From field analysis, we obtained information during

testing where the WWTP was filled full of water in a


condition where the WWTP has not been
waterproofed and a leak occurs (cracks occur initial)
where the inside of the WWTP should be given a
waterproof layer before testing after that the new
structure is loaded. The wall thickness design along
with the reinforcement dimensions is very
economical.

So what can we do:

o The B axis wall was dismantled and the new


wall thickness was 600 mm and carried out
additional reinforcement and existing
reinforcement will be maintained
o The walls of axis A are strengthened using a
100mm thick jacketing method from the
outside and inside in an elevation of 0.00 –
6.40 m including the other side that does not
fail, a crack pattern occurs first reinforced
with carbon fiber reinforced polymer plates.
o For elevations of 6.40 -12.65 m, all walls are
strengthened using the section jacketing
method 100 mm thick.
Analyze
Calculation
Structure of the
WWTP with
Computer Analysis
We design load combination in full water condition &
empty condition.

a. Load combination in Full water condition

b. Load combination in Empty condition

In this load combination, we trial and error up to 8


type combination of the water treatment simulation.
And we get the need of the jacketing rebar.
Exsisting rebar need for the structure waste water
treatment.

Need of the rebar after repair condition

Need of the rebar after repair condition