 Byte Control Data, 4 Byte Signaling Data
Type 1: 4 Byte Control Data, 10 Byte Signaling Data

If no valid value is entered to this interface, all outputs will be reset, the block is no longer
processed and the output PARAM_FT is set to 1-Signal (Parameter failure).

I_ADDR Input start address Default: 0


Format INTEGER
SIMOCODE Input start address as configured in HW Config (must be in the process image)

O_ADDR Output start address Default: 0


Format INTEGER
SIMOCODE Output start address as configured in HW Config (must be in the process image)

8 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

Input interfaces
EN_ACYC Enable acyclic read function Basic state 0-signal
Format BOOL
With a one-signal at this interface the acyclic read function from SIMOCODE is enabled and the
two bytes acyclic data from SIMOCODE are read.

Caution: Due to the fact that an acyclic read functions to DP-Slaves is an additional load to
! the Profibus-Network it is recommended to use this functionality only in case the cyclic read bits
are not sufficient for the necessary binary information from SIMOCODE.

EN_PWR Enable Power measurement Basic state 0-signal


Format BOOL
With a one-signal at this interface the function block assumes that on Byte 4,5,6 and 7 of the
read data the power value from SIMOCODE is transfered. This interface is only evaluated with
Basictype = 1. If this function is active the power value will be converted into kW and linked to
the function block output “PWR” in REAL-Format. Further the power value will be displayed in
the facplate and the trend - faceplate of the C_SIM_AD.

S_CYC_00 …. S_CYC_17 Send Cyclic Data Bits to SIMOCODE Basic state 0-signal
Format BOOL
This interfaces should be connected as per requirement. The two bytes are send directly to the
SIMOCODE and must be connected using SIMOCODE ES Software within the SIMOCODE to
it’s appropriate function.

S_CAV Send Cyclic Analog Value Default: 0


Format INTEGER
This Interface could be connected to an Integer and used within the SIMOCODE as an analog
Setpoint.

ACK Additional acknowledge signal Basic state 0-signal


Format BOOL
The acknowledgement of the SIMOCODE fault is normally carried out together with the
acknowledgement of any alarm within the same AS (default setting). Interface ACK is only
needed for individual acknowledgement (via push-button) or in case of group-wise
acknowledgement.
A signal change from "0" to "1" at ACK acknowledges the fault at the SIMOCODE Adapter
block.
In case of a conventional control desk, a push-button can be connected to ACK (for individual
acknowledgement) or to the acknowledgement interface at block C_PUSHBT can be used (for
AS-wise acknowledgement).

Caution: Using ACK for individual acknowledgement, the acknowledgement interface at the
! C_PUSHBT must not be connected.

For group-wise acknowledgement connect the output ACK of the corresponding group to
interface ACK of the SIMOCODE Adapter block. See Engineering Manual, chapter AS-
Engineering.

Copyright Ó Siemens AG. All Rights Reserved. 9

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

F_AV1 Factor Analog Value 1 Default: 1.0


Format REAL
This factor is multiplied with the first analog value (Byte 2/3) received from SIMOCODE and the
result is available on an output of the function block and in the faceplate as well. Due to the fact
that the first analog value from SIMOCODE is specified to be the motor current [%], this factor
should be the end of scale from the used current transmitter in order to match the actual motor
amps.

F_AV2 Factor Analog Value 2 (Basictyp 1) Default: 1.0


Format REAL
This factor is multiplied with the second analog value (Byte 4/5) received from SIMOCODE and
the result is available on an output of the function block and in the faceplate as well. For
Basictyp 2 this factor will not be evaluated.
If, for Basictyp 1, the power measurement is enabled, the power value will be connected to Byte
4/5 and Byte 6/7 because it is a double word within the SIMOCODE. In this case this factor
should have the initial value.

F_AV3 Factor Analog Value 3 (Basictyp 1) Default: 1.0


Format REAL
This factor is multiplied with the third analog value (Byte 6/7) received from SIMOCODE and the
result is available on an output of the function block and in the faceplate as well. For Basictyp 2
this factor will not be evaluated.
If, for Basictyp 1, the power measurement is enabled, the power value will be connected to Byte
4/5 and Byte 6/7 because it is a double word within the SIMOCODE. In this case this factor
should have the initial value.

F_AV4 Factor Analog Value 4 (Basictyp 1) Default: 1.0


Format REAL
This factor is multiplied with the fourth analog value (Byte 8/9) received from SIMOCODE and
the result is available on an output of the function block and in the faceplate as well. For
Basictyp 2 this factor will not be evaluated.

