BSP - BG29 Compliant PICV Valve Pack - Installation Instructions MAY 22
BSP - BG29 Compliant PICV Valve Pack - Installation Instructions MAY 22
If you know the kW ra�ng of the hea�ng system: If you know the kW ra�ng of the cooling system:
Total hea�ng system kW Pipe size to/from hea�ng system Total cooling system kW Pipe size to/from cooling system
660kW to 3,000kW ½” pipe to the Filter Pot Mini 530kW to 2,400kW ½” pipe to the Filter Pot Mini
3,000kW to 4,400kW ¾” pipe to the Filter Pot Mini 2,400kW to 3,500kW ¾” pipe to the Filter Pot Mini
4,400kW to 7,500kW 1” pipe to the Filter Pot Mini 3,500kW to 6,000kW 1” pipe to the Filter Pot Mini
Total Volume of System NOTE: You can es�mate the system volume by mul�plying the kW ra�ng:
= L/sec
86400
Hea�ng kW x 12 = Litres or for Cooling kW x 15 = Litres
Example: You can then set the Danfoss PICV (Pressure Independent Control Valve)
37,500L
= 0.43 L/sec to 0.43L/sec. This will now limit the flow through the Filter Pot to comply
86400
with BSRIA regula�ons (see typical installa�on drawings below).
BMS Fill/
Return
Control Valve SYSTEM
BMS PUMPS
Drain
POWER
ISOLATOR PS
PICV
PS Pressure Sensor POWER
SFI
ISOLATOR
PS
FILTER PS
MONITOR IV CIRCULATING IV
PUMP FILTER
MONITOR PICV
SYSTEM SYSTEM
FLOW FLOW
SYSTEM
FLOW
FLOW ADJUSTMENT ②
DN15 (�⁄�"), DN20 (�⁄�") & DN25 (1")
①
100% ≠ 10% ③ ④
h h+ 2 mm,DN15 & DN20
h+ 4 mm,DN25
⑤
Building Services Products Limited reserves the right to change and/or amend details, specifications and/or dimensions of the BSP Filter Pot Mini at any time and without notice. Version 1.0 05/2022