MTL5045

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Hazardous area Safe area

MTL5045 ISOLATING
DRIVER
4/20mA
6 7
5 8
4 9
3 I 10
+ –
P 2 11
I
4/20mA
– 1 I 12
4/20mA
+
The MTL5045 isolates and passes on a 4/20mA signal from a
controller located in the safe area to a load of up to 800Ω in the 13 Vs–
hazardous area. It has a high output capacity of 16V at 20mA 14 Vs+
20 to 35V dc
combined with a low (4V) drop across its input terminals and excellent
accuracy.

SPECIFICATION
See also common specification
Terminal Function
Number of channels
1 Output –ve
One
2 Output +ve
Location of load
11 Input –ve
Zone 0, IIC, T4–6 hazardous area if suitably certified
12 Input +ve
Div. 1, Group A hazardous location
13 Supply –ve
Safe-area input
14 Supply +ve
Signal range: 4 to 20mA
Under/over range: 0 to 24mA
Hazardous-area output
Maximum load resistance: 800Ω (16V at 20mA) LED indicator
Output resistance Green: power indication
>2MΩ Supply voltage
Input voltage drop 20 to 35V dc
<4V at 20mA Maximum current consumption
Input and output circuit ripple 50mA at 24V
<40µA peak-to-peak 60mA at 20V
Transfer accuracy at 20°C 40mA at 35V
Better than 20µA Maximum power dissipation within unit (with 20mA signal)
Temperature drift 1.0W at 24V
<1µA/°C 1.1W at 35V
Response time Safety description
Settles to within 10% of final value within 250µs 28V, 300Ω, 93mA; Um = 250V rms or dc

EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 281 571 8065 Fax: +1 281 571 8069
ASIA PACIFIC Tel: +65 6 487 7887 Fax: +65 6 487 7997
Aug 2008
E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com