T_S_CYC_00 … T_S_CYC_17 String variable for Cyclic Send Bit description


Format STRING[24]
This variables contains the description of the Cyclic Send Data bits. This variables could be
defined either via CFC or via Diagnosis Faceplate of the C_SIM_AD block.

T_S_CAV String variable for the Cyclic Send Analog Value description
Format STRING[24]
This variable contains the description of the Cyclic Send Analog Value. This variable could be
defined either via CFC or via Diagnosis Faceplate of the C_SIM_AD block.

10 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

T_R_CYC_00 … T_R_CYC_17 String variable for Cyclic Receive Bit description


Format STRING[24]
This variables contains the description of the Cyclic Receive Data bits. This variables could be
defined either via CFC or via Diagnosis Faceplate of the C_SIM_AD block.

T_R_ACY_00 … T_R_ACY_17 String variable for Acyclic Receive Bit description


Format STRING[24]
This variables contains the description of the Acyclic Receive Data bits. This variables could be
defined either via CFC or via Diagnosis Faceplate of the C_SIM_AD block.

T_R_AV_1 … T_R_AV_4 String variable for Cyclic Receive Analog Value description
Format STRING[24]
This variables contains the description of the Cyclic Receive Analog Values. This variables
could be defined either via CFC or via Diagnosis Faceplate of the C_SIM_AD block.

Additional inputs as Interface to the OS:


COMMAND Command word Default: 16#00
Format WORD
Interface to OS
For more information see Variable details.

Copyright Ó Siemens AG. All Rights Reserved. 11

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

Output interfaces
I_PERC Current value in %
Format INT
The current value in % is displayed in the SIMOCODE Faceplate.

STAT_SC Status SIMOCODE


Format BYTE
This parameter contains the status information of the SIMOCODE (the state of the bits 1.5 to
1.7 : “Device OK”, “General Fault” and “General Warning”), and should be connected to the
corresponding input parameter of the drive function block in order to enable the correct display
of the SIMOCODE status in the drive diagnosis faceplate.

R_CYC_00 …. R_CYC_17 Status of Cyclic Receive Data (Byte 0/1) from SIMOCODE
Format BOOL
This interfaces should be connected as per requirement. The two bytes are received directly
from the SIMOCODE and their meaning is as linked within the SIMOCODE using SIMOCODE
ES Software.

Essential: The following linking must be done using SIMOCODE ES Software to ensure the
functionality of the SIM_AD block:
! Send Cyclic 1.5 must be linked to “Device ok”
Send Cyclic 1.6 must be linked to “General Fault”
Send Cyclic 1.7 must be linked to “General Warning”

R_ACY_00 …. R_ACY_17 Status of Acyclic Receive Data from SIMOCODE


Format BOOL
This interfaces should be connected as per requirement. The two bytes are received acyclic
from the SIMOCODE if the read acyclic function is released. Their meaning is as linked within
the SIMOCODE using SIMOCODE ES Software.

AV_1 … AV_2 SIMOCODE analog values


Format REAL
This outputs contains the SIMOCODE analog values incorporated with the corresponding
factors F_AV1 … F_AV4 and can be used to be connected to C_MEASUR blocks. The output
AV_1 normally contains the motor current in [Amps] assuming the factor F_AV1 is adjusted
correctly.

PWR Power in kW (only for basic type 1 and released power measurement)
Format REAL
The Power value in kW is only available for Basic type 1 and if the power measurement
(EN_PWR) is enabled. The power value is displayed in the SIMOCODE faceplate and in the
Trend.

12 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

SIMO_FLT General Fault SIMOCODE


Format BOOL
1-Signal means general fault at the SIMOCODE.

PARAM_FT Parameter Fault


Format BOOL
1-Signal means, the value for BASICTYP is neither 1 nor 2, or I_ADDR, O_ADDR contain a
negative address.

Additional outputs as Interface to the OS:


STATUS_R Status Receive bits
Format DWORD
The status information of the receive bits, used for OS display.

STATUS_S Status Send bits


Format WORD
Interface to OS
The status information of the send bits, used for OS display.

Time characteristics
The run sequence can be chosen as desired for the C_SIM_AD module.

Message characteristics
There are no alarms generated from the C_SIM_AD module. The corresponding messages are
released through the related drive function block.

Copyright Ó Siemens AG. All Rights Reserved. 13

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

Engineering

Settings and Configuration for SIMOCODE

For the SIMOCODE_PRO 3UF70 you need the SIMOCODE ES 2007 software.

