DREIPHASEN SYNCHRON GENERATOR

THREE-PHASE SYNCHRONOUS GENERATOR

MJB 500 MB 4
FREQUENZ FREQUENCY Hz 50
SPANNUNG VOLTAGE (± 10%) V 415
STROM CURRENT A 2070
NENNLEISTUNG RATED POWER @ 0.8 p.f. kVA 1488

u=1.1 u=1 u=0.9


1.0
P/S
0.9

0.8

0.7

0.6

0.5

0.4

0.3
jmax
0.2

0.1

0.0
-1.0 -0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

Q/S (untererregt / underexcited) Q/S (übererregt / overexcited)

U /Un
u=0.9 u = 0.95 u=1 u = 1.05 u=1.1
1) QStab 503 561 621 685 752 kVAr
PStab p.f.=0,90 1039 1158 1283 1414 1552 kWe
2)
PStab p.f.=0,95 1531 1706 1890 2084 2287 kWe
cosphi max 0.921 0.905 0.887 0.867 0.846 p.f.
S 1292 1316 1343 1373 1408 kVA
3)
P 1190 1190 1190 1190 1190 kWe
Q 503 561 621 685 752 kVAr
cosphi n 0.800 0.800 0.800 0.800 0.800 p.f.
Sn 1488 1488 1488 1488 1488 kVA
4)
Pn 1190 1190 1190 1190 1190 kWe
Qn 893 893 893 893 893 kVAr
5) QMax 1190 1190 1190 1190 1190 kVAr

Bemerkungen Remarks
1) Blindleistung QStab bei max. Untererregung (UE) 1) Reactive power QStab at max. under-excitation (UEXC)
2) Theor. Wirkleistung bei QStab (max. UE) 2) Theor. active load at QStab (max. UEXC)
3) Zul. Punkt bei QStab unter Einhaltung von SN und PN 3) Perm. Point at QStab under consideration of SN and PN
4) Nennpunkt 4) Rated point
5) Blindleistung bei max. Übererregung (ÜE) 5) Reactive load at max. over-excitation

Datum - Date 17.03.2020