Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

FOR CONSTRUCTION

0 May.04,'16 FOR CONSTRUCTION J.D.KIM J.Y.LEE S.D.PARK

REV. DATE DESCRIPTION DSGN CHKD APPD

OWNER :

Therma Visayas, Inc.,


EPC CONTRACTOR : SUB-CONTRACTOR:

PROJECT :

Therma Visayas Energy Project


DESIGNED BY DATE TITLE :

J.D.KIM May.04,'16

CHECKED BY DATE Pump Data Sheet


for Circulating Water Pump
J.Y.LEE May.04,'16

APPROVED BY DATE DOCUMENT NUMBER REV.

S.D.PARK May.04,'16 TVEP-0-V-131-09-00001 0


DOC. NO. TVEP-0-V-131-09-00001

1 SPECIFICATION ■ FOR MFG


PUMP DATA SHEET □ ESTIMATED
2 OF PUMP

3 CUSTOMER HYUNDAI ENGINEERING.CO.,LTD. LOCATION PHILIPPINES

4 PROJECT NAME THERMA VISAYAS ENGERGY PROJECT SERVICE CIRCULATING WATER PUMP

5 ITEM NO. 12/22PAC11/12AP001 NO. OF PUMPS 4 SETS JOB NO. TVEP-PO-M-008 ORDER NO. 1500696

6 PUMP MODEL VMF1500-1000C NO. OF STAGE 1 INSTALLATION □ INDOOR ■ OUTDOOR

7 SUPPLIER HYOSUNG GOODSPRINGS DRIVER ■ MOTOR □ ENGINE □ TURBINE

8 MANUFACTURE HYOSUNG GOODSPRINGS NO. OF DRIVER 4 SETS SETS SETS

9 OPERATING CONDITIONS PERFORMANCE

10 LIQUID SEA WATER SPEED 508 RPM EFF. 88 %

11 CAPACITY RATED 20,180 m3/hr NOR. - m3/hr NPSHre 9.5 m RATED BHP 1,376 kW

12 TOTAL HEAD 21.5 m NPSHav 12.7 m MIN. FLOW 14,126 m3/hr MAX. BHP 1,440 kW

13 SUCTION - kg/cm
2
DIFF. 2.20 kg/cm
2
MATERIALS
PRESS
14 DISCHARGE - kg/cm2 VAPOR kg/cm2 PART NAME ASTM

15 PUMPING TEMP. NORMAL 30 ℃ MAX ℃ CASING A890 Gr. 1B

16 VISCOSITY - CP S.GRAVITY 1.025 IMPELLER A890 Gr. 1B

17 SIZE - mm CORR/EROS - SHAFT A276 S31803


SOLID
18 CONTENT - % CAUSED BY - SHAFT SLEEVE A890 Gr. 1B

19 CONSTRUCTIONS MOTOR STOOL A36 or Eq.

20 MOUNTING VERTICAL COLUMN PIPE A240 S31803

21 SPLIT TYPE RADIAL BASE PLATE A36 + A240 316L


CASING
22 MAWP 4 kg/cm
2
JOURNAL BEARING TEFLON

23 HYDRO.TEST 6 kg/cm2 DRIVER SHAFT COLUMN A240 S31803

24 FLANGE SIZE RATING FACING POSITION DISCHARGE BEND A240 S31803

25 SUCTION Ø2000 mm N/A N/A BOTTOM SEALING WATER □ YES ■ NO

26 DISCHARGE Ø1500 mm AWWA C207 Class D FF SIDE INLET SIZE - mm RATING

27 PUMP LENGTH (TOP FLOOR TO SUCTION BELL) 7.8 m OUTLET SIZE - mm RATING

28 MOUNTING JOURNAL TYPE SEMI-OPEN PRESS Kg/cm


2
Q'ty ℓ/min

29 IMPELLER DIA. SIZE RATED LATER ELECTORIC MOTOR


(mm) MAX / MIN LATER LATER MANUFACTURER HYUNDAI ENCLOSURE TEFC
30
31 RADIAL JOURNAL THRUST ANTI-FRICTION R.OUTPUT 1600 kW NO.OF POLE 14 POLE
BEARING
32 LUBRICANT SELF-LUBRICANT SYN.SPEED 508 rpm CYCLES 60 Hz

33 BASE PLATE SOLE PLATE PHASE 3 Φ INS.CLASS F

34 COUPLING GEAR COUPLING VOLTAGE 6,600 V TEMP.RISE 84.4 ℃

35 TRANSMISSION DIRECT ACCESSORIES

36 ROTATION VIEWD FROM DRIVER CW COUPL. SET YES BASE PLATE YES

37 VENT DRAIN GAUGE CONNEC. COUNT. FLANGE NO ANCH. BOLT YES


CONNECTION
38 3" 1" 1" FUNNEL NO GAUGE COCK NO

39 ■ PACKING □ MECH. SEAL SUC.STRAINER NO PRESS.GAUGE YES

40 SHAFT SEAL SIZE □ 19 PLAN EXPANSION JOINT YES

41 TURN 3 MFG. APPENDED DRAWINGS

42 SHOP TEST PERFORMANCE TVEP-0-V-131-09-00003

43 PERFORMANCE TEST ■ WITNESS □ NON-WITNESS OUTLINE DWG. TVEP-0-V-131-10-00001

44 HYDRO STATIC TEST □ WITNESS ■ NON-WITNESS SECTIONAL DWG. TVEP-0-V-131-12-00001

45 NPSHre TEST □ WITNESS □ NON-WITNESS ■ N/A WEIGHTS (APPROX)

46 NOTES PUMP 21,600 kg DRIVER 13,800 kg

47 1 Except Details specified on this Data Sheet, BASE PLATE 2,400 kg MOTOR STOOL 9,400 kg

48 all subjects including test shall be performed in accordance with TOTAL 47,200 kg

49 TVEP-0-V-131-05-00001 Inspection & Test Plan for Pump REV. PREP CHK APP

50 TVEP-0-V-131-05-00003 Inspection and test Procedure for Pump A 2015-7-21 J.D.KIM J.Y.LEE S.D.PARK

51 B 2015-8-21 J.D.KIM J.Y.LEE S.D.PARK

52 C 2015-12-14 J.D.KIM J.Y.LEE S.D.PARK

53 D 2016-1-14 J.D.KIM J.Y.LEE S.D.PARK

You might also like