B66-S-0121 (Orginal Sheet) - Water - Res - Slab - Wall - BS - Code
B66-S-0121 (Orginal Sheet) - Water - Res - Slab - Wall - BS - Code
B66-S-0121 (Orginal Sheet) - Water - Res - Slab - Wall - BS - Code
C-667-1316-001<00A>
SHEET 5 OF 45 .
3- GEOMETRY & OUTLINE
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 6 OF 45 .
4- CALCULATIONS
LOADING
Live Load = 3.60 KN/m2
Empty Wt. of equipment = KN
Erection Wt. of equipment = KN
Operating Wt. of equipmen = KN
Test load of equipment = KN
Thickness of Chequered pl = 0.0060 m
Weight of Each Pump 10.00 KN
No. Of Pumps 2
Total Weight of Pump = 20.00 KN
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 7 OF 45 .
= 8555 KN
b: Operational Load
Total Load = Dead load + Live Load + Weight of pump + Operation Load + Wt of soil over projected slab
= 9251.79 KN
( Water Table at highest Level, with only Dead Loads and the weight of soil over projected slab portions)
Total Load = Dead load + Weight of Pump+ Weight of soil over projected slab portion
Downward Loads = 1569 + 20.00 + 318 = 1908 KN
Uplift = 0 KN
O.K Satisfied
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 9 OF 45 .
4.4- DESIGN OF SLABS
4.4.1- Design Of Top Slab (TS-1)
cc = Clear Cover = 75 mm
d = h-cc-(dia bar/2) = 167 mm
rt = 0.00180
b = 1000 mm
ly / lx = 1.71
lx = 3.4 m
ly
Area = 19.72 m2
Wt of slab = 97.2 KN
Live Load = 71.0 KN
Weight Of Pump = 20.0 KN
Weight of Walls = 0.0 KN Not Applicable
M= CF x W x Lx2 Where CF= Moment Coefficient taken from the slab graph (SEE SKETCH -2)
Q=CF x W x Lx CF = Shear coefficient taken from the slab graph (SEE SKETCH -2)
W= Total factored load in KN
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 10 OF 45 .
For Rectangular Loading:-
CF W Lx2
Mx1 (-ve) = 0.0800 x 12.892 x 11.56 = 11.92 KN-m
Mx2 (+ve) = 0.0375 x 12.892 x 11.56 = 5.59 KN-m
Qx1 = 0.5200 x 12.892 x 3.40 = 22.79 KN
My1 (-ve) = 0.0570 x 12.892 x 11.56 = 8.49 KN-m
My2 (+ve) = 0.0100 x 12.892 x 11.56 = 1.49 KN-m
Qy1 = 0.4700 x 12.892 x 3.40 = 20.60 KN
Mu = 11.92 KN-m
r = 0.85 x fc' 2 x Mu
1- 1-
fy 0.85 x 0.9 x fc' x b x d2
1.33r = 0.00152
As = rx b x d = 253.75 mm2/m
Therefore
D16 @ 250 mm C/C Top & Bottom Both ways
Shear Check:
Vu = 22.79 KN
f Vc = 0.85 x (fc')1/2 x b x d
6
= 125.19 KN > 22.79 KN O.K Satisfied
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 11 OF 45 .
4.4.2- Design Of Top Slab (TS-2)
cc = Clear Cover = 75 mm
d = h-cc-(dia bar/2) = 169 mm
rt x = 0.00180
b = 1000 mm
ly / lx = 2.35
lx = 2.600 m
ly
Area = 15.86 m2
Wt of slab = 95.2 KN
Live Load = 57.1 KN
Weight Of Pump = 0.0 KN
Weight of Walls = 0.0 KN Not Applicable
M= CF x W x Lx2 Where CF= Moment Coefficient taken from the slab graph (SEE SKETCH -1)
Q=CF x W x Lx CF = Shear coefficient taken from the slab graph (SEE SKETCH -1)
W= Total factored load in KN
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 12 OF 45 .
