Professional Documents
Culture Documents
DeltaV Power and Grounding
DeltaV Power and Grounding
2
Contents
D800118X022
Contents
Chapter 1 Preface: Read this section first........................................................................................9
1.1 Important.........................................................................................................................................9
1.2 Conventions for colors in wiring diagrams...................................................................................... 10
1.3 Using this manual........................................................................................................................... 10
1.4 CE statement..................................................................................................................................11
1.5 Conventions used in this manual.................................................................................................... 11
1.5.1 General definitions...................................................................................................................... 11
1.5.2 Power and grounding definitions.................................................................................................12
iii
Contents
D800118X022
iv
Contents
D800118X022
v
Contents
D800118X022
vi
Contents
D800118X022
vii
Contents
D800118X022
Construction considerations................................................................................................................185
Production floor and remote installations ........................................................................................... 185
HVAC system considerations...............................................................................................................186
Purging system considerations............................................................................................................186
Enclosure and room air pressure calculations ......................................................................................186
Maintaining environmental control systems ....................................................................................... 186
7.11 References................................................................................................................................. 187
viii
Preface: Read this section first
D800118X022
Notices
The following types of notices are used in this manual:
Notes provide clarification, emphasis, or exceptions.
Cautions provide guidance that you must follow to ensure the highest reliability and
availability.
Warnings provide guidance that you must follow to prevent a safety risk or equipment
damage.
1.1 Important
Complying with the codes and regulations of authorities having jurisdiction is essential to
ensuring personnel safety. The guidelines and recommendations in this manual are
intended to meet or exceed applicable codes and regulations. If differences occur
9
Preface: Read this section first
D800118X022
between this manual and the codes and regulations of authorities having jurisdiction,
those codes and regulations must take precedence.
All DeltaV installationprocedures must be performed by qualified personnel and
DeltaVequipment must be used only for the purposes described.
10
Preface: Read this section first
D800118X022
1.4 CE statement
This manual describes installation and maintenance procedures for products that have
been tested to be in compliance with appropriate CE directives. To maintain compliance,
these products must be installed and maintained according to the procedures described in
this document. Failure to follow the procedures may compromise compliance.
11
Preface: Read this section first
D800118X022
12
Preface: Read this section first
D800118X022
Clean power-- Power without known power-quality issues such as transients, harmonics,
surges, and sags. Power-conditioning equipment such as UPSs, isolation transformers, and
surge protection devices (SPDs) typically provide power to the control system.
Equipotential bonding system--A system in which every location in the grounding
network is at the same potential voltage. Used in this document to refer to both protective
and functional equipotential bonding, as defined in IEC 60364-4-44 444.3.3.
DC ground (DCG)--DeltaV isolated DC ground reference scheme to which all DC power
source commons are connected. IEC refers to this as functional earthing. Refer to IEC
60364-5-54 541.3.11.
Local area DCG--DeltaV DCG busbar used to consolidate DCG cables from multiple DeltaV
Cabinets in a localized area.
DeltaV instrument ground (DIG)--The final point of the equipotential bonding system
connecting the DeltaV CG (chassis ground) and DCG (DC ground) to the plant grounding
system. This is often referred to in industry as the master reference ground (MRG). IEC
refers to this as the main earthing terminal in IEC 60364-5-54 541.3.9.
Earthing electrode network--A foundation electrode network such as a Ufer or platform;
a bonded grid network; a triad; or a ring. In addition, each type of grounding system such
as functional earth, protective earth (safety), or lightning earthing may be connected to a
unique earth electrode network. All earthing electrode networks must be bonded
together.
EMC--Electromagnetic compatibility: the study of the effects of electromagnetic energy
on equipment and the immunity of equipment to those effects.
Equipment grounding conductor (EGC)--The conductive path that provides a ground-
fault current path and connects normally non–current-carrying metal parts of equipment
together and to the system grounded conductor or to the grounding electrode conductor,
or both. Some codes, regulations, and world areas refer to the EGC as a protective earthing
conductor or an Equipment Bonding Conductor.
Functional earth--Earthing a point or points in a system or in an installation or in
equipment, for purposes other than electrical safety. Refer to IEC 60364-5-54 541.3.11.
Isolation transformer--A shielded transformer with galvanic separation between primary
and secondary circuits. This provides both normal-mode and common-mode noise
attenuation. An isolation transformer creates an independent electrical system also called
a separately derived system with a local ground reference.
Plant ground grid--Common ground system of the plant to which all electrical power
system protective earthing grounds are connected.
Protective earth (PE)--Protective conductor provided for protective earthing. Refer to IEC
60364 - International Electrotechnical Commission (IEC).
Safety ground--Grounding system for personnel protection. NFPA70 National Electrical
Code refers to this as equipment grounding conductor or grounding electrode system.
EU/IEC refers to this as protective earthing conductor (PE) or earthing electrode network.
Refer to NFPA70:2017 Article 250 – National Electric Code; IEC Standard 60364-4-44.
SELV--Safety extra-low-voltage system. An extra-low-voltage system that is electrically
isolated from the earth and from other systems in such a way that a single fault cannot
give rise to the risk of electric shock. DeltaV is designed and certified as an SELV.
13
Preface: Read this section first
D800118X022
System power supply--DeltaV DC/DC power supplies mounted in the DeltaV carrier
providing power to the DeltaV controllers and I/O cards.
14
Introduction
D800118X022
2 Introduction
Before you install a DeltaV Digital Automation System, your site must be electrically and
environmentally prepared to receive the system. Proper site preparation is foundational to
personnel safety and to control system efficiency and reliability. This manual provides
most of the information you need to prepare your site before installing a DeltaV Digital
Automation System.
Following the appropriate national and local electrical codes is essential to ensuring
personnel safety. Efficient and reliable system operation is greatly enhanced when power
distribution systems, ground systems, and signal wiring follow best engineering practices.
Temperature, humidity, dust, and corrosive vapors must be maintained within system
specifications.
These guidelines and recommendations cover most situations. At some sites, specific
circumstances may require alternative approaches. If your site requires a different
approach, contact your Emerson Local Business Partner or Field Sales Office (LBP/FSO).
Before contact, you may want to prepare drawings of your proposed power and grounding
system for their review.
Product-specific information and guidance details are found in Books Online; the
supporting installation and reference documents included in the DeltaV DVD
Documentation Library provided with each system; and are available through Guardian
Support. Contact your Emerson Local Business Partner or Field Sales Office (LBP/FSO) for
assistance in locating these documents.
15
Introduction
D800118X022
• Electrical noise effects are normally minimized by using isolated AC power sources and
single-point grounding schemes, by protecting against undue influence on I/O signals
from stray magnetic fields, and by selecting appropriately sized and designed cables
and pathways, including adequate cable separation.
• Minimize EMI noise and RF interference to increase system reliability.
• Shielded, twisted-pair cable for traditional I/O results in the best solution to provide
electrical noise immunity.
• Use the shortest possible power and ground cables to minimize overall impedance.
• Minimize exposure to extreme environmental conditions such as temperature,
humidity, and corrosive elements.
• There is no single, perfect solution that can eliminate all unwanted interference.
However, a stable ground reference (1 Ω to 5 Ω) can protect the control system from
facility faults, lightning, and other voltage events affecting other ground areas. A
single-point, dedicated connection for the DeltaV isolated DCG bus to true earth
ground minimizes electrical noise interference from other ground systems.
• Make sure no other system in the plant is connected to the DeltaV Instrumented
Ground (DIG).
Not all applications require the same level of power and grounding design. Mission-critical
sites, such as refining, petrochemical, and safety instrumented systems, require the
highest level of power, ground, and surge integrity and protection. However, not all
systems need the same level of availability. Many processes can accommodate an
interruption due to a safety trip. Assuring a safe shutdown of the process is the
requirement of a safety system. An interruption in many processes does not always result
in significant financial loss. Therefore, many systems economically do not justify the
highest availability, but safety systems require the highest integrity systems.
16
DeltaV power and power quality
D800118X022
1. In Europe and many other regions, most facilities with 220/380 V and 240/415 V
systems have made the transition to 230/400 V.
In Europe and many other regions, most facilities with 380/660 V systems have
made the transition to 400/ 690 V.
17
DeltaV power and power quality
D800118X022
18
DeltaV power and power quality
D800118X022
An integrated control system must maintain a relatively steady state condition by rapidly
reacting to transient events and the dynamic conditions introduced both from the sources
and loads connected to the grid. A 1976 IEEE report on power disruption listed the
following most common causes of disruptive events.
19
DeltaV power and power quality
D800118X022
Substations are configured and interconnected radially with lateral services; through
loops; or in networked grids of interconnected feeders supplied from several substations.
Power may be provided to Industrial customers from any of these types of distribution
systems or their facility may be the sole recipient of one of these distribution networks.
Generating plants, transmission systems, distribution substations and integrated control
systems use switches, relays, and fuses to redistribute power and, in most cases, reapply
power to correct for disruptions. Many disruptions are intermittent and cleared once
power is restored to the circuit. For example, if a tree limb falls across a transmission line
causing a temporary short: 1) the short is detected; 2) the circuit with the short is removed
from the power network; 3) a reclosing breaker is activated to reestablish the original
power source to the network after the fault has cleared. This type of situation can cause
multiple power quality issues for control systems, such as interruptions, sags,
undervoltage, swells on reclosure, or transients from the event or reclosure attempts.
Care should be taken when deriving control system power from multiple sources. If the
sources are from two independent distribution substations, a localized power control
interconnect system between the distribution substations should be in place to assure
equality of voltage, frequency, and phase. If the phase from source one is not completely
20
DeltaV power and power quality
D800118X022
matched to that of source two, there may be additional neutral current from these
separately derived systems with a commonly grounded neutral.
21
DeltaV power and power quality
D800118X022
When connecting multiple grounding systems together, such as the plant ground grid and
the lightning grounding in the figure above and the DeltaV Instrument Ground (DIG), the
lightning ground should have its bonding connection as far as practical from the DIG
bonding location on the plant ground grid.
The following figure shows an isolated single-phase system with redundant power. When
connecting single-phase power from three-phase plant power distribution, it is important
to choose the correct phasing between legs of the service to maintain proper load
balancing. A balanced load on the three-phase power reduces harmonics. Harmonics in
the system can result in transformer overheating and other power-quality issues.
22
DeltaV power and power quality
D800118X022
23
DeltaV power and power quality
D800118X022
24
DeltaV power and power quality
D800118X022
WARNING
Floating or high resistance ground systems allow for a single ground fault to occur without
loss of power to critical systems. A second fault will result in loss of power and/or hazard to
personnel and property. Fault sensing and alarming will allow maintenance to locate and
correct the ground fault.
Some equipment failure conditions can produce an imbalance in the line currents when
using floating power. For example, bearing wear will cause a rotational imbalance that will
affect the line currents. When a non-hazardous current imbalance is detected, an alarm
alerts personnel to the need to troubleshoot and clear the issue. This sensing is important
to maintain power availability to the process.
Detection of current imbalance is accomplished by measuring leakage with current
monitors, such as those listed below, which compare the phase to phase and phase to
ground current. The resultant current or net current will be zero. Minor imbalances are a
result of wire insulation breakdown or load issues. When an imbalance is observed, action
can be taken depending on the severity of the issue. If the imbalance is minor, such as
early signs of insulation breakdown, the cable can be replaced at the next scheduled
preventive maintenance if the issue does not progress.
The following figure shows a marine application that incorporates surge protection, earth
leakage detection, and a solution for phase imbalance or loss of a phase.
25
DeltaV power and power quality
D800118X022
The surge protection device (SPD) is solidly grounded and if properly maintained will not
be a source of leakage. In other words, leakage detection from the SPD to the structure is
not generally required because the ground connection is only used in the event of a high
voltage surge. The SPD at the first disconnect from the Medium Voltage (MV) distributed
3-phase bus can be either type 1 or type 2 depending on the conditions at the site. The
SPD will attenuate surges from phase to phase or phase to hull/structure.