After the installation of CEMAT you will find under D:\Cemat_CS\Tools\SIMOCODE some
example SIMOCODE files and descriptions.
Basic type 1 and 2 are supported.
- Basic type 1: (10 bytes read and 4 byte write) (with Current- and Power Value)
- Basic type 2: (4 bytes read and 4 byte write) (with Current Value)

Because PCS7 V7 Driver do not support SIMOCODE you need to uncheck the diagnosis
interrupts as shown below :

14 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

The cyclic receive bits 1.5, 1.6 and 1.7 as well as the analog value 1 (Byte 2 and 3) must be
linked as shown below in order to ensure the functionality of the C_SIM_AD function block.

For all further information refer to the SIMOCODE manual.

Copyright Ó Siemens AG. All Rights Reserved. 15

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

Software configuration
Naming conventions in CFC
The SIMOCODE Adapter block (C_SIM_AD) must have the same tagname as the
corresponding drive plus the appendix "_SC"

Example:
A motor has the following tagname: 312_SC1/M01
The chart name is as follows: 312_SC1

The instance name for the motor is: M01


The instance name for the SIMOCODE Adapter must be: M01_SC

16 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

Example: C_DRV_1D with C_SIM_AD

Copyright Ó Siemens AG. All Rights Reserved. 17

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

Using the SIMOCODE blocks from SIMOCODE PCS7 library


The SIMOCODE Adapter block C_SIM_AD reads only the cyclic (and if released the two bytes
acyclic) data from the SIMOCODE.
If additional information from SIMOCODE is needed, such as additional measurement or
statistic values, the SIMOCODE AS Modules and faceplates have to be used.
In this case you have to install the Software “PCS7 SIMOCODE pro V7”. The library contains
drive functions as well as additional blocks for measurement and statistic values.
Depending on the desired functions place the SIMOCODE Blocks into the CFC and connect it
with the CEMAT drive blocks.

Example: C_DRV_1D with SMC_REV

For further information please refer the SIMOCODE library documentation.

18 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

Visualisation
SIMOCODE faceplate
Click on the block icon to open the drive faceplate

To call up the SIMOCODE adapter faceplate from a drive


faceplate press button “SIMOCODE”

Depending on the BASICTYP and enabled Power


measurement the Power value will be shown.

Copyright Ó Siemens AG. All Rights Reserved. 19

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

Diagnosis dialog
The diagnosis dialog shows the status of the send and receive bits as well as the analog values
received from and sent to the SIMOCODE.

20 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

Trend curve dialog

In the Curve dialog are shown the current value in Amps and, if available and enabled, the
active power value in kW.

Copyright Ó Siemens AG. All Rights Reserved. 21

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

I/O-bar of C_SIM_AD
C_SIM_AD

Permitted
Element Meaning Format Default Type Attr. HMI
Values
Basic type
BASICTYP INT 2 I +
(2 = standard, 1 = extended)

EN_ACYC Enable acyclic reading BOOL 0 I U +

EN_PWR Enable power measurement BOOL 0 I U +

I_ADDR Input start address INT 0 I +

O_ADDR Output start address INT 0 I +

Cyclic Send to SIMOCODE


S_CYC_00 BOOL 0 I
Bit 0.0
Cyclic Send to SIMOCODE
S_CYC_01 BOOL 0 I
Bit 0.1
Cyclic Send to SIMOCODE
S_CYC_02 BOOL 0 I
Bit 0.2
Cyclic Send to SIMOCODE
S_CYC_03 BOOL 0 I
Bit 0.3
Cyclic Send to SIMOCODE
S_CYC_04 BOOL 0 I
Bit 0.4
Cyclic Send to SIMOCODE
S_CYC_05 BOOL 0 I
Bit 0.5
Cyclic Send to SIMOCODE
S_CYC_06 BOOL 0 I
Bit 0.6
Cyclic Send to SIMOCODE
S_CYC_07 BOOL 0 I
Bit 0.7
Cyclic Send to SIMOCODE
S_CYC_10 BOOL 0 I U
Bit 1.0
Cyclic Send to SIMOCODE
S_CYC_11 BOOL 0 I U
Bit 1.1
Cyclic Send to SIMOCODE
S_CYC_12 BOOL 0 I U
Bit 1.2
Cyclic Send to SIMOCODE
S_CYC_13 BOOL 0 I U
Bit 1.3
Cyclic Send to SIMOCODE
S_CYC_14 BOOL 0 I U
Bit 1.4
Cyclic Send to SIMOCODE
S_CYC_15 BOOL 0 I U
Bit 1.5
Cyclic Send to SIMOCODE
S_CYC_16 BOOL 0 I U
Bit 1.6
Cyclic Send to SIMOCODE
S_CYC_17 BOOL 0 I U
Bit 1.7
Cyclic Send Analog Value
S_CAV INT 0 I U +
to SIMOCODE

