Item2 - Surge Arrester

Datasheet

Surge arrester
POLIM-H..SD

Document ID 1HC0075860 D01 AA


Protection of
• Rolling Stock & railroad installations
• other medium voltage equipment

Application
• DC
• Outdoor and Indoor
Item2 - Surge Arrester

Technical Data
Metal oxide surge arrester without spark gaps. Direct moulded silicone housing, grey color.
Designed and tested according to IEC 61992-5

Nominal discharge current In 8/20 µs 20 kA (pk)


Line discharge class 4
High current operating duty test Ihc 4/10 µs 100 kA (pk)
Long duration current impulse 1350 A / 2000 µs
Short circuit rating Is DC 40 kA DC for 0.2 s

The thermal stability of the MO-surge arrester is proved in the operating duty test according to LD4 which gives an
energy input 10.5 kJ/kV (Uc DC).

Ambient air temperature -60 to +40 °C (for higher values contact manufacturer)
Altitude up to 1800 m (for higher values contact manufacturer)
Frequency DC
Weather ageing tested according to series A (1000 h salt fog)

Uc Ur Residual voltage (Ures) in kV (pk) at specified impulse current

Continuous
Rated
operating wave 1/ ... µs wave 8/20 µs wave 30/60 µs
voltage
voltage

kV (DC) kV (DC) 10 kA (pk) 20 kA (pk) 2 kA (pk) 5 kA (pk) 10 kA (pk) 20 kA (pk) 40 kA (pk) 500 A (pk) 1 kA (pk) 2 kA (pk)

1.0 1.25 2.62 2.81 2.20 2.30 2.40 2.62 2.93 2.03 2.09 2.15
1.5 1.88 3.93 4.22 3.29 3.45 3.60 3.93 4.40 3.04 3.13 3.23
2.0 2.50 5.24 5.62 4.39 4.60 4.80 5.24 5.86 4.06 4.17 4.30
2.5 3.13 6.65 7.14 5.57 5.85 6.10 6.65 7.45 5.15 5.30 5.46
3.0 3.75 7.85 8.43 6.58 6.90 7.20 7.85 8.79 6.08 6.25 6.45
4.2 5.25 10.90 11.70 9.13 9.58 10.00 10.90 12.20 8.44 8.68 8.95
4.7 5.88 12.21 13.11 10.23 10.73 11.20 12.21 13.67 9.46 9.73 10.03

ABB 2
Item2 - Surge Arrester

Dimensions and Clearances


Dimensions (in mm)

Mechanical loads:
Torque moment 50 Nm
Tensile strength 1000 N
Maximal bending moment 250 Nm
MPSL 2500 N

(MPSL is applied in the type test on the longest housing


of the surge arrester)

Creepage Flashover Insulation withstand voltage


Uc Recommended clearances Height H Weight
distance distance of empty housing
E min. F min. 1.2/50 µs 60 s wet
mm mm mm mm mm kg kV (pk) kV (DC)
1.0 270 129 80 160 90 < 2.0 120 15
1.5 270 129 80 160 90 < 2.0 120 15
2.0 270 129 80 160 90 < 2.0 120 15
2.5 270 129 80 160 90 < 2.0 120 15
3.0 270 129 80 160 90 < 2.0 120 15
4.2 270 129 80 160 90 < 2.0 120 15

3 ABB
Item2 - Surge Arrester

For further information please contact: Note:


ABB Switzerland Ltd. We reserve the right to make technical changes
High Voltage Products or modify the contents of this document without
Surge Arresters prior notice. With regard to purchase orders,
Jurastrasse 45 the agreed particulars shall prevail. ABB AG
CH-5430 Wettingen/Switzerland does not accept any responsibility whatsoever
for potential errors or possible lack of informa-
Tel. +41 58 585 29 11 tion in this document. We reserve all rights in
Fax +41 58 585 55 70 this document and in the subject matter and
illustrations contained therein. Any reproduc-
Email: sales.sa@ch.abb.com tion, disclosure to third parties or utilization of
www.abb.com/arrestersonline its contents – in whole or in parts – is forbidden
without prior written consent of ABB AG.

Copyright© 2010 ABB


All rights reserved

Detailed information for dimensioning of our products see


following ABB documents:

Application Guidelines Overvoltage Protection in medium voltage systems


Application Guidelines Overvoltage Protection in railway facilities

pdf or print version, please send e-mail to:


sales.sa@ch.abb.com

Our products do have following


certification:
ISO 9001, 14001, 18001 and IRIS