Professional Documents
Culture Documents
HIMAP-BCS Manual (Eng)
HIMAP-BCS Manual (Eng)
HIMAP-BCS Manual (Eng)
, LTD
1
Manual Revision history
2
CONTENTS
Ⅲ. Protection Functions…………………..….…………….……………………… 45
Ⅳ. Manager Software……………………………………….……………………… 70
Ⅴ. Protection List…………………………………………………………………… 83
3
HIMAP-BCS
Installation Guide
4
1. General check point
□ In the case of long term storage, keep away from direct sun rays, excessive humidity and
especially, out of salinity.
□ Check the body including parts where there are broken, tanned, polluted or not.
□ Check the main body and case as well as terminal block injured or not.
□ Check the proper specification of CT/PT/ZCT/GPT.
2. Operation Condition
□ Ambient Temperature
1) Operation Temperature: -10oC ~ 55oC
2) Storage Temperature: -25oC ~ 70oC
□ Relative humidity: Not exceeding 80%
□ Atmospheric pressure: 860mbar - 1060mbar
□ Place to install
1) Altitude above sea level: Not exceeding 1,000 m
2) No abnormal vibration and impact
3) No polluted air and dirt
5
Mounting □ Mounting on the panel, be aware of front case broken while mounting bolt
screwing.
□ Check the mounting status and loosed screws of each parts.
Control □ For use DC control voltage, pay attention to connect direction of input
Voltage polarities(P, N) to main breaker on panel.
□ For use DC control voltage, check the use of Clamping Diode and it’s
polarities.
Password □ Prior to use the relay, previously setup the Password and prevent unwanted
operation by unauthorized persons.
Connection □ Check the CT Terminal (TB NO. 1 ~ 16), PT Terminal (RB NO. 17 ~22),
and GPT Terminal (TB NO. 23/24) connections.
□ Check the Output Terminal (TB NO. 51 ~ 64) and Remote control
Terminal (TB NO. 69/70, 73/74-CB ON, 71/72, 75/76-CB OFF)
connection
□ For use ZCT, pay attention to direction of connection to TB NO.(9/10)
CB ON/OFF
PWR
COMM
6
Communication □ Optical cable wiring information
-. Regard Optic cable wiring, does not use panel internal terminal block
and directly connect between IEDs using optic cable and also separate
data cables and power cables wiring.
-. To connect optic cord to FO1 and FO2, Optic cord connection should
be compartmentalize Rx(blue: top), Tx(red: bottom) each.
-. Power cable (400V, 200V), binary input and optic cable wiring
Separately.
-. To prevent optic cable bending while wiring, maintain the maximum
round cornering as well as straight direction.
-. In the case of communication cable wiring, check the connection point
of each connector.
z Test purpose connection may use Hook type lug instead of Ring type
lug.
7
4. Check point for SWGR design
□ For Magnetic contact and Inductive load may use Clamping diode.
□ For the purpose of prevent the counter electromotive force inflow, ACC’Y Varistor
should be added into the Circuit Breaker When you order the Digital protective relay
mounted Circuit Breaker (ACB, VCB).
□ All wired power cable should be used Twisted cable.
□ Connection cable between ZCT and HIMAP-BCS should be used shield cable (2 Cores
+ 1 Shield).
Ground line □ Panel enclosure ground line and relay frame ground line should be wired
Separate wiring separately where the separate ground Bus bars.
□ Digital device frame ground Bus bar should be mounted in the end panel of
array.
Digital device
Common
ground Bus
Insulator
Panel enclosure common ground Bus
8
□ Surge Arrestor cables wired along with left side cable route to ground
Bus bar.
Digital device
Common
ground Bus
Panel enclosure
common ground Bus
9
5. Check point for the function test
□ The withstand voltage / insulation resistance test should be not necessary but in the
case of necessity the test should be performed with unwired frame ground and power
supply line.
□ CT / PT should be isolated before the test (use CTT / PTT).
□ The function test should be performed by 3 phase test equipments but, in the
unavoidable case, single phase test equipments would be permitted.
□ All the function test equipments should be approved of each yearly certification and
inspection procedures for precise reliability.
□ All the setting value of Each Relay should be confirmed based on the setting table
value before the test.
□ Connect relay and test equipment after check the each terminals of CT(1/5A),
PT(110/190V), GPT, ZCT.
