Addendum to SES Addendum No: 1

IEC-E06-E01 Date: Sept 2015


Guidelines for Selecting IEC and API
ENGINEERING STANDARD Standards for AC Motors 150 kW and Page: 1 of 2
Larger

S.N. SES No.: IEC-E06-E01 Rev. No.: 1 Paragraph No.: 2


1 Original Text:
2. References
As is
New Text:
2. References
Add:
CIGRE/CIRED/UIE Joint Working Group
C4.110 Voltage Dip Immunity of Equipment and Installations, April 2010

S.N. SES No.: IEC-E06-E01 Rev. No.: 1 Paragraph No.: 9 (new)


2 Original Text:

New Text:
Add new section:
9. Voltage Dip Immunity
The motors shall be mechanically and thermally capable of riding through a voltage dip in
accordance to the Process Immunity Time (PIT) and motor stability study (see e.g. in Figure 1
below) voltage dips scatter plot lasting up to 30 cycles. Refer technical paper “CIGRE/CIRED/UIE
Joint Working Group C4.110, Voltage Dip Immunity of Equipment and Installations”

S.N. SES No.: IEC-E06-E01 Rev. No.: 1 Paragraph No.: 9(new)


3 Original Text:

New Text:
Add new figure as below:

Notes:
1. Template shall be repeated for each addendum proposal
2. Separate forms shall be used for different standards.
IEC-E06-E01-Addendum-1.docx
Addendum to SES Addendum No: 1

IEC-E06-E01 Date: Sept 2015


Guidelines for Selecting IEC and API
ENGINEERING STANDARD Standards for AC Motors 150 kW and Page: 2 of 2
Larger

Figure 1: Example of a Synchronous Motor Voltage Dip Immunity Curve

Notes:
1. Template shall be repeated for each addendum proposal
2. Separate forms shall be used for different standards.
IEC-E06-E01-Addendum-1.docx
NUMBER IEC-E06-E01
REV. No. 1
ENGINEERING STANDARD DATE MAR 2015
PAGE 1 OF 4

Guidelines for Selecting IEC and API Standards for AC


Motors 150 kW and Larger
(This is an addendum to PIP ELEMT01, April 2013)

This document is issued by PE, SABIC E&PM, Jubail Industrial City, Kingdom of Saudi Arabia. The information contained in this
document is the confidential property of SABIC. It cannot be disclosed, copied or used for any purpose without approval from SABIC.
If you are not authorized to possess this document, please destroy it immediately.
NUMBER IEC-E06-E01
Guidelines for Selecting IEC and REV. No. 1
API Standards for AC Motors 150 DATE MAR 2015
kW and Larger
ENGINEERING STANDARD PAGE 2 OF 4

1. Purpose
Process industry Practices (PIP) ELEMT01 is adopted as a SABIC Engineering Standard with the
following addendum.

2. General
2.1 Throughout the document, substitute the documents/information in 1st column of Table I with
the indicated equivalent in column 2.
Table I
Replacement Table
Original Text Replace With:

ELEMT01 SES IEC-E06-E01

Owner SABIC

Purchaser SABIC or SABIC’s authorized agent

3. Addenda
The following section, subsection and paragraph numbers refer to PIP ELEMT01 “Guidelines for
Selecting IEEE and API Standards for AC Motors 250 HP (185 kW) and Larger”.

2. References
Add:
2.3 SABIC Engineering Standards (SES)
IEC-E02-G01 Electrical System Design Criteria
IEC-E06-X01 Data Sheet for AC Squirrel Cage Induction Motor Specification (4000
Volts and Below)
IEC-E06-S02-01 Form-Wound Squirrel-Cage Induction Motors –370 kW and Larger.
IEC-E06-X02-01 Data Sheets for Form-Wound Squirrel-Cage Induction Motors –370 kW
and Larger.
IEC-E06-S02-02 General-Purpose Form –wound Squirrel Cage Induction Motors – 150
kW and Larger.
IEC-E06-X02-02 Data Sheets for General-Purpose Form –wound Squirrel Cage
Induction Motors – 150 kW and Larger.
IEC-E06-S03 Brushless Synchronous Motors-370 kW and Larger
IEC-E06-X03 Data Sheets for Brushless Synchronous Motors-370 kW and Larger

3. General Guidelines
Add:
In addition to the Table 1 in the PIP ELEMT01, Table 2 below shall be used to choose the
applicable standard.
NUMBER IEC-E06-E01
Guidelines for Selecting IEC and REV. No. 1
API Standards for AC Motors 150 DATE MAR 2015
kW and Larger
ENGINEERING STANDARD PAGE 3 OF 4

IEC-E06-S01 IEC-E06-S02-02/ API IEC-E06-S02-01/API


547 541
Severe duty Severe duty Critical duty
General purpose General purpose Special purpose
service (spared) service (spared) service (unspared)
Induction generator
High Inertia loads
Adjustable speed
drives
Severely Corrosive
atmosphere
Anti friction bearings Sleeve bearings Sleeve bearings
IP 44-54/ IC 411* IP 44-54/IC 411; All enclosures
IPW24/IC01*
Horizontal and Vertical Horizontal Horizontal and Vertical
Source: IEEE Paper No. PCIC-2004-SF1
*Equivalent IEC enclosure types to NEMA enclosure types TEFC/WP-II API 541 shall be
applied to all “critical motors”, “unspared” motors.

Delete section:

4. IEEE 841
Substitute with:

4. IEC-E06-S01
SES IEC-E06-S01 shall be applied for design, construction and testing of motors in accordance
with IEC requirements for single-speed, horizontal or vertical, polyphase squirrel cage induction
motors 150 kW and below.
SES IEC-E06-S01 and data sheet IEC-E06-X01 are an adaption of PIP ELSMT01G- IEC AC
Squirrel Cage Induction Motor Specification (1000 Volts and Below).

5. API 541
Add:
Motors for above applications shall be as per SES IEC-E06-S02-01 and IEC-E06-X02-01.

6. API 546
Add:
Motors for above applications shall be as per SES IEC-E06-S03 and IEC-E06-X03.

7. API 547
Add:
Motors for above applications shall be as per SES IEC-E06-S02-02 and IEC-E06-X02-02.
NUMBER IEC-E06-E01
Guidelines for Selecting IEC and REV. No. 1
API Standards for AC Motors 150 DATE MAR 2015
kW and Larger
ENGINEERING STANDARD PAGE 4 OF 4

8. Data Sheets

Delete: 8.1 IEEE 841


Substitute:
8.1. IEC-E06-S01
8.1.1 For motors covered by the IEC-E06-S01 specification, the SABIC Data sheet
IEC-E06-X01 data sheet should be completed in order to completely inform the
motor manufacturer of the requirements.

8.2 API 541, 546, or 547


Substitute:
8.2.1 The API data sheets associated with the API standards referenced in this Practice
should be completed in order to completely inform the motor manufacturer of the
requirements. Refer to IEC-E06-X02-01; IEC-E06-X02-02 and IEC-E06-X03.

4. Revision History
Revision No. 1, March 2015 Complete Revision. PIP ELEMT01 is adopted with addendums