ID551 WEIGHING CONTROLLER

OPERATION MANUAL

Bagging PAC

2019/07
Rev 1.07

1
ID551 Bagging PAC

Contents
CHAPTER 1.0 INTRODUCTION ............................................................................................................. 3
CHAPTER 2.0 KEYPAD AND MENU ............................................................................................................. 4
2.1 KEYPAD ....................................................................................................................................................... 4
2.2 MENU & SETUP ......................................................................................................................................... 4
2.2.1 [1 ] Calibration Block .............................................................................................................. 4
2.2.2 [2 ] Scale Application Block .................................................................................................... 5
2.2.3 [3 ] Target Controller Block ..................................................................................................... 6
2.2.4 [4 ] Input Assignment .............................................................................................................. 9
2.2.5 [5 ] Output Assignment .......................................................................................................... 15
2.2.6 [6 ] Communication Block .................................................................................................... 21
2.2.11[11 ] Maintenance Block ......................................................................................................... 21
CHAPTER 3.0 SERIAL PORT APPLICATION – MODBUS-RTU ............................................................ 22
CHAPTER 5.0 PRESET POINT APPLICATION .................................................................................. 25
5.1 PRESET POINT FEATURE .............................................................................................................................. 25
CHAPTER 6.0 HARDWARE ................................................................................................................... 26
6.1 I/F & HOUSING .......................................................................................................................................... 26
6.2 I/O APPLICATION ....................................................................................................................................... 27
6.3 DIP SWITCH & LEDS................................................................................................................................. 27

Version Change Log


Version Changes Time
st
V0.1 1 Version 17-Feb-2011
V0.2 Add Over/Under Function Mar-2011

V0.3 Serial port adds continuous output/command input July-2011


V0.4 Add serial port baud rate 1200,2400,4800 Oct-2012
Software Version: 551T.07 above
V0.5 Add 2.5, 2.6 Menu Nov-2014
V0.6 Add valve pocket 15-Apr-2018
V0.7 Add flap function 18-July-2019

2
ID551 Bagging PAC

Chapter 1.0 Introduction

ID551 is a DIN rail housing process weighing terminal,Target to


industry process weighing, bagging PAC support

filling, packaging and blending system applications,it is very easy to


build a master/slave controlling system via RS232/485 serial port with
touch screen and PLC host devices,ID551 is a very good solution for
one master/multi-scale slaves system.

Standard Features Overview


 24VDC power input, not more than 3W power consumption
 One analog load cell platform I/F(up to 6x350 ohm load cells)
 Up to 100,000 Display Division
 Communication Ports
 One RS232/485 serial port for MODBUS-RTU slave
 8Input / 8Output
 200Hz A/D weighing updating speed

 4 bagging Control Mode


■ No Bucket bagging
■ Bucket bagging
■ Target Controller Mode
■ Accept Tolerance Test Mode

 DIN rail housing

 Operating Environment
Operating Temperature: -100C400C
Humidity: 10%95% non-condensing

3
ID551 Bagging PAC

Chapter 2.0 Keypad and Menu

2.1 Keypad

Key Description
〖ZERO〗, in home page, Zero Scale if gross weight in Zero range.
In setup mode, as ESC Key or Exit Key

〖TARE〗。In home page, Tare scale and save the current weight as tare
weight. In setup mode, increse cycly.

〖Clear〗。In net mode, clear tare and go back to gross weight mode.
In setup mode, Move to right cycly.

〖Enter〗。In home page, Enter setup mode


In Setup mode,Accept chage and go back to next step.

Press ,Enter Setup Mode

[1 ] Calibration Block  [2 ] Scale Application Block [3 ] Target


Controller Block [4 ] Input Assignment [5 ] Output Assignment
[6 ] Communication Block [11 ] Maintenance Block

2.2 Menu & Setup

2.2.1 [1 ] Calibration Block

[1.1 ] Increment Size


0 (0.001), 1 (0.002), 2 (0.005), 3 (0.01), 4 (0.02), 5 (0.05),
6 (0.1), 7 (0.2), 8 (0.5), 9 (1), 10 (2), 11 (5),
12 (10), 13 (20), 14 (50), 15 (100)

[1.2 ] Capacity

4
ID551 Bagging PAC
[1.3 ] Calibration Mode
0 - 2-pint calibration,[1.4 ] (zero point adjustment) and [1.6 ] (End
point Calibration)
1 - without big test weight calibration [1.4 ] (zero point adjustment), and
[1.7 ] (CalFree block )

[1.4 ] Zero Point Calibration

Calibration steps:
[ CAL-0] [ 10]  [ 9] …[ 0] [ SAVE?]
10、9… 2、1: Calibration in progress 100 – In dynamic
255 – Calibration failure 0 – Calibration complete
0 – Calibration complete

[1.6 ] End Point Calibration

Calibration steps:
[ CAL-2] Input testing weight [ 3000] [ Ld-SP2] Add testing weight

[ 10]  [ 9] …[ 0] [ SAVE?]