□ The test equipment voltage / current line should be connected with CTT / PTT.
□ Input voltage / current tolerance should be confirmed before test.
□ The target relay should be enabled as well as non-tested relay be disabled.
□ Check and decide the protection items to be set to enable or disable.
□ For relay protection function test of protection operation within 1 second,
characteristic delay of test equipment should be considered.
□ The injection value should be more than 110% of setting value of relay during the
definite time / inverse time operation test.
□ ZCT K and L polarity should be cautiously considered while perform the SGR test.
□ For zero phase sequence, injection current value should be up to 3A and 1 sec during
SGR test.
□ “I/O test” function can be used in case of the relay and VCB are interlocked.
□ Operator should check the inversed phase voltage / current during relay operation.
□ Operator should not change the setting value while VCB is ‘ON’.
10
7. Check point during maintenance
11
8. Notification procedure of TRIP occurrences
9. Brief troubleshooting
12
□ Digital input 31-34(Spare), 36-39(Spare), 42-44(Spare) related to no.35, 40 and
45(Com).
□ Digital contact input uses dry contact, unpowered contact.
□ If the system does not recognize input signals, short the terminal between (31-34) ↔35,
(36-39)↔40, (41-44)↔45, (46-49) ↔50, and then find out if the fault is in HIMAP-BCS
itself.
□ For the check and confirm the digital input of HIMAP-BCS, you may use local setting
menu on HIMAP-BCS LCD, (F2)→Status View→In / Output Status, then displayed
present status of input and output use.
□ In the case of communication error, check the matching between defined application of
input contacts and TAG of single diagram.
13
* For the check and confirm the relay setting, you may use local setting menu on HIMAP-
BCS LCD, Display(F2)→Set View→Relay Setting.
□ Using measurement menu of display(F2), confirm the correspondence with input value.
□ In the case of output error while the display output contact is working, check the
output setup and the digital output terminal block connection.
□ Calculate operating time and check the results are matched.
14
HIMAP-BCS
Operation Manual
1. Main display 16
2. Display menu 17
3. Set menu 27
4. Control menu 38
5. Fault message display 40
6. Button navigation 41
7. Connection diagram 42
8. Dimension 44
15
1. Main display
After system initialization, HIMAP-BCS displays main display as below Fig 1.
Main display provide user modifiable displays using mimic editor, include name of
device, status value, measured value and power system mimic diagram. Main display also
able to move to sub-screen using arrow buttons(◀▶).
Main display contains the four separate sub menu, FI Main, F2 Display, F3 Set and F4
Control. To move the sub-menu, using the function button (F1, F2, F3, F4) and/or direct
touch the touch screen LCD.
F2 Display menu provides measured value, oscillograph, vector diagram as well as
motor/transformer status value, event record and setting value.
F3 Set menu provides the system setting that sets the various parameter of system and the
relay setting that sets the relay functions.
F4 Control menu provides the functions for breaker control.
16
2. Display menu
Display menu provides six kinds of sub menus, Measurement, Status View, Graph View,
Event View, Vector Diagram and Set View.
17
Fig 3 Measurement display (Overview)
Current menu provides measured current values on a single page as Fig 4 and Max
value describes maximum value of measured data. If you click the Max button, all
displayed value would be reset to zero and operation power off also measured data reset
to zero.
18
Voltage menu provide measured voltage values on a single page as Fig 5 and Vo describes
maximum value of measured data.
Power menu provide measured power values and frequency as Fig 6. Power value
displays each line by line (Line1, Line2, Line3), in the case of 3 phase 4 wire
configuration. Frequency value describes minimum and maximum value. If you click
the Freq max/min button, all displayed values would be reset to zero.
19
Fig 6 Measurement display (Power)
Energy menu provides measured energy values and measured data stored into non-
volatile memory, it maintained the data when off the system till the reset the value.
Harmonic menu provide harmonic value(2nd to 13th), THD (Total Harmonics Distortion),
20
TDD (Total Demand Distortion) for the current (Ia, Ib, Ic) and voltage (Va, Vb, Vc) using
bar graph as well as text value.
Trip circuit supervision menu provides circuit breaker state and supervised data for circuit
breaker coil.