ACK Additional acknowledge signal BOOL 0 I U

F_AV1 Factor analog value 1 REAL 1.0 I U +

22 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

Permitted
Element Meaning Format Default Type Attr. HMI
Values

F_AV2 Factor analog value 2 REAL 1.0 I U +

F_AV3 Factor analog value 3 REAL 1.0 I U +

F_AV4 Factor analog value 4 REAL 1.0 I U +

Description Send cyclic STRING


T_S_CYC_00 ‘’ I U +
Bit 0.0 [24]
Description Send cyclic STRING
T_S_CYC_01 ‘’ I U +
Bit 0.1 [24]
Description Send cyclic STRING
T_S_CYC_02 ‘’ I U +
Bit 0.2 [24]
Description Send cyclic STRING
T_S_CYC_03 ‘’ I U +
Bit 0.3 [24]
Description Send cyclic STRING
T_S_CYC_04 ‘’ I U +
Bit 0.4 [24]
Description Send cyclic STRING
T_S_CYC_05 ‘’ I U +
Bit 0.5 [24]
Description Send cyclic STRING
T_S_CYC_06 ‘’ I U +
Bit 0.6 [24]
Description Send cyclic STRING
T_S_CYC_07 ‘’ I U +
Bit 0.7 [24]
Description Send cyclic STRING
T_S_CYC_10 ‘’ I U +
Bit 1.0 [24]
Description Send cyclic STRING
T_S_CYC_11 ‘’ I U +
Bit 1.1 [24]
Description Send cyclic STRING
T_S_CYC_12 ‘’ I U +
Bit 1.2 [24]
Description Send cyclic STRING
T_S_CYC_13 ‘’ I U +
Bit 1.3 [24]
Description Send cyclic STRING
T_S_CYC_14 ‘’ I U +
Bit 1.4 [24]
Description Send cyclic STRING
T_S_CYC_15 ‘’ I U +
Bit 1.5 [24]
Description Send cyclic STRING
T_S_CYC_16 ‘’ I U +
Bit 1.6 [24]
Description Send cyclic STRING
T_S_CYC_17 ‘’ I U +
Bit 1.7 [24]
Description Send cyclic STRING
T_S_CAV ‘’ I U +
analog value [24]
Description Receive cyclic STRING
T_R_CYC_00 ‘’ I U +
Bit 0.0 [24]
Description Receive cyclic STRING
T_R_CYC_01 ‘’ I U +
Bit 0.1 [24]
Description Receive cyclic STRING
T_R_CYC_02 ‘’ I U +
Bit 0.2 [24]
Description Receive cyclic STRING
T_R_CYC_03 ‘’ I U +
Bit 0.3 [24]
Description Receive cyclic STRING
T_R_CYC_04 ‘’ I U +
Bit 0.4 [24]
Description Receive cyclic STRING
T_R_CYC_05 ‘’ I U +
Bit 0.5 [24]
Description Receive cyclic STRING
T_R_CYC_06 ‘’ I U +
Bit 0.6 [24]