10、9… 2、1: Calibration in progress 100 – In dynamic
255 – Calibration failure 0 – Calibration complete

2.2.2 [2 ] Scale Application Block

[2.1 ] Filter
0 – Low 1 – Middle 2 – High

[2.3 ] Keypad Zero


0 – Disable
±1%, ±2%,±5%,±10%,±20% - Enable

[2.4 ] Motion Checking


0 - Disable
(1 ~ 99) x0.1d – Enable

[2.5 ] Auto Zero Range


0 - Disable auto zero
0.1 ~ 9.9 d – Enable Auto Zero

[2.6 ] Auto Zero Speed


0 - Disable auto zero
0.1 ~ 9.9 d/s – Enable Auto Zero and auto zero with this setting speed.

5
ID551 Bagging PAC

2.2.3 [3 ] Target Controller Block

[3.1 ] Bagging PAC Mode


0 – With bucket bagging with bag clamp control
1 – No bucket bagging with bag clamp control
2 – Target Control and time delay to start empty automatically without bag clamp
control
3 – Target Control and Manual empty without bag clamp
4 – Electric valve pocket
5 -- Pneumatic valve pocket

[3.2 ] Target weight value


[3.3 ] Middle Feed Value

[3.4 ] Fine Feed Value


[3.5 ] Spill weight value
[3.6 ] Upper tolerance weight value (+Tol)
[3.7 ] Lower tolerance weight value (-Tol)
[3.8 ] Zero Tolerance weight value

[3.9 ] Auto Zero Period


0 – Disable Auto Zero before start weight in.
1 – Each cycle auto zero first and then start weight in
>1 – in Each configured cycles only auto zero one time before
weight in

[3.10 ] Auto Spill Period


0 – Disable Auto Spill
>=1, Auto Spill after each setting filling times.
[3.11 ] Auto Spill Factor:
0 – Auto Spill adjustment according internal rules, if filling result error is big and
adjustment range is big, if filling result error is small and adjustment range is small.
1~100 – Auto Spill adjustment according setting value

[3.12 ] Feeder Control Output Mode


Output Mode Fast Feed Middle Feed Fine Feed
0 SP1 = ON SP1 = OFF SP1 = OFF
SP2 = ON SP2 = ON SP2 = OFF
SP3 = ON SP3 = ON SP3 = ON
1 SP1 = ON SP1 = OFF SP1 = OFF
SP2 = OFF SP2 = ON SP2 = OFF
SP3 = OFF SP3 = OFF SP3 = ON

[3.13 ] Drain time


0~999 x 0.01S

[3.14 ] JOG ON time


6
ID551 Bagging PAC
0~999 x 0.01S,
0 – Disable JOG
> 0 if weight is under lower tolerance, keep fine feed ON setting time for times
to make sure weight is not under lower tolearnce

[3.15 ] Delay time to start empty


0~999 x 0.01S

[3.16 ] Delay time to complete empty


0~999 x 0.01S

[3.17 ] Out of Tolerance Alarm


0 – Disable Alarm
1 – Enable Alarm,if weight is out of tolerance after weight in, it is necessary to
clear alarm and then start empty

[3.18 ] Delay time to Clamp bag ON


0~999 x 0.01S,
0 – Disable clamp bag control,
>0 Clamp bag control work

[3.19 ] Delay time to Clamp bag OFF


0~999 x 0.01S

[3.20 ] Fast Inhabit Time


0~999 x 0.01S
Fast Inhabit Time is used to inhabit compare some time when start Fast Feed

[3.21 ] Middle Inhabit Time


0~999 x 0.01S
Middle Inhabit Time is used to inhabit compare some time when start Middle
Feed

