Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

HARMADI DAVID BONDAN

0 14-03-2023
ORIGINAL ISSUE FA
14-03-2023 14-03-2023
ESTABLISHED CHECKED APPROVED
REV. MODIFICATION STATUS
DATE DATE DATE

OWNER

PT. PLN ( PERSERO )


UIT JAWA BAGIAN TENGAH

CONTRACT NO. : 0056.Pj/DAN.01.03/E35000000/2022 TANGGAL : 27 SEPTEMBER 2022

PROJECT :
UPRATING PENGHANTAR
GI 150KV BRINGIN BAY MOJOSONGO 1&2, GI 150KV MOJOSONGO BAY BRINGIN 1&2,
GI 150KV MASARAN BAY PALUR 1&2, GI 150KV PALUR BAY MASARAN 1&2

CONTRACTOR :

PT. CITRA RIANTARA SEJAHTERA


Jalan Pelanduk No.77 Makassar-Indonesia 90142
DATE SIGN NAME TITLE

ESTABLISHED 14-03-2023 HARMADI 150KV PALUR SUBSTATION


CALCULATION NOTE
CHECKED 14-03-2023 DAVID
HV. APPARATUS PI STEEL SUPPORT
APPROVED 14-03-2023 BONDAN
SCALE SIZE CONTRACTOR DRAWING NUMBER :
EM
1/150 A3 PLR/150/CRS/0003/CN
CIVIL
OWNER DRAWING No. PAGE
SURVEY
138
SUMMARY

I) TECHNICAL DATA APPLICABLE FOR ALL STRUCTURES

1.) TECHNICAL DATA APPLICABLE FOR ALL STRUCTURES


1.1) INTRODUCTION
1.2) ELEMENTARY LOADING CASES
1.3) LOAD COMBINASION
1.4) CLIMATIC HYPOTHESES

II) CALCULATION NOTE FOR PI STEEL SUPPORT STRUCTURE

1.) 150KV PI STEEL SUPPORT H=2,5m

Sub-Chapters Load Calculation as follows:

1 ) Simplified drawing
2 ) Characteristics of apparatus support
3 ) Characteristics of the apparatus
4 ) Characteristics of the connections
5 ) Loads applied on the top of the support:

Sub-Chapters Computer Print Out as follows:

1 ) Job Information Data


2 ) 3D View Structure
3 ) Node Number Data
4 ) Beam Number Data
5 ) Section Properties Profile
6 ) Basic Load Cases
7 ) Combination Load Cases
8 ) Code Group Verification Ratio
9 ) Reaction in Coordinate System
10 ) Node Displacement Summary

2
1.) TECHNICAL DATA APPLICABLE FOR ALL STRUCTURES

1.1) INTRODUCTION

1.1.a) General points


This calculation note, will be done according to following documents:
- Steel structure - Technical Specification

The calculation is performed with computer program (STAAD PRO)

1.1.b) Steel quality

According to steel structure specification


Steel S235JR (yield stress = 235 MPa) is used.

1.1c) Reference documents

Technical Specification of HV. Equipment

1.2) ELEMENTARY LOADING CASES

1 Dead Weight
2 Additional vertical load of 1kN (weight of man with tools)
3 Normal wind load along x direction ( 90°to connections)
4 Normal wind load along y direction (// to connections)
5 high wind load along x direction (90°to connections)
6 High wind load along y direction (// to connections)
7 Earthquake along X+ and Z- direction
8 Earthquake along Y+ and Z- direction
9 Earthquake along X+ and Z+ direction
10 Earthquake along Y+ and Z+ direction
11 Connection forces due to self weight and minimum Temperature
(Basic state)
12 Connection forces due to self weight + normal wind // x and short-circuit effect
(State 1)
13 Connection forces due to self weight + extreme wind // x and short-circuit effect
(State 2)
14 Connection forces due to self weight + short-circuit effect
(State 3)
15 Connection forces due to self weight + normal wind // y and short-circuit effect
(State 4 - When the connections are //x or vertical concerning H.V. apparatus)
16 Connection forces due to self weight + extreme wind // y and short-circuit effect
(State 5 - When the connections are //x or vertical concerning H.V. apparatus)

3
1.3) LOAD COMBINAISONS

Loads due to connection between H.V. appparatus

Basic load combinations : (with safety factors used)

