1 Original Text:
1.6 Referenced Publication
As is
New Text:
1.6 Referenced Publication
Add:
CIGRE/CIRED/UIE Joint Working Group
C4.110 Voltage Dip Immunity of Equipment and Installations, April 2010

S.N. SES No.: IEC-E06-S02-02 Rev. No.: 0 Paragraph No.: 2.2.2.8 (new)
2 Original Text:

New Text:
Add new section to API 547:

2.2.2.8 Voltage Dip Immunity


The motor shall be mechanically and thermally capable of riding through a voltage dip in
accordance to the Process Immunity Time (PIT) and motor stability study (see e.g. in Figure 1
below) voltage dips scatter plot lasting up to 30 cycles. Refer technical paper “CIGRE/CIRED/UIE
Joint Working Group C4.110, Voltage Dip Immunity of Equipment and Installations”

S.N. SES No.: IEC-E06-S02-02 Rev. No.: 0 Paragraph No.: 2.2.2.8 (new)
3 Original Text:

New Text:
Add new figure as below:

Notes:
1. Template shall be repeated for each addendum proposal
2. Separate forms shall be used for different standards.
IEC-E06-S02-02-Addendum-1.docx
Addendum to SES Addendum No: 1

IEC-E06-S02-02 Date: Sept 2015


General-purpose Form-wound Squirrel Cage
Induction Motors— 150 kW and Larger Page: 2 of 2
ENGINEERING STANDARD (API 547, First Edition)

Figure 1: Example of a Motor Voltage Dip Immunity Curve

Notes:
1. Template shall be repeated for each addendum proposal
2. Separate forms shall be used for different standards.
IEC-E06-S02-02-Addendum-1.docx
NUMBER IEC-E06-S02-02
REV. No. 0
ENGINEERING STANDARD DATE MAR 2015
PAGE 1 OF 4

General-purpose Form-wound Squirrel Cage


Induction Motors— 150 kW and Larger
(This is an addendum to API 547, First Edition)

This document is issued by PE, SABIC E&PM, Jubail Industrial City, Kingdom of Saudi Arabia. The information contained
in this document is the confidential property of SABIC. It cannot be disclosed, copied or used for any purpose without
approval from SABIC. If you are not authorized to possess this document, please destroy it immediately.
NUMBER IEC-E06-S02-02
General-purpose Form-wound REV. No. 0
Squirrel Cage Induction Motors -
DATE MAR 2015
150 kW and Larger
ENGINEERING STANDARD PAGE 2 OF 4

1. Purpose
American Petroleum Institute (API) standard 547, First Edition, June 2004 is adopted as SABIC
Engineering Standard for ‘General-purpose Form-wound Squirrel Cage Induction Motors— above
150 kW’. This standard shall be applied for motors as specified in Section ‘1.1: SCOPE’ of API 547
for IEC based motors above 150 kW.

2. General
2.1 Motors manufactured to this specification shall conform to API 547, First Edition, except as
modified by this specification, as set forth on the SES IEC-E06-X02-01, project specification
or by the purchase order.
2.2 This SES is for IEC based motors, manufactured in accordance with performance
requirement of API 547.
2.3 Motors shall be able to operate continuously at their nameplate rating in the environmental
conditions specified in IEC-E02-G01 Section 3.0, without damage or degradation of
operating characteristics.
2.4 Refer to SES IEC-E06-E01 for selection of standards for motor application.
2.5 Refer to SES G03-S01 for requirements on lubrication, shaft-sealing, control oil systems and
auxiliaries’.
2.6 Refer to SES G19-S01 for requirements on machinery protection systems.
2.7 Refer to SES S20-G01 for requirements on noise limits for plant equipment.
2.8 Decision or additional information required for paragraphs in API 547 indicated by a round
bullet (•) at the beginning of a paragraph is to be provided by the purchaser (Contractor or
affiliate). This information should be indicated on the datasheets IEC-E06-X02-02 (adopted
from Appendix A of API 547); otherwise it should be stated in the quotation request or in the
order.