[3.22 ] Fine Inhabit Time


0~999 x 0.01S
Fine Inhabit Time is used to inhabit compare some time when start Fine Feed

[3.23 ] Delay time to start weight IN


0~999 x 0.01S

[3.24 ] Display hold time


0~999 x 0.01S

[3.25 ] Auto Spill Range

[3.26 ] Total Mode


0 – Disable Total,
1 – Always Total,
2- Only total for in tolerance

[3.27 ] Total Counter


Max data is 60000, total will stop if total counter reach 60000
7
ID551 Bagging PAC
[3.28 ] Total Weight

[3.30 ] Gas Pluse1 ON Time


0~999 x 0.01S

[3.31 ] Gas Pluse1 OFF Time


0~999 x 0.01S

[3.32 ] Gas Pluse2 ON Time


0~999 x 0.01S

[3.33 ] Gas Pluse2 OFF Time


0~999 x 0.01S

[3.34 ] Fast Feed Pluse1 ON Time


0~999 x 0.01S,

[3.35 ] Fast Feed Pluse1 OFF Time


0~999 x 0.01S

[3.36 ] Fast Feed Pluse2 ON Time


0~999 x 0.01S

[3.37 ] Fast Feed Pluse2 OFF Time


0~999 x 0.01S

[3.38 ] Push Bag Time


0~999 x 0.01S

[3.39 ] Release Bag Time


0~999 x 0.01S

[3.40 ] Auto Start Mode


0 – Disable
1 – Enable

[3.41 ] Auto Start Minimum Weight


Detect the minimum weight of the automatic starting package, and allow the
automatic starting function only when it is greater than 1 dividing value;Otherwise
prohibited

[3.42 ] Auto Start Maximum Weight


Detect the maximum weight of the automatic starting package,

[3.43 ] Flap Times


0 – Disable
>0 – Enable

[3.44 ] Flap Output ON Holding Time


0~999 x 0.01S

[3.45 ] Flap Output OFF Holding Time


0~999 x 0.01S

8
ID551 Bagging PAC

2.2.4 [4 ] Input Assignment

-0-Bucket Mode with Bag Clamping Control

[4.1 ] IN1
Start/ Stop
When input 24VDC and keep IN1 on, indicator work in auto bagging mode
If IN1 OFF, indicator complete the current bagging and then work in stop mode

[4.2 ] IN2
Stop and last bag command
OFF-> ON , this rising edge inform indicator process the last bag function, stop
filling and then total weight and then complete this bag.
In general IN1 OFF first and then keep IN2 ON some time

[4.3 ] IN3
Enable or disable empty, before start empty, checking IN3 first, it is necessary to
make sure IN3 off and then start empty.
ON - Disable empty(weight out)
OFF – Enable empty

[4.4 ] IN4
OFF  ON : start empty

[4.5 ] IN5
Clamp bag switch input

[4.6 ] IN6
OFF  ON : Clear Alarm

[4.7 ] IN7
ON - Manual JOG,
Only work when [3.17 ] out of tolerance alarm is enabled and weight is under lower
tolerance.

[4.8 ] IN8
Force SP1, SP2, SP3 ON

9
ID551 Bagging PAC

-1-No Bucket Mode with Bag Clamping Control

[4.1 ] IN1
Start/ Stop
When input 24VDC and keep IN1 on, indicator work in auto bagging mode
If IN1 OFF, indicator complete the current bagging and then work in stop mode

[4.2 ] IN2
Stop and last bag command
OFF-> ON , this rising edge inform indicator process the last bag function, stop
filling and then total weight and then complete this bag.
In general IN1 OFF first and then keep IN2 ON some time

[4.3 ] IN3
Enable or disable empty, before start empty, checking IN3 first, it is necessary to
make sure IN3 off and then start empty.
ON - Disable empty(weight out)
OFF – Enable empty

[4.4 ] IN4
OFF  ON : start empty

[4.5 ] IN5
Clamp bag switch input

[4.6 ] IN6
OFF  ON : Clear Alarm

[4.7 ] IN7
ON - Manual JOG,
Only work when [3.17 ] out of tolerance alarm is enabled and weight is under lower
tolerance.