Copyright Ó Siemens AG. All Rights Reserved. 23

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

Permitted
Element Meaning Format Default Type Attr. HMI
Values
Description Receive cyclic STRING
T_R_CYC_07 ‘’ I U +
Bit 0.7 [24]
Description Receive cyclic STRING
T_R_CYC_10 ‘’ I U +
Bit 1.0 [24]
Description Receive cyclic STRING
T_R_CYC_11 ‘’ I U +
Bit 1.1 [24]
Description Receive cyclic STRING
T_R_CYC_12 ‘’ I U +
Bit 1.2 [24]
Description Receive cyclic STRING
T_R_CYC_13 ‘’ I U +
Bit 1.3 [24]
Description Receive cyclic STRING
T_R_CYC_14 ‘’ I U +
Bit 1.4 [24]
Description Receive cyclic STRING
T_R_CYC_15 ‘’ I U +
Bit 1.5 [24]
Description Receive cyclic STRING
T_R_CYC_16 ‘’ I U +
Bit 1.6 [24]
Description Receive cyclic STRING
T_R_CYC_17 ‘’ I U +
Bit 1.7 [24]
Description Receive acyclic STRING
T_R_ACY_00 ‘’ I U +
Bit 0.0 [24]
Description Receive acyclic STRING
T_R_ACY_01 ‘’ I U +
Bit 0.1 [24]
Description Receive acyclic STRING
T_R_ACY_02 ‘’ I U +
Bit 0.2 [24]
Description Receive acyclic STRING
T_R_ACY_03 ‘’ I U +
Bit 0.3 [24]
Description Receive acyclic STRING
T_R_ACY_04 ‘’ I U +
Bit 0.4 [24]
Description Receive acyclic STRING
T_R_ACY_05 ‘’ I U +
Bit 0.5 [24]
Description Receive acyclic STRING
T_R_ACY_06 ‘’ I U +
Bit 0.6 [24]
Description Receive acyclic STRING
T_R_ACY_07 ‘’ I U +
Bit 0.7 [24]
Description Receive acyclic STRING
T_R_ACY_10 ‘’ I U +
Bit 1.0 [24]
Description Receive acyclic STRING
T_R_ACY_11 ‘’ I U +
Bit 1.1 [24]
Description Receive acyclic STRING
T_R_ACY_12 ‘’ I U +
Bit 1.2 [24]
Description Receive acyclic STRING
T_R_ACY_13 ‘’ I U +
Bit 1.3 [24]
Description Receive acyclic STRING
T_R_ACY_14 ‘’ I U +
Bit 1.4 [24]
Description Receive acyclic STRING
T_R_ACY_15 ‘’ I U +
Bit 1.5 [24]
Description Receive acyclic STRING
T_R_ACY_16 ‘’ I U +
Bit 1.6 [24]
Description Receive acyclic STRING
T_R_ACY_17 ‘’ I U +
Bit 1.7 [24]
Description Receive cyclic STRING
T_R_AV_1 ‘’ I U +
analog value 1 [24]
Description Receive cyclic STRING
T_R_AV_2 ‘’ I U +
analog value 2 [24]

24 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

Permitted
Element Meaning Format Default Type Attr. HMI
Values
Description Receive cyclic STRING
T_R_AV_3 ‘’ I U +
analog value 3 [24]
Description Receive cyclic STRING
T_R_AV_4 ‘’ I U +
analog value 4 [24]

COMMAND Command word WORD 16#00 I U +

I_PERC Current in % INT 0 O +

STATUS_R Status word receive DWORD 16#00 O U +

STATUS_S Status word send WORD 16#00 O U +

Status SIMOCODE (for


STAT_SC BYTE 16#00 O
connection to drive)
Cyclic Receive from
R_CYC_00 BOOL 0 O
SIMOCODE Bit 0.0
Cyclic Receive from
R_CYC_01 BOOL 0 O
SIMOCODE Bit 0.1
Cyclic Receive from
R_CYC_02 BOOL 0 O
SIMOCODE Bit 0.2
Cyclic Receive from
R_CYC_03 BOOL 0 O
SIMOCODE Bit 0.3
Cyclic Receive from
R_CYC_04 BOOL 0 O
SIMOCODE Bit 0.4
Cyclic Receive from
R_CYC_05 BOOL 0 O
SIMOCODE Bit 0.5
Cyclic Receive from
R_CYC_06 BOOL 0 O
SIMOCODE Bit 0.6
Cyclic Receive from
R_CYC_07 BOOL 0 O
SIMOCODE Bit 0.7
Cyclic Receive from
R_CYC_10 BOOL 0 O
SIMOCODE Bit 1.0
Cyclic Receive from
R_CYC_11 BOOL 0 O
SIMOCODE Bit 1.1
Cyclic Receive from
R_CYC_12 BOOL 0 O
SIMOCODE Bit 1.2
Cyclic Receive from
R_CYC_13 BOOL 0 O
SIMOCODE Bit 1.3
Cyclic Receive from
R_CYC_14 BOOL 0 O
SIMOCODE Bit 1.4

R_CYC_15 SIMOCODE available BOOL 0 O

R_CYC_16 SIMOCODE general fault BOOL 0 O

R_CYC_17 SIMOCODE general warning BOOL 0 O

Acyclic Receive from


R_ACY_00 BOOL 0 O U
SIMOCODE Bit 0.0
Acyclic Receive from
R_ACY_01 BOOL 0 O U
SIMOCODE Bit 0.1
Acyclic Receive from
R_ACY_02 BOOL 0 O U
SIMOCODE Bit 0.2