For Rectangular Loading:-
CF W Lx2
Mx1 (-ve) = 0.0000 x 12.96 x 6.76 = 0.00 KN-m
Mx2 (+ve) = 0.1300 x 12.96 x 6.76 = 11.39 KN-m
Qx1 = 0.5200 x 12.96 x 2.60 = 17.52 KN
My1 (-ve) = 0.0000 x 12.96 x 6.76 = 0.00 KN-m
My2 (+ve) = 0.0120 x 12.96 x 6.76 = 1.05 KN-m
Qy1 = 0.5500 x 12.96 x 2.60 = 18.53 KN
Mu = 11.39 KN-m
r = 0.85 x fc' 2 x Mu
1- 1-
fy 0.85 x 0.9 x fc' x b x d2
1.33r = 0.001416
As = rx b x d = 239.37 mm2/m
Therefore
D12 @ 200 mm C/C Top & Bottom Both ways
Shear Check:
Vu = 18.53 KN
f Vc = 0.85 x (fc')1/2 x b x d
6
= 126.69 KN > 18.53 KN O.K Satisfied
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 13 OF 45 .
4.4.3- Design Of Bottom Slab (BS-1)
cc = Clear Cover = 75 mm
d = h-cc-(dia bar/2) = 415 mm
rt = 0.00180
b = 1000 mm
ly / lx = 2.30
ly = 12.90 m
lx Area = 72.24 m2
Wt of Steel = 47.8 KN
Live Load = 260.1 KN
Weight Of Pump = 0.0 KN
Weight of Walls = 3386.3 KN
M= CF x W x Lx2 Where CF= Moment Coefficient taken from the slab graph (SEE SKETCH -2)
Q=CF x W x Lx CF = Shear coefficient taken from the slab graph (SEE SKETCH -2)
W= Total factored load in KN
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 14 OF 45 .
For Rectangular Loading:-
CF W Lx2
Mx1 (-ve) = 0.0830 x 62.8044 x 31.4 = 163.47 KN-m
Mx2 (+ve) = 0.0410 x 62.8044 x 31.4 = 80.75 KN-m
Qx1 = 0.5200 x 62.8044 x 5.6 = 182.89 KN
My1 (-ve) = 0.0570 x 62.8044 x 31.4 = 112.26 KN-m
My2 (+ve) = 0.0105 x 62.8044 x 31.4 = 20.68 KN-m
Qy1 = 0.4600 x 62.8044 x 5.6 = 161.78 KN
Mu = 163.47 KN-m
r = 0.85 x fc' 2 x Mu
1- 1-
fy 0.85 x 0.9 x fc' x b x d2
1.33r = 0.003417
Therefore
D20 @ 200 mm C/C Top & Bottom Both ways
Shear Check:
Vu = 182.9 KN
f Vc = 0.85 x (fc')1/2 x b x d
6
= 311.10 KN > 182.9 KN O.K Satisfied
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 15 OF 45 .
4.4.4- Design Of Bottom Slab (BS-2)
cc = Clear Cover = 75 mm
d = h-cc-(dia bar/2) = 415 mm
rt = 0.00180
b = 1000 mm
ly / lx = 1.71
lx = 3.40 m
Area = 19.72 m2
ly
Wt of TS-1 = 97.2 KN
Live Load = 71.0 KN
Weight Of Pumps = 20.0 KN
Weight of Walls = 1155.8 KN
M= CF x W x Lx2 Where CF= Moment Coefficient taken from the slab graph (SEE SKETCH -2)
Q=CF x W x Lx CF = Shear coefficient taken from the slab graph (SEE SKETCH -2)
W= Total factored load in KN
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 16 OF 45 .
