00 30-Sep-17
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Emergency Eyewash/Shower System Installation SAIC-B-4002 30-Nov-17 PLUMB
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
A Emergency Eyewash/Shower
Emergency eyewashes and showers shall be permanently installed except in
the following situations where temporary installations are permitted if SAES-B-069
A1
approved by the Chief Fire Prevention Engineer or his representative in Para 5.1.5
consultation with the Environmental Compliance Division
Eye / face wash units shall be positioned with water nozzles 33 inches to 45
SAES-B-069
A4 inches from the floor and 6 inches minimum from the wall or the nearest
Para 7.1
obstruction. (ANSI Z358.1 Para 7.4.1)
Hand-held sprays are permitted in temporary installations in place of safety SAES-B-069
A5
showers Para 5.1.5
In permanent installations, hand-held drench hoses may be used only as
SAES-B-069
A6 auxiliary equipment in support of eyewash and shower units, not in place of
Para 5.1.6
eyewash
Emergency and shower units.
Eyewashes and Showers shall be accessible locations that
require no more than 10 seconds to reach [no closer than 3 m (10 ft) nor
further than 15 m (50 ft) from a hazard except where specifically allowed
SAES-B-069
A7 below]. The nature, severity, and environment of the chemical hazard shall
Para 7.2.1 a
be considered in determining the maximum allowable unobstructed distance.
For severe hazards, consult with the Industrial Hygiene Unit and Medical
Services
Emergency to determine
Eyewashes the proper
and distance.
Showers shall be accessible from the hazard SAES-B-069
A8
without the use of stairs, a ladder or a door. Para 7.2.1 d
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Shower Enclosures, if used, shall provide for a minimum unobstructed area SAES-B-069
B9
of 34 inches in diameter. (ANSI Z358.1 Para 4.4) Section 7.1
Water supply systems shall be certified as suitable for the purpose by Saudi
SAES-B-069
B10 Aramco Environmental Compliance Division/ Environmental Protection
Para 7.7.1
Department.
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
SAES-B-069
C7 Color Coding and Identification
Para 7.4
All newly constructed and existing repaired or modified domestic water
piping shall be protected from contamination during installation and shall be SAES-S-060
C8
disinfected in accordance with the requirements of Section SASC-S-17, of Para 613.0
Saudi Aramco Sanitary Code, GI-0151.006.
REMARKS:
REFERENCE DOCUMENTS:
1-SAES-B-069 -- Emergency Eyewash and Showers, 27 November 2016
2-SAES-B-067 -- Safety Identification and Color-Coding, 11 March 2015
3-SAES-S-070 -- Installation of Utility Piping System, 1 March 2017
4-ANSI Z-358.1 -- American National Standard for Emergency Eyewash and Shower Equipment, 2004
###