A single isolated ground path should be maintained from the isolation transformers, UPS,
transfer switch through to the distribution disconnect to ensure that any leakage current is
detected through dedicated ground wires. Earth leakage current will be detected by the
current transformer (CT) located between the disconnect and the DIG at the structure.
The ground bus in the DeltaV cabinet will be isolated and monitored by a leakage
detector. Once leakage is detected the source should be located and eliminated.
Current imbalance relays as shown in the DeltaV cabinets can be set to monitor phase
imbalance. This imbalance can be an indication of an issue such as loss of one of the three
phases or a component failure.
Offshore applications use the hull of the ship or platform as the ground reference. Leakage
current to and throughout the structure will result in a build-up of non-conductive
oxidation, i.e. electrolysis. Therefore, it is important to detect and eliminate the cause of
the leakage.
The following detection methods are used to maintain the integrity of the hull, to assure
the availability of the process, and to protect personnel and property:
Differential ground fault protection is a process of detecting an imbalance in the pole
current with respect to a ground, either functional earth or protective.
Differential current monitor is the method and/or device to measure the pole current
imbalance by means of current transformers (CT). This is the most general term for
current monitoring in that it can measure a single pole with respect to ground; pole to
pole; multiple pole current sharing; or multiple pole and the ground leakage.
26
DeltaV power and power quality
D800118X022
Differential relays are used in conjunction with Differential current monitors to achieve a
level of protection in cases of current imbalance by interrupting circuits with faults. In
cases with multiple power sources they may also be used to reconfigure circuit power
from the fault to the non-fault circuits.
Residual current devices (RCD) – Measures imbalance in power lines. These RCDs will detect
if the current supplied has an equal and opposite current through the return pole
conductor(s). If leakage is detected, the RCD interrupts all poles. The interrupt can be fast
acting or delayed. Two types of RCDs are RCCB and RCBO listed below.
Residual-current circuit breaker (RCCB) opens power circuits when a current imbalance exists
between the poles.
Residual-current circuit breaker with overcurrent protection (RCBO) – protect against
current imbalance between the poles, short-circuit, overloads, and earth faults by
interrupting power circuits during an event.
Residual current relays are used in conjunction with Residual current devices to achieve a
level of protection in cases of current imbalance by interrupting circuits with faults. In
cases with multiple power sources they may also be used to reconfigure circuit power
from the fault to the non-fault circuits.
Earth Leakage detectors (ELD) are used in a grounded power system, such as low voltage AC
power, DC power, or signal wires.
Ground Fault Circuit Interrupter (GFCI) as defined by Article 100 of the NEC “A device
intended for the protection of personnel that functions to de-energize a circuit or portion
thereof within an established period of time when a current to ground exceeds the values
established for a Class A device.” The Class A devices will trip when the current to ground is
<= 6mA. GFCIs are primarily used in North America with applications in residential and
office environments. The GFCIs are in the form of receptacle or breaker and can be
considered a non-inclusive subset of differential ground fault protection.
Another method of increasing power availability is using a high-resistance grounding
system. If you use floating or high-resistance ground, insulation and interrupt devices
must be sufficiently sized to accommodate the possibility of line-to-line fault conditions.
Residual current devices (RCDs) should also be incorporated on the supply lines to quickly
detect leakage current and provide power interruption if required.
Although AC power and isolated input or output field power can be floating, the DeltaV DC
power must remain solidly grounded.
WARNING
Use only DeltaV isolated AC I/O products with floating or high-resistance ground. DeltaV
AC discrete I/O products are tested and certified for use with solidly grounded AC systems
and should not be used on a floating or high-resistance ground.
Note
Isolated AC channels are permitted.
Emerson bulk power supplies can provide up to 1500 VDC isolation from AC power and
must be installed in accordance with the manufacturers' instructions. AC power and
grounding is governed by the applicable codes and regulations and is independent of the
DeltaV DC power requirements.
27
DeltaV power and power quality
D800118X022
If you are using a high-resistance ground, install a surge protection device (SPD) with
filters immediately before the DeltaV bulk power supply. SPDs protect the integrity of the
DeltaV system from re-strike transients. Re-strike transients are generated in HRGs to find
system faults.
28
DeltaV power and power quality
D800118X022
A similar correlation can be made from the lightning protection zone (LPZ) of the figure
below.
29
DeltaV power and power quality
D800118X022
Higher availability and integrity require greater protection from surges. Lightning
protection zones, immunity zones, and hazardous location zones do not have a perfect
one-to-one correlation. For example, immunity zone C is similar to LPZ1; immunity zone B
is similar to LPZ2; and immunity zone A is similar to LPZ3.
One common misbelief is that surge suppression is not necessary if the process is in an
area with a low risk of lightning. It is prudent to include isolation, such as a UPS or isolation
transformer, with surge suppression at every zone boundary to maintain high availability
and high integrity in industrial applications. For an example, refer to Figure 3-6.
Surge protection devices (SPD) are designed to specific standards such as UL 1449:2015
Standard for Safety Surge Protective Devices for North America, and Internationally in IEC
61643-11:2011Low-voltage surge protective devices -Part 11 Surge protective devices
connected to low-voltage power systems – requirements and test methods. This manual uses
the UL type designation for SPDs, which classifies the SPD class as Type 1, Type 2, and Type
3.
Low-voltage (LV) service entrances from LPZ0 to LPZ1 should have a Type 1 SPD. If your
application requires high availability or high integrity, you should use SPDs regardless of
the frequency of lightning in the area.
SPD should be coordinated between LPZs to limit energy entering more sensitive LPZs.
DeltaV products meet industrial surge requirements and criteria listed in IEC
61326-1Electrical equipment for measurement, control and laboratory use – EMC
requirements – Part 1: General requirements Table 2 – Immunity test requirements for
equipment intended to be used in an industrial electromagnetic environment. For control
systems located entirely within and powered in a Zone C or LPZ 3, no additional surge
protection should be required. However, some degree of filtering and isolation, such as
that provided by an isolation transformer, may still be necessary.
Figure 3-7 shows standalone DeltaV systems that are powered from separately derived
sources, such as those in Figure 3-2 and Figure 3-3. This is often the case in remote
buildings that are not close to the main plant grounding system. These remote DeltaV
centers will require separate localized grounding, such as a triad. When there are several
30
DeltaV power and power quality
D800118X022
remote systems that are in close proximity, cost can be minimized by connecting to local
grounding busses with a single DIG/triad. For installations where the distance to the
separately derived source is greater than 100m, the best engineering practice is to include
SPDs for mitigation of noise interference in DeltaV systems. All surge protection devices
should be designed in a coordinated effort as seen in Figure 3-5 and Figure 3-6. Surge
protection devices used with remote DeltaV enclosures as depicted in should be SPD Type
3. The SPD in the enclosure below will protect transients from Line-Line and Line/Neutral-
Ground. Unwanted energy will dissipate through the remote triad and/or the ground at
the separately derived source. When a transient event occurs, the energy will seek
multiple paths back to the origin. In a system with multiple ground points, SPD ground to
triad or SPD ground to plant ground grid, the unwanted energy dissipates more quickly
and has less influence on the control system. The following figure illustrates grounding of
SPDs for DeltaV.
31
DeltaV power and power quality
D800118X022
If the DeltaV system is farther than 100 m (300 ft) from the power distribution source, or if
there is a high lightning or disruptive risk, install SPDs as shown in Figure 3-8. In addition to
the surge suppression provided by SPDs, these devices also enable the creation of a
separately derived ground. The SPDs do not provide a galvanically isolated ground as
could be established by an isolation transformer, but they do provide good isolation,
enabling the grounding system to mitigate interference.
Field wiring may also require surge suppression if the signals enter a protection zone
outside the zone the controller and cards are in. When SPDs are used with field wires it is
best to have SPDs at both ends of the field transmitter/receiver pair.
In small systems, such as a remote CHARM enclosure, the DC Ground and the Chassis
Ground can be connected inside the enclosure and taken to a low impedance ground.
32
DeltaV power and power quality
D800118X022
33
DeltaV power and power quality
D800118X022
may momentarily drop line voltage up to 15%. To maintain adequate power quality,
electrical disturbances must be designed around or controlled.
To operate your DeltaV system at the highest level of integrity (that is, to maintain the
system with the least amount of disruptive events due to power anomalies), a properly
designed power conditioning system should be considered.
DeltaV requires clean AC power. Clean AC power is a sinusoidal wave that maintains its
characteristics with both linear and non- linear loads. The following commonly used
standards address power quality:
• IEEE 1159-2009 Recommended Practice for Monitoring Electric Power Quality
• IEEE 519-2014 Recommended Practices and Requirements for Harmonic Control in Electrical
Power Systems
• EC 61000-3-11 Electromagnetic compatibility (EMC) Limitations of voltage changes, voltage
fluctuations and flicker in public low voltage supply systems
• IEC 61000-3-12 Electromagnetic compatibility (EMC) Limits for harmonic currents produced
by equipment connected to public low voltage systems
• IEC 61000-4-30 Testing and measurement techniques – Power quality measurement
methods
Table 2‑3 and Table 2‑4 list the most prevalent factors that influence the quality of power.
Common causes for power quality issues with corresponding recommendations for
corrective measures can also be found in the tables.
CAUTION
Any three-phase source, such as transformer or UPS, providing power to a DeltaV system
must only power DeltaV products, safety systems, or the control system. Therefore, no
VFDs, HVAC, motors, fans, compressors, ballasts, and so on shall be connected to any
output phase of a transformer or UPS that is also used to power the DeltaV system.
34
DeltaV power and power quality
D800118X022
CAUTION
The primary power source should be free of power interruptions longer than 20 ms. A
power interruption longer than 20 ms can cause loss of configuration data, process data,
and even loss of process control.
35
DeltaV power and power quality
D800118X022
A double-conversion uninterruptible power supply can also mitigate most power quality
issues. Isolation transformers are an excellent means to significantly reduce common-
mode noise, typically up to 750 kHz. The isolation transformer also allows for a separately
derived source of power that creates a stable ground reference point close to the DeltaV
system. Filters are a readily available solution for normal-mode noise reduction in the
range of a few hertz up to 10 MHz. Surge suppressor/filters can prevent surge voltages
from indirect lightning or large upstream power faults from damaging control equipment.
They also reduce normal-mode noise. A power quality evaluation of the site can easily
determine the best solution to meet your individual requirements.
A UPS that supplies power to control systems should be double-conversion type. Typically,
its input voltage is provided from a low voltage (100 VAC to 600 VAC) feeder, with either
single- or three-phase power. The AC power from the source is rectified to DC and used as
leveling power to maintain batteries or to supply energy for a flywheel. The inverter stage
produces harmonic-free AC sine wave output using power from the DC storage section -
batteries or a flywheel. Use only a UPS that reproduces high-quality sine waves. A UPS that
produces sine waves rich in harmonics is detrimental to control systems.
36
DeltaV power and power quality
D800118X022
Most UPS devices provide a degree of protection from power failure, power sag, and
power surges. However, some provide an excellent solution for most of the power quality
issues found in the tables above.
A bypass transformer with static switchover allowing for UPS maintenance is either
supplied as an integral component or can be connected externally to the UPS. If you are
using the type of UPS recommended above, select a shielded bypass transformer.
Some UPS models provide three-phase output power. When using a UPS with a three-
phase output, all phases should be connected only to the control system and to non-
interfering equipment. Never connect one phase to the DeltaV system and another phase
to a different device, such as a VFD or air-conditioning unit.
