Professional Documents
Culture Documents
ME201 - Refrigeration & Airconditioning 2022
ME201 - Refrigeration & Airconditioning 2022
Refrigeration cycles transfer heat from a lower temperature region to a higher temperature
one, at the expense of work input to the system.
Refrigeration Capacity
Ton of Refrigeration : It is the cooling capacity that can freeze 1 ton (2000 Ib) of liquid
water at 0C into ice at 0C in 24 hours.
1 ton Refrigeration = 200 BTU/min = 12000 BTU/h = 211kJ/min = 3024 Kcal/h = 3.516 kW
APPLICATIONS OF REFRIGERATION
COP should be high, ie. Less power requirement for cooling in desirable
The cost of the refrigerant is a significant criteria, specially for large units
CFC Refrigerants : R-11, R-12 (CF2CL2, Di-chloro Di-floro Methane), Chlorine of Chloro-
Floro-Carbon (Freon) breaks up the atmospheric Ozone, causing depletion of Ozone
layer.
HCFC Refrigerants : Hydrogenated CFCs, eg. R-22, Structure contains H atoms which
react with Chlorine first as they breakup, saving the O3.
HFC Refrigerants : Hydrogenated Floro-Carbons, R-134a, does not contain any Chlorine
atom, so much more environment friendly.
The problem was detected in early 70’s ; Montreal Protocol was signed in 1992 ; Hopefully
the depletion level will go back to pre-70 condition by 2025. GWP is the current concern.
Other Refrigerants : NH3 (R-717), CO2 (R-744), Water (R-718), Air (R-729), Azeotropes
(mixture of more than one refrigerant eg. R-410, R-502) etc.
Compressor and Condenser are on the high pressure side. Expansion device and
Evaporator are on the low pressure side of the refrigerant flow circuit.
Condenser: It cools the high pressure refrigerant vapour. Condenser rejects the heat to
the atmosphere (typically air or water) and transforms the high pressure refrigerant vapour
to high pressure liquid.
Expansion Device: This part (typically a valve) reduces the pressure of cooled refrigerant
liquid. In the expansion device the enthalpy remains constant.
Evaporator: This is the coolest component of a refrigeration system. Here low pressure
refrigerant evaporates absorbing lot of heat typically from the refrigerated space. From the
evaporator the low pressure refrigerant vapour is re-circulated to the compressor.
Basically the closed circuit allows the same refrigerant to absorb heat from low
temperature at the evaporator (by vaporization at low pressure) and reject heat at high
temperature (by condensation at high pressure). Generally the cooling rate is varied by
controlling the mass flow rate of the refrigerant.
Air conditioning is the automatic control of temperature and humidity to values which
provide a sense of comfort for human beings.
This is achieved by –
Typically we are comfortable at around 20°C temperature and 60% Relative Humidity.
CLASIFICATIONS
These are air conditioning units which are mass produced, which are installed within or
near the conditioned space. Here the air comes in to direct contact of the cooling coils in
which the refrigerant evaporates extracting heat. They are manufactured to limited
capacity (much less than 50 tons) and the system layout can not be changed very much.
This type of air conditioners are packaged as self-contained Window type and divided
Split type packages.
In all air system meets all the cooling required by cold air supplied by a central air handling
unit (AHU), which is distributed to various parts of a building as per requirement. The air
from the room is returned back to the AHU, mixed with some fresh ventilation, cooled and
sent to the rooms again. This system is more expensive but makes good humidity control.
In all water system meets all the cooling required by chilled water supplied by a central
refrigeration system, which is distributed to various parts of a building as per requirement.
In each room Fan-Coil Units (FCU) are used to cool the room air. In the FCU a fan draws
in a mixture of room air with some fresh air and blows it across the cooling colid of chilled
water. This system is less costly but can not achieve good humidity control.
WATER-AIR SYSTEM
This system employs a combination of both air and water circulation to control the room air
condition. This may require less air to be circulated through AHU as part of the heat is
taken away by smaller FCU. Make the system more cost effective in large or high rise
buildings.
Cooling load in a room can be estimated by summing the possible heat gains through
various ways. These may include -
Standard calculation procedures are used for the cooling load calculation, eg. using
ASHRAE code.