For Rectangular Loading:-
CF W Lx2
Mx1 (-ve) = 0.0800 x 83.2269 x 11.6 = 76.97 KN-m
Mx2 (+ve) = 0.0410 x 83.2269 x 11.6 = 39.45 KN-m
Qx1 = 0.5250 x 83.2269 x 3.4 = 148.56 KN
My1 (-ve) = 0.0570 x 83.2269 x 11.6 = 54.84 KN-m
My2 (+ve) = 0.0100 x 83.2269 x 11.6 = 9.62 KN-m
Qy1 = 0.4600 x 83.2269 x 3.4 = 130.17 KN
Mu = 76.97 KN-m
r = 0.85 x fc' 2 x Mu
1- 1-
fy 0.85 x 0.9 x fc' x b x d2
1.33r = 0.00158919983
As = rx b x d = 659.518 mm2/m
Therefore
D20 @ 250 mm C/C Top & Bottom Both ways
Shear Check:
Vu = 148.6 KN
f Vc = 0.85 x (fc')1/2 x b x d
6
= 311.10 KN > 148.6 KN O.K Satisfied
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 17 OF 45 .
4.4.5- Design Of Bottom Slab (BS-3)
cc = Clear Cover = 75 mm
d = h-cc-(dia bar/2) = 315 mm
rt = 0.00180
b = 1000 mm
ly / lx = 2.12
lx = 2.600 m
ly
Area = 14.3 m2
M= CF x W x Lx2 Where CF= Moment Coefficient taken from the slab graph (SEE SKETCH -2)
Q=CF x W x Lx CF = Shear coefficient taken from the slab graph (SEE SKETCH -2)
W= Total factored load in KN
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 18 OF 45 .
For Rectangular Loading:-
CF W Lx2
Mx1 (-ve) = 0.0830 x 87.67 x 6.8 = 49.19 KN-m
Mx2 (+ve) = 0.0530 x 87.67 x 6.8 = 31.41 KN-m
Qx1 = 0.5200 x 87.67 x 2.6 = 118.53 KN
My1 (-ve) 0.057 0.0570 x 87.67 x 6.8 = 33.78 KN-m
My2 (+ve) 0.01 0.0100 x 87.67 x 6.8 = 5.93 KN-m
Qy1 0.46 0.4600 x 87.67 x 2.6 = 104.85 KN
Mu = 49.19 KN-m
r = 0.85 x fc' 2 x Mu
1- 1-
fy 0.85 x 0.9 x fc' x b x d2
1.33r = 0.001765
As = rx b x d = 556 mm2/m
Therefore
D20 @ 250 mm C/C Top & Bottom Both ways
Shear Check:
Vu = 118.5 KN
f Vc = 0.85 x (fc')1/2 x b x d
6
= 236.13 KN > 118.5 KN O.K Satisfied
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 19 OF 45 .
4.5- Design Of Walls
4.5.1- Design Of Walls (W-1 & W-2)
Ko = 1 - sin q = 0.40
Ka = tan2 ( 45o - f / 2) = 0.25
ly / lx = 1.84 b = 1000 mm
ly = 12.90 m
Soil Surcharge
lx
qs qq
qs = Ka x gs x Hs = 31.17 KN/m2
Wv Total Factored Triangular Load = (1.6 x qs) 1.6 x 31.17 = 49.9 KN/m2
Wu Total Factored Uniform Load = (1.6 x qq) 1.6 x 2.486 = 3.977 KN/m2
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 20 OF 45 .
For Triangular Loading:- ( Due to soil)
Where
M= CF x Wv x H2 CF = Moment coefficient taken from the wall with 3 sides fixed graph
Q= CF x Wv x H CF = Shear coefficient taken from the wall with 3 sides fixed graph
Wv= Total factored trinagular load in KN
ly = 12.90 m
Water
lx
qw
qw = gwater x H = 70 KN/m2
Consider 1m strip:-
r = 0.85 x fc' 2 x Mu
1- 1-
fy 0.85 x 0.9 x fc' x b x d2
rx = 0.00401 > 0.00333 So use :- 0.00401
ry = 0.00283 < 0.00333 So use :- 0.00333
1.33rx = 0.00533
1.33ry = 0.00377
Therefore
Providing D25 @ 200 C/C In Vertical Direction Both Faces
Providing D25 @ 250 C/C In Horizontal Direction Both Faces
Shear Check:
Vu(max) = 337.1 KN
f Vc = .85 x (fc')1/2 x b x d
6
= 384.19 KN > 337.1 KN O.K Satisfied
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 23 OF 45 .