[4.8 ] IN8
Force SP1, SP2, SP3 ON

10
ID551 Bagging PAC

-2-Automatic delay feeding and emptying without bag clamping


control

[4.1 ] IN1
Start/ Stop
When input 24VDC and keep IN1 on, indicator work in auto bagging mode
If IN1 OFF, indicator complete the current bagging and then work in stop mode

[4.2 ] IN2
Stop and last bag command
OFF-> ON , this rising edge inform indicator process the last bag function, stop
filling and then total weight and then complete this bag.
In general IN1 OFF first and then keep IN2 ON some time

[4.3 ] IN3
Enable or disable empty, before start empty, checking IN3 first, it is necessary to
make sure IN3 off and then start empty.
ON - Disable empty(weight out)
OFF – Enable empty

[4.4 ] IN4
OFF  ON : start empty

[4.5 ] IN5
Reserve

[4.6 ] IN6
OFF  ON : Clear Alarm

[4.7 ] IN7
ON - Manual JOG,
Only work when [3.17 ] out of tolerance alarm is enabled and weight is under lower
tolerance.

[4.8 ] IN8
Force SP1, SP2, SP3 ON

11
ID551 Bagging PAC

-3-Feeding and manual emptying without bag clamping control


[4.1 ] IN1
Start/ Stop
When input 24VDC and keep IN1 on, indicator work in auto bagging mode
If IN1 OFF, indicator complete the current bagging and then work in stop mode

[4.2 ] IN2
Stop and last bag command
OFF-> ON , this rising edge inform indicator process the last bag function, stop
filling and then total weight and then complete this bag.
In general IN1 OFF first and then keep IN2 ON some time

[4.3 ] IN3
Enable or disable empty, before start empty, checking IN3 first, it is necessary to
make sure IN3 off and then start empty.
ON - Disable empty(weight out)
OFF – Enable empty

[4.4 ] IN4
OFF  ON : start empty

[4.5 ] IN5
Reserve

[4.6 ] IN6
OFF  ON : Clear Alarm

[4.7 ] IN7
ON - Manual JOG,
Only work when [3.17 ] out of tolerance alarm is enabled and weight is under lower
tolerance.

[4.8 ] IN8
Force SP1, SP2, SP3 ON

12
ID551 Bagging PAC

-4- Electric valve pocket


[4.1 ] IN1
Start/ Stop
When input 24VDC and keep IN1 on, indicator work in auto bagging mode
If IN1 OFF, indicator complete the current bagging and then work in stop mode

[4.2 ] IN2
Reserve

[4.3 ] IN3
Stop feeding
ON--forces the current feed process to stop, closing all outputs

[4.4 ] IN4
Reserve

[4.5 ] IN5
Clamp bag switch input

[4.6 ] IN6
OFF  ON : Clear Alarm

[4.7 ] IN7
Manual clearance
ON - forces O1,O2,O3,O4 ON

[4.8 ] IN8
No push bag input

13
ID551 Bagging PAC

-5- Pneumatic valve pocket


[4.1 ] IN1
Start/ Stop
When input 24VDC and keep IN1 on, indicator work in auto bagging mode
If IN1 OFF, indicator complete the current bagging and then work in stop mode

[4.2 ] IN2
Reserve

[4.3 ] IN3
Stop feeding
ON--forces the current feed process to stop, closing all outputs

[4.4 ] IN4
Reserve

[4.5 ] IN5
Clamp bag switch input

[4.6 ] IN6
OFF  ON : Clear Alarm

[4.7 ] IN7
Manual clearance
ON - forces O1,O2,O3,O4 ON

[4.8 ] IN8
No push bag input

14
ID551 Bagging PAC

2.2.5 [5 ] Output Assignment

-0-Bucket Mode with Bag Clamping Control

[5.1 ] O1
SP1 – Fast feed output

[5.2 ] O2
SP2 – Middle feed output

[5.3 ] O3
SP3 - Fine feed output

[5.4 ] O4
Empty output

[5.5 ] O5
Clamp bag output

[5.6 ] O6
light - Running
Flash – weight-in completed, and wait to empty

[5.7 ] O7
Out of tolerance alarm output

[5.8 ] O8
Error alarm output. (such as: return zero error, Out tolerance
Waiting for confirmation, No Empty Enable IN)

[5.9 ] O9
Flapping output, flapping bag after feeding (only allow flapping
function can have output)

