S600+ Hardware - CPU


Main Processor Board - P152
Heart of the FloBoss S600+
– ColdFire MPC8313C
• 333MHz / 300 MIPS
– 256 Mb FLASH
– 4 Mb SRAM (non-volatile)
– 10 Available Serial Ports
• 3 RS232 (1 dedicated download
port on front panel)
• 3 RS422 / 485
• 4 RS485

– 2 Ethernet Ports
– USB Port
P152 – Power Requirements
24Volts dc Supply (2 Amps)
– Will operate between 20 & 32 Volts dc

Protected by 2.5Amp anti-surge fuse

Start-up in-rush current may draw 6Amps (Approx 100ms)


Significant when multiple machines are powered from a single
supply
P152 – Power Source
On-board regulated 15V & 24V Supplies
– Powering Loops
– Powering Pre-amplifiers

Protected by Thermal fuses


TB-1 Power Connections
Pin Function
1 +24Vdc Input
2 0V (Return) Input
3 +24Vdc Output (500mA)
4 +15Vdc Output (100mA)
5 0V (Return) Output
P152 – Power Source
• Normally Open or Normally Closed terminals provides the
watchdog status
A CPU failure causes the relay to de-energize

TB-1 Power Connections


Pin Function
6
Normally Closed

7 Common
8 Normally Open
P152 – Watchdog Relay

Single Pole, Double Throw Relay


– Normally open (N/O) or Normally closed (N/C)
– Fail-safe action on CPU Failure

TB-1 Pin Connections


Pin Function
6 Normally Closed
7 Common
8 Normally Open
P152 – Battery Back-up
• Board Mounted Nickel-Metal Hydride Cell
Backup contents of SRAM (Configuration)
Backup BIOS CMOS
On-board Calendar Clock

• Lithium Rechargeable 3.0Volt, 1500mAmp/hour, user-


replaceable
P152 – Battery Back-up

Battery is Load-tested once per week

– Early Warning Alarm (“BATT FAIL”)


Make Arrangements to Replace Battery ASAP

Typical Battery Life approx 5-7 Years


if in use!
P152 – Battery Back-up
• Battery is Load-tested once per week
• If the battery fail alarm appears, the battery will need replacing
within two weeks
• Battery Specification
Charging Time (20%-80%) 48 hours
Hold-up Time (without 3 months at 20° C (68° F), 1 month at 40° C
recharge) (104° F)
Battery Life (Typical) 5-7 years
Battery Backup 2 weeks at 20° C (68° F)
Holdup Time (after
battery has failed its
load test)
Hardware-CPU
Fuse
Hardware-CPU
Hardware-CPU
Hardware-CPU
Hardware-CPU
Hardware-CPU
Hardware-CPU
The CPU has 12 standard
communication ports

Nine serial and 2 ethernet


Hardware-CPU

RS 232
RS 232

RS 422/485
RS 422/485
RS 422/485
Hardware-CPU
Use the 2.0 USB port on the
CPU module to export alarm
history and report history
information to a USB
flash drive.
You access the export
facility either through the
USB Port
S600+ front panel or the
web browser
(Tech/Engineer > USB)