NOTE
A 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE A
NOTED AND COORDINATES ARE IN MILLIMETERS UNLESS
OTHERWISE NOTED.
2. FINISHED GROUND LEVEL (FGL) = EL.+4,500mm
FINISHED GROUND FLOOR LEVEL(FGFL) = EL.+4,800mm
PN 3. CONCRETE STRENGTH
TN 1) f’c=30.0MPa : ALL BUILDINGS AND THEIR FOUNDATIONS, STACKS
AND ASH SILOS (INCLUDING FOUNDATION)
2) f'c=24.0MPa : OTHER FOUNDATION
3) f’c=13.8MPa : PLAIN CONCRETE FOR ENCASEMENTS, THRUST
B BLOCKS, ELECTRICAL DUCTS, LEAN CONCRETE BACKFILL, AND B
SIMILAR
WHERE, f’c=CYLINDER COMPRESSIVE STRENGTH AT 28 DAY
4. REINFORECING BAR STRENGTH
1) ROUND BARS
GRADE SR295, fy=300 MPa
2) DEFORMED BAR
GRADE SD390, fy=400MPa
3) MESH REINFORCEMENT
GRADE SD490, fy=500MPa
5. CEMENT
C TYPE OF CEMENT WILL BE TYPE 1 PORTLAND CEMENT FOR C
GENERAL APPLICATIONS AND FOR SEAWATER APPLICATIONS
4 3 2 1 PORTLAND BLAST FURNACE CEMENT OR EQUIVALENT ALONG
WITH WATERPROOFING COMPOUND SHALL BE USED.
17,000 6. CONCRETE COVER (CAST-IN-PLACE CONCRETE)

CAST-IN-PLACE CONCRETE(NON PRESTRESSED)


6,000 5,500 5,500
CONDITION OF EXPOSURE FOUNDATION COLUMN WALL
BEAM SLAB
CONCRETE NOT - 40 20
D
EXPOSED TO WATER D
CONCRETE EXPOSED TO
EARTH OR WEATHER 75 40 40
(GROUND WATER (75) (75) (75)
500 500 OR SEA WATER)
CONCRETE CAST AGAINST
N 7,550,000 250 250 250 250 AND PERMANENTLY 75 75 75
E 3,841,000 EXPOSED TO EARTH
7. CHAMFERED CORNERS OF CONCRETE COLUMN & WALL
: ALL EXPOSED CORNERS (ANGLE OF 90‘ OR LESS) OF
REINFORCED CONCRETE SHOULD BE CHAMFERED. (25mmX25mm)
E E
8. FOR THE FOLLOWING ITEMS, SEE STANDARD DRAWINGS UNLESS

250 250
250 250 NOTED OTHERWISE.
500

500
A
- MINIMUM CONCRETE COVER
C1 C2 C2 C1 - HOOK, DEVELOPMENT AND SPLICES OF REBAR
9. MEMBERS WITHOUT DIMENSION
: SYMMETRICAL WITH RESPECT TO CENTER LINE

F F
8,000

REFERENCE DOCUMENTS/DRAWINGS
DOC/DWG NO. TITLE

NS2-UC07-P0ZEN-110001 SITE PLAN


NS2-UC07-P0ZEN-110002 PLOT PLAN
G NS2-VB00-P0ZEN-170001 DESIGN MANUAL FOR BUILDINGS & STRUCTRES G
NS2-UV01-P0ZEN-170102~11 STANDARD DRAWINGS
NS2-YD00-P0SGA-120390 FIRE FIGHTING PUMP SYSTEM_GENERAL ARRANGEMENT
NS2-VE04-P0USG-171119 FIRE FIGHTING PUMP HOUSE_CALCULATION
NS2-VW00-P0USG-171123 FIRE FIGHTING PUMP HOUSE_GROUND FLOOR PLAN

B
H H
C1 C2 C2 C1
FOR CONSTRUCTION
N 7,567,000 THIS DRAWING IS THE PROPERTY OF DOOSAN HEAVY INDUSTRIES VIETNAM.
IT IS NOT TO BE COPIED OR USED IN ANY WAY DETRIMENTAL TO THE COMPANY.
E 3,849,000

J 0 05.04.2019 FOR CONSTRUCTION C.M.CHOI S.H.PARK J.T.SEO J


Date
Rev. (DD.MM.YYYY) DESCRIPTION DRAWN CHKD. APPD.
COLUMN ARRANGEMENT PLAN Project

SCALE- 1 : 60
NGHI SON 2 BOT THERMAL POWER PLANT PROJECT

Owner

K KEY PLAN K
Owner's Engineer

Contractor

Doosan Heavy Industries Vietnam

TN
PN
FIRE FIGHTING PUMP HOUSE
L Sub-supplier L

DRAWING TITLE

COLUMN MEMBER LIST FIRE FIGHTING PUMP HOUSE


MEMBER W L EA COLUMN ARRANGEMENT PLAN
C1 500 500 4
M M
C2 500 500 4 SCALE DRAWING NUMBER SHEET NO. REV. NO.

1/60 NS2-XB02-P0USG-171142 1 of 1 0

A1 (841 x 594)