37
DeltaV power and power quality
D800118X022
38
DeltaV power and power quality
D800118X022
Option B
• UPS with the following features:
— Neutral/ground bond point to establish a separately derived ground reference
— Power failure, power sag, and power surge protection
— Capable of regulating under-voltage and over-voltage input power
• UPS to DeltaV cabinet distance of less than 100 meters
• Surge suppressor/filter prior to bulk supply (optional if signal shields are not located in
Zone 0 or Zone 1 lightning area)
• Bypass isolated transformer with single isolated shielding
• Power lines in armored cable or metal conduit (optional)
Option C
• Isolation transformer
• Neutral/ground bond point to establish a separately derived ground reference
• Transformer to DeltaV cabinet distance of less than 100 meters
• Surge suppressor/filter prior to bulk supply (optional if signal shields are not located in
Zone 0 or Zone 1 lightning area)
• Power lines in armored cable or metal conduit (optional)
39
DeltaV power and power quality
D800118X022
CAUTION
Emerson defines clean power for DeltaV according to the descriptions in EN 61000-3-11
Electromagnetic compatibility (EMC) – Part 3-11: Limitation of voltage changes, voltage
fluctuations and flicker in public low-voltage supply systems –Equipment with rated current
≤75 A and subject to conditional connection, and EN61000-3-12: Electromagnetic
compatibility (EMC) –Part 3-12: Limits for harmonic currents produced by equipment
connected to public low-voltage systems with input current >16A and ≤75 A per phase.
Option G
Highest integrity
AC source (1)
• UPS with the following features:
— Neutral/ground bond point to establish a separately derived ground reference
— Power failure, power sag, and power surge protection
— Capable of regulating under-voltage and over-voltage input power
— Line noise elimination, frequency variation correction, switching transient filter
harmonic interference filter
• UPS to DeltaV cabinet distance of less than 100 meters
— Surge suppressor/filter prior to bulk supply
— Bypass isolated transformer with single isolated shielding
— Power lines in armored cable or metal conduit (optional)
AC source (2)
40
DeltaV power and power quality
D800118X022
• Isolation transformer
• Neutral/ground bond point to establish a separately derived ground reference
• Transformer to DeltaV cabinet distance of less than 100 meters
• Surge suppressor/filter prior to bulk supply
• Power lines in armored cable or metal conduit (optional)
Option H
AC source (1 & 2)
• Isolation transformer
• Neutral/ground bond point to establish a separately derived ground reference
• Transformer to DeltaV cabinet distance of less than 100 meters
• Surge suppressor/filter prior to bulk supply
• Power lines in armored cable or metal conduit (optional)
CAUTION
Emerson defines clean power for DeltaV according to the descriptions in EN 61000-3-11
Electromagnetic compatibility (EMC) – Part 3-11: Limitation of voltage changes, voltage
fluctuations and flicker in public low-voltage supply systems –Equipment with rated current
≤75 A and subject to conditional connection, and EN61000-3-12: Electromagnetic
compatibility (EMC) –Part 3-12: Limits for harmonic currents produced by equipment
connected to public low-voltage systems with input current >16A and ≤75 A per phase.
41
DeltaV power and power quality
D800118X022
42
DeltaV power and power quality
D800118X022
43
DeltaV power and power quality
D800118X022
and 85% efficiency. The resonate tank circuit of a CVT requires additional core material
which adds to the weight and also increases the audible noise. For most industrial
locations if noise and weight is not an issue the CVT if sized properly is an excellent choice
for an insolation transformer.
44
DeltaV power and power quality
D800118X022
• The primary power source cannot meet the 20-millisecond requirement for
uninterrupted power.
• Power loss from a commercial power source is probable.
• Power loss requires manual setting of relays or solenoids.
• Power loss can cause the process to enter an uncontrollable state.
• Power loss causes a process reaction that creates a hazardous condition or an extensive
loss of product.
An Uninterruptible Power Supply (UPS) is a recommended backup means. Small supplies
are available to back up selected plant areas. Large supplies are available to back up entire
systems. When large supplies back up control equipment spread across plant areas, each
area must be electrically isolated in a manner duplicating primary source isolation.
45
DeltaV power and power quality
D800118X022
46
DeltaV system cabinets and enclosures
D800118X022
47
DeltaV system cabinets and enclosures
D800118X022
48
DeltaV system cabinets and enclosures
D800118X022
instrument damage from corrosive environments occurs either during storage or during
construction periods, when instruments are already installed but not protected from a
poorly controlled environment.
Emerson electronic components are supplied in static protective packaging. These
Emerson-supplied DeltaV components are often removed from their packaging and
installed in an enclosure by a fabrication or integration facility. Protection from damage
due to static must be taken during installation in an enclosure and during transport. Refer
to . for more information. The DeltaV DCG bar should be grounded to the enclosure
chassis with a temporary jumper until final installation and connection of the permanent
ground system. Refer to Figure 4-1 for an example.
49
DeltaV system cabinets and enclosures
D800118X022
50
DeltaV system cabinets and enclosures
D800118X022
Note
DC fans in DeltaV cabinets or enclosures must be non-commutating.
Refer to DeltaV power and power quality for more detailed information about power
quality.
51
DeltaV system cabinets and enclosures
D800118X022
High-availability designs use AC/DC bulk power supply redundancy and DeltaV system
power supply (SPS) redundancy. A redundant bulk supply can be mounted in the same
enclosure as a primary bulk supply or in a separate enclosure. In either case, the redundant
supply must be connected to the same DC ground bus (DCG) as the associated primary
supply.
If a redundant DeltaV DC system power supply backs up a primary DeltaV DC system
power supply, the redundant supply must be located on the same carrier system as the
primary supply.
Redundant power supplies must be sized such that if one supply fails, its backup power
supply has the capacity to power the entire load. A new installation should include
capability for expansion. A rule of thumb is to size the power supply for a maximum load of
70%.
52
DeltaV system cabinets and enclosures
D800118X022
should be included if the AC power is not provided from a Dual Conversion UPS or an
isolation transformer.
For the highest availability, four bulk AC to DC power supplies are provided AC from the
two independent power sources with their DC outputs connected through redundancy
modules for the Primary and Secondary DeltaV System Power Supplies (SPS).
Highest integrity installations can also be accomplished utilizing a redundant pair or pairs
of AC to DC bulk power supplies in N+1 configurations.
WARNING
In all cases, the 24 VDC return (-) terminal of the power supplies feeding DeltaV must be
connected to DeltaV DC ground. The bussed DC ground wire is connected to the DC
ground isolated bus (DCG). For wiring inside DeltaV cabinets, Emerson recommends 14
AWG (2.5 mm2) minimum wire size. Wire inside DeltaV cabinets must be large enough to
handle the maximum current of the largest bulk power supply during a fault condition.
Figure 4-1shows a simplex bulk power supply feeding simplex system power supplies
similar to the ones shown in Figure 4-8. Loss of the AC feed results in a loss of power to the
system power supplies. This results in a controller shutdown. The field power is supplied
from a separate AC to DC bulk power supply.
53
DeltaV system cabinets and enclosures
D800118X022
Figure 4-2 shows a higher availability with redundant bulk power supplies to feed the
simplex system power supplies in Figure 4-8. Each bulk power supply receives AC from a
different clean power source and provides DC power to the simplex system power supplies
through a redundancy module. Loss of one of the AC feeds does not result in a loss of the
system power supplies. However, a high voltage spike that gets through a bulk power
supply, or a power supply that fails to a high DC voltage might result in loss of the system
power supplies and a controller shutdown. The field power is supplied from a separate
redundant AC to DC power supply pair with a redundancy module.
54
DeltaV system cabinets and enclosures
D800118X022
Filter/surge-suppression devices are added in the following figure for added protection if
the AC power sources are not provided from a UPS or Isolation transformer or if the area
has a high susceptibility to lightning or disruptive power events.
55
DeltaV system cabinets and enclosures
D800118X022
Figure 4-3: Redundant bulk power simplex cntroller with surge protection
Figure 4-4 shows higher availability using two bulk power supplies to independently feed
the primary and secondary System Power Supplies. DeltaV field instrumentation power is
fed from a redundant pair of bulk power supplies.
56
DeltaV system cabinets and enclosures
D800118X022
Figure 4-4: Redundant independent bulk power supplies for redundant controllers
Each bulk power supply receives AC from a different clean power source and provides DC
power to either a primary system power supply or a secondary system power supply. The
primary bulk supply backs up a primary system power supply and the secondary bulk
power supply backs up a secondary system power supply. The field power is supplied from
a separate redundant AC to DC power supply pair with a redundancy module. In this
scheme, the failure of an AC power sources or the loss of one of the bulk supplies will result
in the primary controller switching its control to the secondary controller. The controllers
are fully redundant and designed to switchover the control bumpless.
The practice of connecting a set of power supplies through OR’ing diodes with a common
connection to the primary and secondary System Power Supplies is not recommended.
This method was followed for many years as a lower cost approach to providing power
supply redundancy. With the OR’ing diode approach, a single point failure between the
Primary and Secondary DeltaV controllers connected to the same voltage supply can
occur. This method can result in process upsets when high DC voltage causes both the
primary and secondary controllers to shut down. While not a normal failure mode, a power
57
DeltaV system cabinets and enclosures
D800118X022
supply can fail at higher than the acceptable DC voltage for the System Power Supply,
resulting in a controller shutdown. Additionally, a high voltage spike might pass through a
DC power supply and result in the primary and secondary shutdown on high voltage. Clean
power and surge protection from Isolation/Regulation transformers or additional SPDs are
required for feeding power supplies in this OR’ing diode schema due to the added risk. If a
project decides to utilize this approach, the risks need to be fully understood and
evaluated with the customer and project team.
Figure 4-5 shows the highest availability and highest integrity scheme. This configuration
provides a redundant power supply pair with a redundancy module for each the primary
and the secondary system power supply feeds. For highest integrity, it includes filter/surge
suppression devices (SPDs) added on the AC feeds to the bulk power supplies. This is
important if the AC power sources are not from a double conversion UPS or from proper
isolation transformers. These SPDs might also be required if the AC power feeds to the
bulk power supplies are long or if the area has a high susceptibility to lightning or
disruptive power events.
58
DeltaV system cabinets and enclosures
D800118X022
Note
Field power supplies are not shown.
This scheme avoids a signal point of failure in the power feed circuits. Each pair of bulk
power supplies would have feeds from two independent clean power sources. Loss of a
single AC feed or loss of a single bulk power supply does not result in a loss of power to any
of the system power supplies.
A separate redundant pair of bulk power supplies with redundancy module would supply
field instrumentation power.
Highest integrity requires AC from dedicated clean power. This can be accomplished with
isolation transformers or UPSs, or by adding filter surge suppression.
59
DeltaV system cabinets and enclosures
D800118X022
60
DeltaV system cabinets and enclosures
D800118X022
The power supply configuration in Figure 4-7 can supply power to DeltaV systems such as
those shown in Figure 4-9, Figure 4-11, and Figure 4-12.
For additional information, refer to DC distribution system and to DC feed to DeltaV
CHARMs enclosure fom bulk power supply cabinets or from plant DC power systems.
61
DeltaV system cabinets and enclosures
D800118X022
Note
M-Series system power supplies are available for use with AC power feeds or 12 VDC bulk
power supply feeds. Emerson recommends using 24 VDC bulk power supply feeds to the
DeltaV hardware for all new or upgraded installations.
62
DeltaV system cabinets and enclosures
D800118X022
63
DeltaV system cabinets and enclosures
D800118X022
64
DeltaV system cabinets and enclosures
D800118X022
The following figure shows a redundant M-series System Power Supply (SPS) with
extended power.
Note
For M-Series systems with 12 VDC SPS input, do not attach the SPS return to the carrier
ground terminal. The SPS provides the ground reference through the 12 VDC return.
Note
Never daisy-chain the DC return to bulk power supplies and then to the DCG bus bar. This
creates DC return current flow in the DCG bus bar. Always tie an individual wire from the
negative or return of each bulk power supply to the DCG bus bar.
DC ground wires should always be as short as possible and, where several are routed to a
DCG bus bar, should be routed as close to each other as possible.
65
DeltaV system cabinets and enclosures
D800118X022
DC ground busses inside the enclosure are isolated from the enclosure metal and serve as
the termination point for DC grounds to maintain a zero equipotential.
DeltaV components operate on DC. A signal change is quantified as the change from a
reference. The DC negative is the reference used by DeltaV. DeltaV components that are
connected to DC negative references at different potentials can yield inaccurate
measurements. Referencing all DC negatives by terminating at one reference point and
isolating/insulating the references from all external sources that could bias the reference
potential ensures the functionality and accuracy of the signals.