3. Addenda
The following section, subsection and paragraph numbers refer to API 547, First Edition.
Section 1 - General
1.4 Substitute the paragraph as follows:
Any conflict between this specification and other contract or procurement documents, unless
specifically indicated as an exception, shall be resolved at the discretion of SABIC.
1.6 Referenced Publication
Add the following paragraph:
The following documents are part of this addendum. The latest issues, amendments and
supplements to these documents shall apply unless otherwise indicated.
SABIC Engineering Standards (SES)
IEC-E02- G01 Electrical System Design Criteria (NEC)
IEC-E06-E01 Selection of AC Motors
IEC-E06-X02-01 Form-wound Squirrel-Cage Induction Motor-500 Horsepower -Data
Sheets
G03-S01 Lubrication, Shaft Sealing, Control Oil System and Auxiliaries
G19-S01 Machinery Protection Systems
NUMBER IEC-E06-S02-02
General-purpose Form-wound REV. No. 0
Squirrel Cage Induction Motors -
DATE MAR 2015
150 kW and Larger
ENGINEERING STANDARD PAGE 3 OF 4

S20-G01 Plant Equipment Noise Limits


International Electrotechnical Commission (IEC)
IEC 61000-6-4 Electromagnetic compatibility (EMC) – Part 6-4:
Generic standards – Emission standard for industrial environments
2.2 Electrical Design
2.2.1 Rating and Voltage
2.2.1.2 Substitute the paragraph as follows:
Refer to SES IEC-E02-G01 Section 4.0 for Utilization Voltages.
Motor voltage for motors supplied as per this specification shall be 4160 V with the Bus
voltage as 4,160 V, 3 phase, 60 Hz. Other voltage requirements are subject to SABIC
approval. In general, motor ratings shall be selected to operate at the following voltage
levels:

Motor kW Motor Voltage Bus Voltage

150- 5200 4160 4,160 V, 3 phase, 60 Hz

2600 - Above 13,8 00 13,800 V, 3 phase, 60 Hz

All the motor power ratings shall be based on a 50 °C ambient temperature at 1.0
service factor. When the power requirement of the driven equipment falls between two
standard motor ratings, the motor having the larger power rating shall be selected.

2.4 MECHANICAL DESIGN


Add in the beginning before 2.4.1:
Unless otherwise specified, the type of mounting for standard machines shall be IM B3 (IM
1001), IM B5 (IM 3001), IM V1 (IM 3011), or IM V6 (IM 1031) in accordance with IEC 60034-
7.
The mechanical and thermal performance of the motor shall meet the requirements of
section 8 and 9 of IEC 60034-1.
2.4.2 Substitute the paragraph as follows:
Frame and Mounting Plates
Frame sizes shall be in accordance with IEC 60072-1 and IEC 60072-2.
Dimensions of foot-mounted machines and mounting flange dimensions shall be
in accordance with IEC 60072-1 and IEC 60072-2. Unless otherwise specified,
requirements for motor mounting shall be specified by the vendor with unit
responsibility.
2.4.8 Lubrication
Add:
When Antifriction bearings are allowed to be used according to 2.4.7.1.3, 2.4.7.1.5,
then they may be lubricated with grease. Grease-lubrication shall meet the conditions
of API 610, 6.11.4.
6. Vendor’s Data
6.1 PROPOSALS
Add the following paragraph:
NUMBER IEC-E06-S02-02
General-purpose Form-wound REV. No. 0
Squirrel Cage Induction Motors -
DATE MAR 2015
150 kW and Larger
ENGINEERING STANDARD PAGE 4 OF 4

6.1.20 Spare parts and spare parts documentation shall be provided in accordance
with the Purchase Order. As a minimum, one set of spare parts shall be provided for
every motor rating/design purchased. When multiple motors of the same
rating/design are purchased, a complete set of spare parts may be supplied for every
two (2) motors. However, a separate price shall be included in the base quote for
startup and commissioning spare parts as follows:
(a) One (1) set of front and rear bearings.
(b) One (1) set of oil rings for each bearing.
(c) One (1) set of oil labyrinth seals (internal and external).
(d) One (1) complete set of reusable air filters (If applicable).

4. Revision History
Revision No.0, March 2015 Revised to adopt API 547, First Edition with addendums, with
IEC 60034 as base standard.