15
ID551 Bagging PAC

-1- NO Bucket Mode with Bag Clamping Control

[5.1 ] O1
SP1 – Fast feed output

[5.2 ] O2
SP2 – Middle feed output

[5.3 ] O3
SP3 - Fine feed output

[5.4 ] O4
Empty output

[5.5 ] O5
Clamp bag output

[5.6 ] O6
light - Running
Flash – weight-in completed, and wait to empty

[5.7 ] O7
Out of tolerance alarm output

[5.8 ] O8
Error alarm output. (such as: return zero error, Out tolerance
Waiting for confirmation, No Empty Enable IN)

[5.9 ] O9
Flapping output, flapping bag after feeding (only allow flapping
function can have output)

16
ID551 Bagging PAC

-2-Automatic delay feeding and emptying without bag clamping


control
[5.1 ] O1
SP1 – Fast feed output

[5.2 ] O2
SP2 – Middle feed output

[5.3 ] O3
SP3 - Fine feed output

[5.4 ] O4
Empty output

[5.5 ] O5
On--feed complete

[5.6 ] O6
light - Running
Flash – weight-in completed, and wait to empty

[5.7 ] O7
Out of tolerance alarm output

[5.8 ] O8
Error alarm output. (such as: return zero error, Out tolerance
Waiting for confirmation, No Empty Enable IN)

[5.9 ] O9
Flapping output, flapping bag after feeding (only allow flapping
function can have output)

17
ID551 Bagging PAC

-3-Feeding and manual emptying without bag clamping control


[5.1 ] O1
SP1 – Fast feed output

[5.2 ] O2
SP2 – Middle feed output

[5.3 ] O3
SP3 - Fine feed output

[5.4 ] O4
Empty output

[5.5 ] O5
Reserve

[5.6 ] O6
light - Running
Flash – weight-in completed, and wait to empty

[5.7 ] O7
Out of tolerance alarm output

[5.8 ] O8
Error alarm output. (such as: return zero error, Out tolerance
Waiting for confirmation, No Empty Enable IN)

[5.9 ] O9
Flapping output, flapping bag after feeding (only allow flapping
function can have output)

18
ID551 Bagging PAC

-4- Electric valve pocket


[5.1 ] O1
SP1 – Fast feed output

[5.2 ] O2
SP3 - Fine feed output

[5.3 ] O3
Gas Pluse1

[5.4 ] O4
Gas Pluse2

[5.5 ] O5
Clamp bag output

[5.6 ] O6
light - Running
Flash – weight-in completed, and wait to empty

[5.7 ] O7
Push bag output

[5.8 ] O8
Release bag output

[5.9 ] O9
Flapping output, flapping bag after feeding (only allow flapping
function can have output)

19
ID551 Bagging PAC

-5- Pneumatic valve pocket


[5.1 ] O1
Fast Feed Pluse1

[5.2 ] O2
Fast Feed Pluse2

[5.3 ] O3
Gas Pluse1

[5.4 ] O4
Gas Pluse2

[5.5 ] O5
Clamp bag output

[5.6 ] O6
light - Running
Flash – weight-in completed, and wait to empty

[5.7 ] O7
Push bag output

[5.8 ] O8
Release bag output

[5.9 ] O9
Flapping output, flapping bag after feeding (only allow flapping
function can have output)

20
ID551 Bagging PAC

2.2.6 [6 ] Communication Block

[6.1 ] Node Address

Input range is 1 ~ 99
MODBUS-RTU : 1 ~ 99
[6.2 ] Serial Port Baud Rate
0 – 1200,8,1,N 1 – 2400,8,1,N
2 – 4800,8,1,N 3 – 9600,8,1,N
4 – 19200,8,1,N 5 – 38400,8,1,N
6 – 57600,8,1,N

2.2.11[11 ] Maintenance Block

[11.1 ] Load Cell I/F


Checking terminal load cell I/F and load cells via see A/D internal code, in general, the is
from about 30 to 35000, and just jump several digits

[11.2 ] Input(IN6 ~ IN1)Diagnostics


000000(Left to Right) : IN6,IN5,IN4,IN3,IN2,IN1
0 - OFF,1 - ON
For example: 001001: IN1 and IN4 are ON,IN2、IN3、IN5、IN6 are OFF

[11.3 ] Input(IN8 ~ IN7)Diagnostics


00(Left to Right) : IN8,IN7
0 - OFF,1 - ON

[11.4 ] Output(OUT6 ~ OUT1)Diagnostics


000000(Left to Right) : OUT6,OUT5,OUT4,OUT3,OUT2,OUT1, 0 - OFF,1 - ON
For example: 001001: OUT1 and OUT4 are ON,
OUT2, OUT3, OUT5, OUT6 are OFF

