1 EQUIPMENT PANEL 26.245 0.8 20.996 400 30.522 28.152 27.174 9.382 3 3P 100 125 36 4-22mm² THHN 8.0mm² THHN CABLE TRAY OR LADDER 1 POWER OUTLET 1 15.000 400 21.651 3 3P 80 125 36 4-30mm² THHN 8.0mm² THHN 20mm DIA. PVC PIPE
2. ALL ELECTRICAL WORKS HEREIN INCLUDED SHALL BE EXECUTED BY PERSONNEL WITH
2 UPS 20.000 0.8 18.000 400 28.868 3 3P 60 63 10 4-8.0mm² THHN 8.0mm² THHN CABLE TRAY OR LADDER 2 SPACE - - - - - - - - - -
ELECTRICAL EXPERIENCE AND WORKS SHALL BE NEATLY PLACED, SECURELY
3 LIGHTING & POWER PANEL 22.949 0.8 18.359 400 11.296 11.796 11.470 21.651 3 3P 125 125 36 4-60mm² THHN 14mm² THHN CABLE TRAY OR LADDER 3 CONVENIENCE OUTLET 1 0.900 230 3.913 1 1P 20 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE
FASTENED AND PROPERLY FINISHED.
4 UPS (FOR REDUNDANCY) 20.000 0.3 6.000 400 28.868 3 3P 60 63 10 4-8.0mm² THHN 8.0mm² THHN CABLE TRAY OR LADDER 4 CONVENIENCE OUTLET 2 1.620 230 7.043 1 1P 20 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE
5 TX - COOLING CABINET & MAIN POWER SUPPLY 15.000 0.8 12.000 400 21.651 3 3P 30 63 10 4-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER 5 CONVENIENCE OUTLET 3 1.080 230 4.696 1 1P 20 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE
3. ALL LV AC WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE UNLESS
6 UPS AC BYPASS - - - - - 3 3P 60 63 10 4-8.0mm² THHN 8.0mm² THHN CABLE TRAY OR LADDER 6 GFCI 0.900 230 3.913 1 1P 20 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE
OTHERWISE INDICATED IN THE PLAN. THE MINIMUM SIZE OF WIRE AND CONDUIT SHALL
7 WELDING MACHINE, 3 PHASE 12.000 0.3 3.600 400 17.321 3 3P 30 63 10 4-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER 7 LIGHTING OUTLET 1 0.903 230 3.926 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE
BE 3.5mm2 THHN IN 15mmØ PVC.
8 MAIN TX LCP SUPPLY (CC1 & 2) 3.500 0.8 2.800 400 5.052 3 3P 15 63 10 4-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER 8 LIGHTING OUTLET 2 0.525 230 2.283 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE
9 AC CONDENSING UNIT 1 3.970 1 3.970 400 5.730 3 3P 30 63 10 4-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER 9 AIR-CON UNIT 1 0.012 230 0.052 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE
4. WIRING METHOD SHALL BE AS FOLLOWS:
10 AC CONDENSING UNIT 2 9.080 1 9.080 400 13.043 3 3P 30 63 10 4-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER 10 AIR-CON UNIT 2 0.011 230 0.048 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE
A. FEEDERS AND RISERS - CABLE TRAY OR LADDER
11 BATTERY CHARGER 125VDC 20.000 1 20.000 400 28.868 3 3P 100 125 36 4-30mm² THHN 8.0mm² THHN CABLE TRAY OR LADDER 11 AIR-CON UNIT 3 0.032 230 0.139 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE
B. LIGHTING, POWER RECEPTACLE - PVC BRANCH CIRCUIT &
12 SPARE 1.500 0.8 1.200 400 2.165 3 3P 15 63 10 - - - 12 AIR-CON UNIT 4 0.032 230 0.139 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE
AUXILLIARY
B 13
14
BATTERY CHARGER 125VDC (FOR REDUNDANCY)
SPACE
20.000
-
0.3
-
6.000
-
400
-
28.868 3
-
3P
-
100
-
125
-
36
-
4-30mm² THHN
-
8.0mm² THHN
-
CABLE TRAY OR LADDER
-
13
14
AIR-CON UNIT 5
AIR-CON UNIT 6
0.085
0.085
230
230
0.370
0.370
1
1
1P
1P
15
15
63
63
10
10
2-3.5mm² THHN
2-3.5mm² THHN
3.5mm² THHN
3.5mm² THHN
15mm DIA. PVC PIPE
15mm DIA. PVC PIPE 1 5. ALL EXPOSED CONDUIT INSTALLATIONS FOR LIGHTING, POWER AND AUXILLIARY B
15 WELDING MACHINE, 1 PHASE (PROVISION) 6.900 0.5 2.070 230 30.000 1 1P 60 63 10 - - - 15 AIR-CON UNIT 7 0.085 230 0.370 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE SYSTEM SHALL BE RIGID STEEL CONDUIT (RSC) FOR EMBEDDED WORKS SHALL BE
16 SPACE - - - - - - - - - - - - - 16 AIR-CON UNIT 8 0.085 230 0.370 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE
POLYVINYL CHLORIDE CONDUIT (PVC).
