Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Zone Checksums

By Trane
QUIROFANO - 001

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 15 Mo/Hr: 6 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 72 / 52 / 58 OADB: 72 OADB: 33 SADB 53.1 69.3
Ra Plenum 73.2 63.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 73.2 63.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 73.1 61.7
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.4 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 1,013 1,013 3 0 0 Roof Cond 0 -1,285 9.36
Glass Solar 21,868 0 21,868 60 21,868 64 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond -145 0 -145 0 -145 0 Glass/Door Cond -6,189 -6,189 45.05
Cooling Heating
Wall Cond 2,035 1,238 3,273 9 2,035 6 Wall Cond -1,464 -2,347 17.08
Partition/Door 581 581 2 581 2 Partition/Door 0 0 0.00 Diffuser 2,587 2,587
Floor 586 586 2 586 2 Floor 0 0 0.00 Terminal 2,587 2,587
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 2,587 2,587
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 24,924 2,251 27,175 75 24,924 73 Sub Total ==> -7,653 -9,821 71.49 Nom Vent 182 182
AHU Vent 182 182
Internal Loads Internal Loads Infil 0 0
Lights 3,754 0 3,754 10 3,754 11 Lights 0 0 0.00 MinStop/Rh 0 0
People 4,050 0 4,050 11 2,250 7 People 0 0 0.00 Return 2,587 2,587
Misc 3,072 0 3,072 8 3,072 9 Misc 0 0 0.00 Exhaust 182 182
Sub Total ==> 10,876 0 10,876 30 9,076 27 Sub Total ==> 0 0 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 127 -127 0 0 127 0 Ceiling Load -122 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 -2,765 -8 0 0 Ventilation Load 0 -4,059 29.55 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0 0 0.00
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 144 -1.05 ENGINEERING CKS
Exhaust Heat -149 -149 0 OA Preheat Diff. 0 0.00
Sup. Fan Heat 1,088 3 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 7.0 7.0
Duct Heat Pkup 0 0 0 System Plenum Heat 0 0.00 cfm/ft² 7.59 7.59
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 833.59
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 109.80
Btu/hr·ft² 109.29 -55.39
Grand Total ==> 35,927 1,975 36,225 100.00 34,127 100.00 Grand Total ==> -7,775 -13,736 100.00 No. People 9

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 3.1 37.2 37.2 2,587 73.7 58.2 90.9 53.1 52.1 90.9 Floor 341 Main Htg -13.7 2,587 61.7 69.3
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 187 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 318
Total 3.1 37.2 Roof 341 0 0 Humidif -5.1 182 8.7 73.1
Wall 368 177 48 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -18.9

Project Name: DLP-22- TRACE® 700 v6.2.4 calculated at 10:21 PM on 09/04/2022


Dataset Name: HOSPITAL DE SUCRE.trc Alternative - 1 System Checksums Report Página 1 de 1