DC ground wires should be insulated to avoid unintentional ground loops that can occur if
bare ground wires touch metal enclosure framing or each other.
66
DeltaV system cabinets and enclosures
D800118X022
After installation and prior to process startup, verify these DCG wires and bus bar are
properly isolated from the CG and cabinet enclosure. Refer to the checklists in Power And
Grounding Audit Worksheets for verifying site power and grounding.
Connect the enclosure DCG bus to the local area DeltaV DC bus bar, or directly to the DIG.
67
DeltaV system cabinets and enclosures
D800118X022
68
DeltaV system cabinets and enclosures
D800118X022
Figure 4-12: S-series redundant extended power between extender and carriers
69
DeltaV system cabinets and enclosures
D800118X022
70
DeltaV system cabinets and enclosures
D800118X022
The following figure adds surge suppression devices to achieve the highest integrity
design if the isolation transformer is not close to the CHARM enclosure or if the area
includes a high risk of electrical noise.
71
DeltaV system cabinets and enclosures
D800118X022
72
DeltaV system cabinets and enclosures
D800118X022
73
DeltaV system cabinets and enclosures
D800118X022
74
DeltaV system cabinets and enclosures
D800118X022
Most DeltaV control products can be installed in Class I Division 2, and Zone 2 in egress
protection IP54 enclosures. The range of DeltaV products can interface to field
instrumentation in Hazardous areas including Class I Division 1, Class I Division2, Zone 0,
Zone 1, and Zone 2. Refer to NFPA70 Article 500 and IEC 60079 series.
IEC 60079-14:2013 defines Zones as follows:
Hazardous area--area in which an explosive atmosphere is present, or may be expected to
be present, in quantities such as to require special precautions for the construction,
installation and use of equipment.
Zones--hazardous areas classified into zones based upon the frequency of the occurrence
and duration of an explosive atmosphere.
Zone 0--place in which an explosive atmosphere consisting of a mixture with air of
flammable substances in the form of gas or vapour is present continuously or for long
periods or frequently.
Zone 1--place in which an explosive atmosphere consisting of a mixture with air of
flammable substances in the form of gas or vapour is likely to occur in normal operation
occasionally.
Zone 2--place in which an explosive atmosphere consisting of a mixture with air of
flammable substances in the form of gas or vapour is not likely to occur in normal
operation but, if it does occur, will persist for a short period only.
NFPA 70:2017 Article 500 defines Class I locations as locations in which flammable gases,
flammable liquid–produced vapors, or combustible liquid–produced vapors are or may be
present in the air in quantities sufficient to produce explosive or ignitable mixtures.
Qualifications of personnel
In accordance with IEC 60079-14: 2013, the design of the installation, the selection of
equipment, and the erection of DeltaV shall be carried out only by persons whose training
has included instruction on the various types of protection and installation practices,
relevant rules and regulations, and general principles of area classification. The
competency of persons shall be relevant to the type of work to be undertaken.
Appropriate continuing education or training shall be undertaken by personnel on a
regular basis.
Note
Competency may be demonstrated in accordance with a training and assessment
framework relevant to national regulations or standards or user requirements.
75
DeltaV system cabinets and enclosures
D800118X022
76
DeltaV system cabinets and enclosures
D800118X022
The following excerpt is from IEC 60079-25:2010 Section 11 Earthing and bonding of
intrinsically safe systems:
In general, an intrinsically safe circuit shall either be fully floating or bonded to the
reference potential associated with a hazardous area at one point only. The level of
isolation required (except at that one point) is to be designed to withstand a 500 V
insulation test in accordance with the dielectric strength requirement of IEC 60079-11.
Where this requirement is not met, the circuit shall be considered to be earthed at that
point. More than one earth connection is permitted on a circuit, provided that the circuit is
galvanically separated into sub-circuits, each of which has only one earth point.
Screens shall be connected to earth or the structure in accordance with IEC 60079-14.
Where a system is intended for use in an installation where significant potential
differences (greater than 10 V) between the structure and the circuit can occur, the
preferred technique is to use a circuit galvanically isolated from external influences such as
changes in ground potential at some distance from the structure. Exercise particular care if
part of the system is intended to be used in Zone 0 or Zone 20 locations or when the
system has a very high level of protection so as to conform to EPL Ma requirements.
The following is from IEC 60079-14:2013 Section 16.3 Installations to meet the requirements
of EPL “Ga” or “Da”:
If part of an intrinsically safe circuit is installed in locations requiring EPL “Ga” or “Da” such
that the apparatus and the associated apparatus are at risk of developing hazardous
potential differences within the locations requiring EPL “Ga” or “Da”, e.g., through the
presence of atmospheric electricity, a surge protection device shall be installed between
each non-earth bonded core of the cable and the local structure as near as is reasonably
practicable, preferably within 1 m, to the entrance to the locations requiring EPL “Ga” or
“Da”. Examples of such locations are flammable liquid storage tanks, effluent treatment
plants and distillation columns in petrochemical works. A high risk of potential difference
is generally associated with a distributed plant and/or exposed equipment location, and
the risk is not alleviated simply by using underground cables or tank installation.
The surge protection device shall be capable of diverting a minimum peak discharge
current of 10 kA (8/20 μs impulse according to IEC 60060-1, ten operations). The
connection between the protection device and the local structure shall have a minimum
cross-sectional area equivalent to 4 mm2 copper.
Note
The IEC acronym EPL refers to Equipment Protection Level, which is related to Hazardous
Area Zones.
77
DeltaV system cabinets and enclosures
D800118X022
Flexibility is provided with IS CHARMs to separate IS and non-IS shields. IS baseplate shield
bars are isolated from non-IS baseplate shield bars. The following figure references both
the IS and non-IS shield bars to the CG bar.
78
DeltaV system cabinets and enclosures
D800118X022
Some customers request a separate IS Isolated Ground system in the CHARMs enclosure
connected to the hazardous area ground system.
79
DeltaV system cabinets and enclosures
D800118X022
These ground methods provide proper electrical grounding for the IS CHARMs system. For
more information, refer to ISA-RP12.06.01-2003 Recommended Practice for Wiring Methods
for Hazardous (Classified) Locations Instrumentation Part 1: Intrinsic Safety.
IS carrier-based cards
The DeltaV M-Series IS power supply and Localbus Isolator provide isolation between M-
Series IS cards and the Delta non-IS system. The DC output of the IS power supply
connects directly to the IS I/O cards through the carrier backplane. The Localbus Isolator
electrically isolates IS I/O cards from non-IS I/O cards. The following figure shows the
locations of the power supply and isolator on the IS I/O carrier.
80
DeltaV system cabinets and enclosures
D800118X022
The DC reference for the carrier is connected from the carrier grounding lug to the DC
ground bus. The carrier shield bar is connected to the chassis ground (CG) bus. These
grounds provide proper electrical ground for the I/O cards and the IS power supply. Power
leads to the IS power supply are connected to a 24 VDC bulk power supply. The IS power
supply negative (-) terminal is grounded through the DC return reference ground at the
bulk power supply negative (-) terminal.
81
DeltaV system cabinets and enclosures
D800118X022
Figure 4-21: SLS redundant power - high integrity with good availability
82
DeltaV system cabinets and enclosures
D800118X022
Figure 4-22: SLS redundant power with isolation transformers and surge suppression
83
DeltaV system cabinets and enclosures
D800118X022
Figure 4-23: SLS redundant power - highest integrity with highest availability
84
DeltaV system cabinets and enclosures
D800118X022
Figure 4-24: SLS Highest integrity and highest availability - surge protection and
isolation transformers
85
DeltaV system cabinets and enclosures
D800118X022
86
DeltaV system cabinets and enclosures
D800118X022
The following figure shows the highest-integrity power and grounding scheme for a
CHARMs SIS enclosure with injected power.
87
DeltaV system cabinets and enclosures
D800118X022
Figure 4-27: CSLS Highest integrity power and grounding with injected power
The following figure shows redundant injected field power connected to a SIS CHARMs
and Logic Solver enclosure.
88
DeltaV system cabinets and enclosures
D800118X022
Additional references
In addition to the power and grounding information in this chapter, the following
documents contain application and installation information you need for your DeltaV SIS
system:
• D800025, Installing Your DeltaV SIS™ Process Safety System Hardware.
• D800028, DeltaV SIS Accessories Installation and Safety Manual.
• D800032, DeltaV SIS Process Safety System Safety Manual.
• D800033, DeltaV SIS Users Guide.
• D800056, DeltaV SIS™ CHARMs Smart Logic Solver Hardware Installation.
• D800057, DeltaV SIS™ CHARMs Smart Logic Solver Hardware Reference.
• D800058, DeltaV SIS with Electronic Marshalling Safety Manual.
89
DeltaV system cabinets and enclosures
D800118X022
90
Signal wiring
D800118X022
5 Signal wiring
Minimizing electrical noise induced on process control input and output (I/O) signals is
extremely important for reliable operation of any control system. Many external sources
can produce electromagnetic interference (EMI) on I/O signals. In addition, digital
communication systems, traditional discrete signals, and fast-switching discrete signals
can make the inside of a system enclosure the hottest area for electrical interference,
often as cross-talk. This chapter describes best practices for minimizing electrical noise
induced on I/O signals.
1 This standard has been withdrawn but it contains much useful information.
91
Signal wiring
D800118X022
92
Signal wiring
D800118X022
93
Signal wiring
D800118X022
for this interference, connect shields at a single point only, either to a DeltaV shield bar or
to a well-grounded field device.
Individual pairs of wiring carrying a signal should have the pair shield grounded at one
point. That point can be at the field device, at a junction box, or at the DeltaV enclosure.
Emerson recommends grounding signal cable shields at the DeltaV enclosure. Consistency
in selecting the location of a single grounding point reduces the risk of creating ground
loops, and makes it easier to troubleshoot grounding issues.
One exception to the grounding recommendation is thermocouple shielding. Some
thermocouples are isolated from the sheath and some are not. If the sheath is in electrical
contact with the metal thermowell, the shield may be bonded to earth in the field. In that
case, bonding again at the DeltaV enclosure, for example, would create a ground loop that
could induce unwanted energy onto the thermocouple leads.
Emerson strongly recommends connecting I/O cable shield grounds to chassis ground and
not to DC ground. This is a requirement rather than a recommendation for SIS equipment.
Chassis ground routes electrical noise back to the source, whereas DC ground is a passive
ground that creates a zero equipotential reference for the control system. Connecting
cable shield grounds to DC ground introduces electrical noise and can cause errors. All
drawings in this manual show shields connected to chassis ground.
Be sure to strip the insulation of shield wires properly at the grounded end and wrap them
at the ungrounded end. Refer to the following figure for examples.
Note
Keep the stripped length of wire as short as possible. 1-3 in. is typical.
94
Signal wiring
D800118X022
Minimizing electrical noise induced on I/O signals is extremely important for reliable
operation of any control system. Many external sources can produce electromagnetic
interference (EMI) on I/O signals. In addition, digital communication systems, traditional
discrete signals, and fast-switching discrete signals can make the inside of a system
enclosure the most susceptible area for electrical interference, often as cross-talk.
95
Signal wiring
D800118X022
Notes
1. Refer to the instrument manufacturer’s documentation and DeltaV Books Online
for detailed information about signal termination.
2. Use 14 AWG (2.5 mm2) to 18 AWG (0.75 mm2) stranded, twisted-pair wire with
overall shield and drain wire.
3. Use cable specified for thermocouple signals with overall shield and drain wire.
4. Ground shield at thermocouple for grounded thermocouples.
5. Ground shield at carrier shield bar for ungrounded thermocouples.
96
Signal wiring
D800118X022
6. Use three/four conductor cable specified for RTD signals with overall shield and
drain wire.
7. Shields should extend to within 2 in. of termination. For ends that are not
terminated, trim and cover with tape or heat shrink to prevent accidental
grounding.
8. Pass-through only. Shields are grounded at one point only.
9. Normally, the signal is isolated from the case in four-wire transmitters. Therefore,
grounding the case does not cause a ground loop.