21
2-2. Status View menu
Status View menu provide motor, transformer, reclosing, input/output status, event
Status and Resistance temperature detector (RTD). Each sub items are able to select using
menu select bar. Fig 10, 11 and 12 describes motor, transformer and reclosing status. While
using the protection relay element (49, 51LR, 66, 87T, 79), it also described automatically
on the display screen.
22
Fig 12 Status View display (Reclosing Status)
In/Output Status menu provide status of digital input(1~16) and digital output(1~12).
Active Event Status menu provide activated digital input and output values as well as
CPU status (Good/Bad) of HIMAP-BCS.
23
Fig 14 Status View display (Active Event Status)
RTD menu shows the user all the available measured temperature inputs.
24
is possible to analyze the input distortion influenced by external noise and find out the
transmission line problems. The waveform also provides two kinds of colors.
25
Event View menu provide various event logs; relay element operation, I/O input and
output, various setting and control operation. Maximum number of events is up to 100,000
and also specific event allows additional detailed information. Each event could sort by
title, date and time.
26
3. Configure the Set menu
F3 Set menu requires enter the password to change the settings. If user entered incorrect
password, ‘Wrong Password’ message would be popup and then automatically move to
main display.
27
Set menu provide the system setting that set the various parameter of system and the relay
setting that set the relay functions.
General Parameter Values menu provide setting the motor rated current value, select
motor protections, confirm the number of events that is stored on the CF memory, check
the backup file of event waveform, reset to zero for stored values as well as local/remote
mode select for circuit breaker control.
28
Fig 22 System Setting (General Parameter Values)
Etc menu provide date and time setting, brightness control, breaker control password
change and setting password change.
29
I/O Configure menu provide naming the each digital input and output point by user. It
is possible to easily recognize event point by means of user defined point name.
Network Setting menu provide setting the parameters for MODBUS card.
30
In the recorder setting menu all settings for the recording unit can be set.
TCS Setting menu provide setting the parameters for trip circuit supervision of circuit
breaker.
31
HIMAP-BCS provides three RTD channels. For each channel, the temperature range,
limit type and limit delay time are selected by user.
32
3-2. Relay Setting menu
Relay Setting menu provide setting the protection element, provided totally 31 kinds of
protection functions, of HIMAP-BCS.
33
(3) Neg.Seq.OverCurr.Relay(46) (4) Neg.Seq. OverVoltage Relay(47N)
34
(11) Time Overcurrent Relay(51) (12) AC Time Gnd Overcurr.Relay(51G)
35
(17) Start Inhibit Relay(66) (18) Directional Overcurr. Relay(67)
36
(25) Under frequency Relay(81U) (26) Frequency rate of change Relay(81R)
(27) Direc. active PWR Relay(32P) (28) Direc. reactive PWR Relay(32Q)
Fig 30 Setting the each protection functions
37
4. Configure the Control menu
Control menu provide control the circuit breaker directly via HIMAP-BCS in the case of
‘Local’ setting condition. To enter the Control menu, user should enter the password.
If incorrect password entered or in case of Remote mode, ‘Wrong Password or Remote
Mode’ message will popup and then move to main display automatically.
If correct password entered, displays move to breaker control display automatically and
breaker ready to selectable status with red box in the mimic diagram. After then, user select
the desired breaker using arrow key (▲▼) and Enter Key and/or touch the touch screen
panel directly.
38
Fig 32 Breaker select display
After the breaker selected, popup window shows and ready to CB control command. User
performs breaker control using control key (○, l) and ESC key and also using the touch
screen directly.
39
5. Fault Message display
Due to the power system failure, fault message screen displays while HIMAP-BCS
protection function operates. Fault message display contains information of protection
function, fault date, fault mode, trip ratio, trip time and fault phase.
To acknowledge the fault status, press ACK key or touch the touch screen directly.