4.5.2- Design Of Walls (W-3 & W-4)
Ko = 1 - sin q = 0.40
Ka = tan2 ( 45o - f / 2) = 0.25
ly / lx = 2.06 b = 1000 mm
lx = 3.40 m
Soil Surcharge
ly
qs qq
qs = Ka x gs x Hs = 31.17 KN/m2
Wv Total Factored Triangular Load = (1.6 x qs) 1.6 x 31.17 = 49.9 KN/m2
Wu Total Factored Uniform Load = (1.6 x qq) 1.6 x 2.486 = 3.977 KN/m2
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 24 OF 45 .
For Triangular Loading:- ( Due to soil)
Where
M= CF x Wv x H2 CF = Moment coefficient taken from the wall with 4 sides fixed graph
Q= CF x Wv x H CF = Shear coefficient taken from the wall with 4 sides fixed graph
Wv= Total factored trinagular load in KN
lx = 3.4 m
Water
ly
qw
qw = gwater x H = 70 KN/m2
Consider 1m strip:-
r = 0.85 x fc' 2 x Mu
1- 1-
fy 0.85 x 0.9 x fc' x b x d2
rx = 0.00149 < 0.00333 So use :- 0.00199
ry = 0.00164 < 0.00333 So use :- 0.00218
1.33rx = 0.00199
1.33ry = 0.00218
Therefore
Providing D25 @ 250 C/C In Horizontal Direction Both Faces
Providing D25 @ 250 C/C In Vertical Direction Both Faces
Shear Check:
Vu(max) = 152.3 KN
f Vc = 0.85 x (fc')1/2 x b x d
6
= 234.26 KN > 152.3 KN O.K Satisfied
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 27 OF 45 .
4.5.3- Design Of Walls (W-5 , W-6 & W-7)
Ko = 1 - sin q = 0.40
Ka = tan2 ( 45o - f / 2) = 0.25
c/c distan
ly / lx = 1.21 b = 1000 mm
lx = 5.80 m
Soil Surcharge
ly
qs qq
qs = Ka x gs x Hs = 31.17 KN/m2
Wv Total Factored Triangular Load = (1.6 x qs) 1.6 x 31.17 = 49.9 KN/m2
Wu Total Factored Uniform Load = (1.6 x qq) 1.6 x 2.486 = 3.977 KN/m2
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 28 OF 45 .
For Triangular Loading:- ( Due to soil)
Where
M= CF x Wv x H2 CF = Moment coefficient taken from the wall with 3 sides fixed graph
Q= CF x Wv x H CF = Shear coefficient taken from the wall with 3 sides fixed graph
Wv= Total factored trinagular load in KN
lx = 5.80 m
Water
ly
qw
qw = gwater x H = 70 KN/m2
Consider 1m strip:-
r = 0.85 x fc' 2 x Mu
1- 1-
fy 0.85 x 0.9 x fc' x b x d2
rx = 0.003740 > 0.00333 So use :- 0.00374
ry = 0.001844 < 0.00333 So use :- 0.00245
1.33rx = 0.00497
1.33ry 0.00245
Therefore
Providing D20 @ 250 C/C In Horizontal Direction Both Faces
Providing D20 @ 250 C/C In Vertical Direction Both Faces
Shear Check:
Vu(max) = 42.2 KN
f Vc = 0.85 x (fc')1/2 x b x d
6
= 236.13 KN > 42.2 KN O.K Satisfied
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 31 OF 45 .