17 PERIMETER LIGHTING 1 1.050 0.8 0.840 230 4.565 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER 17 EXHAUST FAN 0.540 230 2.348 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE
18 PERIMETER LIGHTING 2 1.050 0.8 0.840 230 4.565 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER 18 LIGHTING OUTLET 3 (WITH PHOTOSWITCH) 0.054 230 0.235 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN 15mm DIA. PVC PIPE 6. CONDUITS SHALL BE PROTECTED AGAINST DAMAGES BY THE ENTRANCE OF WATER
19 SPARE 1.000 0.8 0.800 230 4.348 1 1P 15 63 10 - - - 19 SPARE 0.500 230 2.174 1 1P 15 63 10 - - - AND FOREIGN MATTERS DURING CONSTRUCTION. ALL ENDS OF CONDUITS SHALL BE
20 BATTERY CHARGER 48VDC 5.000 1 5.000 230 13.043 1 1P 125 125 36 2-22mm² THHN 8.0mm² THHN CABLE TRAY OR LADDER 20 SPARE 0.500 230 2.174 1 1P 15 63 10 - - - PLUGGED TO EXCLUDE MOISTURE AND DUST IMMEDIATELY AFTER THE CONDUITS ARE
21 SERVER PANEL (WORKSTATION) 0.008 0.8 0.006 230 0.033 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER 21 SPACE - - - - - - - - - - PLACED.
22 SUBSTATION LIGHTING (WITH PHOTOSWITCH) 0.550 0.8 0.440 230 2.391 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER 22 SPACE - - - - - - - - - -
23 OLTC SUPPLY 1.000 0.8 0.800 230 4.348 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER MAIN 22.949 400 11.296 11.796 11.470 21.651 3 3P 125 125 36 4-60mm² THHN 14mm² THHN CABLE TRAY OR LADDER
11 GATEWAY PANEL 0.313 230 1.359 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER
12 MAIN 1 TRANSFORMER PROTECTION PANEL 0.313 230 1.359 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER
13 MCB EMERGENCY OUTLET 0.720 230 3.130 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER
19 SPACE - - - - - - - - - -
AMPERE (A) CIRCUIT BREAKER
CKT. LOAD VOLTAGE GROUND WIRE
LOAD DESCRIPTION (kW) (V) PHASE FEEDER SIZE CONDUIT SIZE & TYPE 20 SPACE - - -
NO. AN BN CN 3ɸ POLE AT AF kAIC SIZE - - - - - - -
MAIN 15.319 400 23.496 24.000 19.109 3 3P 40 63 10 4-8.0mm² THHN 8.0mm² THHN CABLE TRAY OR LADDER
1 MARSHALLING PANEL 3.000 400 4.330 3 3P 32 63 10 4-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER
2 TX - TERMINAL BOX POWER SUPPLY 3.500 400 5.052 3 3P 15 63 10 4-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER
3 CAP BANK - COOLING & LIGHTING CIRCUIT 3.000 230 13.043 1 1P 40 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER
9 SERVER 0.250 230 1.087 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER
CKT. LOAD VOLTAGE AMPERE CIRCUIT BREAKER GROUND WIRE
LOAD DESCRIPTION (kW) (V) (A) FEEDER SIZE CONDUIT SIZE & TYPE
10 PCB MOTOR DRIVE POWER 1.500 230 6.522 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER NO. POLE AT AF kAIC SIZE
E 11 TRANSFORMER PROTECTION 0.250 230 1.087 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER
1 MVSG - 1ST CONTROL POWER 5.250 125 42.000 2P 125 125 36 2C-60mm² PVC - CABLE TRAY OR LADDER
E
12
13
GATEWAY PANEL
1.500
230
230
1.087
6.522
1
1
1P
1P
15
15
63
63
10
10
2-3.5mm² THHN
2-3.5mm² THHN
3.5mm² THHN
3.5mm² THHN
CABLE TRAY OR LADDER
21 MAIN 1 TRANSFORMER PROTECTION M1 PANEL 0.250 230 1.087 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER
10 MAIN 2 TRANSFORMER PROTECTION M1 PANEL 0.087 125 0.696 2P 15 63 10 2C-3.5mm² PVC - CABLE TRAY OR LADDER
C 04/13/2022 ISSUED FOR REVIEW NAC JRS THP
11 115kV LINE M1 & M2 PROTECTION PANEL 0.097 125 0.776 2P 15 63 10 2C-3.5mm² PVC - CABLE TRAY OR LADDER
22 MAIN 2 TRANSFORMER PROTECTION M1 PANEL 0.250 230 1.087 1 1P 15 63 10 2-3.5mm² THHN 3.5mm² THHN CABLE TRAY OR LADDER
12 FPP (FROM 69KV M1 & M2) 0.122 125 0.972 2P 15 63 10 2C-3.5mm² PVC - CABLE TRAY OR LADDER
B 03/16/2022 ISSUED FOR REVIEW NAC JRS THP
23 SPARE 0.500 230 2.174 1 1P 15 63 10 - - -
13 EVENT RECORD PANEL 1.000 125 0.800 2P 15 63 10 2C-3.5mm² PVC - CABLE TRAY OR LADDER
A 02/04/2022 ISSUED FOR REVIEW NAC JRS THP
24 SPARE 0.500 230 2.174 1 1P 15 63 10 - - -
14 BCU PANEL 1.000 125 0.800 2P 15 63 10 2C-3.5mm² PVC - CABLE TRAY OR LADDER REV DATE DESCRIPTION Prepd. Chkd. Appd.
25 SPARE 0.500 230 2.174 1 1P 15 63 10 - - -
15 BCU PANEL 1.000 125 0.800 2P 15 63 10 2C-3.5mm² PVC - CABLE TRAY OR LADDER
26 SPACE - - - - - - - - - -
16 GATEWAY (EST) 0.375 125 3.000 2P 15 63 10 2C-3.5mm² PVC - CABLE TRAY OR LADDER
Project Title:
27
28
SPACE
SPACE
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
17
18
RTCC (EST)
SPARE
0.375 125 3.000 2P 15 63 10 2C-3.5mm² PVC
-
-
-
CABLE TRAY OR LADDER
-
75 MWac Pinugay Solar Power Plant
0.500 125 4.000 2P 15 63 10
F 29 SPACE - - - - - - - - - -
19 SPARE 0.500 125 4.000 2P 15 63 10 - - -
Barangay Pinugay, Baras, Rizal, Philippines F
30 SPACE - - - - - - - - - -
20 SPARE 0.500 125 4.000 2P 15 63 10 - - -
MAIN 26.245 400 30.522 28.152 27.174 9.382 3 3P 100 125 36 4-22mm² THHN 8.0mm² THHN CABLE TRAY OR LADDER
21 SPACE - - - - - - - - - -
22 SPACE - - - - - - - - - -
23 SPACE - - - - - - - - - -
24 SPACE - - - - - - - - - -
MAIN 18.602 125 140.812 2P 250 250 36 2C-95mm² PVC - CABLE TRAY OR LADDER
48VDC PANEL
PANEL TAG: 48VDC LOCATION: BATTERY ROOM
MAIN CIRCUIT BREAKER: 125AT/125AF MCCB DC, 2P, 36kAIC ENCLOSURE: NEMA 12
PHASE: 1 PHASE SYSTEM VOLTAGE: 48V DC, 60HZ
FED FROM: BATTERY CHARGER 48VDC BUS RATING: 125 A
G 2 MULTIPLEXER PROVISION (EST) 0.625 48 13.021 2P 20 63 10 2C-5.5mm² PVC - CABLE TRAY OR LADDER G
3 48VDC GATEWAY (FOR MERALCO PROVISION) 0.500 48 10.817 2P 20 63 10 2C-5.5mm² PVC - CABLE TRAY OR LADDER
5 SPACE - - - - - - - - - -
6 SPACE - - - - - - - - - -
MAIN 2.025 48 42.188 2P 125 125 36kAIC 2C-25mm² PVC - CABLE TRAY OR LADDER Document Title.:
Donald Antonio
MAIN CONTROL BUILDING
AUXILIARY LOAD SCHEDULE
Electrical Engineer
August 28,2022
EE-3401 SCALE NTS DATE. 08/25/2022 Project No. : 45-2020-GBP FILENAME: GBP02
THIS DOCUMENT IN WHOLE OR IN PART MAY NOT BE USED BY ANY PERSON FOR ANY PURPOSE OTHER THAN THAT SPECIFIED, WITHOUT THE
EXPRESS WRITTEN PERMISSION OF SOLENERGY. ANY LIABILITY ARISING OUT OF USE BY A THIRD PARTY OF THIS DOCUMENT FOR PURPOSE NOT
WHOLLY CONNECTED WITH THE ABOVE SHALL BE THE RESPONSIBILITY OF THAT PARTY WHO SHALL INDEMNIFY SOLENERGY AGAINST ALL CLAIMS
COSTS DAMAGES AND LOSSES ARISING OUT OF SUCH USE.