Copyright Ó Siemens AG. All Rights Reserved. 25

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

Permitted
Element Meaning Format Default Type Attr. HMI
Values
Acyclic Receive from
R_ACY_03 BOOL 0 O U
SIMOCODE Bit 0.3
Acyclic Receive from
R_ACY_04 BOOL 0 O U
SIMOCODE Bit 0.4
Acyclic Receive from
R_ACY_05 BOOL 0 O U
SIMOCODE Bit 0.5
Acyclic Receive from
R_ACY_06 BOOL 0 O U
SIMOCODE Bit 0.6
Acyclic Receive from
R_ACY_07 BOOL 0 O U
SIMOCODE Bit 0.7
Acyclic Receive from
R_ACY_10 BOOL 0 O U
SIMOCODE Bit 1.0
Acyclic Receive from
R_ACY_11 BOOL 0 O U
SIMOCODE Bit 1.1
Acyclic Receive from
R_ACY_12 BOOL 0 O U
SIMOCODE Bit 1.2
Acyclic Receive from
R_ACY_13 BOOL 0 O U
SIMOCODE Bit 1.3
Acyclic Receive from
R_ACY_14 BOOL 0 O U
SIMOCODE Bit 1.4
Acyclic Receive from
R_ACY_15 BOOL 0 O U
SIMOCODE Bit 1.5
Acyclic Receive from
R_ACY_16 BOOL 0 O U
SIMOCODE Bit 1.6
Acyclic Receive from
R_ACY_17 BOOL 0 O U
SIMOCODE Bit 1.7

AV_1 Actual motor current [A] REAL 0.0 O +

AV_2 Analog value 2 REAL 0.0 O U +

AV_3 Analog value 3 REAL 0.0 O U +

AV_4 Analog value 4 REAL 0.0 O U +

PWR Actual motor power [kW] REAL 0.0 O U +

Parameter failure
PARAM_FT BOOL 0 O
(engineering failure)

SIMO_FLT General Fault SIMOCODE BOOL 0 O

26 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

OS-Variable table
C_SIMO_AD

PLC Data
OS Variable Description OS Data Type
Type
Basic type
BASICTYP INT Signed 16-bit value
(2 = standard, 1 = extended)

EN_ACYC Enable acyclic reading BOOL Binary variable

EN_PWR Enable power measurement BOOL Binary variable

I_ADDR Input start address INT Signed 16-bit value

O_ADDR Output start address INT Signed 16-bit value

Cyclic Send Analog Value


S_CAV INT Signed 16-bit value
to SIMOCODE

F_AV1 Factor analog value 1 REAL 32-bit floating-point number IEEE 754

F_AV2 Factor analog value 2 REAL 32-bit floating-point number IEEE 754

F_AV3 Factor analog value 3 REAL 32-bit floating-point number IEEE 754

F_AV4 Factor analog value 4 REAL 32-bit floating-point number IEEE 754

Description Send cyclic STRING


T_S_CYC_00 Text variable 8-bit character set
Bit 0.0 [24]
Description Send cyclic STRING
T_S_CYC_01 Text variable 8-bit character set
Bit 0.1 [24]
Description Send cyclic STRING
T_S_CYC_02 Text variable 8-bit character set
Bit 0.2 [24]
Description Send cyclic STRING
T_S_CYC_03 Text variable 8-bit character set
Bit 0.3 [24]
Description Send cyclic STRING
T_S_CYC_04 Text variable 8-bit character set
Bit 0.4 [24]
Description Send cyclic STRING
T_S_CYC_05 Text variable 8-bit character set
Bit 0.5 [24]
Description Send cyclic STRING
T_S_CYC_06 Text variable 8-bit character set
Bit 0.6 [24]
Description Send cyclic STRING
T_S_CYC_07 Text variable 8-bit character set
Bit 0.7 [24]
Description Send cyclic STRING
T_S_CYC_10 Text variable 8-bit character set
Bit 1.0 [24]
Description Send cyclic STRING
T_S_CYC_11 Text variable 8-bit character set
Bit 1.1 [24]
Description Send cyclic STRING
T_S_CYC_12 Text variable 8-bit character set
Bit 1.2 [24]
Description Send cyclic STRING
T_S_CYC_13 Text variable 8-bit character set
Bit 1.3 [24]
Description Send cyclic STRING
T_S_CYC_14 Text variable 8-bit character set
Bit 1.4 [24]
Description Send cyclic STRING
T_S_CYC_15 Text variable 8-bit character set
Bit 1.5 [24]
Description Send cyclic STRING
T_S_CYC_16 Text variable 8-bit character set
Bit 1.6 [24]