Notes
1. Refer to the instrument manufacturer’s documentation and DeltaV Books Online
for detailed information about signal termination.
2. Use 14 AWG (2.5 mm2) to 18 AWG (0.75 mm2) stranded, twisted-pair wire with
overall shield and drain wire.
3. Shields should extend to within 2 in. of termination. For ends that are not
terminated, trim and cover with tape or heat shrink to prevent accidental
grounding.
4. Pass-through only. Shields are grounded at one point only.
97
Signal wiring
D800118X022
5. Normally, the signal is isolated from the case in four-wire transmitters. Therefore,
grounding the case does not cause a ground loop.
6. Three-wire transmitters require a return path to the transmitter for the 4-20 mA
signal.
Notes
1. Refer to the instrument manufacturer’s documentation and DeltaV Books Online
for detailed information about signal termination.
98
Signal wiring
D800118X022
2. Use 14 AWG (2.5 mm2) to 18 AWG (0.75 mm2) stranded, twisted-pair wire with
overall shield and drain wire.
3. Intrinsically safe (I.S.) installations must conform to local codes and regulations.
Refer to NEC Article 504, IEC 60079-11, and IEC 60079-25. See also ANSI/ISA RP12.6
Wiring practices for hazardous (classified) locations, instrumentation, Part 1: Intrinsic
Safety.
4. Devices must be I.S. certified if not considered a "simple apparatus." Refer to IEC
60079-11.
5. I.S. devices, cables, and connections shall be clearly marked and identifiable. Where
color is used for this purpose, it shall be light blue. Refer to IEC 60079-11.
6. Shields should extend to within 2 in. of termination. For ends that are not
terminated, trim and cover with tape or heat shrink to prevent accidental
grounding.
7. Normally, the signal is isolated from the case in four-wire transmitters. Therefore,
grounding the case does not cause a ground loop.
8. I.S. CHARMS are intrinsically safe through galvanic isolation. A barrier is not
required.
99
Signal wiring
D800118X022
signals received and transmitted by system instruments. Ground loops in shields are
particularly harmful to bus communication.
Many of the same issues that affect I/O signal wiring also affect I/O bus wiring. However,
each bus protocol is subject to other issues. The following list provides a few examples:
• Standards set by the designated authority for the bus protocol.
• Digital communications speed or baud rate. Profibus DP is capable of up to 12
megabaud while Fieldbus is capable of only 31.24 kilobaud.
• Underlying physical layer. For example, Fieldbus, Profibus PA, and AS-I use Manchester
data encoding.
100
Signal wiring
D800118X022
Note
Emerson recommends against connecting AS-i devices directly to AS-i card terminals. Use
one AS-i cable to connect the AS-i card to the power supply and use another AS-i cable to
connect to field devices. If using extenders and repeaters, refer to their data sheets for
additional cable recommendations.
The following figure shows typical AS-i power and grounding. For more information on AS-
i and installation of AS-i devices, refer to the AS-i Web site: http://www.as-interface.net
101
Signal wiring
D800118X022
Note
When replacing the DeviceNet card in a DeltaV system, refer to the related Knowledge
Base Articles (KBA)s for information about properly wiring specific DeltaV DeviceNet cards.
102
Signal wiring
D800118X022
103
Signal wiring
D800118X022
104
Signal wiring
D800118X022
105
Signal wiring
D800118X022
106
Ground Design For DeltaV
D800118X022
107
Ground Design For DeltaV
D800118X022
low impedance to its DeltaV Instrument Ground (DIG), such faults have less significant
effects on the DeltaV Instrument Ground (DIG) potential.
Lightning protection refers to preventing nearby lightning strikes from harming personnel
or damaging property.
Lightning mitigation refers to minimizing the risk of equipment failure caused by
lightning. For DeltaV this is accomplished by keeping the DeltaV grounding systems close
together and interconnected. All metal enclosures are connected to the safety ground
system. Separately derived systems, such as isolation transformers and UPSs, should be as
close to the DeltaV systems as possible. Case studies have shown that induced energy
because of lightning strikes have disrupted and even damaged instrumentation
equipment due to variance in ground potentials at multiple locations. Keeping all metal
components connected to the safety ground system equalizes induced voltages. Multiple
eddy current paths minimize the need for any single conductor to shunt the equalization
current.
Equipotential ground means that every location in the grounding network is at the same
potential voltage. This is the ideal solution for any grounded system. There are many
grounding methods that can achieve this goal. IEC 60364-4-44, Low-voltage electrical
installations - Part 4-44: Protection for safety - Protection against voltage disturbances and
electromagnetic disturbances, is an excellent source for grounding topologies. When
connecting ground cables, avoid excessive service loops in the cables that can form
inductors. The ground cables should be in as direct a path as possible. When crossing
power lines, maintain as great a separation as possible and ensure that ground cables
cross at right angles to power cables.
108
Ground Design For DeltaV
D800118X022
in this area can be rewarded with big savings from continuous, reliable control system
performance.
109
Ground Design For DeltaV
D800118X022
110
Ground Design For DeltaV
D800118X022
111
Ground Design For DeltaV
D800118X022
2 EC 60364-4-44, Low-voltage Electrical Installations Part 4-44: Protection for safety - Protection against voltage disturbances and
electromagnetic disturbances, Ed. 2.0, 2007.
3 IEEE Standard 1100-2005, Recommended Practice for Power and Grounding.
112
Ground Design For DeltaV
D800118X022
113
Ground Design For DeltaV
D800118X022
Figure 6-4 illustrates an effective, organized ground network. It brings all grounds to a
single point on the plant ground grid. In this configuration, ground connections cannot
produce ground loops. The network includes CG and DCG ground busses located in
enclosures, isolated master or local ground busses for each local area, a DeltaV
instrumentation ground (DIG), with a dedicated connection to the plant ground grid.
The following figure shows separation of DeltaV system ground and plant ancillary
equipment and feeds.
Notes
1. Conductor used to bond the source neutral ground of a separately derived
instrument power system to the DeltaV Instrumentation Ground (DIG), as required
by NEC 250-30(a)(2), CSA C22.1 Section 10. Refer to Table 6-2.
2. Conductors used to provide a low-impedance ground path for the DC power system
and for EMI/RFI noise protection for instruments and field wiring installed in
enclosures.
3. Conductor used to connect the DeltaV Instrument Ground (DIG) directly to the
plant ground grid. This conductor also provides a low impedance ground path for
EMI/RFI noise, as required by NEC 250-54-Supplemental Grounding Electrode
250-50(a)(2). Refer to Table 6-2.
4. The DeltaV Instrumentation Ground must be effectively bonded to building steel
[refer to NEC 250-50(b)], and building steel must be properly grounded to earth
ground.
5. Chassis ground bus and isolated DC ground bus (isolated from chassis) used to
provide reference ground for devices installed in the enclosure grouping. For
distances greater than 10 ft (3 m) between the AC or DC ground bus and isolated
114
Ground Design For DeltaV
D800118X022
master or local ground bus, use stranded, insulated 1/0 to 4/0 AWG (50 to 120
mm2). For distances less than 10 ft (3 m), 2 AWG (35 mm2) cable may be used.
Refer to Table 6-2.
6. Side-by-side enclosures bolted together, but open to each other.
7. Cable used to bond grouped enclosures where an AC ground bus and a DC ground
bus are installed in open-sided grouped enclosures. Be sure to strap grouped
enclosures together; do not depend on bolts to provide ground. Use 12 mm (0.5
in.) wide, braided grounding strap for distances up to 15 cm (6 in.). For longer
bonding, use insulated 10 AWG (6 mm2) wire. Refer to NEC Table 250-122 and Article
250-119.
8. Enclosures in a local area, or side-by-side bolted together with panels between
enclosures. Each enclosure requires its own CG bus and DC ground bus. Use
stranded, insulated 14 to 12 AWG (2.5 to 4 mm2) between instrument and shield
grounds and the CG and DCG busses.
9. Local area ground busses are not necessary if a master ground bus will suffice. See
Controlling Ground System Costs in text.
10. A and Z depict the end points of ground paths. For optimum EMF protection, the
maximum path length is 100 m (300 ft). Use cables as described in the notes above.
115
Ground Design For DeltaV
D800118X022
voltage and the current, you can calculate the resistance. Soil sampling places soil samples
in specially designed boxes to measure the resistance with laboratory instruments.
The chemical composition of soil and its resulting resistivity varies vastly from one
geographic area to another, and even from one stratum to another.
The following table lists typical and average resistivity for several types of soil. The table is
based on Table 10, Resistivity of Soils and Resistance of Single Rods, in IEEE 142-1991, IEEE
Recommended Practice for Grounding of Industrial and Commercial Power Systems.
Table 6-1: Resistivity of soils and resistance of single rods
Soil Description Average Resistivity (Ωm) Resistance of 16 mm (5/8 in.)
x3m
(10 ft) Rod (Ω)
Well-graded gravel 600-1,000 180-300
Poorly graded gravel 1,000-2,500 300-750
Clayey gravel 200-400 60-120
Silty sand 100-800 30-150
Clayey sand 50-200 15-60
Silty or clayey sand with slight 30-80 9-24
plasticity
Fine sandy or silty soil 80-300 24-90
A change of soil moisture from 0 to 30% (by weight) can decrease soil resistivity from 1
MΩ-m to below
10 Ω -m.
Soil compaction can either increase or decrease soil resistivity. If the soil is so compact that
moisture is forced out, the resistivity will be higher. However, if the compaction decreases
the distance between conductive soil components, the resistivity will be lower.
You can decrease the soil resistivity of the earthing electrode network in several ways.
Adding minerals such as coke breeze (carbon) or salts, adding other conductive elements
or compounds, and adding moisture to the soil all decrease resistivity.
Surface area – Having more surface area of the earthing electrode network in contact with
the soil decreases the ground resistance. A linear increase in soil resistivity requires an
exponential increase in surface area. The amount of surface area can be calculated before
construction and adjusted during construction.
A well-designed DeltaV Instrument Ground often consists of a network of ground rods
commonly referred to as a triad. However, depending on the soil resistivity, your network
may require more or fewer than three ground rods. You can estimate the number of
ground rods required based on the soil resistivity where the rods will be installed. Emerson
recommends a documented verification of resistance before finalizing installation (e.g.,
before paving over the soil). Your network may require additional measures to achieve the
optimal 1 Ω to earth. Recognized industry guidance for the distance between ground rods
is 2X the ground rod length. Closer distances might work and meet the requirements, but
are less efficient due an overlapping sphere of influence between rods.
116
Ground Design For DeltaV
D800118X022
To take an example, one 16 mm (5/8 in.) x 3 m (10 ft) ground rod installed in 100 Ωm soil
has a calculated resistance of approximately 30 Ω to earth. Using three rods at the same
depth, ∼6m (20 ft) apart, results in approximately 13 Ω.
Corrosion of grounding components can create points of higher resistance where
components are bonded. An example of this is copper sulfate forming where bare copper
comes into contact with sulfur compounds in the soil.
117
Ground Design For DeltaV
D800118X022
• Inspect sub-earth grounding components near grade by digging a few inches of soil
away from the rods, conductors, or straps. In many cases, you can see or feel corrosion
just at the surface.
• Test the earth electrode network as described in IEEE Standard 81-2012, IEEE Guide for
Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a
Grounding System.
You can reduce the resistance of your grounding system by doing the following:
• Decrease soil resistivity by adding non-corrosive, conductive salts or other soil
additives.
• Increase conductor sizes.
• Bond all below-grade grounding components with uninsulated (bare) conductors to
add to the overall sub-earth portion of the ground system.
• Increase the surface area of the grounding components in contact with the soil. For
example, you can use longer grounding rods or increase the number of grounding
rods.
118
Ground Design For DeltaV
D800118X022
119
Ground Design For DeltaV
D800118X022
• Torque lug bolts to specification, and mark each bolt to provide a visual indication if
the bolt has moved after being torqued.