(5)
(4)
(2)
(3)
40
(1) Display shift function key
(2) Remote/Local mode select button for breaker control
(3) Breaker On/Off button
(4) Arrow key
(5) Alarm status acknowledge key
(6) Select and cancel button
41
7. Connection diagram
42
- Terminal block layout (rear cover)
43
8. Dimension drawings
44
HIMAP-BCS
Protection Function Setting
1. 50 46
2. 51 46
3. 50G 47
4. 51G 47
5. 87T 48
6. 87G 54
7. 67N 59
8. 67 61
9. 81O 63
10. 81U 63
11. 81R 64
12. 32P 64
13. 32Q 65
14. 49 66
15. 51LR 67
16. 46 67
17. 27 68
18. 59 68
19. 64 69
45
1. 50 (Over Current Relay)
a) Setting Window
47
5. 87T (Differential Relay)-(Transformer)
a) Setting Window
87T(DFR) Enable / Disable
48
1) Transformer primary, secondary current setting value
(Example)
I1’
120/1
I1
10MVA
50/20kV
I2 I2’
4) Instantaneous mode
: At the 87T Characteristic curve above, in the case of Instantaneous differential
ratio(Transformer Primary, Secondary current / Transformer Secondary setting current) bigger
than Instantaneous Ratio, 87T might be operate as Instantaneous mode immediately.
: If not used, this mode should be set to 0.
49
(Example of Instantaneous mode)
Setting value: Primary Current: 0.5A
Secondary Current: 1A
Transformer Type: Yy0 (Select the simplest case for convenience of calculation)
Zero Compensation: Disable
Input value: Input the A-phase current to Primary and Secondary respectively, for convenience
of calculation.
Primary A-phase current: 1A Secondary A-phase current: 8A
Primary B-phase current: 0A Secondary B-phase current: 0A
Primary C-phase current: 0A Secondary C-phase current: 0A
<Description>
① Because of differ from Primary setting current and Secondary setting current, it is needed
‘Scale Factor’ for regulate a balance.
Scale factor = Secondary current setting /Primary current setting = 1 / 0.5 = 2.0
② For the purpose of calculate Differential current between inputted Primary and Secondary
current, in the first place multiply Primary input current by Scale factor, and then, subtract
Secondary input current from that result. If Primary input current is 2A, and Secondary input
current is 4A, then,
Differential = Primary input current * Scale factor – Secondary input current
= 2A * 2.0 - 4A = 0
③ The Primary and Secondary input current is 1.8A respectively, Id (Differential ration)
and Ir (Restraining current ratio) results as follows,
Differential = 1A * 2.0 - 8A = 6A
Id = Differential / Secondary setting current = 6A/1A = 600%
Ir = Secondary input current / Secondary setting current = 8A/1A = 800%
50
④ Regarding above graph, Instantaneous Mode should be operate while “Instantaneous
Differential Operation Area” covers Instantaneous operation point.
5) Percent mode
: Percent mode represents operation mode using various curves (from Min.Pickup Ratio, Knee
point1, Slope1, Knee point2, Slope2) from 87T characteristic graph.
: Support Instantaneous / Definite time mode
: If not used, Min.Pickup Ratio set to 0.
51
Mode: Definite
Delay Time: 2.5sec
Min.Pickup Ratio: 100%
Knee Point 1: 100%
Slope 1: 50%
Knee Point 2: 400%
Slope 2: 100%
2nd Harmonic Content: 0% (Set to 0 for convenience)
Input value: Input the A-phase current to Primary and Secondary respectively, for convenience
of calculation.
<Description>
① The Primary and Secondary input current is 1.8A respectively, Differential current value
results as follows,
Differential = Primary input current * Scale factor – Secondary input current
= 2A * 2.0 - 2A = 2A
52
③ Regarding above graph, Percent Mode should be operate while “Percent Differential
Operation Area” covers Percent mode operation point.
Note: Both of two modes will operate while Instantaneous mode and percent mode were
activated at same time, and also operation points were located simultaneously.
53
6. 87G (Restricted Earth Fault Relay)
a) Setting Window
87G(REF) Enable / Disable
54
1) Setting phase current and ground current
(Example)
2) Instantaneous mode
: At the 87G Characteristic curve above, in the case of Instantaneous differential
ratio(Differential current of 3Io and Ig / Setting current) bigger than Instantaneous
Ratio, 87G might be operate as Instantaneous mode immediately.
: If not used, Instantaneous ratio should be set to 0.
55
<Description>
① Because of differ from Phase setting current and Ground setting current, it is needed ‘Scale
Factor’ for regulate a balance.
Scale factor = Ground current setting / Phase current setting = 2 / 1 = 2.0
② For the purpose of calculate Differential current between 3Io and Ig, in the first place
multiply 3Io by Scale factor, and then, subtract Ig from that result.