Copyright Ó Siemens AG. All Rights Reserved. 27

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

PLC Data
OS Variable Description OS Data Type
Type
Description Send cyclic STRING
T_S_CYC_17 Text variable 8-bit character set
Bit 1.7 [24]
Description Send cyclic STRING
T_S_CAV Text variable 8-bit character set
analog value [24]
Description Receive cyclic STRING
T_R_CYC_00 Text variable 8-bit character set
Bit 0.0 [24]
Description Receive cyclic STRING
T_R_CYC_01 Text variable 8-bit character set
Bit 0.1 [24]
Description Receive cyclic STRING
T_R_CYC_02 Text variable 8-bit character set
Bit 0.2 [24]
Description Receive cyclic STRING
T_R_CYC_03 Text variable 8-bit character set
Bit 0.3 [24]
Description Receive cyclic STRING
T_R_CYC_04 Text variable 8-bit character set
Bit 0.4 [24]
Description Receive cyclic STRING
T_R_CYC_05 Text variable 8-bit character set
Bit 0.5 [24]
Description Receive cyclic STRING
T_R_CYC_06 Text variable 8-bit character set
Bit 0.6 [24]
Description Receive cyclic STRING
T_R_CYC_07 Text variable 8-bit character set
Bit 0.7 [24]
Description Receive cyclic STRING
T_R_CYC_10 Text variable 8-bit character set
Bit 1.0 [24]
Description Receive cyclic STRING
T_R_CYC_11 Text variable 8-bit character set
Bit 1.1 [24]
Description Receive cyclic STRING
T_R_CYC_12 Text variable 8-bit character set
Bit 1.2 [24]
Description Receive cyclic STRING
T_R_CYC_13 Text variable 8-bit character set
Bit 1.3 [24]
Description Receive cyclic STRING
T_R_CYC_14 Text variable 8-bit character set
Bit 1.4 [24]
Description Receive cyclic STRING
T_R_CYC_15 Text variable 8-bit character set
Bit 1.5 [24]
Description Receive cyclic STRING
T_R_CYC_16 Text variable 8-bit character set
Bit 1.6 [24]
Description Receive cyclic STRING
T_R_CYC_17 Text variable 8-bit character set
Bit 1.7 [24]
Description Receive acyclic STRING
T_R_ACY_00 Text variable 8-bit character set
Bit 0.0 [24]
Description Receive acyclic STRING
T_R_ACY_01 Text variable 8-bit character set
Bit 0.1 [24]
Description Receive acyclic STRING
T_R_ACY_02 Text variable 8-bit character set
Bit 0.2 [24]
Description Receive acyclic STRING
T_R_ACY_03 Text variable 8-bit character set
Bit 0.3 [24]
Description Receive acyclic STRING
T_R_ACY_04 Text variable 8-bit character set
Bit 0.4 [24]
Description Receive acyclic STRING
T_R_ACY_05 Text variable 8-bit character set
Bit 0.5 [24]
Description Receive acyclic STRING
T_R_ACY_06 Text variable 8-bit character set
Bit 0.6 [24]
Description Receive acyclic STRING
T_R_ACY_07 Text variable 8-bit character set
Bit 0.7 [24]
Description Receive acyclic STRING
T_R_ACY_10 Text variable 8-bit character set
Bit 1.0 [24]

28 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

PLC Data
OS Variable Description OS Data Type
Type
Description Receive acyclic STRING
T_R_ACY_11 Text variable 8-bit character set
Bit 1.1 [24]
Description Receive acyclic STRING
T_R_ACY_12 Text variable 8-bit character set
Bit 1.2 [24]
Description Receive acyclic STRING
T_R_ACY_13 Text variable 8-bit character set
Bit 1.3 [24]
Description Receive acyclic STRING
T_R_ACY_14 Text variable 8-bit character set
Bit 1.4 [24]
Description Receive acyclic STRING
T_R_ACY_15 Text variable 8-bit character set
Bit 1.5 [24]
Description Receive acyclic STRING
T_R_ACY_16 Text variable 8-bit character set
Bit 1.6 [24]
Description Receive acyclic STRING
T_R_ACY_17 Text variable 8-bit character set
Bit 1.7 [24]
Description Receive cyclic STRING
T_R_AV_1 Text variable 8-bit character set
analog value 1 [24]
Description Receive cyclic STRING
T_R_AV_2 Text variable 8-bit character set
analog value 2 [24]
Description Receive cyclic STRING
T_R_AV_3 Text variable 8-bit character set
analog value 3 [24]
Description Receive cyclic STRING
T_R_AV_4 Text variable 8-bit character set
analog value 4 [24]