• Field wiring may also require surge suppression if the signals enter a protection zone
outside the zone which includes the controller and cards. When SPDs are used with
field wires it is best to have SPDs at both ends of the field transmitter/receiver pair.
• If a coating is required to protect against corrosion, use a clear coating material to
allow visual inspection of the bolt, lug, and copper.
• Use Belleville (conical spring) washers on the lug bolts to maintain consistent force in
varying temperatures.
• Label ground bars for identification.
The following figure shows a commercially available ground bar suitable for use with
DeltaV. This kind of ground bar is typically used in data centers. Verify the ground bars
materials are compatible with the environment where the bars will be installed.
The following figure shows properly installed isolating standoffs for a ground bar.
120
Ground Design For DeltaV
D800118X022
121
Ground Design For DeltaV
D800118X022
122
Ground Design For DeltaV
D800118X022
123
Ground Design For DeltaV
D800118X022
The following figure shows grounding for DeltaV systems with multiple separately derived
power sources on multiple stories. The neutral-to-ground connection of each power
source is bonded to a local safety ground bar before the DIG.
124
Ground Design For DeltaV
D800118X022
125
Ground Design For DeltaV
D800118X022
126
Appendices
D800118X022
7 Appendices
7.1 Interference And Transients
The dashed return path through DeltaV represents the path noise takes when the shields
are tied to the isolated instrument ground. The noise returns to the location where the
chassis ground and DC ground are first connected to building steel. At that point a parallel
path is established. Some current will travel through building steel, with the remainder
following the copper to steel, then to its source.
• Noise tends to return to its source following the path of least resistance.
• Steel is 10 times more resistive than copper.
• However, because of the skin effect and the multiple paths in the steel, the path
through steel is 4.5 times less resistive overall than the copper path.
Connecting signal shields to building steel ensures that noise returns to its source more
efficiently.
127
Appendices
D800118X022
Typically, voltage differential faults that result from equipment failure, utility faults, or
lightning create a transient signal that subsides with a type a diminishing ring similar to
the gate function (sin(x)/x). However, the decay more closely resembles a zero-order
Bessel function. Because noise tends to return to its source, the actual elevation in impulse
voltage at one area establishes a differential with respect to more remote locations.
Multiple paths through steel and copper grounds eventually equalize due to the heating
(I2 •R) losses throughout the numerous return eddy paths.
128
Appendices
D800118X022
onto the signal during the precipitation process. This coupling process was due to
inductive coupling as shown in the following figure.
129
Appendices
D800118X022
ground system yielding the least amount of disruptive events is required, then the shields
should be connected to the CG for the following reasons:
• Noise tends to return to its source following the path of least resistance.
• Scientific evidence confirms that noise on shields connected to DC ground adversely
influences system integrity. The Pin 1 Problem first recognized by Neil Muncy and
documented in his 1994 Audio Engineering Society paper has been confirmed in
multiple studies. Although this issue has been of particular concern to audio engineers,
the conclusion applies to all engineering disciplines including control systems.
• Standard recommending shields be connected to enclosure or chassis ground:
• ANSI/ISA-RP12.06.01-2003 Recommended Practice for Wiring Methods for Hazardous
(Classified) Locations Instrumentation Part 1: Intrinsic Safety requires that shields be
connected to equipment or chassis ground.
Equipment manufacturers are continually designing products to be smaller, with less
weight, and at an increased savings. This has led to products operating at higher
frequencies resulting in electrical components, such as indictors and transformers, being
much smaller. Emerson has been and will remain a leader in providing a power and
grounding solutions for controlling equipment designed for today's adverse environments
as well as unforeseen future applications.
130
Appendices
D800118X022
• Personnel safety is enhanced because ground contact does not depend on a single rod.
The distance between rods in a multiple rod system must not be greater than twice the
immersion depths of the rods. For more information on installing and testing ground
systems, you may wish to obtain the publication, Getting Down to Earth from the Megger
Group Limited.
If an existing grid is accessible and the grid-to-true-earth meets the resistance
requirements, the existing grid can be used for the control system ground. If the existing
grid is not accessible or the resistance is not within specifications, a new grid is required.
One point (preferably at a ground rod) on the grid and close to the control system is used
for the DeltaV dedicated connection. The control system ground is connected to the
chosen ground rod with 4/0 AWG (120 mm2) shielded, stranded-copper cable. The cable
at the rod end may be hydraulically crimped or thermally welded to the rod.
For cable to cable connections, thermal welding historically provides good long term
integrity. Field experience infers that hydraulic crimping may provide better integrity for
cable-to-rod or cable-to-building connection due to occasional difficulty in making reliable
thermal welds of these joints.
131
Appendices
D800118X022
132
Appendices
D800118X022
133
Appendices
D800118X022
134
Appendices
D800118X022
135
Appendices
D800118X022
Note
Refer to Figure 7-4 for footing detail.
136
Appendices
D800118X022
137
Appendices
D800118X022
An earth ground tester is used to determine the total resistance of an earth ground
system. The tester contains an electric current source and connections for probes.
When earth ground systems must provide 5 Ω or less resistance, the resistance of the test
leads can no longer be assumed to be negligible, especially since the leads can be many
feet or meters long. Therefore, lead resistance should be measured and subtracted from
the earth ground reading.
138
Appendices
D800118X022
Table 7-1: Depths and measuring points for three-point testing method
Depth of ground rods at point Points E and P Points E and C
E
6 ft (1.8 m) 45 ft (13.7 m) 72 ft (22.0 m)
8 ft (2.4 m) 50 ft (15.2 m) 80 ft (24.4 m)
10 ft (3.0 m) 55 ft (16.8 m) 88 ft (26.8 m)
12 ft (3.7 m) 60 ft (18.3 m) 96 ft (29.3 m)
18 ft (5.5 m) 71 ft (21.6 m) 115 ft (35.1 m)
20 ft (6.1 m) 74 ft (22.6 m) 120 ft (36.6 m)
30 ft (9.1 m) 86 ft (26.2 m) 140 ft (42.7 m)
Resistance value is obtained by measuring the current between C and E and the voltage
between P and E. Many earth ground testers convert these measurements to resistance
and show the resistance on an ohmmeter. Ohm's Law can be used to determine the
resistance if an ammeter and voltmeter are used on the tester.
It is recommended that measurements be made and recorded in several directions from
the ground system and the values entered in a table. The values will indicate good earth
ground areas and also high resistance areas to be avoided. Since earth ground resistance
varies with changes in ground moisture and temperature, resistance measurements
should be made at different times during a year.
139
Appendices
D800118X022
can be limited by obstacles such as buildings, highways, railroads, and by other ground
systems where the electrical currents in those systems could influence the measurements
of the system under test. Also, if measurements are attempted inside the perimeter of a
ground grid system, inaccurate readings can result.
The setup reduces the distance necessary to make a measurement. Terminals P and C are
tied together and connected to a known adequate ground system, such as that of a power
utility neutral ground. Then, earth ground resistance can be measured between the known
system and the system under test. If a voltmeter is used in conjunction with an ammeter,
the voltmeter is connected between P/C and E.
140
Appendices
D800118X022
7.5.1 General
Most DeltaV™ DCS and DeltaV SIS™ products, such as controllers, I/O cards, logic solvers,
and related items, are designed for natural airflow cooling. For maximum product
availability and expected unit lifetime, sufficient airflow through the products and proper
ambient air temperature in and around them must be sufficient to maintain the specified
operating temperature range.
Environmental conditions such as elevated temperature can cause gradual performance
degradation, intermittent failures, and malfunctions in all electronic equipment. To
prevent problems during the operation of both control and safety systems, consider the
effects of heat and airflow on equipment in enclosures when designing DeltaV systems.
Consider the actual operating temperature when evaluating the useful life of electronic
equipment, including DeltaV and DeltaV SIS components.
141
Appendices
D800118X022
must be such that their specified operating temperature range is maintained. Proper
temperature levels promote good system health and product availability.
All DeltaV DCS and DeltaV SIS products are designed to operate within a specific
temperature range, for example, -40 °C to 70 °C. Consult the product datasheet for each
product to determine the specific temperature range. The published information indicates
the temperature range a product can withstand; however, running the product at the
higher end of the temperature range for long periods of time increases the failure rate of
electronic components.
7.5.5 Solutions
Consider the following methods of improving heat dissipation:
1. Proper placement of pieces of equipment in relationship to each other, including
the following:
a. Power supplies
b. Raceways
c. Cable wiring into and out of the enclosure
d. Device placement for maximum air circulation
Note
When designing an enclosure, consider the minimum distances specified by the
equipment vendors. For DeltaV equipment, consult the planning and design
142
Appendices
D800118X022
documentation. The wiring must at least conform to NFPA, NEC, and applicable
local, regional, and national codes to ensure that it can conduct load safely without
overheating.
3. Design circuits so that all the power does not dissipate inside an enclosure. For
example, some circuits such as an AS-Interface can be wired in parallel or series.
Series wiring dissipates more energy inside the unit and enclosure, whereas parallel
wiring dissipates more energy in the field devices.
4. Place enclosure fans so that they work more efficiently and effectively.
a. Locate fans to move air in such a way that enclosure sheet metal can
dissipate heat.
b. Locate fans to provide maximum airflow over and through all installed
devices. Sometimes, fans are mounted so that they are ineffective in actual
cooling or providing critical airflow. Fan placement is an important aspect of
the enclosure design. Consider the following guidelines when selecting the
fan location for your application:
1. Place fans in the bottom of the enclosure to create positive pressure,
and place vents at the top rear of the enclosure to exhaust the hot air.
This method can maximize cooling and airflow because it works with
the physics of convection currents.
2. Place exhaust fans at the top back of the enclosure and pull air through
from the bottom, creating negative pressure. The drawback to this
method is that air in connected conduits can be pulled in.
3. Roof cabinet fans have significant advantages over door cabinet fans
because roof fans generally have a bigger air-displacement capacity
than door-mounted fans. Additionally, the placement of roof fans
right above the equipment ensures a bigger cooling effect than door
fans.
143
Appendices
D800118X022
a. Mount devices with high heat loads near the top of the enclosure so the heat
they dissipate does not pass around or through other devices.
b. Mount devices with high heat loads near the sides of the enclosure.
c. Mount devices with high heat loads in such a way that natural airflow
circulations (higher temperature on one side and cooler temperature on the
other) are generated.
These methods can help maximum system availability and expected unit lifetime by better
controlling enclosure heat. Such control is fundamental to good enclosure design.
It is recommended to perform periodic audits to ensure proper temperature levels within
enclosures as well as identifying “hot spots.” Adequate airflow can be determined by
measuring the inside temperature at the top, middle, and bottom of the cabinet or
enclosure. However, thermal images are the preferred method to measure temperature. A
hot spot reading could be an indicator of a bigger issue that needs to be reviewed and
remedied. Among other things the audit should confirm that fan directions, fan speed and
that airflow is correct.
WARNING
Both AC power and 24 VDC power with large current capabilities are powering installed
equipment. To avoid personal injury and damage to equipment, use extreme caution
when making temperature measurements.
144
Appendices
D800118X022
CAUTION
Preventing condensation is extremely important. Corrosive vapors dissolving in
condensation turn into acids that slowly erode conductive lands, component leads,
connector pins, and other metal on electronic equipment. The equipment can become
damaged beyond repair.
145
Appendices
D800118X022
qr = the heat dissipated by the load, in BTU/hr; you can find this amount by multiplying the
load power in watts (W) by 3.4.
CLF = the cooling load factor; generally, it applies to intermittent operations. For
continuous operation, use 1.0.
With these assumptions, the equation becomes:
qs = 0.33(qr)
where
qr = 3.4 × V × I, for DC power
qr = 3.4 × V × I × pf, for single-phase AC power
qr = 3.4 × V × I × pf × 1.73, for three-phase AC power (assuming well-balanced loading of
each phase in a manner consistent with good engineering practice).
(V = input voltage; I = input current; pf = power factor)
The resultant cooling-load measurement units are BTU per hour. Convert the load to tons
of refrigeration by dividing by 12,000.