4.5.4- Design Of Wall (W-8)
Ko = 1 - sin q = 0.40
Ka = tan2 ( 45o - f / 2) = 0.25
ly / lx = 1.10 b = 1000 mm
ly = 5.50 m
Soil Surcharge
lx
qs qq
qs = Ka x gs x Hs = 22.91 KN/m2
Wu Total Factored Uniform Load = (1.6 x qq) 1.6 x 2.486 = 3.977 KN/m2
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 32 OF 45 .
For Triangular Loading:- ( Due to soil)
Where
M= CF x Wv x H2 CF = Moment coefficient taken from the wall with 3 sides fixed graph
Q= CF x Wv x H CF = Shear coefficient taken from the wall with 3 sides fixed graph
Wv= Total factored trinagular load in KN
ly = 5.50 m
Water
lx
qw
qw = gwater x H = 50 KN/m2
Consider 1m strip:-
r = 0.85 x fc' 2 x Mu
1- 1-
fy 0.85 x 0.9 x fc' x b x d2
rx = 0.00075 < 0.00333 So use :- 0.00100
ry = 0.00195 < 0.00333 So use :- 0.00260
1.33rx = 0.00100
1.33ry 0.00260
Therefore
Providing D20 @ 250 C/C In Vertical Direction Both Faces
Providing D20 @ 250 C/C In Horizontal Direction Both Faces
Shear Check:
Vu(max) = 132.0 KN
f Vc = 0.85 x (fc')1/2 x b x d
6
= 236.13 KN > 132.0 KN O.K Satisfied
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 35 OF 45 .
4.5.5- Design Of Walls (W-9 & W-10)
(Designing the most critical wall among these three which is wall W-7)
gsoil = Soil Density = 19 KN/m3
gwater = Water Density = 10 KN/m3
Ko = 1 - sin q = 0.40
Ka = tan2 ( 45o - f / 2) = 0.25
ly / lx = 1.92 b = 1000 mm
lx = 2.600 m
Soil Surcharge
ly
qs qq
qs = Ka x gs x Hs = 22.91 KN/m2
Wv Total Factored Triangular Load = (1.6 x qs) 1.6 x 22.91 = 36.7 KN/m2
Wu Total Factored Uniform Load = (1.6 x qq) 1.6 x 2.486 = 3.977 KN/m2
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 36 OF 45 .
For Triangular Loading:- ( Due to soil)
Where
M= CF x Wv x H2 CF = Moment coefficient taken from the wall with 3 sides fixed graph
Q= CF x Wv x H CF = Shear coefficient taken from the wall with 3 sides fixed graph
Wv= Total factored trinagular load in KN
lx = 2.600 m
Water
ly
qw
qw = gwater x H = 50 KN/m2
Consider 1m strip:-
r = 0.85 x fc' 2 x Mu
1- 1-
fy 0.85 x 0.9 x fc' x b x d2
rx = 0.00024 < 0.00333 So use :- 0.00032
ry = 0.00296 < 0.00333 So use :- 0.00333
1.33rx = 0.00032
1.33ry 0.00394
Therefore
Providing D16 @ 250 C/C In Horizontal Direction Both Faces
Providing D16 @ 250 C/C In Vertical Direction Both Faces
Shear Check:
Vu(max) = 80.1 KN
f Vc = 0.85 x (fc')1/2 x b x d
6
= 162.67 KN > 80.1 KN O.K Satisfied
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 39 OF 45 .
4.6- REINFORCEMENT
JOB NO. 0-3850-20 DOC NO. C-667-1316-001<00A>
SHEET 40 OF 45 .
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 41 OF 45 .
4.7- ATTACHMENT (MOMENT GRAPHS).
4.7.1-
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 42 OF 45 .
4.7.2-
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 43 OF 45 .
4.7.3-
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 44 OF 45 .
4.7.4-
JOB No. 0-3850-20 DOC No. C-667-1316-001<00A>
SHEET 45 OF 45 .
4.7.5-