Load Schedule - 2 Storey Res - Summerfield - Ar Kevin
Load Schedule - 2 Storey Res - Summerfield - Ar Kevin
Load Schedule - 2 Storey Res - Summerfield - Ar Kevin
Load Description
Circuit RATING
VA Amperes VOLTAGE Size of Conductor Size of Conduit
No.
Load Qty AT P AF
2
2 - 3.5 mm THHN Cu. Wire 15 mm Dia.PVC
1 Lighting Outlets 10 1000 4.35 230 15 2 50 2
1- 2.0 mm THHN Cu. Wire(G) Conduit
2
2 - 3.5 mm THHN Cu. Wire 15 mm Dia.PVC
2 Lighting Outlets 11 1100 4.78 230 15 2 50
1- 2.0 mm2 THHN Cu. Wire(G) Conduit
2 - 3.5 mm2 THHN Cu. Wire 15 mm Dia.PVC
3 Lighting Outlets 10 1000 4.35 230 15 2 50
1- 2.0 mm2 THHN Cu. Wire(G) Conduit
2 - 3.5 mm2 THHN Cu. Wire 15 mm Dia.PVC
4 Lighting Outlets 10 1000 4.35 230 15 2 50
1- 2.0 mm2 THHN Cu. Wire(G) Conduit
2 - 3.5 mm2 THHN Cu. Wire 15 mm Dia.PVC
5 Lighting Outlets 7 700 3.04 230 15 2 50
1- 2.0 mm2 THHN Cu. Wire(G) Conduit
2 - 3.5 mm2 THHN Cu. Wire 20 mm Dia.PVC
6 Convenience Outlet 7 1260 5.48 230 20 2 50
1- 3.5 mm2 THHN Cu. Wire(G) Conduit
2 - 3.5 mm2 THHN Cu. Wire 20 mm Dia.PVC
7 Convenience Outlet 6 1080 4.70 230 20 2 50
1- 3.5 mm2 THHN Cu. Wire(G) Conduit
2 - 3.5 mm2 THHN Cu. Wire 20 mm Dia.PVC
8 Refrigerator 1 1500 6.52 230 20 2 50
1- 3.5 mm2 THHN Cu. Wire(G) Conduit
2 - 5.5 mm2 THHN Cu. Wire 20 mm Dia.PVC
9 E. Range and Rangehood 1 3500 15.22 230 30 2 50
1- 3.5 mm2 THHN Cu. Wire(G) Conduit
2 - 3.5 mm2 THHN Cu. Wire 20 mm Dia.PVC
10 Convenience Outlet 7 1260 5.48 230 20 2 50
1- 3.5 mm2 THHN Cu. Wire(G) Conduit
2
2 - 5.5 mm THHN Cu. Wire 20 mm Dia.PVC
11 ACU 1.0 Hp 1 1840 8.00 230 30 2 50
1- 3.5 mm2 THHN Cu. Wire(G) Conduit
2 - 5.5 mm2 THHN Cu. Wire 20 mm Dia.PVC
12 ACU 1.0 Hp 1 1840 8.00 230 30 2 50
1- 3.5 mm2 THHN Cu. Wire(G) Conduit
2 - 3.5 mm2 THHN Cu. Wire 20 mm Dia.PVC
13 Convenience Outlet 7 1260 5.48 230 20 2 50
1- 3.5 mm2 THHN Cu. Wire(G) Conduit
2 - 5.5 mm2 THHN Cu. Wire 20 mm Dia.PVC
14 ACU 1.5 Hp (Split Type) 1 2300 10.00 230 30 2 50
1- 3.5 mm2 THHN Cu. Wire(G) Conduit
I wire =
I total + (25% LML) I CB = I total + (150% LML)
= 100.93 Amperes = 113.43 Amperes
@ 85% DF 85.79 Amperes @ 85% DF 96.42 Amperes
Note:
Use GFCI type C.O. for outlets Located at Toilet and Barthroom, Laundry Area, and near kitchen sinks.
Use GFCI type Circuit Breaker for Laundry Circuit
Use Weather Proof type outlet for C.O. located at terrace and garrage,
Use 14 mm2 for the grounding and bonding conductor of the panel board