Example: Calculating heat generated within an enclosure
A group of enclosures in a rack-room contain various combinations of instruments. What
is the required cooling load?
First, add the electrical current drawn by the equipment in each enclosure. For this
example, the assumption is 270 A at 24 VDC total for all enclosures.
Next, apply the equation and determine the BTU per hour cooling required:
qs = 0.33 × 3.4 × 24 VDC × 270 A (DC)
qs = 7,271 BTU/hr
From this, the refrigeration requirement is:
Refrigeration = 7,271/12,000 = 0.61 tons
146
Appendices
D800118X022
A = the total exposed surface area of the enclosure (disregard unexposed surfaces such as
back panels on back to back enclosures or floor panels on floor-mounted enclosures.
∆t = the difference between the desired internal temperature and the temperature outside
the enclosure.
Example: Calculating heat transferred into an enclosure
Assume an enclosure with 36 ft2 exposed metal surface and a temperature that averages
40 °F hotter than the desired temperature inside the enclosure. The net heat gain is:
qs = (1)(36)(40) = 1,440 BTU/hr
From this, the refrigeration requirement is:
Refrigeration = 1,440/12,000 = 0.12 tons.
The 0.12 tons is the additional cooling required on top of cooling required for instrument
heat.
The effective cooling of the incoming air is: Effect = 1.08(1.2)(75 - 70) = 6.43 BTU/hr
This figure is then used to determine the overall heat gain.
Note
If additional cooling is required, a vortex cooler can be added.
7.5.10 Conclusions
Achieving expected system reliability and longer expected unit lifetime is possible by
proper system design and maintenance. Please contact your local Emerson sales office for
information about maintenance programs to achieve maximum system availability.
147
Appendices
D800118X022
1. Preferred or recommended.
2. Required.
3. Commonly used in industry but not mandated by NEC. Brown, orange, yellow, and
gray are commonly used for higher voltages. Black, red, blue, and white are
commonly used for lower voltages. AC ground is typically green, and DC ground is
often green/yellow.
4. Orange is required on the high leg of a 4-wire delta with midpoint grounding.
5. Required for greater than 60 V.
6. IEC/EN 60445-2017 - Basic and safety principles for man-machine interface.
7. C-22.1-15 - Canadian Electrical Code, Part I.
8. NFPA70-2017 - National Electrical Code.
9. Government of India General Specifications for Electrical Work-2013; SP 30 (2011):
National Electrical Code of India.
148
Appendices
D800118X022
For ordinary non-classified locations, Marine Certified installations, and other information,
refer to the applicable D8000xxxxxx hardware installation and reference manuals.
149
Appendices
D800118X022
only electrically qualified personnel to work at voltages equal to or greater than 50 VAC or
75 VDC. (NFPA70E Standard for Electrical Safety in the Workplace; EUR-Lex Directive
2014/35/EU)
The following are some examples of warning labels:
• If more than one bussed field power source is used at a bussed field power connector,
place a label near the connector. Add the following statement in appropriate local
languages to the label:
WARNING: MORE THAN ONE LIVE CIRCUIT. SEE INSTALLATION DIAGRAM.
• If AC and DC field power are connected to the same connector, it must be marked with
a warning label as follows in appropriate local languages:
WARNING: THIS CONNECTOR CONTAINS BOTH 120 VAC (OR 240 VAC) AND 24 VDC.
BE SURE TO DISCONNECT BOTH AC AND DC POWER BEFORE UNPLUGGING THE
CONNECTOR.
Although you mark a connector with the warning label, connecting AC and DC field power
on the same connector is never recommended. Lethal voltages are possible. Additionally,
it is never considered to be good engineering practice to connect both AC and DC power
to the same connector.
Warning labels should be in local language and are often required to be in multiple
languages as seen in the following figure.
150
Appendices
D800118X022
7.9.1 Introduction
When a PlantWeb Automation System is first installed, or when the system is not
operating as designed, it is sometimes necessary to perform a site audit to determine
what factors could be contributing to the degraded performance. Often these factors are
external to the system and may include but not be limited to the power and grounding
quality.
7.9.2 Purpose
The worksheets in this section are intended to ensure the environment in which the
system is situated and the implementation of the power and grounding systems are
correct. This document has no other purpose and is not intended for issues outside of the
subject of power and grounding, or complications arising from power and grounding
issues, such as electrical noise and component failures.
Worksheets and associated data sheets are used to guide the audit. The checklists provide
a record of conditions at the time of inspection and are an integral part of the Emerson
Automation Solutions Systems Life Cycle approach. The records assure compliance and
are very helpful when used as part of an on-going maintenance program. Note that all
checklists may not be applicable to each particular situation and consideration should be
made for each and every audit.
151
Appendices
D800118X022
7.9.7 Definitions
Buildings – Location of nodes of DeltaV equipment that may or may not be located within
cabinets or enclosures, but more than likely will be mounted on panel-mounted DIN rails.
The building may be dedicated to the use of the control system or there may be a room
where the control system equipment and hardware are located within the building. The
building normally provides protection from weather and external elements, and controls
temperature and humidity for the equipment within. Buildings might be built by a
fabrication facility with some or all equipment installed and tested, then transported to
the final designated location. Additional names used for what is defined as building within
this document are:
• Enclosure, as in remote instrument enclosures (RIEs)
• Shelter
• Remote instrument buildings (RIBs)
Equipment may be mounted in a cabinet that protects the equipment from the elements
and meets the criteria for controlling the environment. Under these circumstances, use
this worksheet to verify the proper installation of DeltaV nodes.
Cabinet – Possible location of the panel-mounted DeltaV equipment in buildings. A
cabinet provides protection to the control hardware within a building. This can include
preventing errant intrusion by unauthorized personnel, facilitating further climate control
for the hardware, and segregating different areas of the control hardware from other
areas. An example of this might be a fire and gas system from the Basic Process Control
System (BPCS) or the power for the BPCS from the actual BPCS hardware it is powering.
Another name for a cabinet is an enclosure. Since this is common terminology for a
building as well, this document will use cabinet and building in its definition.
Earthing sub-system – This is the grounding system below grade. This could include the
DeltaV triad, plant grid, or building ground ring.
152
Appendices
D800118X022
Triad – Common name for a series of ground rods, which could commonly be three
ground rods and are part of the earthing sub-system. These series of ground rods could be
anywhere from a single to more than three rods. The number of rods used has more to do
with meeting the Emerson recommendation for a 1 ohm ground in the soil and the soil
resistivity.
Soil resistivity – This is a measurement of the ability of the soil to conduct electrical
energy. A high soil resistivity resists the flow of electrical energy and therefore requires a
larger amount of surface area in contact with the soil to conduct the same amount of
electrical energy as a low-resistivity soil.
7.9.8 Commenting
When commenting, please document the location of the verification. If possible, use
pictures to supplement the issue description.
153
Appendices
D800118X022
154
Appendices
D800118X022
155
Appendices
D800118X022
156
Appendices
D800118X022
Signoff
Project Number
Emerson Lead Engineer
Date of Service
Customer Representative Signature #1
Customer Representative Signature #2
157
Appendices
D800118X022
158
Appendices
D800118X022
Comments:
159
Appendices
D800118X022
160
Appendices
D800118X022
Comments:
161
Appendices
D800118X022
162
Appendices
D800118X022
163
Appendices
D800118X022
164
Appendices
D800118X022
Comments:
AC Power System & Distribution for Each Cabinet Page _____ of _____
Use this sheet for cabinets with at least one source of AC
Power. Either the primary, secondary, or utility power must
be AC powered.
165
Appendices
D800118X022
Comments:
DC Power System & Distribution for Each Cabinet Page _____ of _____
Enclosure Breaker Recorded Complete
Location: Location: Value
Verify that all DC powered devices are switched off or
disconnected. Make a note if the Cabinet in use and cannot be
powered down and isolated.
With disconnected DC power system, measure impedance of
system from DC supply positive and negative connections to
chassis ground. (Impedance MUST be High.)
(Note: Internal to a cabinet, Isolated grounds are to be kept
separate from chassis grounds and therefore should have a high
impedance. This test is to insure AC and chassis grounds are
isolated from the DC isolated grounds. External to the cabinet,
isolated grounds meet chassis ground at the DIG, and therefore
would read low impedance. Certain networking components,
ie. Network Switches and CIOCs, have an impedance from their
DC- to Chassis Ground.)
Verify that power can safely be applied to the system. Isolate
power to the field as necessary to insure safety. Energize bulk
power supplies.
Measure the voltage at the Primary Bulk Power Supply or
Source.
Measure the voltage at the Secondary Bulk Power Supply or
Source.
If the System DC Power is using 24 VDC:
Verify that the Primary System Power Supplies (SPS) 24 VDC
inputs are within specifications. (Nominal setting is 24.2 to
24.6 VDC. Absolute maximum at an SPS input should be 28.8
VDC and 11 VDC at the last carrier.)
Verify that the Secondary SPS 24 VDC input are within
specifications. (Nominal setting is 24.2 to 24.6 VDC. Absolute
maximum at an SPS input should be 28.8 VDC and 11 VDC at
the last carrier.)
If the SPS DC Power is using 12 VDC:
166
Appendices
D800118X022
Comments:
Signoff
167
Appendices
D800118X022
168
Appendices
D800118X022
By:Date:
Earthing Electrodes
(Use if the site has an installed earth electrode system either standalone or in conjunction
with a plant grid or ground ring.)
Verification Answer
If “No” Please comment
169
Appendices
D800118X022
By:
Date:
170
Appendices
D800118X022
14
15
Comments:
Comments:
Signoff
Project Number
Emerson Lead Engineer
Date of Service
Customer Representative Signature #1
Customer Representative Signature #2
171
Appendices
D800118X022
Electrostatic sources
Static electricity is caused by physical contact, followed by separation, of dissimilar
materials. This means that static electricity can have an almost infinite number of sources.
The generated voltage potential depends upon the materials, the relative humidity, and
other factors.
Table 7-4: Common sources of static electricity
Means of static generation Electrostatic voltage
10 to 20 percent relative 65 to 90 relative humidity
humidity
Walking across carpet 35,000 1,500
Walking over vinyl floor 12,000 250
Working at a bench 6,000 100
Picking up a vinyl envelope for 7,000 600
work instructions
Picking up a common poly bag 20,000 1,200
from bench
Sitting and moving in a chair 18,000 1,500
padded with polyurethane
foam
172
Appendices
D800118X022
• Moving air (for example, air moved by solder suckers, heat guns, cold sprays)
173
Appendices
D800118X022
174
Appendices
D800118X022
175
Appendices
D800118X022
Note
Atmospheric dust varies considerably in particle size as well as constituents. In the table
sample, there were very few particles found larger than 30 microns in average diameter.
With this as an upper limit, the particles were divided into six size ranges as indicated, with
Column 2 indicating the average particle size for each group. For example, the largest
group consisted of particles ranging between 30 and 10 microns - or an average of 20
microns. In this size range, the number of particles found was 1,000, as shown in Column
176
Appendices
D800118X022
3. This represents the proportionate quantities by count and indicates the relative number
of particles in each size range based on 1,000 particles for the average 20 micron size.
Proper installation
In a vibration and shock environment, care must specifically be taken to properly anchor
all process control system components, especially controller and I/O cards, field
instrument electronics, instrument cases, and wire terminations. Small vibrations or shock
can affect terminations, cable integrity, and card connector integrity, causing a range of
faults from intermittent operation to complete failure.
Proper support and connection methods must be included in system design to minimize
faults. As a minimum, equipment must be installed per equipment installation
instructions, including proper tightening of mounting bolts, clamps, etc.
Product specifications
For vibration and shock limits for DeltaV products, see Environmental Specifications in the
manual, Installing Your DeltaV Digital Automation System. Any method used to minimize
mechanical influences should keep the influences below specified limits.
Note
Limits apply to infrequent events. Equipment exposed to continuous vibration or shock
may require additional mounting considerations. Consult your Emerson Automation
Solutions local business partner or field sales office (LBP/FSO) for more information.