Differential = |(Scale_factor*3Io) – Ig| (vector sum)
= (2*(-4.402+ j0.376)) – (3.464 + j2) = -12.268-j1.249
= sqrt((-12.268)^2+(-1.249)^2) = 12.331[A]
③ Using calculated Differential value and Input value, extracts Id[%](Differential current
ratio), Ir[%](Retraining current ratio) and mark on the graph,
Differential = 12.331[A]
Id[%] = 3Io and Ig, differential current / Ig setting current = 12.331/2 ≒ 6.166
= 616.6[%]
Ir[%] = Ig input current / Ig setting current = 4/2 = 2 = 200[%]
[
Instantaneous Mode characteristic curve]
56
④ Regarding above graph, Instantaneous Mode should be operate while “Instantaneous
Differential Operation Area” covers Instantaneous mode operation point.
3) Percent mode
: Percent mode represents operation mode using various curves (from Min.Pickup Ratio,
Slope1, Knee point, Slope2) from 87G characteristic graph.
: Support Instantaneous / Definite time mode
: If not used, Min.Pickup Ratio set to 0.
57
[Percent Mode Characteristic curve]
③ Regarding above graph, Percent Mode should be operate while “Percent Differential
Operation Area” covers Percent mode operation point.
Note: Both of two modes will operate while Instantaneous mode and percent mode
were activated at same time, and also operation points were located simultaneously.
58
7. 67N (Directional Ground Overcurrent Relay)
a) Setting Window
67N(DOCGR) Enable / Disable
<Setting values>
▶ Vo Source: Setting reference Vo type.
☞ Meas.Vo: Apply Vo value input from GPT
Calc.3Vo: Apply 3Vo value calculated from Va, Vb, Vc
▶ Current Limit: Io setting value
▶ Voltage Limit: Vo setting value
▶ Ref. Angle: Reference angle
☞ Reference angle defined by phase of reference voltage (Vo)
▶ Trip Zone: Trip zone
☞ Trip zone(±Trip zone) defined by reference angel(Ref. Angle)
<Descriptions>
▶ 67N activates while altogether with current(Io) and voltage(Vo) over the setting value
as well as current (Io) phase located on the setting coverage where is set based on
reference voltage(Vo).
59
c) Characteristic curve
60
8. 67 (Directional Overcurrent Relay)
a) Setting Window
<Setting values>
▶ Current Limit : Current (Ia,Ib,Ic) setting value
▶ Ref. Angle : Reference angel
☞ Reference angle defined by phase of reference voltage(Vbc, Vca, Vab)
▶ Trip Zone : Trip zone
☞ Trip zone(±Trip zone)defined by Reference angel(Ref. Angle)
▶ Voltage Limit : Voltage(Vbc, Vca, Vab) setting value
<Description>
▶ In the case of 3phase 3wiring wire type, HIMAP-BCS applied line voltage so that is
reference voltage (Vbc, Vca, Vab) applied at each channel.
In the case of 3phase 4wiring wire type, HIMAP-BCS applied phase voltage so that is
reference voltage (Vbc, Vca, Vab) calculate voltage applied at each channel.
61
▶ DOCR (67) protection operate through phase related to voltage and current level, and
corresponding phases are as below,
Ia ↔ Vbc (reference voltage)
Ib ↔ Vca (reference voltage)
Ic ↔ Vab (reference voltage)
DOCR (67) activates while altogether with current and voltage over the setting value as
well as current phase located on the setting coverage.
ex) 67 protection activates while Ia and Vbc(reference voltage) over the setting value, and
phase ‘A’ located on setting coverage where is set based on Vbc(reference voltage).
c) Characteristic curve
62
9. 81O (Over Frequency Relay)
a) Setting Window
63
11. 81R (Frequency Rate Of Change Relay)
a) Setting Window
64
b) Setting values and Descriptions
▶ Power Limit : Active power setting value
▶ Phase Mode : This setting selects the phase for active power
☞ 1 phase / 3 phase
▶ Direction Mode : This setting selects the direction for active power
☞ Forward / Reverse
▶ Delay Time : Operation time setting value
65
14. 49 (Thermal Overload Relay)
a) Setting Window
b) Characteristic formula
※ Calculated Values* : These are not setting values, but automatically calculated values
66
15. 51LR (Locked Rotor Relay)
a) Setting Window
2) 46-2 Mode(Instantaneous/Definite
Normal Inverse/Very Inverse/
Extremely Inverse/Curve-D/Curve-E/
Curve-F/INV-K/VINV-K)
3) 46-2 Inverse time OP Level Setting
※ Refer to Appendix
67
17. 27(Under Voltage Relay)
27(UVR) Enable / Disable
a) Setting Window
set 0)
68
19. 64(Over Voltage Ground Relay)
69
HIMAP-BCS
Manager Quick Guide
70
1. Initial display and Icons
Below displays HIMAP-BCS Manager Software initial display.