[11.5 ] Output(OUT7 ~ OUT8)Diagnostics


00(Left to Right) : OUT8,OUT7
0 - OFF,1 - ON

21
ID551 Bagging PAC

Chapter 3.0 Serial Port Application –

MODBUS-RTU

MODBUS-RTU Floating data format


Address Description Operation
40001/2 Display weight, FP32 floating data, Byte order 3412 R
40003/4 Gross weight, FP32 floating data, Byte order 3412 R

Bit 0 – IN1( 0 – OFF, 1 – ON )


Bit 1 – IN2( 0 – OFF, 1 – ON )
Bit 2 – IN3( 0 – OFF, 1 – ON )
Bit 3 – IN4( 0 – OFF, 1 – ON )
Bit 4 – IN5( 0 – OFF, 1 – ON )
Bit 5 – IN6( 0 – OFF, 1 – ON )
Bit 6 – IN7( 0 – OFF, 1 – ON )
40005 Bit 7 – IN8( 0 – OFF, 1 – ON )
R/W
Bit 8 – OUT1( 0 – OFF, 1 – ON )
Bit 9 – OUT2 ( 0 – OFF, 1 – ON )
Bit 10 – OUT3 ( 0 – OFF, 1 – ON )
Bit 11 – OUT4 ( 0 – OFF, 1 – ON )
Bit 12 – OUT5 ( 0 – OFF, 1 – ON )
Bit 13 – OUT6 ( 0 – OFF, 1 – ON )
Bit 14 – OUT7 ( 0 – OFF, 1 – ON )
Bit 15 – OUT8 ( 0 – OFF, 1 – ON )
Bit 0 – 1 – Start bagging, 0 – Stop bagging
40006 Bit0 = 1 or IN1=1: Start bagging,
Both Bit0 and IN1 are 0: Stop bagging
Bit 1 – 0->1 Start empty
Bit 2 – 0->1 Zero Scale
Bit 3 – 0->1 Tare Scale
Bit 4 – 0->1 Clear Scale
Bit 5 - 0 –Normal , 1 – IN/OUT checking mode
Bit 6- 0 – Disable remote calibration
1- Enable remote calibration
Bit 7 – 1 - Fast Feed ON R/W
Bit 8 – 1 - Middle Feed ON
Bit 9 – 1 - Fine Feed ON
Bit10 - Clip Bag

Bit 15- 01 Re-init scale


40007/8 Target weight value, FP32 floating data, Byte order 3412 R/W
40009/10 Middle Feed weight Value, FP32 floating data, Byte order 3412 R/W
40011/12 Fine Feed weight Value, FP32 floating data, Byte order 3412 R/W
40013/14 Spill , FP32 floating data, Byte order 3412 R/W
40015/16 Upper Tolerance, FP32 floating data, Byte order 3412 R/W
40017/18 Lower Tolerance , FP32 floating data, Byte order 3412 R/W
22
ID551 Bagging PAC
40019/20 Zero Tolerance, FP32 floating data, Byte order 3412 R/W
40021 Auto Zero period: 0-99 R/W
40022 Drain Time: 0-999 R/W
40023 JOG ON: 0 -999 R/W
40024 [3.15] Delay time to start empty 0~999 x 0.01S R/W
40025 [3.16] Delay time to complete empty 0~999 x 0.01S R/W
40026 [3.17] Out of Tolerance Alarm: 0 or 1 R/W
40027 [1.2] Capacity R/W
40028 [1.1] Increment Size Index R/W
0 (0.001), 1 (0.002), 2 (0.005), 3 (0.01), 4 (0.02),
5 (0.05), 6(0.1), 7(0.2), 8(0.5), 9(1),
10(2), 11(5), 12(10), 13(20), 14(50),
15(100)
40029 Calibration Test Weight R/W
40030 Calibration command R/W
0->1 : Zero point calibration
0->3 : End point calibration
40031 [2.1] Filter: 0,1,2 R/W
40032 [2.3] Keypad Zero Index R/W
0 – Disable, 1(±1%),2(±2%), 3(±10%)
40033 [2.4] Motion Checking: 0…99 R/W
40034 [2.5] Auto Zero Range: 0…99 x0.1d R/W
40035 [2.6] Auto Zero Speed: 0…99 x0.1d/s R/W
40036 [3.12] Feeder Control Output Mode R/W
40037 [3.10]Auto Spill Period R/W
40038 [3.11 ] Auto Spill Factor R/W