COMMAND Command word WORD Unsigned 16-bit value

I_PERC Current in % INT Signed 16-bit value

STATUS_R Status word receive DWORD Unsigned 32-bit value

STATUS_S Status word send WORD Unsigned 16-bit value

AV_1 Actual motor current [A] REAL 32-bit floating-point number IEEE 754

AV_2 Analog value 2 REAL 32-bit floating-point number IEEE 754

AV_3 Analog value 3 REAL 32-bit floating-point number IEEE 754

AV_4 Analog value 4 REAL 32-bit floating-point number IEEE 754

PWR Actual motor power [kW] REAL 32-bit floating-point number IEEE 754

Copyright Ó Siemens AG. All Rights Reserved. 29

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
SIMOCODE Adapter C_SIM_AD Reference Manual Objects

Variable details
Internal structure of the Visualization status:

OS- Msg Fault


Parameter Function Designation German Designation English
Addr. Class Class

COMMAND Kommandowort Commandword


COM_B20 0
COM_B21 1
COM_B22 2
COM_B23 3
COM_B24 4
COM_B25 5
COM_B26 6
COM_B27 7

COM_B10 8
COM_B11 9
COM_B12 10
COM_B13 11
COM_B14 12
COM_B15 13
COM_B16 14
COM_B17 15

STATUS_S Statuswort Send Status word Send


STAT_S_B20 S_CYC_00 0
STAT_S_B21 S_CYC_01 1
STAT_S_B22 S_CYC_02 2
STAT_S_B23 S_CYC_03 3
STAT_S_B24 S_CYC_04 4
STAT_S_B25 S_CYC_05 5
STAT_S_B26 S_CYC_06 6
STAT_S_B27 S_CYC_07 7

STAT_S_B10 S_CYC_10 8
STAT_S_B11 S_CYC_11 9
STAT_S_B12 S_CYC_12 10
STAT_S_B13 S_CYC_13 11
STAT_S_B14 S_CYC_14 12
STAT_S_B15 S_CYC_15 13
STAT_S_B16 S_CYC_16 14
STAT_S_B17 S_CYC_17 15

30 Copyright Ó Siemens AG. All Rights Reserved.

N:\00_Cemat_Entwicklung\V8\V8200\30_Doku\Doku_Englisch\Reference\ADD ONs\000_Normal\C_SIM_AD_009.doc
Reference Manual Objects SIMOCODE Adapter C_SIM_AD

OS- Msg Fault


Parameter Function Designation German Designation English
Addr. Class Class

STATUS_R Statuswort Receive Status word Receive


STAT_R_B40 R_CYC_00 0
STAT_R_B41 R_CYC_01 1
STAT_R_B42 R_CYC_02 2
STAT_R_B43 R_CYC_03 3
STAT_R_B44 R_CYC_04 4
STAT_R_B45 R_CYC_05 5
STAT_R_B46 R_CYC_06 6
STAT_R_B47 R_CYC_07 7

STAT_R_B30 R_CYC_10 8
STAT_R_B31 R_CYC_11 9
STAT_R_B32 R_CYC_12 10
STAT_R_B33 R_CYC_13 11
STAT_R_B34 R_CYC_14 12
STAT_R_B35 R_CYC_15 13 SIMOCODE verfügbar SIMOCODE available
STAT_R_B36 R_CYC_16 14 Sammelstörung General Fault
STAT_R_B37 R_CYC_17 15 Sammelwarnung General warning

STAT_R_B20 R_ACY_00 16
STAT_R_B21 R_ACY_01 17
STAT_R_B22 R_ACY_02 18
STAT_R_B23 R_ACY_03 19
STAT_R_B24 R_ACY_04 20
STAT_R_B25 R_ACY_05 21
STAT_R_B26 R_ACY_06 22
STAT_R_B27 R_ACY_07 23

STAT_R_B10 R_ACY_10 24
STAT_R_B11 R_ACY_11 25
STAT_R_B12 R_ACY_12 26
STAT_R_B13 R_ACY_13 27
STAT_R_B14 R_ACY_14 28
STAT_R_B15 R_ACY_15 29
STAT_R_B16 R_ACY_16 30
STAT_R_B17 R_ACY_17 31

Copyright Ó Siemens AG. All Rights Reserved. 31