Measurement’ and also monitored real time Overview, Current, Voltage, Power, Energy, and
71
Harmonics.
- : Output the report.
While parameter display displayed, click this icons produce parameter setup information report,
and at the event analysis displayed, produce event information report, and also at the fault
analysis displayed, fault information report should be produced. Report should be out to excel
format. parameter report stored to “C:\HIMAP_BCS\Report\SettingReport” folder,
event report stored to “C:\HIMAP_BCS\Report\EventReport” folder,
fault report stored to “C:\HIMAP_BCS\Report\FaultReport” folder, automatically.
8) : Display present HIMAP-BCS version.
9) : ezLadder software open. At that time, communication port of HIMAP-BCS Manager
were opened, ezLadder software should be closed automatically.
10) : Mimic drawer software open. At that time, communication port of HIMAP-BCS
Manager were opened, ezLadder software should be closed automatically.
11) : Screen pull and down.
2. User guide
2) Click icon operates read the parameters from HIMAP-BCS and display as below figure.
72
2-1) At the upper left side pull down menu contains three kinds of sub-
menu which is ActiveRelay, Relay and System. Above figure describes ActiveRelay
displays and shows entire protection function as well as Enable/Disable/Reclose status.
If specific single relay were selected by click, detailed description should be displayed.
73
2-3) Left sides show Relay numbers and its descriptions. While select single relay, detailed
contents displayed on right sides and each parameters are able to download. And also, provides
characteristic curves if needed. Each setting parameters are downloadable to HIMAP-BCS.
“Download to HIMAP-BCS” button operate download parameters of present page. If required
to download all setting values which protections and system setup, “Download All” button
click makes it.
2-4) “Save Parameter” button save and store the present parameter values, named “*.param”
file extension. “Load Parameter” button loads stored parameter named “*.param” file
extensions. Parameter means all kinds of relay elements and system elements.
74
2-6) System display provide HIMAP-BCS system setup and download functions same as relay
setting display.
75
3) Click icon operates read event list from HIMAP-BCS.
3-1) HIMAP-BCS able to backup the events by time through the event list were increased.
Above figure describes stored event lists by time. HIMAP-BCS create 1 backup file for 10,000
events, and empty backup only displays current event.
3-2) To view specific event contents, select desired event index and click “UPLOAD” button.
Below figure describes detailed event display.
3-3) Event list orders newest event display on the top of table and oldest listed on the bottom
for the user convenience. Description row also describe brief summary of event content.
3-4) Bottom of display shows “Detail Information” describes Trip event detailed information.
76
77
4) Click icon operates read fault list from HIMAP-BCS and display.
4-1) Fault stored up to 100, newest fault listed on the top of table. Fault index and Backup fault
time describes easy to understand.
4-2) To view specific fault contents, select desired fault index and click “UPLOAD” button.
Fault file upload takes about 25 seconds for read and display.
Below figure describes detailed fault analysis display.
78
4-3) Fault wave shows Primary current (Ia, Ib, Ic, In), Secondary current(Ia (2), Ib (2), Ic (2)),
Voltage (Va, Vb, Vc, Vn) and digit information. Upper right sides of display describe detailed
fault wave information. Two yellow bar cursors on the waveform makes wave data translate to
table value of upper left sides. Detailed button descriptions are as below,
① : Grab curser
79
⑩ : Gradually minimize the graph
⑪ : While analyze the fault, vector diagram popup and able to analyze the vector
diagram
⑫ : While analyze the fault, harmonic histogram popup and able to analyze the
harmonic histogram
⑭ : Move left the cursor on the fault graph, able to check the detailed value.
⑮ : Move right the cursor on the fault graph, able to check the detailed value.
5) At the upper middle side pull down menu, select “File Download” makes
move to file download page. HIMAP-BCS Manager able to download setup files and execution
files to HIMAP-BCS.
