Professional Documents
Culture Documents
YRG116 INI Parameters
YRG116 INI Parameters
YRG116 INI Parameters
Project:
User:
Information
Default
Parameter Value Information Setting
A1 Initialization
A1-02 Control method 5 2
A1-06 Select application 8 ESP Function 0
A2 User Parameters
A2-01 User parameter 1 d2-02 Frequency reference lower limit A1-02
A2-02 User parameter 2 E2-01 Motor rated current b1-01
A2-03 User parameter 3 L3-02 StallP acceleration level b1-02
A2-04 User parameter 4 L3-06 StallP running level b1-03
A2-05 User parameter 5 L5-01 Number of auto restart attempts C1-01
A2-06 User parameter 6 L5-04 Fault Reset Interval Time C1-02
A2-07 User parameter 7 L5-05 Auto restart selection C6-01
A2-08 User parameter 8 L5-51 Restart Clr Time C6-02
A2-09 User parameter 9 L5-52 OL4 Restart Sel d1-01
A2-10 User parameter 10 L6-01 Torque detection selection 1 d1-02
A2-11 User parameter 11 L6-02 Torque detection level 1 d1-03
A2-12 User parameter 12 L6-03 Torque detection time 1 d1-04
A2-13 User parameter 13 L6-04 Torque detection selection 2 d1-17
A2-14 User parameter 14 L6-05 Torque detection level 2 E1-01
A2-15 User parameter 15 L6-06 Torque detection time 2 E1-03
A2-16 User parameter 16 P1-01 P Sensor Type E1-04
A2-17 User parameter 17 P1-02 Pressure Scaling E1-05
A2-18 User parameter 18 P1-03 Hi Pres Flt Lvl E1-06
A2-19 User parameter 19 P1-04 Low Pres Flt Lvl E1-09
A2-20 User parameter 20 P1-05 Det Dly at Start E1-13
A2-21 User parameter 21 P1-06 Hi Pres Det Dly E2-01
A2-22 User parameter 22 P1-07 Low Pres Det Dly E2-04
A2-23 User parameter 23 P4-04 Current Ratio E2-11
A2-24 User parameter 24 ----- H4-02
A2-25 User parameter 25 ----- L1-01
A2-26 User parameter 26 ----- L3-04
b1 Operation Mode Selection
b1-01 Reference selection 3 Option card 1
b1-02 Operation method selection 3 Option card 1
b1-07 Local/remote run selection 1 Accept External Run - If the run command is closed when 0
switching from LOCAL mode or alternative reference to
REMOTE mode, the drive will run.
DriveWizard Industrial for Windows (C) by Yaskawa America, Inc. 1/3
Default
Parameter Value Information Setting
b1-08 Run command at programming 1 Enabled - Run command accepted in all menus (except when 0
C1 Acceleration and Deceleration Times b1-02 = 0).
L2-01 Momentary power loss detection 3 KEB Mode 1 (with L2-02 timer for UV1) 0
L2-05 Undervoltage detection level 420 VDC 380 VDC
L2-29 KEB Mode Selection 1 Single Mode KEB2 0
L3 Stall Prevention Function
L3-04 StallP deceleration selection 0 Disabled - The drive decelerates at the selected Dec time.If the 1
L3-21 Deceleration rate operation gain 2,80 load is too large or the Dec time is too short, an OV fault may 1,00
occur.
L3-24 Inertia conversion motor acceleration time 1,667 sec 0,100 sec
L5 Fault Reset
L5-04 Fault Reset Interval Time 60,0 sec 10,0 sec
L5-52 OL4 Restart Sel 0 Disabled 1
n8 Permanent Magnet Motor Control
n8-47 Pull-In Current Compensation Time 0,0 s 5,0 s
n8-51 Constant*
Acceleration Time Pull-In Current* 0% 50 %
n8-62 Output voltage limit 460,0 VAC 400,0 VAC