Electromagnetic measurement
Signals from sources closer than one meter are called near field signals. Signals from
sources at a distance of one meter or greater are called far field signals.
177
Appendices
D800118X022
Near field signals consist of a radiation field and an induction field emitted by the radio
antenna. In the near field area, both the radiation field and the induction field are
important. At a distance from the antenna equal to the wavelength divided by 2 π , or
slightly less than wavelength λ/6, the radiation field and the induction field have equal
intensity.
Far field signals consist of a radiation field and a remnant of an induction field emitted by
the radio antenna. At distances of greater than one meter from the antenna, and in the
frequency range of most hand-held radios, only the radiation field is of concern. The
induction field at these distances has negligible effects.
Measuring radio signal field strength around enclosures should be part of a checkout
procedure before startup, and then periodically thereafter. However, significant errors can
occur if the measuring instruments are set up too closely to the antenna. And, in a near
field area, radio signal field strength usually cannot be calculated or tested in a repeatable
manner.
178
Appendices
D800118X022
procedures are done in accordance with this standard, which includes closed enclosure
doors and all equipment properly electrically grounded.
where
E = Electrical field intensity in V/m
d = Distance in m from antenna
p = Manufacturer’s advertised rating in W
λ= Wavelength in m
k = Coefficient found by testing
An analysis of tests run by the Electrical Research Association (E.R.A.) and the French
research department of Electricité de France (EdF) on hand-held two-way radios shows a
wide variation for the coefficient k. Tests of radios with power ratings between 0.5 W and
12 W at both VHF and UHF frequencies from six manufacturers showed a range of
coefficients from k = 0.45 to k = 3.35, with a mean of k = 1.6.
Because testing by EdF was done in a shielded enclosure, we can assume an efficient
ground plane, which could result in a higher value for k. However, because two-way radios
are usually held and keyed by plant maintenance people, ground planes are normally less
efficient and result in additional losses. With the additional losses, the expression above is
an adequate guide for approximating field strength.
179
Appendices
D800118X022
required for effective EMI protection. Refer to earlier chapters in this manual for detailed
electrical grounding information.
Using low-pass capacitive filters on instrument signal wires provide additional EMI
protection. Such filters are usually feed-through devices connected in series with
instrument wires.
Minimizing radiation from a source also minimizes EMI. Therefore, do not mount radio
antennas near a control system. Also, avoid using radio communication while performing
maintenance, especially when enclosure doors are open.
CAUTION
Magnetic media is especially sensitive to EMI. To prevent loss or corruption of stored data,
never use radio communication near magnetic media.
The table above lists average gas concentration levels for various contaminants in the class
ratings. These levels, for reference purposes, approximate copper reactivity levels listed
180
Appendices
D800118X022
in , if relative humidity is less than 50 percent. For a given gas concentration, the severity
level increases by one level for each 10 percent increase in relative humidity above 50
percent, and also increases by at least one level for a relative humidity rate of change
greater than 6 percent per hour.
Class G1 through GX ratings shown in the tables are taken from ISA Standard S71.04,
Environmental Conditions for Process Measurement and Control Systems: Airborne
Contaminants. The standard contains rating definitions and application information.
Emerson uses this standard as a guide for product design and environmental
measurement.
181
Appendices
D800118X022
CAUTION
Damage by corrosive atmospheres occurs to most control systems during initial
installation and at maintenance shutdowns. Also, if the system is stored in a harsh
environment or exposed to corrosive vapors when the environmental control system is not
operational, damage will occur.
1 If copper turns black in about three weeks, the atmosphere is extremely harsh to electronic
components. You should either lower the corrosive level or move the equipment to another
location.
182
Appendices
D800118X022
When low relative humidity is indicated, it implies that very little moisture condensed onto
the coupons either because the atmosphere contained little moisture inherently or the
moisture was well controlled. The low humidity may have caused the copper sulfide film
formation to be attenuated. Additional testing of the environment is recommended.
When few humidly effects are indicated, relative humidity conditions present during the
test period are considered not to have had any unusual effect on the copper sulfide film
formation.
When high relative humidity is indicated, substantial moisture has condensed on the
coupons. The humidity may have caused the copper sulfide film formation to accelerate.
Consideration should be given to controlling the humidity in this environment.
183
Appendices
D800118X022
184
Appendices
D800118X022
Note
Engineering a proper environment requires qualified and proven environmental experts
who can provide a total system approach. Experience indicates that a casual approach to
environmental control does not bring the expected results.
185
Appendices
D800118X022
may be used. The criteria for environmental control in enclosures are the same as that for
control rooms. As with control rooms, the amount and types of control must be
determined and then designed into the enclosure. For example, control might include
temperature only, humidity and particulate filtration only, or particulate filtration only.
HVAC system considerations
If temperature control and humidity control are needed, they can be achieved using a
small HVAC unit mounted on the enclosure or a central unit that feeds several enclosures
in various locations.
Purging system considerations
Often, remote process areas experience high temperature and high relative humidity,
which change with weather and time of year. In addition, dust contamination may be high,
and high levels of corrosive gases may be present.
A destructive remote process area environment can be overcome by using a purging
system that supplies clean, cool, dry air or inert gas to pressurize an enclosure. Correct
enclosure size and type (normally plastic or fiberglass in a corrosive environment), and
maintaining air pressure of 0.08 inches of water column (0.02 millibars) in the enclosure
adds protection. Possible clean air sources are high quality instrument air and air from a
locally placed chemical and particulate filtration system.
Additionally, the purging system must be sized adequately to clean the air after an
enclosure door has been opened and then closed. Also, an enclosure should be located out
of direct sunlight.
186
Appendices
D800118X022
CAUTION
The importance of environmental control system maintenance cannot be
overemphasized. Failure of this system has a direct effect on the reliability of the process
control system. Once corrosion begins on process control equipment, the damage is
normally not reversible.
Air filters are usually ignored. However, clogged air filters directly contribute to early
instrument failure by inhibiting proper instrument cooling. Clogged or used up chemical
filters allow corrosive contaminants to surround instruments. Damaged air-lock seals or
propped-open air-lock doors allow contaminants to enter otherwise protected rooms or
enclosures. Periodic environmental control system maintenance must be part of overall
plant maintenance.
7.11 References
General reference
Joffe, Elya B. and Lock, Kai-Sang, Grounds for Grounding: A Circuit-to-System Handbook, IEEE
Wiley & Sons, 2010.
Ott, Henry, Electromagnetic Compatibility Engineering, Wiley & Sons, 2009.
Vijayaraghavan, G., Brown, Mark, and Barnes, Malcolm, Practical Grounding, Bounding,
Shielding and Surge Protection, Elsevier, 2004.
Power transmission reference
Electrical Transmission and Distribution Reference Book, Westinghouse, 1950.
Reference books for personnel and property safety
Soares Book on Grounding and Bonding, 13th Edition, International Association of Electrical
Inspectors, 2017.
National Electric Code (NEC) 2017 Handbook,NFPA 70, 2017.
BS 7671:2008 Requirements for Electrical Installations 17th Edition, IET Wiring Regulations,
2008.
Cook, Paul, Commentary on IET Wiring Regulations 17th Edition BS 7671:2008 Requirements
for Electrical Installations, Institute of Engineering and Technology, 2008.
American standards
ANSI/ISA-RP12.06.01-2003, Recommended Practice for Wiring Methods for Hazardous
(Classified) Locations Instrumentation Part 1: Intrinsic Safety.
ANSI/ISA-12.12.01:2015 / CAN/CSA C22.2 NO. 213-15, Nonincendive Electrical Equipment for
Use in Class I and II, Division 2 and Class III, Divisions 1 and 2 Hazardous (Classified) Locations.
ANSI/ISA-TR12.12.04:2011 - Electrical Equipment in a Class I, Division 2/Zone 2 Hazardous
Location.
ISA Standard 51.1-1979 (R1993), Process Instrumentation Terminology.
ISA-71.01-1985 Environmental Conditions for Process Measurement and Control Systems:
Temperature and Humidity.
187
Appendices
D800118X022
188
Appendices
D800118X022
EN 61000-3-11 Ed. 1.0, Electromagnetic compatibility (EMC) - Part 3-11: Limits - Limitation of
voltage changes, voltage fluctuations and flicker in public low-voltage supply systems -
Equipment with rated current ≤ 75 A and subject to conditional connection.
EN 61000-3-12 Ed. 1.0, Electromagnetic compatibility (EMC) - Part 3-12: Limits - Limits for
harmonic currents produced by equipment connected to public low-voltage systems with input
current > 16 A and ≤ 75 A per
IEC 60038:2009, IEC Standard Voltages.
IEC 60079-0:2011-06, Explosive atmospheres – Part 0: Equipment – General requirements.
IEC 60079-7:2015-06, Explosive atmospheres – Part 7: Equipment protection by increased
safety "e".
IEC 60079-11:2011-06, Explosive atmospheres – Part 11: Equipment protection by intrinsic
safety "i".
IEC 60079-15:2010-01, Explosive atmospheres – Part 15: Equipment protection by type of
protection "n".
IEC 60079-18:2014-12, Explosive atmospheres – Part 18: Equipment protection by
encapsulation "m".
IEC 60079-25:2010-02, Explosive atmospheres – Part 25: Intrinsically safe systems.
IEC 60079-26:2014-10, Explosive atmospheres – Part 26: Equipment with equipment
protection level (EPL) Ga.
IEC 60079-28:2006-08, Explosive atmospheres – Part 28: Protection of equipment and
transmission systems using optical radiation.
IEC 60204-1, Ed. 5.1 2009, Safety of Machinery -Electrical equipment of Machines - Part 1:
General Requirements.
IEC 61326-1:2012-07, Electrical Equipment for Measurement, Control and Laboratory Use -
EMC Requirements.
IEC 61326-3-1:2017 Electrical Equipment for Measurement, Control and Laboratory Use - EMC
Requirements.
IEC 61326-3-2:2017 Electrical Equipment for Measurement, Control and Laboratory Use - EMC
Requirements.
IEC 60364-1: Low-voltage electrical installations - Part 1: fundamental principles, assessment of
general characteristics, definitions.
IEC 60364-4-41: Low-voltage electrical installations - Part 4-41: protection for safety -
protection against electric shock.
IEC 60364-4-44: Low-voltage electrical installations - Part 4-44: protection for safety -
protection against voltage disturbances and electromagnetic disturbances.
IEC 60364-5-52: Low-voltage electrical installations - Part 5-52: selection and erection of
electrical equipment – wiring systems.
IEC 60364-5-54: Low-voltage electrical installations - Part 5-54: selection and erection of
electrical equipment - earthing arrangements and protective conductors.
IEC 61000-4-30: Testing and measurement techniques – Power quality measurement methods.
IEC 61131-4:2004, Programmable Controllers - Part 4: User guidelines.
189
Appendices
D800118X022
IEC 61140, Ed. 3.1 2009, Protection Against Electric Shock - Common Aspects for Installation
and Equipment.
IEC 61511-1 Ed. 1.0: 2003, Functional safety - Safety instrumented systems for the process
industry sector - Part 1: Framework, definitions, system, hardware and software requirements.
IEC 61643-11:2011, Low-voltage surge protective devices - Part 11.
Lightning references
NFPA 780, Standard for the Installation of Lightning Protection Systems, 2011. NUREG/CR-6866
ORNL/TM-2001/140, Technical Basis for Regulatory Guidance on Lightning Protection in
Nuclear Power Plants, 2011.
Lightning Protection for Engineers, National Lightning Safety Institute, 2016.
IEC 62305-1:2010, Protection against lightning - Part 1: General principles.
IEC 62305-2, Protection against lightning – Part 2: Risk Management.
IEC 62305-3, Protection against lightning – Part 3: Physical damage to structures and life
hazard.
IEC 62305-4, Protection against lightning – Part 4: Electrical and Electronic Systems Within
Structures.
US Military Handbook
MIL-HDBK-419A, Grounding, Bonding, and Shielding for Electronic Equipment and Facilities
(Vol. 1 Basic Theory; Vol. 2 Applications), 1987.
190
D800118X022
191
D800118X022