After finished file download, HIMAP-BCS reset popup windows occurs. File download and
system renewal might be completed after reset procedure.
80
6) IEC61850 connection and file send/receive
6-1) This function requires HIMAP-BCS should be connected to HNIC board via LAN,
otherwise it might be occurs communication errors.
6-2) Click IEC61850 button at the upper right sides operates HIMAP-BCS communicate to
HNIC board via optic LAN on the IEC61850 protocol that is possible to edit program files of
HNIC board from HIMAP-BCS Manger. It also able to edit HNIC board program, download
icd file and configuration file, event and fault file upload, status check and confirm by HIMAP-
BCS Manager.
6-4) IED Name and IP Address at the left sides of displays shows present values. At the right
sides “Configuration of ‘osicfg.xml” able to add new IED and new IP Address by means of
write down new IED Name and new IP Address. Click the “Add” button updates new IEC and
IP Address modified by osicfg.xml configuration. The “Delete” button will delete the IDE
81
what the selected. Below figure describes detailed display after click “Select” button.
6-5) Click at the upper left “View Event & Fault Lists” button displays detailed information
that is event lists and fault lists read from selected specific IED. Desired event and fault files,
HIMAP-BCS, downloaded to right sides, My Computer, by using “>>” button. For the IED
setup changing, datamap.cfg, HIMAP-BCS.icd and startup.cfg files are able to uploaded using
“<<” button to left sides, HIMAP-BCS.
6-6) Downloaded fault files from IED is translated to Comtrade file automatically, and selected
Comtrade file displays fault data on the Manager by using “View Data” button.
82
HIMAP-BCS
Protective function List
1. Protective Functions 84
83
1. HiMAP-BCS Protective Functions
Rated Current AC 5A
Inverse-type F, Kepco inverse, Kepco very inverse : (Op Level : 0.05 ~ 10,
0.01 step)
Rated Current AC 5A
Inverse-type F, Kepco inverse, Kepco very inverse : (Op Level : 0.05 ~ 10,
0.01 step)
Rated Current AC 5A
Inverse-type F, Kepco inverse, Kepco very inverse : (Op Level : 0.05 ~ 10,
0.01 step)
84
Rated Current AC 5A
UCR
Setting Range 0.20A ~ 2.50A(0.01A step)
(37)
Characteristic Definite (0.05sec ~ 10sec, 0.01sec step)
Rated Current AC 5A
Inverse-type F, Kepco inverse, Kepco very inverse : (Op Level : 0.05 ~ 10,
0.01 step)
Rated Current AC 5A
Characteristic Hot/Cold limit : 0.5sec ~ 180sec(0.1sec step), tc/th : 0.1 ~ 20(0.1 step)
Rated Current AC 5A
Inverse-type F, Kepco inverse, Kepco very inverse : (Op Level : 0.05 ~ 10,
0.01 step)
85
Rated Voltage AC 190V
Inverse-type F, Kepco inverse, Kepco very inverse : (Op Level : 0.05 ~ 10,
0.01 step)
Characteristic Instantaneous
Rated Current AC 5A
0.01 step)
Rated Current AC 5A
0.01 step)
Rated Current AC 5A
DGR
86
Rated Voltage AC 190V
Rated Current AC 5A
Rated Current AC 5A
Rated Current AC 5A
87
Rated Current AC 5A
Breaker Failure
Setting Range 0.50A ~ 20.00A(0.01A step)
(50BF)
Characteristic Definite : (0.05sec ~ 10sec, 0.01sec step)
Characteristic Definite
Rated Current AC 5A
APR Setting Range 2 W ∼ 4500 W (1 W step)
(32P-1/32P-2)
Mode1 : Single phase / Three phase
88
Setting Range 2 Var ∼ 4500 Var (1 Var step)
89
Appendix
1. Characteristic curve 91
2. Logic (Example) 106
90
1. Characteristic curve
91
Very Inverse Curve
92
Extremely Inverse Curve
93
Inverse Curve-D
94
Inverse Curve-E
95
Inverse Curve-F
96
Inverse-K (KEPCO) Curve
97
Very Inverse-K (KEPCO) Curve
98
THR, 51LR Curve
99
DGR Curve
100
SGR Curve
101
87T Curve
102
87G Curve
103
67N Curve
104
67 Curve
105
2. Logic (Example)
106
107
108
109
110
111
112