Load
Comb. Elementary load cases - For Steel structure
Code

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
DW DW DW DW DW DW
SC SC SC SC SC
NWx HWx NWy HWy
DW Avl HWx HWy NWx NWy EyEz- ExEz- EyEz+ ExEz+ BS S1 S2 S3 S4 S5
101 1.5 1.5 1.5
102 1.5 1.5 1.5
103 1.5 1.5 1.5
104 1.5 1.5 1.5
105 1.5 1.5 1.5
106 1.5 1.5 1.5
107 1.5 1.5 1.5
108 1.5 1.5 1.5
109 1.5 1.5 1.5
DW = Dead weight EyEz- = Earthquake along Y+ and Z- direction
Avl = Additional vertical load of 1KN ExEz- = Earthquake along X+ and Z- direction
NWx = Normal Wind along x direction EyEz+ = Earthquake along Y+ and Z+ direction
NWy = Normal Wind along y direction ExEz+ = Earthquake along X+ and Z+ direction
HWx = High Wind along x direction SC = Short circuit effect
HWy = High Wind along y direction

Additional load combinations :

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
DW Avl HWx HWy NWx NWy EyEz- ExEz- EyEz+ ExEz+ BS S1 S2 S3 S4 S5
110 1.5 1.5 1.5
111 1.5 1.5 1.5
112 1.5 1.5 1.5
113 1.5 1.5 1.5

4
I.4) CLIMATIC HYPOTHESES
- Basic pressure of normal wind: 38.30 daN/m²
- Basic pressure of extreme wind: 68.00 daN/m²

- Drag coefficient of the exposed area of the support: 1.600


- Drag coefficient of the protected area of the support: 1.247

- Drag coefficient on cylindrical area : 0.624


- Drag coefficient on flat area : 1.750

- Drag coefficient on cable conductor : 1.200


- Drag coefficient on tube conductor : 0.894

- Horizontal seismic coefficient : 0.200 .g


- Vertical seismic coefficient : 0.200 .g

5
150KV POST INSULATOR
3.1) Simplified drawing

Side B
Side A Side C

Element 2

H1 Ht H
+G
Element 1

Hg

Hs

z
My
Mx
x y (Conductor axis)
O
O
3.2) Characteristics of apparatus support

Spatial lattice type => Single lattice support


Type of support => Single bar type => --------------
Phase qty per support => One-phase support

Height of the support : 2,500 m (Hs)

Number of columns => 1 Axis => Along X (if 2 columns)


Distance between axis of columns : m (Ds)

If lattice type :

Base Total width of the support // X : 0,370 m


Total width of the support // Y : 0,370 m
Total width of the support // X : 0,336 m ( Between gravity axis )
Total width of the support // Y : 0,336 m ( Between gravity axis )
Top : Total width of the support // X : 0,370 m
Total width of the support // Y : 0,370 m
Total width of the support // X : 0,336 m ( Between gravity axis )
Total width of the support // Y : 0,336 m ( Between gravity axis )

Nb of lattice panels // X => 6 Nb of lattice panels // Y => 6


kg/m
Lattice => L50x50x5 3,77
Member => L60x60x6 Weight : 5,42
Head => L60x60x6 5,42

Exposed area of the support Wind x : 0,643 m²


Wind y : 0,643 m²
Protected area of the support Wind x : 0,447 m²
Wind y : 0,447 m²

Ratio between filled area / total area : j1 0,522


j2 0,522

j1 j2
//y (Wind x) //x (Wind y)

Z Z

Y X
3.3) Characteristics of the apparatus (one phase)

Element 1 => Cylindrical area Total weight of the apparatus : 105,0 daN

Element 2 => Cylindrical area Total weight of the frost on the apparatus: 0,0 daN

Element 3 => ---

Apparatus Element 1 Element 2 Element 3


Height : H1/H2/H3 1,544 0,050 0,000 m
Width/diameter / Wind x L1y/L2y/L3y 0,308 0,308 0,000 m
Width/diameter / Wind y L1x/L2x/L4x 0,308 0,308 0,000 m
Area center of the apparatus
Position along x / O Px 0,000 0,000 0,000 m
Position along y / O Py 0,000 0,000 0,000 m
Position along z / top of support Pz 1,012 1,912 0,000 m
Position along z / O 3,512 4,412 0,000 m
Gravity center
Position along x / O Xg 0,000 m
Position along y / O Yg 0,000 m
Position along z / top of support Hg 1,038 m
Position along z / O 3,538 m
Plugs Side A Side B Side C
Position along z / top of support HA/B/C 0,000 2,378 2,378 m
Position along x / O ExA/B/C 0,000 0,000 0,000 m
Position along y / O EyA/B/C 0,000 0,000 0,000 m
Position along z / O 2,500 4,878 4,878 m

Height of the support Hs 2,500 m


Total Height of the apparatus: Ht 1,594 m

Wind area by apparatus:


Element 1 Element 2 Element 3
Wind X 0,48 0,02 0,00 m²
Wind Y 0,48 0,02 0,00 m²

Additionnal element:
Control box Weight
Wind X 0,00 m² -Fz 0,0 daN
Wind Y 0,00 m²
Frost weight
Area center (for wind) : Control box -Fz 0,0 daN
Position along x / O 0,000 m
Position along y / O 0,000 m
Position along z / O 0,000 m
3.4) Climatic hypotheses

- Basic pressure of normal wind: 38,3 daN/m²


- Basic pressure of extreme wind: 55,2 daN/m²

- Drag coefficient of the exposed area of the support: 1,600 88,34 61,34
- Drag coefficient of the protected area of the support: 0,598 33,01 22,92

- Drag coefficient on cylindrical area : 0,624 34,47 23,93


- Drag coefficient on flat area : 1,750 96,63 67,10

- Drag coefficient on cable conductor : 1,200 66,26 46,01


- Drag coefficient on tube conductor : 0,894 49,38 34,29

- Horizontal seismic coefficient : 0,200 .g


- Vertical seismic coefficient : (downward) 0,200 .g

- Thickness of the frost on cable conductors: (mm) 0,00 0,00 0,00


- Thickness of the frost on tubular conductors: (mm) 0,00 0,00 0,00
- Thickness of the frost on the support and the apparatus: 0,00 mm
- Density of the frost: 0,00
- Reduction coefficient for the wind in case of frost: 0,00

3.5) Characteristics of the connections


Side A Side B Side C

- Type of conductor: Cable --- Cable

- Section area of component of conductor: 845,10 845,10 mm²


- Diameter of component of conductor: 37,80 37,80 mm
- Nb of cables in the conductor (or 1 tube): 2 2
- Lineic weight of one component of conductor: 2,341 2,341 daN/m

- Direction of the connection: Vert. --- Horiz.

- Horizontal distance between anchoring points : 0,000 2,500 m


- Differential level between anchoring points : 10,000 0,000 m
- Distance between two adjacent phases : 3,250 3,250 m
- Sag of the connexion in % of the length (/slope) : 0,00 8,00 %
- Sag of the connexion : 0,000 0,000 0,200 m

- Normal wind pressure on the connection: 46,0 0,0 46,0 daN/m²


- Extreme wind pressure on the connection: 66,3 0,0 66,3 daN/m²
- Intensity of the short-circuit: 40,00 40,00 kA

- Linéic weight of the connection: 4,682 0,000 4,682 daN/m


- Force due to normal wind: 3,478 0,000 3,478 daN/m
- Force due to extreme wind: 5,009 0,000 5,009 daN/m
- Force due to short-circuit: 16,97 0,00 16,97 daN/m
- Weight of the frost on the connection: 0,000 0,000 0,000 daN/m
- Force due to normal wind on the connection with frost: 0,000 0,000 0,000 daN/m
- Force due to extreme wind on the connection with frost: 0,000 0,000 0,000 daN/m
10) Loads applied on the nodes of the top of support:
z
1 4

y
(Direction of conductors)

2 3
x

Comb Nœud Fx Fy Fz Comb Nœud Fx Fy Fz


1 0 0 -27 1 30 18 331
2 0 0 -27 2 30 18 142
1 11
3 0 0 -27 3 30 18 -345
4 0 0 -27 4 30 18 -157
1 3 0 19 1 31 18 339
2 3 0 -19 2 31 18 134
2 12
3 3 0 -19 3 31 18 -353
4 3 0 19 4 31 18 -149
1 0 3 19 1 27 18 313
2 0 3 19 2 27 18 160
3 3 0 3 -19 13 3 27 18 -327
4 0 3 -19 4 27 18 -175
1 5 0 27 1 27 21 331
2 5 0 -27 2 27 21 178
4 14
3 5 0 -27 3 27 21 -345
4 5 0 27 4 27 21 -193
1 0 5 27 1 27 22 339
2 0 5 27 2 27 22 186
5 15
3 0 5 -27 3 27 22 -353
4 0 5 -27 4 27 22 -201
1 6 -2 -38 1 0 0 0
2 6 -2 -103 2 0 0 0
6 16
3 6 -2 -61 3 0 0 0
4 6 -2 5 4 0 0 0
1 0 6 -17 1 0 0 0
2 0 6 -17 2 0 0 0
7 17
3 0 6 -82 3 0 0 0
4 0 6 -82 4 0 0 0
1 6 2 103 1 0 0 0
2 6 2 38 2 0 0 0
8 18
3 6 2 -5 3 0 0 0
4 6 2 61 4 0 0 0
1 0 9 124 1 0 0 0
2 0 9 124 2 0 0 0
9 19
3 0 9 -26 3 0 0 0
4 0 9 -26 4 0 0 0
1 0 5 58 1 0 0 0
2 0 5 58 2 0 0 0
10 20
3 0 5 -73 3 0 0 0
4 0 5 -73 4 0 0 0