MOS-E002Grounding Grid - Mesh MOS
MOS-E002Grounding Grid - Mesh MOS
Project :
3. REFRENCE
TES-P-119.10 Grounding
4. RESPONSIBILITIES
Project Manager
???Responsible for ensuring and monitoring that all cable trays installation activities are executed as per client required SEC procedures, approved ITP’s and MOS.
Forman
???Responsible to execute activity of installation as per IFC drawings and this MOS.
Safety Officer
???Responsible for ensuring best Health& Safety practices across working, storage areas and during equipment operations. He must prepare risk assessment for
effective controls.
Project :
6. PROCEDURE
Installation
Ensure that grounding conductor and rods are as per approved BOQ and drawings for use.
Ensure the depth of excavated trench for buried grounding conductor is as per client specification before laying of grounding mesh.
Obtain PTW (Permit to work) if required.
The spacing of grounding mesh shall be laid as per approved drawing.
Grounding rod shall be driven vertically up to required length.
Thermite weld mold size and powder type shall be same brand for joints connection.
Weld all junctions with thermite weld mold and weld powder properly .
Ensure solid junction and connection as result of thermo-welding.
Apply bituminous paints for additional protection of all joints after cleaning thermite weld connection, with steel brush.
Wrapped the applied bituminous paint with vinyl tape.
Testing
Measure contact resistance of all bolted or thermite welded joints at 100 A DC.
Check and verify all thermite welded joints, securely connected to mesh.
Check electrical resistance of grounding points and main grounding system according to IEEE Standards.
Measure the grounding grid system by “ fall of potential ” method .
7. ADDITIONAL INFORMATION
Attachment
8. ATTACHEMENTS
1. TES-P-119.10 SEC Standard