40039 [3.1] Bagging PAC Mode R/W


0, 1,2,3
40040 [3.18 ] Delay time to Clamp bag ON: 0~999 x 0.01S R/W
40041 [3.19 ] Delay time to Clamp bag OFF: 0~999 x 0.01S R/W
40042 [3.20 ] Fast Inhabit Time R/W
0~999 x 0.01S
40043 [3.21 ] Middle Inhabit Time R/W
0~999 x 0.01S
40044 [3.22 ] Fine Inhabit Time 0~999 x 0.01S R/W
40045 [3.23 ] Delay time to start weight IN R/W
0~999 x 0.01S
40046 [3.24] Display hold time R/W
0~999 x 0.01S
40047/48 [3.25] Auto Spill Range R/W
40049 [3.26] Total Mode: 0 , 1, 2 R/W
40050 [3.27] Total Counter R/W
40051/52 [3.28] Total weight R/W

40053 User Parameter 1 R/W


40054 User Parameter 2 R/W
40055 User Parameter 3 R/W
40056 User Parameter 4 R/W
40057 User Parameter 5 R/W
40058 [3.30 ] 0~999 x 0.01S Gas Pluse1 ON Time R/W
23
ID551 Bagging PAC

40059 [3.31 ] 0~999 x 0.01SGas Pluse1 OFF Time R/W


40060 [3.32 ] 0~999 x 0.01SGas Pluse2 ON Time R/W
40061 [3.33 ] 0~999 x 0.01SGas Pluse2 OFF Time R/W
40062 [3.34 ] 0~999 x 0.01S Fast Feed Pluse1 ON Time R/W
40063 [3.35 ] 0~999 x 0.01SFast Feed Pluse1 OFF Time R/W
40064 [3.36 ] 0~999 x 0.01SFast Feed Pluse2 ON Time R/W
40065 [3.37 ] 0~999 x 0.01SFast Feed Pluse2 OFF Time R/W
40066 [3.38 ] Push Bag Time,0~999 x 0.01S R/W
40067 [3.39 ] Release Bag Time,0~999 x 0.01S R/W
40068/69 Record R
40070 Error Code R
Bit0 - Back to Zero Failure
Bit1 - Tolerance Alarm
Bit2 - No Empty Enable IN
Bit3 - Out Tolerance Waiting for Confirmation
40071 Auto Start Mode 0 – Disable 1 – Enable R/W

40072/73 Auto Start Minimum Weight R/W


40074/75 Auto Start Maximum Weight R/W
40076 [3.43 ] Flap Times 0 – Disable >0 – Enable R/W
40077 [3.44 ] Flap Output ON Holding Time R/W
40078 [3.45 ] Flap Output OFF Holding Time R/W
40079 Bit 0 – OUT9( 0 – OFF, 1 – ON ) R/W
Bit 1 – OUT10 ( 0 – OFF, 1 – ON )
Bit 2 – OUT11( 0 – OFF, 1 – ON )
Bit 3 – OUT12( 0 – OFF, 1 – ON )

24
ID551 Bagging PAC

Chapter 5.0 Preset Point Application

5.1 Preset point feature

 If the fine feed quantity is not 0, it is a dual-speed preset point; otherwise, it is a


single-speed preset point (only a slow feed process).
 Enable start/cancel, start/pause/continue, start/pause/cancel, etc
 If set starting value,it will confirm whether the weight heavier than the threshold
value at start.If so,use Preset Point.
 If use auto tare,it will auto tare after start then use Preset Point.
 Enable Tolerance Monitoring
 Enable Run/pause status output

Weight Auto Fast Fine Tolerance


Tare Feed Feed Monitoring

Zero Tol

Start Value

Time
Start Feed(IN)
Fast Feed(Out)
Fine Feed(Out)
Tolerance
Monitoring(Out)
Start(Out)
25
ID551 Bagging PAC

Chapter 6.0 Hardware

6.1 I/F & Housing

26
ID551 Bagging PAC

6.2 I/O Application

6.3 DIP Switch & LEDs

SW Status Description
SW-2 ON 1. Auto Zero is always disabled
2. Calibration mode is always 2-point mode

27