UFU - FEELT - Disc.

- TRANSFORMADORES
3a Prova Parcial 2. Semestre de 2003 Data - 29/10/2003
Duração - 50 min - Sem consulta

Número ____________ Nome ___________________________________

1a. questão) Uma das vantagens das grandezas percentuais é que elas
independem do lado de referência. Prove a partir do ensaio de curto circuito e
através de equações que para um transformador R1% = R2% = R%, X1% =
X2% = X% e portanto Z1% = Z2% = Z%? ( 50% )
Solução:
  N 
2

N2 R .   .I 2 fn
2
R1 fn .I 2 fn .  1 fn 
R .I N1  N
 1  
R1 % = 1 fn 1 fn .100 = .100 =  .100 =
U1 fn N1 U
U 2 fn . 2 fn
N2
R2 fn .I 2 fn
= .100 = R2 % = R%
U 2 fn

  N 
2

N2  X 1 fn .    .I 2 fn
2
X 1 fn .I 2 fn . N
X 1 fn .I1 fn N1   1  
X1 % = .100 = .100 =  .100 =
U1 fn N1 U
U 2 fn . 2 fn
N2
X 2 fn .I 2 fn
= .100 = X 2 % = X %
U 2 fn

e portanto: Z1 % = Z 2 % = Z %
UFU - FEELT - Disc.- TRANSFORMADORES
3a Prova Parcial 2. Semestre de 2003 Data - 29/10/2003
2a. questão) Fazer o diagrama de fasores e determinar o defasamento
angular do transformador trifásico Y-∆ cujo diagrama de conexão interna das
bobinas é dado na figura a seguir. Considere a seqüência de fases no sentido
horário.(50% )

Solução: